Site Plan Review Comments
All Site Plan Review Comments for Case # 18PR0150
Modify comments view for Case # 18PR0150

Go to Case Selection Form or Go to Project List

 
CASE NO: 18PR0150 STATUS: APPROVED - ADMIN
PROJECT NAME: VEOLIA LLC BUILDING - LAST INTERNET UPDATE: 06/18/18
SUBMITTAL TYPE: INDUSTRIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 00 10/25/17 11/15/17 ******** ********
ENVIR.ENGR.-: 01 11/22/17 12/08/17 ******** ********
FIRE DEPT.--: 01 11/22/17 12/08/17 COMPLETE 12/05/17 AWB 717-6167
MAPPING/GIS-: 01 11/22/17 12/08/17 COMPLETE 12/07/17 AMJ 768-7549
PLANNING----: 01 11/22/17 12/08/17 COMPLETE 12/08/17 CH 717-6042
TRANSPORT.--: 01 11/22/17 12/08/17 COMPLETE 12/05/17 SJA 751-4461
UTIL.PLAN.--: 01 11/22/17 12/08/17 ******** ********
UTILITIES---: 01 11/22/17 12/08/17 AMENDED* 12/29/17 LV 748-1863
UTIL.R.O.W.-: 01 11/22/17 12/08/17 ******** ********
VDOT--------: 01 11/22/17 12/08/17 ******** ********
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE #:LINNETTE VASQUEZ, P.E./ 804-748-1863
NAME OF PLAN: VEOLIA BUILDING ADDITION
ADDRESS: 1201 BELLWOOD RD
GPIN#: 799-676-9982 (PART OF)
SUBMISSION DATE: 10/30/17
PLAN DATED: 10/17/17
REVIEW DATE: 11/15/17
SITE NO.: 18PR0150
COMMENTS: 1ST REVIEW NOT APPROVED
1. LABEL ALL ADJACENT PROPERTY OWNERS AND CLEARLY SHOW ALL
PROPERTY LINES AND PROPERTY MARKERS.
*
2. PROVIDE BOXED IN NOTE ON COVER SHEET AND PLAN SHEET THA
" NO NEW WATER OR SEWER FIXTURES ARE PROPOSED WITH THIS
DEVELOPMENT."
*
3. SHOW AND LABEL ALL PRIVATE WATER AND SEWER LINES OR
FACILITIES AND BOTH PLAN AND PROFILE VIEWS AS APPLICABLE.
*
4. PROVIDE CALCULATIONS ENSURING WATER SYSTEM IS DESIGNED
TO MEET REQUIRED FIRE FLOW.
*
5. CLEARLY LABEL LOCATION AND DISTANCE OF THE CLOSEST
PUBLIC FIRE HYDRANT.
*
6. PROJECT NUMBER TO BE ADDED TO PLANS WILL BE PROVIDED TO
ENGINEER.
*
7. NOTE THAT THIS SITE IS LOCATED WHERE ANY NEW PROPOSED
WATER AND/OR SEWER FIXTURES WOULD REQUIRE CONNECTION TO
BOTH COUNTY WATER AND COUNTY SEWER SYSTEMS. THE COUNTY MAY
AUDIT THE FACILITY FOR VERIFICATION OF THIS REQUIREMENT.
*
8. UPDATE SITE DATA NOTE #22 TO LINNETTE VASQUEZ, P.E.
SENIOR ENGINEER 804-748-1863, VASQUEZL@CHESTERFIELD.GO FOR
THE CONTACT INFORMATION.
*
9. PRIOR TO RELEASE TO THE CONSTRUCTION SECTION, A COPY OF
THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER AND /OR ALL
OTHER APPLICABLE LOCAL STATE AND FEDERAL AGENCIES APPROVAL
LETTERS MUST BE RECEIVED BY THE UTILITIES DEPARTMENT.
*
10. AFTER FINAL SITE PLAN APPROVAL, FULL SETS TOTAL OF THE
APPROVED PLAN MUST BE SENT DIRECTLY TO THE UTILITIES
DEPARTMENT FOR STAMPING AND USE DOING CONSTRUCTION
INSPECTION.
