CASE NO: 18PR0105 STATUS: PENDING APPROVAL
PROJECT NAME: RIVERA ROOFING - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: COMMERCIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 01 09/05/17 09/26/17 ******** ********
ENVIR.ENGR.-: 01 09/05/17 09/26/17 ******** ********
FIRE DEPT.--: 01 09/05/17 09/26/17 COMPLETE 09/08/17 AWB 717-6167
MAPPING/GIS-: 01 09/05/17 09/26/17 COMPLETE 09/18/17 AMJ 768-7549
PLANNING----: 01 09/05/17 09/26/17 AMENDED* 09/29/17 BSM 717-6143
TRANSPORT.--: 01 09/05/17 09/26/17 COMPLETE 09/07/17 SJA 751-4461
UTIL.PLAN.--: 01 09/05/17 09/26/17 ******** ********
UTILITIES---: 01 09/05/17 09/26/17 AMENDED* 09/29/17 CRP 796-7126
UTIL.R.O.W.-: 01 09/05/17 09/26/17 ******** ********
VDOT--------: 01 09/05/17 09/26/17 ******** ********
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : RANDY PHELPS / 804-796-7126
NAME OF PLAN : RIVERA ROOFING
ADDRESS : 2637 TURNER ROAD
SUBMISSION DATE : 7/13/17
PLAN DATED : 7/11/17
REVIEW DATE : 7/31/17
SITE PLAN NO. : 18PR0105
COMMENTS : 1ST REVIEW-NOT APPROVED
TABLE REVIEW :
PLAT PROCESS :
1. PLACE COUNTY PROJECT NUMBER 04-0332 ON THE LOWER RIGHT
CORNER OF EACH SHEET.
2. PLEASE PUT UTILITIES CONTACT RANDY PHELPS, 796-
7126, PHELPSC@CHESTERFIELD.GOV ON THE COVER SHEET.
3. ON SHEET C-6, CLEARLY SHOW THE LOCATION OF THE PROPOSE
METER, AND RELOCATE THE NOTE SHOWN SO THAT IT DOESN'
4. ON SHEET C-6, LABEL THE DISTANCE FROM THE EXISTING FIR
HYDRANT ON TURNER ROAD TO THE NORTHERN PROPERTY LINE OF TH
5. ON SHEET C-6, SHOW A MONITORING MANHOLE ON THE 6" SEWE
LATERAL, JUST BEYOND THE EXISTING SANITARY SEWER EASEMENT.
NCLUDE THE APPROPRIATE UTILITIES DEPARTMENT SPECS DETAIL.
6. ON SHEET C-6, SHOW A CLEANOUT ON THE 6" SEWER LATERAL
THE BUILDING LINE.
7. PLEASE PROVIDE A COMPLETED METER SIZING FORM FOR THE
DOMESTIC WATER METER. THIS SHOULD BE SHOWN ON THE PLAN AND
ENT TO THE UTILITIES DEPARTMENT REVIEW ENGINEER.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : RANDY PHELPS / 804-796-7126
NAME OF PLAN : RIVERA ROOFING
ADDRESS : 2637 TURNER ROAD
SUBMISSION DATE : 9/05/17
PLAN DATED : 8/31/17
REVIEW DATE : 9/25/17
SITE PLAN NO. : 18PR0105
COMMENTS : 2ND REVIEW-NOT APPROVED
TABLE REVIEW :
PLAT PROCESS :
PLACE COUNTY PROJECT NUMBER 04-0332 ON THE LOWER RIGHT
CORNER OF EACH SHEET.
. PLEASE PROVIDE A COMPLETED METER SIZING FORM FOR THE D
ESTIC WATER METER. THIS SHOULD BE SHOWN ON THE PLAN AND SE
TO THE UTILITIES DEPARTMENT REVIEW ENGINEER.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: RIVERA ROOFING
SITE PLAN NUMBER: 18PR0105
LATEST PLAN DATE: 07/11/17
DEPT. REC'D. DATE: 07/26/17
SUBMITTAL NUMBER: ONE (MORRISON)
REVIEW DATE: 07/26/17
RECOMMENDATION: NOT APPROVED
PLAT PROCESSING: R/W DEDICATION
.
1. FINAL SITE PLAN APPROVAL IS PENDING RIGHT-OF-WAY
DEDICATION 45' FROM EXISTING CENTERLINE OF TURNER RD FOR
THE ENTIRE PROPERTY FRONTAGE.
.
2. NOTE ON PLANS COUNTY CLASSIFICATION FOR TURNER ROAD
(MAJOR ARTERIAL PER COUNTY THOROUGHFARE PLAN).
