CASE NO: 17PR0264 STATUS: PENDING APPROVAL
PROJECT NAME: RESIDENCE INN HOTEL - LAST INTERNET UPDATE: 12/14/17
SUBMITTAL TYPE: COMMERCIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 01 11/17/17 12/13/17 ******** ********
FIRE DEPT.--: 01 11/17/17 12/13/17 COMPLETE 11/27/17 AWB 717-6167
MAPPING/GIS-: 01 11/17/17 12/13/17 COMPLETE 11/30/17 AMJ 768-7549
PLANNING----: 01 11/17/17 12/13/17 COMPLETE 12/12/17 BSM 717-6143
TRANSPORT.--: 01 11/17/17 12/13/17 COMPLETE 12/13/17 SJA 751-4461
UTIL.PLAN.--: 01 11/17/17 12/13/17 ******** ********
UTILITIES---: 01 11/17/17 12/13/17 ******** ********
UTIL.R.O.W.-: 01 11/17/17 12/13/17 ******** ********
VDOT--------: 01 11/17/17 12/13/17 ******** ********
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: RESIDENCE INN HOTEL
SITE PLAN NUMBER: 17PR0264
LATEST PLAN DATE: 06/22/17
DEPT. REC'D. DATE: 06/30/17
SUBMITTAL NUMBER: ONE (BSMORRISON)
REVIEW DATE: 07/17/17
RECOMMENDATION: NOT APPROVED
PLAT PROCESSING: ADDITIONAL R/W OR ESMTS?
.
1. JOHNSTON WILLIS DR & CENTERVIEW DR ARE ON THE BIKEWAYS
& TRAILS PLAN. FACILITIES SHALL BE PROVIDED IN ACCORDANCE
WITH ZONING ORDINACE SECTION 19.1-208.
.
2. NOTE JOHNSTON WILLIS & CENTERVIEW AS URBAN LOCAL ROADS.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: RESIDENCE INN HOTEL
SITE PLAN NUMBER: 17PR0264
LATEST PLAN DATE: 11/16/17
DEPT. REC'D. DATE: 11/22/17
SUBMITTAL NUMBER: TWO (BSMORRISON)
REVIEW DATE: 12/13/17
RECOMMENDATION: NOT APPROVED
PLAT PROCESSING: ADDITIONAL R/W OR ESMTS?
.
COUNTY STAFF IS REVIEWING THE PROPOSED BIKEWAYS/TRAILS
ACCOMMODATION AND COMMENTS WILL BE FORTHCOMING. DEVELOPER
IS REQUIRED TO ADDRESS THIS PLAN IN ACCORDANCE WITH ZONING
ORDINACE SECTION 19.1-208.
==========================================================
==========================================================
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: BRAD MORRISON / 717-6143
PLAN NAME: RESIDENCE INN
PLAN NUMBER : 17PR0264
ORIGINAL PLAN DATE: 6/22/17
REVISION DATE:
LATEST SUBMISSION DATE: 6/28/17
REVIEW DATE: 7/21/17
SUBMITTAL NUMBER : 1
STATUS: REVISIONS REQUIRED
.
1. INCLUDE ZONING CASE #84SN0109 IN GENERAL NOTES.
[19.1-27F]
.. INCLUDE ZONING OF ADJACENT PROPERTY [19.1-27.F].
.
3. LABEL ON PLANS SETBACK EXCEPTIONS ALLOWED BY
ZONING CASES (84SN01090 [19.1-316].
.
4. COMMENT 4 RETRACTED
.
.
5. SHOW WIDTHS OF ALL DRIVES. WIDTH REQUIREMENT
LISTED IN SEC. 19.1-238.C.
.
6. LABEL PARKING SPACES OCCUPIED BY OFF-SITE-USE.
SPECIFY THE ZONING OF THE OFF-SITE USE OCCUPYING
ONSITE PARKING. [19.1-235B]. USE OF OFF SITE PARKING
SHOULD BE LEASED AND RECORDED WITH CLERK OF THE
CIRCUIT COURT.
.
7. LABEL SQUARE FOOTAGE OF LANDSCAPED AREAS
UTILIZED FOR PARKING LOT LANDSCAPING [19.1-253.B].
.