**********************************************************
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE #:LINNETTE VASQUEZ, P.E./ 804-748-1863
NAME OF PLAN: VEOLIA BUILDING ADDITION
ADDRESS: 1201 BELLWOOD RD
GPIN#: 799-676-9982 (PART OF)
SUBMISSION DATE: 11/27/17
PLAN DATED: 11/21/17
REVIEW DATE: 12/5/17
SITE NO.: 18PR0150
COMMENTS: 2ND REVIEW NOT APPROVED
TABLE REVIEW: REFER TO COMMENT #5.
*
1. IN REFERENCE TO PREVIOUS COMMENT # 2, REVISE BOXED IN
NOTE ON COVER SHEET AND PLAN SHEET TO READ "NO" INSTEAD OF
"NOW" WATER OR SEWER FIXTURES ARE PROPOSED WITH THIS
DEVELOPMENT."
*
2. IN REFERENCE TO PREVIOUS COMMENT # 3, CLEARLY LABEL
TYPE OF EXISTING MANHOLE SHOWN ON UTILITY PLAN SHEET.
*
4. IN REFERENCE TO PREVIOUS COMMENT # 4, PROVIDE
CALCULATIONS ON PLANS ENSURING WATER SYSTEM IS
DESIGNED TO MEET REQUIRED FIRE FLOW.
*
5. SUBMIT PDF SHEETS AT LEAST ONE WEEK PRIOR TO RESUBMITTA
OR TABLE REVIEW HIGHLIGHTING PROPOSED CHANGES.
*
7. NOTE THAT THIS SITE IS LOCATED WHERE ANY NEW PROPOSED
WATER AND/OR SEWER FIXTURES WOULD REQUIRE CONNECTION TO
BOTH COUNTY WATER AND COUNTY SEWER SYSTEMS. THE COUNTY MAY
AUDIT THE FACILITY FOR VERIFICATION OF THIS REQUIREMENT.
*
9. PRIOR TO RELEASE TO THE CONSTRUCTION SECTION, A COPY OF
THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER AND /OR ALL
OTHER APPLICABLE LOCAL STATE AND FEDERAL AGENCIES APPROVAL
LETTERS MUST BE RECEIVED BY THE UTILITIES DEPARTMENT.
*
10. AFTER FINAL SITE PLAN APPROVAL, FULL SETS TOTAL OF THE
APPROVED PLAN MUST BE SENT DIRECTLY TO THE UTILITIES F THE
DEPARTMENT FOR STAMPING AND USE DOING CONSTRUCTION S
INSPECTION.FOR STAMPING AND USE DOING CONSTRUCTION
INSPECTION.
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: VEOLIA LLC BUILDING ADDITION
SITE PLAN NUMBER: 18PR0150
LATEST PLAN DATE: 10/17/17
DEPT. REC'D. DATE: 10/31/17
SUBMITTAL NUMBER: ONE (HALE)
REVIEW DATE: 11/02/17
RECOMMENDATION: APPROVED
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: VEOLIA LLC BUILDING ADDITION
SITE PLAN NUMBER: 18PR0150
LATEST PLAN DATE: 11/21/17
DEPT. REC'D. DATE: 11/27/17
SUBMITTAL NUMBER: TWO (HALE)
REVIEW DATE: 12/05/17
RECOMMENDATION: APPROVED
==========================================================
==========================================================
**********************************************************
REVIEW DEPARTMENT---------PLANNING
REVIEWER / PHONE #--------CHRIS HALE / (804) 717-6042
NAME OF PLAN--------------VEOLIA LLC BUILDING ADDITION
SITE PLAN NUMBER----------18PR0150
ADDRESS-------------------1201 BELLWOOD ROAD
LATEST PLAN DATE----------10/17/17
DEPT. REC'D. DATE---------10/18/18
SUBMITTAL NUMBER----------1
REVIEW DATE---------------11/09/18
RECOMMENDATION------------NOT APPROVED
TABLE REVIEW--------------YES
PLAT PROCESSING-----------NO
LANDSCAPE PLAN STATUS-----NOT REQUIRED
ARCHITECTURAL ELEVATIONS--NOT PROVIDED
LIGHTING PLAN/CUTSHEETS---NOT REQUIRED
IRRIGATION/HOSEBIB PLAN---NOT REQUIRED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS.
RESUBMIT 10 FULL SETS AND ONE COPY OF THE SITE PLAN
SHEET TO THE PLANNING DEPARTMENT FOR YOUR NEXT REVIEW.