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: RIVERA ROOFING
SITE PLAN NUMBER: 18PR0105
LATEST PLAN DATE: 08/31/17
DEPT. REC'D. DATE: 09/05/17
SUBMITTAL NUMBER: TWO (MORRISON)
REVIEW DATE: 09/07/17
RECOMMENDATION: SUBSTANTIAL APPROVAL
PLAT PROCESSING: R/W DEDICATION
.
FINAL SITE PLAN APPROVAL IS PENDING RIGHT-OF-WAY DEDICATIO
45' FROM EXISTING CENTERLINE OF TURNER RD.
==========================================================
==========================================================
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: BRAD MORRISON / 717-6143
PLAN NAME: RIVERA ROOFING
PLAN NUMBER : 18PR0105
ORIGINAL PLAN DATE: 7/11/17
REVISION DATE:
LATEST SUBMISSION DATE: 7/11/17
REVIEW DATE: 7/28/17
SUBMITTAL NUMBER : 1
STATUS: REVISIONS REQUIRED
TABLE REVIEW: NO
.
1. INCLUDE OWNER NAME IN NOTES [19.1-27F].
.
2. SHOW PROPOSED NUMBER OF STORIES AND HEIGHTS FOR
BUILDINGS. [19.1-27F].
.
3. PUT THE CHESTERFIELD COUNTY SITE PLAN NUMBER (18PR0105)
IN THE LOWER RIGHT CORNER OF EACH SHEET [19.1-27F].
.
4. LIST ZONING CASE 91SN0282 IN NOTES [19.1-27.F].
.
5. SPECIFY OUTDOOR STORAGE IS A RESTRICTED USE PER 19.1-52
[19.1-53].
6. SHOW DUMPSTER LOCATION AND SCREENING METHOD
PER 19.1-206. RECOMMEND INCORPORATING INTO SCREENING
PROPOSED WALL.
.
7. PER SEC. 19.1-253.C, THE TOTAL NUMBER OF TREES IN A
PARKING LOT SHALL BE 1 PER 200 S.F. OF LANDSCAPE AREA
IN THE PARKING LOT.
.
8. PER SEC. 19.1-253.C, AT LEAST 50% OF THE TREES
SHALL BE LARGE MATURING TREES THAT ARE IN ISLANDS WITH A
MINIMUM WIDTH OF 15 FEET AND 250 S.F. IN SIZE. SMALL
MATURING TREES SHALL BE IN ISLANDS WITH A MINIMUM WIDTH
OF 9 FEET AND BE 150 S.F. IN SIZE.
.
9. PER SEC. 19.1-246, AT LEAST A CONCEPTUAL
LANDSCAPING PLAN SHALL BE APPROVED PRIOR TO RELEASE OF
FINAL SITE PLAN APPROVAL. LANDSCAPE CRITERIA K MUST BE ME
ON FRONT SETBACK, AND B ON THE SIDE AND REAR [19.1-251].
A DEGREE OF FLEXIBILITY WILL BE GIVEN TO ACCOMMODATE UTILI
CREDIT WILL BE GIVEN FOR PRESERVATION OF LARGE DECIDUOUS
TREES.
.
10. PER SEC. 19.1-205, SHOW ON THE LANDSCAPE PLAN OR
ADDITIONALLY ON A SEPARATE LIGHTING PLAN THE LOCATION OF A
EXTERIOR SITE LIGHTING MOUNTED ON POLES, THE BUILDING, OR
ON THE GROUND AND HAVE THEM KEYED TO CUT SHEETS FOR EACH
LIGHT FIXTURE SHOWN ON THE PLAN.
.
11. PER SEC. 19.1-317 A, B, PROVIDE 2 COPIES OF
RENDERINGS/ELEVATIONS OF THE BUILDINGS WITH ALL BUILDING
MATERIALS AND COLORS IDENTIFIED, LOCATIONS OF JUNCTION AND
ACCESS BOXES SHOWN, AND HOW ALL MECHANICAL
EQUIPMENT IS SCREENED WHETHER IT IS MOUNTED ON THE ROOF
OR ON THE GROUND.
TREES. EPARTMENT: PLANNING
********************************************
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: BRAD MORRISON / 717-6143
PLAN NAME: RIVERA ROOFING
PLAN NUMBER : 18PR0105
ORIGINAL PLAN DATE: 7/11/17
REVISION DATE:
LATEST SUBMISSION DATE: 9/5/17
REVIEW DATE: 9/26/17 & 9/29/17
SUBMITTAL NUMBER : 2
STATUS: REVISIONS REQUIRED
TABLE REVIEW: NO
.
1. PER SEC. 19.1-253.C, AT LEAST 50% OF THE TREES
SHALL BE LARGE MATURING TREES THAT ARE IN ISLANDS WITH A
MINIMUM WIDTH OF 15 FEET AND 250 S.F. IN SIZE. SMALL
MATURING TREES SHALL BE IN ISLANDS WITH A MINIMUM WIDTH
OF 9 FEET AND BE 150 S.F. IN SIZE.
