Site Plan Review Comments
All Site Plan Review Comments for Case # 18PR0150
Modify comments view for Case # 18PR0150

Go to Case Selection Form or Go to Project List

 
CASE NO: 18PR0150 STATUS: PENDING APPROVAL
PROJECT NAME: VEOLIA LLC BUILDING - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: INDUSTRIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 00 10/25/17 11/15/17 ******** ********
ENVIR.ENGR.-: 00 10/25/17 11/15/17 ******** ********
FIRE DEPT.--: 00 10/25/17 11/15/17 COMPLETE 11/02/17 AWB 717-6167
MAPPING/GIS-: 00 10/25/17 11/15/17 COMPLETE 11/14/17 AMJ 768-7549
PLANNING----: 00 10/25/17 11/15/17 COMPLETE 11/09/17 CH 717-6042
TRANSPORT.--: 00 10/25/17 11/15/17 DRAFTING ******** SJA 751-4461
UTIL.PLAN.--: 00 10/25/17 11/15/17 ******** ********
UTILITIES---: 00 10/25/17 11/15/17 ******** ********
UTIL.R.O.W.-: 00 10/25/17 11/15/17 ******** ********
VDOT--------: 00 10/25/17 11/15/17 ******** ********
**********************************************************
REVIEW DEPARTMENT---------PLANNING
REVIEWER / PHONE #--------CHRIS HALE / (804) 717-6042
NAME OF PLAN--------------VEOLIA LLC BUILDING ADDITION
SITE PLAN NUMBER----------18PR0150
ADDRESS-------------------1201 BELLWOOD ROAD
LATEST PLAN DATE----------10/17/17
DEPT. REC'D. DATE---------10/18/18
SUBMITTAL NUMBER----------1
REVIEW DATE---------------11/09/18
RECOMMENDATION------------NOT APPROVED
TABLE REVIEW--------------YES
PLAT PROCESSING-----------NO
LANDSCAPE PLAN STATUS-----NOT REQUIRED
ARCHITECTURAL ELEVATIONS--NOT PROVIDED
LIGHTING PLAN/CUTSHEETS---NOT REQUIRED
IRRIGATION/HOSEBIB PLAN---NOT REQUIRED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS.
RESUBMIT 10 FULL SETS AND ONE COPY OF THE SITE PLAN
SHEET TO THE PLANNING DEPARTMENT FOR YOUR NEXT REVIEW.
PROVIDE A COMPLETE RESPONSE TO COMMENTS FOR ALL
DEPARTMENTS TO THE PLANNING DEPARTMENT. BELOW EACH
COMMENT DESCRIBE HOW YOU HAVE ADDRESSED EACH REVIEW
COMMENT. INDICATE WHICH SHEETS SHOW THE REQUIRED
CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE ANY
CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
2. PUT THE CHESTERFIELD COUNTY SITE PLAN NUMBER IN THE
LOWER RIGHT CORNER OF EACH SHEET: 18PR0150
3. IF ALL DEPARTMENTS AGREE TO A TABLE REVIEW, THEN YOU
MAY BRING SUBMITTAL PLAN SETS AND THE COMMENT RESPONSE
LETTER (WITH 3 OF THE 10 PLAN SETS HIGHLIGHTED WITH
REVISIONS SINCE THE LAST REVIEW), ALONG WITH THE RECEIPT
FOR THE REVIEW FEE, IF REQUIRED (PAYABLE AT THE FRONT
COUNTER), TO THE TABLE REVIEW MEETING. COORDINATION WITH
DEPARTMENTS NOT APPROVED ON THE LAST REVIEW PRIOR TO THE
TABLE REVIEW IS ADVISABLE.
4. ADD THE OWNER NAME, GPIN, ZONING, AND CURRENT SHOWN
WITHIN THE SITE BOUNDARY ON THE EXISTING CONDITIONS
PLAN.
5. PROVIDE 2 COPIES OF ARCHITECTURAL ELEVATIONS OF THE
BUILDINGS WITH ALL BUILDING MATERIALS AND COLORS
IDENTIFIED.
**********************************************************
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : VEOLIA LLC BUILDING ADDITION
CASE NUMBER : 18PR0150
LATEST PLAN DATE : 10/17/17
RECEIVED DATE : 11/1/17
SUBMITTAL NUMBER : 1
REVIEW DATE : 11/14/17
ADDRESS : PENDING
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. COORDINATE POINTS BASED ON THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, NORTH AMERICAN DATUM
1983 ARE NOT PRESENT. TWO POINTS MUST BE SHOWN ON THE
PARCEL BOUNDARY.
2. THE PARCEL BOUNDARY SURVEY IS MISSING. PLEASE
SUPPLY THE METES AND BOUNDS FOR EVERY SEGMENT ALONG THE
TRAVERSE TO INCLUDE CHORD BEARING AND DISTANCE FOR ALL
NON-TANGENT CURVES. IF THE PARCEL IS TOO LARGE TO
CONVENIENTLY FIT ON ONE SHEET, A LARGER SCALE DRAWING
OF THE BOUNDARY IS ACCEPTABLE.
3. IF THE ADDRESS IS TO BE ON THE BUILDING, YOU MUST
SHOW WHERE IT WILL BE LOCATED ON THE BUILDING AND WHAT
IT WILL BE MADE OF. IF THE ADDRESS IS TO BE ON A SIGN,
YOU MUST SHOW WHERE IT WILL BE LOCATED ON THE PROPERTY
AND WHAT IT WILL BE MADE OF.
==========================================================
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: VEOLIA LLC BUILDING ADDITION
SITE PLAN NUMBER: 18PR0150
ADDRESS: 1201 BELLWOOD ROAD
LATEST PLAN DATE: 10/17/17
DEPT. REC'D. DATE: 10/31/17
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 11/2/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. THE FOLLOWING NOTE SHALL BE ADDED TO THE GENERAL
NOTES ON PLANS:
"AN APPROVED KEY BOX SHALL BE PROVIDED FOR THE PROPOSED
BUILDING IN ACCORDANCE WITH THE INTERNATIONAL FIRE CODE,
SECTION 506.1 THE REQUIRED FORMS AND INSTALLATION
INSTRUCTIONS FOR THE KEY BOX CAN BE OBTAINED FROM
CHESTERFIELD FIRE AND EMS, FIRE AND LIFE SAFETY DIVISION,
AT 748-1426."
2. PROVIDE COMPUTER GENERATED WATER FLOW TEST DATA,
PROVIDED BY THE CHESTERFIELD COUNTY UTILITIES
DEPARTMENT, VERIFYING THE REQUIRED WATER FLOW FOR FIRE
PROTECTION IS AVAILABLE AT THE SITE. THE WATERFLOW TEST
RESULTS AND GRAPH SHALL BE SHOWN ON THE SUBMITTED PLAN.
THE MINIMUM REQUIRED FIRE FLOW FOR ALL BUILDINGS, WITH
THE EXCEPTION OF ONE AND TWO-FAMILY DWELLINGS, IS 1500
GPM (SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED) IN
ACCORDANCE WITH THE INTERNATIONAL FIRE CODE (2012) -
SECTION B105.2 AND TABLE B105.1.
3. THE SUBMITTED PLAN SHALL CLEARLY INDICATE THE LOCATION
ALL REQUIRED FIRE HYDRANTS.