Site Plan Review Comments
All Site Plan Review Comments for Case # 18PR0156
Modify comments view for Case # 18PR0156

Go to Case Selection Form or Go to Project List

 
CASE NO: 18PR0156 STATUS: PENDING APPROVAL
PROJECT NAME: SWIFT CREEK PLACE - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: COMMERCIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 00 11/01/17 11/22/17 ******** ********
ENVIR.ENGR.-: 00 11/01/17 11/22/17 ******** ********
FIRE DEPT.--: 00 11/01/17 11/22/17 COMPLETE 11/13/17 AWB 717-6167
MAPPING/GIS-: 00 11/01/17 11/22/17 COMPLETE 11/21/17 AMJ 768-7549
PLANNING----: 00 11/01/17 11/22/17 ******** ********
TRANSPORT.--: 00 11/01/17 11/22/17 ******** ********
UTIL.PLAN.--: 00 11/01/17 11/22/17 ******** ********
UTILITIES---: 00 11/01/17 11/22/17 COMPLETE 11/21/17 WBP 751-4336
UTIL.R.O.W.-: 00 11/01/17 11/22/17 ******** ********
VDOT--------: 00 11/01/17 11/22/17 ******** ********
REVIEW DEPARTMENT: UTILITIES
REVIEWER / PHONE #: W.B. PAYNE III/751-4336
NAME OF PLAN: SWIFT CREEK PLACE
ADDRESS: 13439 & 13501 HULL STREET ROAD
SUBMISSION DATE: 11/3/17
PLAN DATED: 10/26/17
REVIEW DATE: 11/21/17
SITE PLAN NUMBER: 18PR0156
COMMENTS: 1ST REVIEW - NOT APPROVED
ADD THE UTILITY PROJECT NUMBER (17-0232) TO THE PLAN
REVISE THE UTILITIES CONTACT INFORMATION ON THE PLAN
FOR PUBLIC UTILITIES TO W.B. PAYNE III, PRINCIPAL
ENGINEER, 804-751-4336; EMAIL ADDRESS
PAYNEW@CHESTERFIELD.GOV
ADD 225' AS THE ELEVATION REQUIRING INDIVIDUAL PRV'S TO
DES-2, NOTE 4 ON SHEET C-4.7.
UTILITIES RECORDS INDICATE A RESIDENTIAL WATER SERVICE
(3/4" SERVICE LINE AND BOX) IS INSTALLED AT 13501 HULL
STREET ROAD, WHICH IF NOT USED FOR THIS PROJECT MUST BE
ABANDONED. LOCATE THE METER BOX AND SERVICE LINE AND ADD
BOTH TO THE PLAN. ADDITIONALLY, ADD A NOTE TO THE PERTINEN
DEMOLITION SHEETS STATING THE EXISTING WATER SERVICE IS TO
ABANDONED PER SECTION 3.05 OF THE SPECIFICATIONS.
WILL THERE BE A LANDSCAPE PLAN ASSOCIATED WITH THIS
PROJECT? IF SO, PLEASE SUBMIT AND ENSURE ALL EXISTING AND
PROPOSED WATER AND SEWER LINES AND APPURTENANCES ARE
SHOWN. ADDITIONALLY, PROVIDE AT LEAST 10' OF HORIZONTAL
SEPARATION BETWEEN TREES AND WATER/SEWER LINES AND
APPURTENANCES. FINALLY, TREES MAY NOT BE LOCATED WITHIN
WATER AND/OR SEWER EASEMENTS.
THE PLAN INDICATES EACH BUILDING WILL BE INDIVIDUALLY
METERED WITH 1 ½" WM'S HOWEVER METER SIZING FORMS
HAVE NOT BEEN SHOWN ON THE PLAN NOR RECEIVED BY UTILITIES.
PLEASE COMPLETE A WATER METER SIZING FORM (MSF) FOR EACH
PROPOSED WATER SERVICES AND ADD THE INDIVIDUAL FORMS TO
THE PLAN.
RE: COMMENT #6, LABEL THE PROPOSED WM SIZE FOR THE
RESTAURANT ON SHEET C4.1.
WILL AN IRRIGATION SYSTEM(S) BE PROPOSED FOR THIS SITE? IF
SO, PLEASE COMPLETE A MSF FOR EACH IRRIGATION METER AND
ADD TO THE PLAN.
