Site Plan Review Comments
All Site Plan Review Comments for Case # 18PR0133
Modify comments view for Case # 18PR0133

Go to Case Selection Form or Go to Project List

 
CASE NO: 18PR0133 STATUS: PENDING APPROVAL
PROJECT NAME: IVYMONT SQUARE PARCE - LAST INTERNET UPDATE: 02/23/18
SUBMITTAL TYPE: COMMERCIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 01 12/04/17 12/28/17 ******** ********
ENVIR.ENGR.-: 01 12/04/17 12/28/17 ******** ********
FIRE DEPT.--: 01 12/04/17 12/28/17 COMPLETE 12/14/17 AWB 717-6167
MAPPING/GIS-: 01 12/04/17 12/28/17 COMPLETE 12/11/17 AMJ 768-7549
PLANNING----: 01 12/04/17 12/28/17 COMPLETE 02/06/18 JHL 751-4158
TRANSPORT.--: 01 12/04/17 12/28/17 COMPLETE 12/13/17 SJA 751-4461
UTIL.PLAN.--: 01 12/04/17 12/28/17 ******** ********
UTILITIES---: 01 12/04/17 12/28/17 AMENDED* 12/29/17 LV 748-1863
UTIL.R.O.W.-: 01 12/04/17 12/28/17 ******** ********
VDOT--------: 01 12/04/17 12/28/17 ******** ********
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : LINNETTE VASQUEZ, P.E./748-1863
NAME OF PLAN : IVYMONT SQUARE - PARCEL B RETAIL
ADDRESS : 114161 MIDLOTHIAN TPKE
GPIN : 725-708-1077
SUBMISSION DATE : 10/6/17
PLAN DATED : 9/29/17
REVIEW DATE : 10/25/17
SITE PLAN NO. : 18PR0133
UTILTIES PROJ.NO.: 17-0218
COMMENTS : 1ST REVIEW-NOT APPROVED
TABLE REVIEW : NO
PLAT PROCESS :
1. UTILITIES PROJECT 17-0218 NUMBER SHALL BE PLACED ON
THE LOWER RIGHT HAND CORNER OF EACH SHEET.
*
2. ON VICINITY MAP SHOW MORE DETAIL AND PROVIDE LABEL FOR
CLOSEST CROSS STREET.
*
3. SHOW AND LABEL LOCATION OF BENCHMARK.
*
4. UPDATE MATERIALS LIST AS APPLICABLE PER COMMENTS.
*
5. UPDATE SHEET NAME FOR C6.0 TO INCLUDED UTILITIES OR
MOVE LEGEND TO UTILITIES NOTES AND DETAILS SHEET C6.1.
*
6. ADD CHESTERFIELD UTILITIES CONTACT OF LINNETTE D.
VASQUEZ, PE PHONE: (804)748-1863, EMAIL:
VASQUEZL@CHESTERFIELD.GOV
*
7. ADD DES-2 DETAIL AND REMOVE DETAIL MET-2. ON NOTE #4
OF DES-2 ADD "AT OR BELOW" 349 FEET". INDICATE IF A PRV
WOULD BE REQUIRED ON PLANS.
*
8. SUBMIT SIGNED ENGINEERS CHECKLIST PER APP-4-1 IN PART
1 OF CHESTERFIELD COUNTY WATER AND SEWER SPECIFICATIONS.
*
9. NO STRUCTURES CAN BE PROPOSED IN AN EXISTING WATER
AND/OR SEWER EASEMENT. MOVE STORM STRUCTURE #15 OUTSIDE OF
THE EASEMENT.
*
10. REVISE LAYOUT OF PRIVATE WATERLINE TO NOT CROSS PUBLIC
SEWER LINE.
*
11. LABEL ALL EXISTING WATERLINES WITH SIZE, MATERIAL, AND
COUNTY PROJECT # ON PLAN AND PROFILE VIEWS.
*
12. SHOW AND LABEL ALL EXISTING WATER FITTINGS, FIRE
HYDRANTS, VALVES, AND FLUSHING HYDRANTS INCLUDING SIZES ON
PLAN AND PROFILE SHEETS.