.
2. PER SEC. 19.1-246, AT LEAST A CONCEPTUAL
LANDSCAPING PLAN SHALL BE APPROVED PRIOR TO RELEASE OF
FINAL SITE PLAN APPROVAL. LANDSCAPE CRITERIA K MUST BE ME
ON FRONT SETBACK, AND B ON THE SIDE AND REAR [19.1-251].
A DEGREE OF FLEXIBILITY WILL BE GIVEN TO ACCOMMODATE UTILI
CREDIT WILL BE GIVEN FOR PRESERVATION OF LARGE DECIDUOUS
TREES.
3. PER SEC. 19.1-205, SHOW ON THE LANDSCAPE PLAN OR
ADDITIONALLY ON A SEPARATE LIGHTING PLAN THE LOCATION OF A
EXTERIOR SITE LIGHTING MOUNTED ON POLES, THE BUILDING, OR
ON THE GROUND AND HAVE THEM KEYED TO CUT SHEETS FOR EACH
LIGHT FIXTURE SHOWN ON THE PLAN.
.
4. PER SEC. 19.1-317 A, B, PROVIDE 2 COPIES OF
RENDERINGS/ELEVATIONS OF THE BUILDINGS WITH ALL BUILDING
MATERIALS AND COLORS IDENTIFIED, LOCATIONS OF JUNCTION AND
ACCESS BOXES SHOWN, AND HOW ALL MECHANICAL
EQUIPMENT IS SCREENED WHETHER IT IS MOUNTED ON THE ROOF
OR ON THE GROUND.
.
5. SHOW CORRECT PARKING NUMBERS PROVIDED IN GENERAL NOTES.
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : RIVERA ROOFING
CASE NUMBER : 18PR0105
LATEST PLAN DATE : 7/11/17
RECEIVED DATE : 7/17/17
SUBMITTAL NUMBER : 1
REVIEW DATE : 8/2/17
ADDRESS : 2637 TURNER RD
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. THE PARCEL BOUNDARY SURVEY DOESN'T CLOSE. N66-15-50E
63.26 AND N87-32-32-W 228.66 ARE TOO SHORT. PLEASE
SUPPLY THE METES AND BOUNDS FOR EVERY SEGMENT ALONG THE
TRAVERSE TO INCLUDE CHORD BEARING AND DISTANCE FOR ALL
NON-TANGENT CURVES. IF THE PARCEL IS TOO LARGE TO
CONVENIENTLY FIT ON ONE SHEET, A LARGER SCALE DRAWING
OF THE BOUNDARY IS ACCEPTABLE.
2. STREET ADDRESS LOCATION IS NOT SHOWN. IF YOU ARE
USING A MONUMENT SIGN, A DETAIL OF THE MONUMENT SIGN
MUST BE ON THE SITE PLAN.
==========================================================
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON (N)768-7549
PROJECT NAME : RIVERA ROOFING
CASE NUMBER : 18PR0105
LATEST PLAN DATE : 8/31/17
RECEIVED DATE : 9/6/17
SUBMITTAL NUMBER : 2
REVIEW DATE : 9/18/17
ADDRESS : 2637 TURNER RD
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. STREET ADDRESS LOCATION IS NOT SHOWN. IF YOU ARE
USING A MONUMENT SIGN, A DETAIL OF THE MONUMENT SIGN
MUST BE ON THE SITE PLAN.
==========================================================
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: RIVERA ROOFING
SITE PLAN NUMBER: 18PR0105
ADDRESS: 2637 TURNER ROAD
LATEST PLAN DATE: 7/11/17
DEPT. REC'D. DATE: 7/17/17
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 7/17/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE FOLLOWING NOTE SHALL BE ADDED TO THE GENERAL
NOTES ON PLANS:
"AN APPROVED KEY BOX SHALL BE PROVIDED FOR THE PROPOSED
BUILDING IN ACCORDANCE WITH THE INTERNATIONAL FIRE CODE,
SECTION 506.1 THE REQUIRED FORMS AND INSTALLATION
INSTRUCTIONS FOR THE KEY BOX CAN BE OBTAINED FROM
CHESTERFIELD FIRE AND EMS, FIRE AND LIFE SAFETY DIVISION,
AT 748-1426."
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: RIVERA ROOFING
SITE PLAN NUMBER: 18PR0105
ADDRESS: 2637 TURNER ROAD
LATEST PLAN DATE: 8/31/17
DEPT. REC'D. DATE: 9/8/17
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 9/8/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED SITE PLAN IS APPROVED AS SUBMITTED.