WILL THE PARCEL BE SUBDIVIDED; I.E. HAVE INDIVIDUAL LOT
LINES BETWEEN THE BUILDINGS? IF SO, THE SEWER MUST BE
PUBLIC TO THE WESTERN-MOST PARCEL TO BE SERVED AND
SEWER EASEMENT MUST BE PROVIDED. IF NOT, THE SEWER SHOULD
BE PRIVATE AND MUST BE LABELED AS SUCH. PLEASE BE ADVISED
THAT IF THE PARCEL IS EVER SUBDIVIDED AFTER THE PROJECT HA
BEEN COMPLETED:
" PUBLIC SEWER MUST EXTEND TO THE FURTHEST PARCEL
REQUIRING SEWER SERVICE ON THE SITE.
" ALL PRIVATE SEWER MUST BE INSPECTED AND ANY ISSUES
CORRECTED BY THE OWNER/DEVELOPER PRIOR TO UTILITIES
AGREEING TO ACCEPT IT INTO THE COUNTY'S SEWER
SYSTEM.
" SEWER EASEMENT(S) MUST BE DEDICATED AND RECORDED.
PLEASE ADD THE FOLLOWING NOTE TO THE PLAN:
PRIOR TO CONNECTING THE PROPOSED WATER OR SEWER LINES TO T
EXISTING COUNTY SYSTEMS, THE FOLLOWING CRITERIA MUST BE M
:
" ALL PUBLIC WATER AND/OR SEWER LINES MUST EITHER BE
LOCATED WITHIN RECORDED WATER OR SEWER EASEMENTS
OR WITHIN DEDICATED RIGHTS-OF-WAY.
" ALL WATER AND/OR SEWER LINE TESTING HAS BEEN
COMPLETED AND HAS SUCCESSFULLY PASSED.
" ALL ENVIRONMENTAL ENGINEERING AND/OR VDOT
CONDITIONS HAVE BEEN MET.
" ROADS MUST BE READY FOR FINAL PAVING, WITH ALL
CURB & GUTTER AND THE SUBBASE INSTALLED.
IN LIEU OF THE PROPOSED TS&V, PLEASE INSTALL A HARD TEE
CONNECTION ON MOCKINGBIRD LANE AND ADD TWO 8" GV'S
WITH ONE BEING LOCATED ON THE MAIN WATERLINE UPSTREAM OF
THE TEE AND ONE ON THE BRANCH.
NOTE THAT ALL PUBLIC WATERLINES MUST BE ENCLOSED IN 16'
MINIMUM WIDTH WATER EASEMENT(S). BOTH DOMESTIC AND
IRRIGATION METERS MUST BE LOCATED WITHIN THE WATER
EASEMENT.
RE: COMMENT #12, BE ADVISED THAT A UTILITIES LICENSE
AGREEMENT MAY BE REQUIRED FOR ALL CONCRETE ISLANDS AND/OR
C&G TO BE LOCATED WITHIN PUBLIC WATER OR SEWER
EASEMENTS. PLEASE CONTACT JOAN COURSON IN THE RIGHT-OF
WAY SECTION AT 804-748-1362 FOR MORE INFORMATION.
IT IS NOTED THAT ALL FOUR BUILDINGS ARE PROPOSING TO HAVE
INTERNAL DETECTOR CHECKS (DC). PLEASE BE ADVISED FOR
UTILITIES TO APPROVE AN INTERNAL DC, IT MUST BE LOCATED
WITHIN 50' OF THE WATER MAIN. IT APPEARS THIS DISTANCE HAS
BEEN EXCEEDED FOR THE RETAIL A AND RESTAURANT BUILDINGS.
RE: COMMENT #12 FOR INTERNAL DC'S, THE FIRE LINE
SHUT-OFF GV SHOULD BE LOCATED AT THE EDGE OF THE WATER
EASEMENT (OR RIGHT-OF-WAY LINE) TO BE USED AS THE LINE OF
DEMARCATION BETWEEN PUBLIC AND PRIVATE. ADDITIONALLY, THE
ENCLOSED FIRE LINE DETAIL SHOULD BE ADDED TO THE PLAN.
PLEASE NOTE THE PLACEMENTS OF THE DOMESTIC AND IRRIGATION
WM'S IN RELATION TO THE FIRE LINE.
REMOVE THE "TAP TEE" DESIGNATION FOR THE DOMESTIC
SERVICE LINES. WATER TAPS ARE TO BE MADE USING A
CORPORATION STOP AND DIRECTLY TAPPING THE LINE.
RE: THE CONNECTION OF THE PROPOSED 8" SEWER LINE TO THE
EXISTING MH, PLEASE LABEL THE EXISTING MH AS EX MH-31.
IT IS NOTED ON THE 73-7027 AS-BUILT THAT EX MH-31 HAS A
BRICKED UP OPENING HOWEVER A NOTE SHOULD BE ADDED TO THE
PROFILE DIRECTING THE CONTRACTOR TO MATCH THE CROWN OF THE
PROPOSED 8" SEWER LINE WITH THE CROWN OF THE EXISTING 30"
LINE.