*
13. NOTE THAT ALL PUBLIC WATER/SEWER LINES MUST EITHER BE
IN A RECORDED EASEMENT OR DEDICATED RIGHT OF WAY PRIOR TO
ACCEPTANCE BY UTILITIES.
*
14. VERIFY THAT ALL EXISTING HOUSES, BUILDINGS, FENCES,
WELLS AND OTHER STRUCTURES ARE SHOWN ON PLANS. IN LAWN OR
KEPT AREAS TREES AND SHRUBS IN THE EASEMENTS ARE SHOWN
(SIZE AND TYPE).
*
15. SHOW AND LABEL LOCATION AND DIMENSION OF ALL EXISTING
IF APPLICABLE WATER AND SEWER SERVICE CONNECTIONS.
*
16. PLEASE RESPOND IF THERE WILL BE ANY PROPOSED
IRRIGATION FOR THIS SITE.
*
17. SHOW AND LABEL WATER METERS AND PROPOSED HYDRANT A
MINIMUM OF 3 FEET BEHIND THE FACE OF CURB.
*
18. LABEL ALL PROPOSED EASEMENTS AROUND HYDRANTS.
*
19. IT IS RECOMMENDED THAT WATER SERVICE LINES FOR
COMMERCIAL PROJECTS TO BE SIZED ONE NORMAL DIMENSION
GREATER THAN THE PROPOSED METER TO ALLOW FOR FUTURE METER
UPSIZING WITHOUT REPLACING THE SERVICE LINE BACK TO THE
MAIN. FOR THIS PROJECT IT IS RECOMMENDED TO HAVE A 1 ½" OR
2" SERVICE LINE DEPENDING ON YOUR METER SIZE.
*
20. PROVIDE FIRE CALCULATIONS ON PLANS TO ENSURE WATER
SYSTEM IS IN ACCORDANCE WITH AVAILABLE PRESSURES AND THE
REQUIRED FIRE FLOW IS AVAILABLE.
*
21. LABEL THE VALVE TO BE USED FOR CUT OFF DURING THE TIE-
IN. THE ADJACENT PROPERTY AT 14201 IS A WATER DEPENDENT
CUSTOMER. SERVICE CANNOT BE CUT OFF UNTIL CUSTOMER IS
NOTIFIED.
*
22. PROVIDE WITH RESPONSE TO THIS COMMENT THE EXPECTED USE
OF THE PROPOSED BUILDING. IF A RESTAURANT MAY BE PROPOSED
SEWER MONITORING MANHOLE WILL BE REQUIRED. SHOW AND LABEL
ON PLANS AND ADD DETAIL MAN-17 TO PLANS.
*
23. PROVIDE PROFILES FOR ALL PROPOSED WATER LINES 6" AND
LARGER.
*
24. LABEL PRIVATE LINES ON UTILITY PLAN.
*
25. UPDATE METER SIZING FORM TO INCLUDE UTILITIES PROJ.
#17-0218, SIGN, AND INCLUDE PHONE NUMBER. ENSURE THAT THE
METER SIZING FORM ACCOUNTS FOR WORST CASE SCENARIO OF
POSSIBLE TENANTS. PROVIDE FORM ON PLANS AND SEPARATE
ATTACHMENT.
*
26. LABEL ALL EXISTING SEWER LINES SIZE, MATERIAL AND
COUNTY PROJECT # ON PLAN AND PROFILE VIEWS.
*
27. THE OWNER SHALL BE REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
PRIOR TO THE PREPARATION OF THE UTILITIES CONTRACT,
UTILITIES MUST BE IN RECEIPT OF THE "ACCEPTED" BID PROPOSA
BETWEEN THE DEVELOPER AND THE COUNTY APPROVED UTILITIES
CONTRACTOR AS WELL AS THE PROJECT'S INFORMATIONAL SHEET
FOUND ON THE "DEVELOPER'S CHECKLIST". PLEASE SEND THOSE TW
ITEMS TO THE ATTENTION OF LINNETTE VASQUEZ
(VASQUEZL@CHESTERFIELD.GOV). THE BID PROPOSAL
MUST BE BASED ON THE APPROVED SITE PLAN. BE ADVISED THAT I
THE SITE PLAN IS REVISED AND REAPPROVED SUBSEQUENT TO THE
PREPARATION OR RECORDATION OF THE UTILITIES CONTRACT, THE
BID PROPOSAL SHALL BE REVISED ACCORDINGLY AND A REVISED
UTILITIES CONTRACT MAY BE NECESSARY.