PROVIDE A COMPLETE RESPONSE TO COMMENTS FOR ALL
DEPARTMENTS TO THE PLANNING DEPARTMENT. BELOW EACH
COMMENT DESCRIBE HOW YOU HAVE ADDRESSED EACH REVIEW
COMMENT. INDICATE WHICH SHEETS SHOW THE REQUIRED
CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE ANY
CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
2. PUT THE CHESTERFIELD COUNTY SITE PLAN NUMBER IN THE
LOWER RIGHT CORNER OF EACH SHEET: 18PR0150
3. IF ALL DEPARTMENTS AGREE TO A TABLE REVIEW, THEN YOU
MAY BRING SUBMITTAL PLAN SETS AND THE COMMENT RESPONSE
LETTER (WITH 3 OF THE 10 PLAN SETS HIGHLIGHTED WITH
REVISIONS SINCE THE LAST REVIEW), ALONG WITH THE RECEIPT
FOR THE REVIEW FEE, IF REQUIRED (PAYABLE AT THE FRONT
COUNTER), TO THE TABLE REVIEW MEETING. COORDINATION WITH
DEPARTMENTS NOT APPROVED ON THE LAST REVIEW PRIOR TO THE
TABLE REVIEW IS ADVISABLE.
4. ADD THE OWNER NAME, GPIN, ZONING, AND CURRENT SHOWN
WITHIN THE SITE BOUNDARY ON THE EXISTING CONDITIONS
PLAN.
5. PROVIDE 2 COPIES OF ARCHITECTURAL ELEVATIONS OF THE
BUILDINGS WITH ALL BUILDING MATERIALS AND COLORS
IDENTIFIED.
**********************************************************
REVIEW DEPARTMENT---------PLANNING
REVIEWER / PHONE #--------CHRIS HALE / (804) 717-6042
NAME OF PLAN--------------VEOLIA LLC BUILDING ADDITION
SITE PLAN NUMBER----------18PR0150
ADDRESS-------------------1201 BELLWOOD ROAD
LATEST PLAN DATE----------11/21/17
DEPT. REC'D. DATE---------11/22/17
SUBMITTAL NUMBER----------2 (EXPEDITED)
REVIEW DATE---------------12/08/17
RECOMMENDATION------------SUBSTANTIAL APPROVAL
TABLE REVIEW--------------YES
PLAT PROCESSING-----------NO
LANDSCAPE PLAN STATUS-----NOT REQUIRED
ARCHITECTURAL ELEVATIONS--NOT PROVIDED
LIGHTING PLAN/CUTSHEETS---NOT REQUIRED
IRRIGATION/HOSEBIB PLAN---NOT REQUIRED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS.
RESUBMIT 10 FULL SETS AND ONE COPY OF THE SITE PLAN
SHEET TO THE PLANNING DEPARTMENT FOR YOUR NEXT REVIEW.
PROVIDE A COMPLETE RESPONSE TO COMMENTS FOR ALL
DEPARTMENTS TO THE PLANNING DEPARTMENT. BELOW EACH
COMMENT DESCRIBE HOW YOU HAVE ADDRESSED EACH REVIEW
COMMENT. INDICATE WHICH SHEETS SHOW THE REQUIRED
CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE ANY
CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
2. IF ALL DEPARTMENTS AGREE TO A TABLE REVIEW, THEN YOU
MAY BRING SUBMITTAL PLAN SETS AND THE COMMENT RESPONSE
LETTER (WITH 3 OF THE 10 PLAN SETS HIGHLIGHTED WITH
REVISIONS SINCE THE LAST REVIEW), ALONG WITH THE RECEIPT
FOR THE REVIEW FEE, IF REQUIRED (PAYABLE AT THE FRONT
COUNTER), TO THE TABLE REVIEW MEETING. COORDINATION WITH
DEPARTMENTS NOT APPROVED ON THE LAST REVIEW PRIOR TO THE
TABLE REVIEW IS ADVISABLE.
3. PROVIDE 2 COPIES OF ARCHITECTURAL ELEVATIONS OF THE
BUILDINGS WITH ALL BUILDING MATERIALS AND COLORS
IDENTIFIED.
**********************************************************
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : VEOLIA LLC BUILDING ADDITION
CASE NUMBER : 18PR0150
LATEST PLAN DATE : 10/17/17
RECEIVED DATE : 11/1/17
SUBMITTAL NUMBER : 1
REVIEW DATE : 11/14/17
ADDRESS : PENDING
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. COORDINATE POINTS BASED ON THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, NORTH AMERICAN DATUM
1983 ARE NOT PRESENT. TWO POINTS MUST BE SHOWN ON THE
PARCEL BOUNDARY.