RE: COMMENT #17, THE MANUFACTURER'S MAXIMUM
RECOMMENDED ENTRY ANGLE FOR 8" SEWER "BOOTS" IS
7-DEGREES, WHICH THE PROPOSED ENTRY ANGLE AT THE 15%
SLOPE AS SHOWN EXCEEDS. THOUGH THE ENTRY ANGLE WILL BE
REDUCED WHEN THE CROWNS ARE MATCHED, PLEASE REVISE THE
LINE AS NECESSARY SO AS NOT TO EXCEED THE 7-DEGREE
RECOMMENDED MAXIMUM
PLEASE NOTE THAT THERE MUST BE A 3' MINIMUM CLEAR
SPACING BETWEEN FH'S AND SIDEWALKS OR THE BACK OF
CURBING.
THERE APPEARS TO BE 15 TOTAL MH'S WITH 9 STANDARD
MH'S AND 6 MMH'S; PLEASE CONFIRM AS THE QUANTITIES LIST
15 STANDARD MH'S AND 7 SAMPLING MH'S. AS THE TOP STEP IS
REMOVED IN MMH'S, PLEASE LIST THE STANDARD MH'S AND
MMH'S SEPARATELY IN THE QUANTITIES FOR A TOTAL OF 15.
ADDITIONALLY, ADD A MH NUMBER FOR THE UNDESIGNATED MH
AT THE RETAIL B BUILDING AND DENOTE MH'S 5, 7, 8, 10, 13
AND THE UNDESIGNATED MH AS MMH'S ON THE UTILITY SHEETS.
THE QUANTITIES LIST 22 MH INSERTS; PLEASE CONFIRM. BE
ADVISED THAT MH INSERTS ARE NOT INSTALLED IN MMH'S AND
SHOULD THEREFORE BE REMOVED.
RE: COMMENT #22, ADD A NOTE TO THE PLAN INDICATING
THE PARSONS PMI3SE MANHOLE INSERT W/ VALVE, GASKET, AND
STRAP OR APPROVED EQUAL MUST BE PROVIDED.
THE SPECIFICATIONS REQUIRE SEWER LINES CONSTRUCTED IN
FILL BE CLASS 52 DI PIPE WITH MH'S TO BE "FOUNDED" ON
ORIGINAL GROUND. IT APPEARS MH-6 (UNDESIGNATED ON THE
PROFILE; SHEET C4.5) AND THE SURROUNDING SEWER LINE IS
LOCATED IN FILL; PLEASE REVISE THE MH ACCORDINGLY AND
PROVIDE CLASS 52 DI PIPE BETWEEN MH'S FOR ALL SECTIONS OF
PIPE IN FILL AREAS
PROVIDE A PROFILE OF THE SEWER LINE BETWEEN MH-4 AND
MH-5.
ADD A NOTE TO THE PROFILES STATING THE CONTRACTOR IS TO
MATCH THE CROWN OF THE 6" LATERAL WITH THE CROWN OF THE 8"
SEWER LINE FOR ALL LATERAL-TO-MH CONNECTIONS.
ALL CO'S LOCATED WITHIN PAVED AREAS SHOULD COMPLY
WITH THE ENCLOSED SEW-10 (2 OF 2) TRAFFIC-RATED CO DETAIL.
PLEASE ADD THIS DETAIL TO THE PLAN AND DESIGNATE ALL CO'S
LOCATED IN PAVEMENT THAT ARE ACCESSIBLE TO TRAFFIC AS
"PER SEW-10.
LABEL THE PROPOSED GREASE TRAPS (GT) ON THE UTILITY
SHEETS. ADDITIONALLY, A DETAIL WITH THE SIZE(S) OF THE GRE
TRAPS SHOULD BE ADDED TO THE PLAN.
ADD DEFLECTION ANGLES AT MH-10 AND THE UNDESIGNATED
MH LOCATED BEHIND THE RETAIL B BUILDING.
ADD AN 8" GV TO WATERLINE A ADJACENT TO AND
DOWNSTREAM OF THE TEE AT APPROXIMATELY STA 2+59
(STA 0+00 WATERLINE B).
FOR MAXIMUM FLEXIBILITY, UTILITIES RECOMMENDS ADDING
A GV ADJACENT TO AND DOWNSTREAM OF THE FH TEE AT
APPROXIMATELY STA 3+87 (WATERLINE B).
REMOVE THE VERTICAL TRANSITION AT STA 6+38 (WATERLINE
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
AND INSTALL THE 8" WATERLINE OVER THE TOP OF THE STORM PIP
ALLOWING A 6" MINIMUM CLEARANCE AND USING ONE "STICK" OF
CLASS 52 DI PIPE.