*
28. AFTER FINAL SITE PLAN APPROVAL, SUBMIT ONE ADDITIONAL
SET OF APPROVED PLANS DIRECTLY TO THE UTILITIES DEPARTMENT
FOR OUR USE DURING CONSTRUCTION INSPECTION. THIS IS IN
ADDITION TO THE ONE APPROVED SET FROM PLANNING (4 TOTAL
SETS).
**********************************************************
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : LINNETTE VASQUEZ, P.E./748-1863
NAME OF PLAN : IVYMONT SQUARE - PARCEL B RETAIL
ADDRESS : 114161 MIDLOTHIAN TPKE
GPIN : 725-708-1077
SUBMISSION DATE : 12/6/17
PLAN DATED : 12/1/17
REVIEW DATE : 12/28/2017
SITE PLAN NO. : 18PR0133
UTILTIES PROJ.NO.: 17-0218
COMMENTS : 2ND REVIEW-NOT APPROVED
TABLE REVIEW : REFER TO COMMENT # 15
PLAT PROCESS :
*
1. UPDATE MATERIALS LIST AS APPLICABLE PER COMMENTS.
*
2. IN REFERENCE TO PREVIOUS COMMENT # 7, INDICATE IF A
PRV WOULD BE REQUIRED ON PLANS.
*
3. IN REFERENCE TO PREVIOUS COMMENT # 9, NO STRUCTURES
MAY BE PROPOSED IN ANY EXISTING OR PROPOSED WATER OR SEWER
EASEMENT WITHOUT A LICENSE AGREEMENT. THIS INCLUDES ALL
SIGNS, CURB AND GUTTER, PARKING ISLANDS, ETC. PLEASE
CONTACT JOAN COURSON AT 804-748-1362 AND/OR
COURSONJ@CHESTERFIELD.GOV FOR ANY QUESTIONS CONCERNING
OBTAINING A LICENSE.
*
4. IN REFERENCE TO PREVIOUS COMMENT # 10, MOVE THE
DOMESTIC METER SERVICE FROM CONNECTING ON THE FIRE HYDRANT
LINE. SUBMIT IN A PDF A PROPOSED LAYOUT. REFER TO COMMENT
#15.
*
5. IN REFERENCE TO PREVIOUS COMMENT # 11, CLEARLY LABEL
ALL LINE SIZES, MATERIAL, AND COUNTY PROJECT # FOR
WATERLINE CONNECTING TO FIRE HYDRANT. LINE SIZING CHANGES
FROM 8" TO 6". SHOW AND LABEL LINE ON EXISTING CONDITIONS
SHEET AND UTILITY PLAN SHEET.
*
6. IN REFERENCE TO PREVIOUS COMMENT #12, SHOW AND LABEL
ALL EXISTING WATER FITTINGS AND VALVES INCLUDING SIZES ON
PLAN AND PROFILE SHEETS. THERE IS AN EXISTING REDUCER AND
6" GATE VALVE NEAR FIRE HYDRANT LINE.
*
7. IN REFERENCE TO PREVIOUS COMMENT # 17, PROVIDE LABEL
FOR WATER METERS AND PROPOSED HYDRANT OF DISTANCE BEHIND
PROPOSED FACE OF CURB. A MINIMUM OF 3 FEET BEHIND THE FAC
OF CURB IS REQUIRED.
*
8. IN REFERENCE TO PREVIOUS COMMENT # 18, LABEL THE END
OF WATERLINE EASEMENT AROUND PROPOSED HYDRANT TO CLEARLY
SHOW END OF THE LIMITS OF THE EASEMENT IN RELATION TO
PROPOSED HYDRANT.