2. THE PARCEL BOUNDARY SURVEY IS MISSING. PLEASE
SUPPLY THE METES AND BOUNDS FOR EVERY SEGMENT ALONG THE
TRAVERSE TO INCLUDE CHORD BEARING AND DISTANCE FOR ALL
NON-TANGENT CURVES. IF THE PARCEL IS TOO LARGE TO
CONVENIENTLY FIT ON ONE SHEET, A LARGER SCALE DRAWING
OF THE BOUNDARY IS ACCEPTABLE.
3. IF THE ADDRESS IS TO BE ON THE BUILDING, YOU MUST
SHOW WHERE IT WILL BE LOCATED ON THE BUILDING AND WHAT
IT WILL BE MADE OF. IF THE ADDRESS IS TO BE ON A SIGN,
YOU MUST SHOW WHERE IT WILL BE LOCATED ON THE PROPERTY
AND WHAT IT WILL BE MADE OF.
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : VEOLIA LLC BUILDING ADDITION
CASE NUMBER : 18PR0150
LATEST PLAN DATE : 11/21/17
RECEIVED DATE : 11/30/17
SUBMITTAL NUMBER : 2
REVIEW DATE : 12/7/17
ADDRESS : 1201 BELLWOOD RD
STATUS : APPROVED
==========================================================
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: VEOLIA LLC BUILDING ADDITION
SITE PLAN NUMBER: 18PR0150
ADDRESS: 1201 BELLWOOD ROAD
LATEST PLAN DATE: 10/17/17
DEPT. REC'D. DATE: 10/31/17
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 11/2/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. THE FOLLOWING NOTE SHALL BE ADDED TO THE GENERAL
NOTES ON PLANS:
"AN APPROVED KEY BOX SHALL BE PROVIDED FOR THE PROPOSED
BUILDING IN ACCORDANCE WITH THE INTERNATIONAL FIRE CODE,
SECTION 506.1 THE REQUIRED FORMS AND INSTALLATION
INSTRUCTIONS FOR THE KEY BOX CAN BE OBTAINED FROM
CHESTERFIELD FIRE AND EMS, FIRE AND LIFE SAFETY DIVISION,
AT 748-1426."
2. PROVIDE COMPUTER GENERATED WATER FLOW TEST DATA,
PROVIDED BY THE CHESTERFIELD COUNTY UTILITIES
DEPARTMENT, VERIFYING THE REQUIRED WATER FLOW FOR FIRE
PROTECTION IS AVAILABLE AT THE SITE. THE WATERFLOW TEST
RESULTS AND GRAPH SHALL BE SHOWN ON THE SUBMITTED PLAN.
THE MINIMUM REQUIRED FIRE FLOW FOR ALL BUILDINGS, WITH
THE EXCEPTION OF ONE AND TWO-FAMILY DWELLINGS, IS 1500
GPM (SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED) IN
ACCORDANCE WITH THE INTERNATIONAL FIRE CODE (2012) -
SECTION B105.2 AND TABLE B105.1.
3. THE SUBMITTED PLAN SHALL CLEARLY INDICATE THE LOCATION
ALL REQUIRED FIRE HYDRANTS.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: VEOLIA LLC BUILDING ADDITION
SITE PLAN NUMBER: 18PR0150
ADDRESS: 1201 BELLWOOD ROAD
LATEST PLAN DATE: 11/21/17
DEPT. REC'D. DATE: 11/30/17
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 12/5/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. PROVIDE COMPUTER GENERATED WATER FLOW TEST DATA,
PROVIDED BY THE CHESTERFIELD COUNTY UTILITIES
DEPARTMENT, VERIFYING THE REQUIRED WATER FLOW FOR FIRE
PROTECTION IS AVAILABLE AT THE SITE. THE WATERFLOW TEST
RESULTS AND GRAPH SHALL BE SHOWN ON THE SUBMITTED PLAN.
THE MINIMUM REQUIRED FIRE FLOW FOR ALL BUILDINGS, WITH
THE EXCEPTION OF ONE AND TWO-FAMILY DWELLINGS, IS 1500
GPM (SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED) IN
ACCORDANCE WITH THE INTERNATIONAL FIRE CODE (2012) -
SECTION B105.2 AND TABLE B105.1.

Modify comments view for case # 18PR0150