PROVIDE FULLY RESTRAINED CLASS 52 DI PIPE FOR THE
TRANSITIONS AT STA 4+12 (WATERLINE A) AND STA 2+03
(WATERLINE B) PER DETAIL WAT-8 AND ADD THE DI DESIGNATION
AND LIMITS OF RESTRAINT TO THE PROFILES.
PROVIDE A MINIMUM 18" VERTICAL CLEARANCE BETWEEN THE 8"
WATERLINE AND THE PROPOSED SEWER LATERAL AT STA 5+92
(WATERLINE A). IF AN 18" VERTICAL CLEARANCE CANNOT BE ACHI
ONE "STICK" OF CLASS 52 DI PIPE MAY BE USED IF CENTERED OV
THE LATERAL AT THE CROSSING.
LABEL ALL WATERLINE LOCATED IN FILL AS CLASS 52 RESTRAINED
JOINT DI PIPE ON THE PROFILE AND ADD THE REQUIRED RESTRAIN
LENGTH(S) TO THE PLAN.
IT IS RECOMMENDED THAT PDF'S OF ALL REVISIONS BE SUBMITTED
VIA EMAIL FOR INFORMAL REVIEW PRIOR TO FORMAL RESUBMISSION
OF THE PLAN.
PLEASE BE ADVISED THAT ALL PUBLIC WATER AND SEWER LINES
MUST EITHER BE IN RECORDED EASEMENTS OR WITHIN DEDICATED
RIGHTS-OF-WAY PRIOR TO UTILITIES ALLOWING THE CONTRACTOR T
CONNECT THE LINES INTO THE PUBLIC SYSTEMS.
AFTER FINAL SITE PLAN APPROVAL, A TOTAL OF FOUR SETS OF TH
APPROVED PLANS MUST BE SUBMITTED TO THE UTILITIES
DEPARTMENT FOR OUR USE DURING CONSTRUCTION
THE OWNER IS REQUIRED TO ENTER INTO A COUNTY UTILITIES
CONTRACT PRIOR TO THE START OF CONSTRUCTION. PRIOR TO THE
PREPARATION OF THE UTILITIES CONTRACT, UTILITIES MUST BE I
RECEIPT OF THE "ACCEPTED" BID PROPOSAL BETWEEN THE
DEVELOPER AND THE COUNTY APPROVED UTILITIES CONTRACTOR AS
WELL AS THE PROJECT'S INFORMATIONAL SHEET FOUND ON THE
"DEVELOPER'S CHECKLIST". PLEASE SEND THOSE TWO ITEMS TO
THE ATTENTION OF BILL PAYNE (PAYNEW@CHESTERFIELD.GOV OR
BY CALLING 804-751-4336). THE BID PROPOSAL MUST BE BASED
ON THE APPROVED SITE PLAN. BE ADVISED THAT IF THE SITE PLA
REVISED AND REAPPROVED AFTER THE PREPARATION OR RECORDATIO
OF THE UTILITIES CONTRACT, THE BID PROPOSAL SHALL BE REVIS
ACCORDINGLY, AND A REVISED UTILITIES CONTRACT MAY BE
NECESSARY.
ENCL: TYPICAL PLAN VIEW OF PROPOSED 6" OR LARGER FIRE LINE
SYSTEMS DETAIL (EMAIL ATTACHMENT)
FILLABLE MSF
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : SWIFT CREEK PLACE
CASE NUMBER : 18PR0156
LATEST PLAN DATE : 10/26/17
RECEIVED DATE : 11/7/17
SUBMITTAL NUMBER : 1
REVIEW DATE : 11/21/17
ADDRESS : PENDING
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. THE PARCEL BOUNDARY SURVEY DOESN'T CLOSE. THERE ARE
TWO NON-TANGENT CURVES WITHOUT CHORD BEARING AND DISTANCE
INFORMATION. THE DISTANCE FOR S31-13-10E (151.15') IS TOO
LONG.
2. IN THE LAYOUT NOTES ON SHEET C3.0 #10, PLEASE STATE
THE MATERIAL THAT WILL BE USED FOR THE ADDRESS NUMBERS.
==========================================================
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: SWIFT CREEK PLACE
SITE PLAN NUMBER: 18PR0156
ADDRESS: 13439 HULL STREET ROAD
LATEST PLAN DATE: 10/26/17
DEPT. REC'D. DATE: 11/8/17
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 11/13/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. FIRE HYDRANTS SHALL BE LOCATED AT A
MAXIMUM DISTANCE OF 50 FEET BETWEEN HYDRANT
AND FIRE DEPARTMENT CONNECTION FOR ANY
PROPOSED FIRE SPRINKLER SYSTEM OR STANDPIPE
SYSTEM.