*
9. IN REFERENCE TO PREVIOUS COMMENT #19, IT IS
RECOMMENDED THAT WATER SERVICE LINES FOR
COMMERCIAL PROJECTS TO BE SIZED ONE NORMAL DIMENSION
GREATER THAN THE PROPOSED METER TO ALLOW FOR FUTURE METER
UPSIZING WITHOUT REPLACING THE SERVICE LINE BACK TO THE
MAIN. FOR THIS PROJECT IT IS RECOMMENDED TO HAVE A 1 ½" OR
2" SERVICE LINE FROM THE MAIN PUBLIC WATERLINE TO THE METE
DEPENDING ON YOUR METER SIZE.
*
10. IN REFERENCE TO PREVIOUS COMMENT # 21, INDICATE
LOCATION OF LABEL FOR THE VALVE TO BE USED FOR CUT OFF
DURING TIE-IN. THE ADJACENT PROPERTY AT 14201 IS A WATER
DEPENDENT CUSTOMER. SERVICE CANNOT BE CUT OFF UNTIL
CUSTOMER IS NOTIFIED.
*
11. IN REFERENCE TO PREVIOUS COMMENT # 22, LABEL AT
MONITORING MANHOLE FOR TOP STEP TO BE REMOVED. REFERENCE
LOCATION OF DETAIL MAN-17 ON UTILITY PLAN SHEET. VERIFY
INFORMATION HAS BEEN FIELD VERIFIED.
*
12. IN REFERENCE TO PREVIOUS COMMENT 23, PLEASE INDICATE
IF THE FIRE HYDRANT HAS TO BE RELOCATED AS SHOWN IN THE
WATERLINE PROFILE OR IF IT CAN REMAIN AT ITS EXISTING
LOCATION. IS THE SAME EXISTING HYDRANT BEING UTILIZED?
*
13. IN REFERENCE TO PREVIOUS COMMENT # 25, PROVIDE
SEPARATE ATTACHMENT OF WATER METER FORMS.
*
14. IN REFERENCE TO PREVIOUS COMMENT #26, DARKEN OR MOVE
INFORMATION LABEL FOR MONITORING MANHOLE TO BE CLEARLY
LEGIBLE. MOVE NOTE TO ADJUST TOP ELEVATION CLOSE TO
EXISTING INFORMATION NOTE.
*
15. PROVIDE A PDF WITH A DRAFT OF PROPOSED CHANGES
HIGHLIGHTED PRIOR TO RESUBMITTAL TO
VASQUEZL@CHESTERFIED.GOV IN ORDER TO VERIFY THAT ALL
COMMENTS HAVE BEEN ADDRESSED. IF REQUESTING TABLE REVIEW
PROVIDE DRAFT AT LEAST ONE WEEK PRIOR TO SCHEDULED MEETING
PLEASE CALL WITH ANY QUESTIONS AT 804-748-1863.
*
16. THE OWNER SHALL BE REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
PRIOR TO THE PREPARATION OF THE UTILITIES CONTRACT,
UTILITIES MUST BE IN RECEIPT OF THE "ACCEPTED" BID PROPOSA
BETWEEN THE DEVELOPER AND THE COUNTY APPROVED UTILITIES
CONTRACTOR AS WELL AS THE PROJECT'S INFORMATIONAL SHEET
FOUND ON THE "DEVELOPER'S CHECKLIST". PLEASE SEND THOSE TW
ITEMS TO THE ATTENTION OF LINNETTE VASQUEZ
(VASQUEZL@CHESTERFIELD.GOV). THE BID PROPOSAL
MUST BE BASED ON THE APPROVED SITE PLAN. BE ADVISED THAT I
THE SITE PLAN IS REVISED AND REAPPROVED SUBSEQUENT TO THE
PREPARATION OR RECORDATION OF THE UTILITIES CONTRACT, THE
BID PROPOSAL SHALL BE REVISED ACCORDINGLY AND A REVISED
UTILITIES CONTRACT MAY BE NECESSARY.
*
17. AFTER FINAL SITE PLAN APPROVAL, SUBMIT ONE ADDITIONAL
SET OF APPROVED PLANS DIRECTLY TO THE UTILITIES DEPARTMENT
FOR OUR USE DURING CONSTRUCTION INSPECTION. THIS IS IN
ADDITION TO THE ONE APPROVED SET FROM PLANNING (4 TOTAL
SETS).
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: IVYMONT SQUARE PARCEL B RETAIL
SITE PLAN NUMBER: 18PR0133
LATEST PLAN DATE: 10/02/17
DEPT. REC'D. DATE: 10/10/17
SUBMITTAL NUMBER: ONE (MORRISON)
REVIEW DATE: 10/11/17
RECOMMENDATION: APPROVED
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: IVYMONT SQUARE PARCEL B RETAIL
SITE PLAN NUMBER: 18PR0133
LATEST PLAN DATE: 12/01/17
DEPT. REC'D. DATE: 12/06/17
SUBMITTAL NUMBER: TWO (MORRISON)
REVIEW DATE: 12/13/17
RECOMMENDATION: APPROVED
==========================================================
==========================================================
REVIEWER / PHONE #-----JEFF LAMSON
NAME OF PLAN-----------IVYMONT SQUARE - PARCEL B RETAIL
SITE PLAN NUMBER-------18PR0133
ADDRESS----------------14161 MIDLOTHIAN TURNPIKE
LATEST PLAN DATE-------12-1-17
DEPT. REC'D. DATE------12-1-17
SUBMITTAL NUMBER-------TWO
REVIEW DATE------------1-23-18
RECOMMENDATION---------REVISION REQUESTED
TABLE REVIEW-----------NO
PLAT PROCESSING--------
LANDSCAPE PLAN STATUS-- SEE COMMENTS
ARCHITECTURAL ELEVATIONS--NOT YET SUBMITTED
LIGHTING PLAN/CUTSHEETS---NOT YET SUBMITTED
IRRIGATION/HOSEBIB PLAN---HOSE BIBS APPROVED
.
.
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT
10 FULL SETS AND ONE COPY OF THE SITE PLAN SHEET TO THE
PLANNING DEPARTMENT FOR YOUR NEXT REVIEW. PROVIDE A COMPLE
RESPONSE TO COMMENTS FOR ALL DEPARTMENTS TO THE PLANNING
DEPARTMENT.
BELOW EACH COMMENT TO DESCRIBE HOW YOU HAVE ADDRESSED EACH
REVIEW COMMENT. BE SURE TO INDICATE WHICH SHEETS SHOW THE
REQUIRED CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE
ANY CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
.
2. (4.) PROVIDE DB AND PG OF CROSS ACCESS AND PARKING EASE
AGREEMENT
.
3. PROVIDE COPY OF AGREEMENT WITH ADJACENT PROPERTY OWNER
LOCATE AND MAINTAIN PROPOSED REQUIRED PARKING LOT TREES ON
ADJACENT PROPERTY.
.
4. (14.) PER SEC. 19.1-205, SHOW ON THE LANDSCAPE PLAN OR
ADDITIONALLY ON A SEPARATE LIGHTING PLAN THE LOCATION OF A
EXTERIOR SITE LIGHTING MOUNTED ON POLES, THE BUILDING, OR
ON THE GROUND AND HAVE THEM KEYED TO CUT SHEETS FOR EACH
LIGHT FIXTURE SHOWN ON THE PLAN.
.
PROVIDE COPY OF LIGHT FIXTURE CATALOGUE SHEET.
.
5. (15.) PER SEC. 19.1-317 A, B, PROVIDE 2 COPIES OF
RENDERINGS/ELEVATIONS OF THE BUILDINGS WITH ALL BUILDING
MATERIALS AND COLORS IDENTIFIED, LOCATIONS OF JUNCTION AND
ACCESS BOXES SHOWN, AND HOW ALL MECHANICAL
EQUIPMENT IS SCREENED WHETHER IT IS MOUNTED ON THE ROOF
OR ON THE GROUND.
.
6. (16.) 1-317 A, B ARCHITECTURAL COMPATIBILITY IS REQUIRE
BETWEEN BUILDINGS WITHIN THE PROJECT.
.
7. (17.) PER SEC. 19.1-317.C., SHOW THAT JUNCTION AND ACCE
BOXES ARE EITHER SCREENED OR PAINTED TO MATCH THE BUILDING
EXCEPT AS ALLOWED IN I-2 AND I-3 DISTRICTS.
.
8. (18.) PER SEC. 19.1-317.D., MECHANICAL EQUIPMENT, WHETH
ROOF-TOP OR GROUND LEVEL, SHALL BE SHIELDED AND SCREENED
FROM PUBLIC VIEW AND DESIGNED TO BE PERCEIVED AS AN
INTEGRAL PART OF THE BUILDING EXCEPT AS ALLOWED IN I-2 AND
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : IVYMONT SQUARE PARCEL B RETAIL
CASE NUMBER : 18PR0133
LATEST PLAN DATE : 10/2/17
RECEIVED DATE : 10/9/17
SUBMITTAL NUMBER : 1
REVIEW DATE : 10/25/17
ADDRESS : ASSIGNED IN COMMENTS
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. STREET ADDRESS LOCATIONS ARE NOT SHOWN. THEY CAN BE
LOCATED ON THE BUILDING, ON A SIGN OR AS A PART OF A
MONUMENT SIGN. LOCATION AND MATERIAL USED MUST BE NOTED
ON THE SITE PLAN. IF YOU ARE USING A MONUMENT SIGN, A
DETAIL OF THE MONUMENT SIGN MUST BE ON THE SITE PLAN.
2. ADDRESSES WILL BE AS FOLLOWS, FROM EAST TO WEST, FOR
EACH ENTRANCE: 14161, 14163, 14165, 14167, 14169,
14171, 14173 MIDLOTHIAN TPKE.
==========================================================
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON (N) 768-7549
PROJECT NAME : IVYMONT SQUARE PARCEL B RETAIL
CASE NUMBER : 18PR0133
LATEST PLAN DATE : 12/1/17
RECEIVED DATE : 12/6/17
SUBMITTAL NUMBER : 2
REVIEW DATE : 12/11/17
ADDRESS : ASSIGNED IN COMMENTS
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. I SEE THE DESIGN OF THE ADDRESS SIGN BUT I DO NOT SEE
A LOCATION OF WHERE THE ADDRESS SIGN WILL BE. PLEASE
SHOW THE LOCATION OF THE ADDRESSES.
2. ADDRESSES WILL BE AS FOLLOWS, FROM EAST TO WEST, FOR
EACH ENTRANCE: 14161, 14163, 14165, 14167, 14169,
14171, 14173 MIDLOTHIAN TPKE.
==========================================================
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: IVYMONT SQUARE PARCEL B RETAIL
SITE PLAN NUMBER: 18PR0133
ADDRESS: 14161 MIDLOTHIAN TURNPIKE
LATEST PLAN DATE: 10/2/17
DEPT. REC'D. DATE: 10/12/17
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 10/16/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. PROVIDE COMPUTER GENERATED WATER FLOW TEST DATA,
PROVIDED BY THE CHESTERFIELD COUNTY UTILITIES
DEPARTMENT, VERIFYING THE REQUIRED WATER FLOW FOR FIRE
PROTECTION IS AVAILABLE AT THE SITE. THE WATERFLOW TEST
RESULTS AND GRAPH SHALL BE SHOWN ON THE SUBMITTED PLAN.
THE MINIMUM REQUIRED FIRE FLOW FOR ALL BUILDINGS, WITH
THE EXCEPTION OF ONE AND TWO-FAMILY DWELLINGS, IS 1500
GPM (SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED) IN
ACCORDANCE WITH THE INTERNATIONAL FIRE CODE (2012) -
SECTION B105.2 AND TABLE B105.1.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: IVYMONT SQUARE PARCEL B RETAIL
SITE PLAN NUMBER: 18PR0133
ADDRESS: 14161 MIDLOTHIAN TURNPIKE
LATEST PLAN DATE: 12/1/17
DEPT. REC'D. DATE: 12/11/17
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 12/14/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED SITE PLAN IS APPROVED AS SUBMITTED.

Modify comments view for case # 18PR0133