8. THE PROPERTY IS LOCATED ON THE BIKEWAY AND
TRAILS PLAN ON JOHNSTON WILLIS DR AND
CENTERVIEW DR. ADEQUATE FACILITIES MUST BE
INSTALLED ON BOTH FRONTAGES.
THE PROVIDED FACILITIES MUST BE CONSISTENT
WITH THE RECOMMENDATIONS OF THE BIKEWAY AND
TRAILS CHAPTER OF THE COMPREHENSIVE PLAN.
[19.1-27], [19.1-208].
.
ANY OPTION RECOMMENDED BY THE COMPREHENSIVE
MAY BE EXPLORED. A 10' SHARED USE PATH
IS AN OPTION. A 5' BIKE LINE IN CONJUNCTION
WITH A 5' SIDEWALK IS ANOTHER OPTION. IF THE
BIKE LANE AND SIDEWALK OPTION IS CHOSEN,
CENTERIVIEW DR WOULD NEED SIDEWALK INSTALLED.
THE CURB TO CURB WIDTH WILL ACCOMMODATE
STRIPING OF A BIKE LANE AT A LATER DATE.
JOHNSTON WILLIS DRIVE WOULD NEED A SIDEWALK
IN ADDITION TO THE FOLLOWING IMPROVEMENTS
TO ACCOMMODATE A STRIPED BIKE LANE:
A BIKE LANE ALONG THE ENTIRE PROPERTY
FRONTAGE TO JOHNSTON WILLIS DRIVE AND DEDICATE
APPROPRIATE RIGHT-OF-WAY TO ACCOMMODATE THE
FACILITY TO ENSURE VDOT MAINTENANCE. THIS WOULD
RESULT IN 5' PAVEMENT WIDENING WITH DITCH AND
SHOULDER SECTION OR 4' PAVEMENT WIDENING WITH
CURB/GUTTER SECTION, INCLUDING PAVEMENT
MARKINGS AND ASSOCIATED SIGNAGE REQUIRED
BY VDOT. THIS IMPROVEMENT WILL REQUIRE
MODIFICATIONS TO THE EXISTING GUARDRAIL AND
CONCRETE TOWARDS THE SOUTHERN PROPERTY LINE.
LINEAR FOOTAGE OF BIKEWAYS AND TRAILS PROVIDED
SHALL BE LISTED IN THE SITE DATA ON THE COVER SHEET
OF THE SITE PLAN. OTHER DESIGNS CONSISTENT
WITH COMPREHENSIVE PLAN MAY PROPOSED SUCH AS
THE SHARED USE PATH.
.
CURB RAMPS SHOULD BE INSTALLED AT THE CORNER OF
JOHNSTON WILLIS AND CENTERVIEW DR. C
.
PLEASE NOTE PER ZONING ORDINANCE SECTION 19.1-209.B,
SETBACKS SHALL BE MEASURED WITHOUT INCLUDING
THE EXPANDED RIGHT-OF-WAY, EXCEPT THAT THE
SETBACK SHALL NOT BE LESS THAN ONE (1) FOOT
FROM THE EXPANDED RIGHT-OF-WAY.
.
9. PER SEC. 19.1-317 A, B, PROVIDE 2 COPIES OF
RENDERINGS/ELEVATIONS OF THE BUILDINGS WITH
ALL BUILDING MATERIALS AND COLORS IDENTIFIED,
LOCATIONS OF JUNCTION AND ACCESS BOXES SHOWN,
AND HOW ALL MECHANICAL EQUIPMENT IS SCREENED
WHETHER IT IS MOUNTED ON THE ROOF
OR ON THE GROUND.
.
PER SEC.19.1-317 A, B , OR ANY PROJECT WITH MORE THAN
ONE BUILDING, THE DEVELOPER SHALL SUBMIT DOCUMENTS
THAT DEFINE THE OVERALL ARCHITECTURAL THEME.
THE THEME SHALL DESCRIBE HOW EXTERIOR MATERIALS,
COLORS, ARCHITECTURAL STYLE AND BUILDING SCALE
SHALL BE USED TO DEVELOP A CONSISTENT ARCHITECTURAL TREATM
COMPATIBILITY IS REQUIRED BETWEEN BUILDINGS
WITHIN THE PROJECT.
.
10. PUT THE CHESTERFIELD COUNTY SITE PLAN NUMBER
(17PR0264) IN THE LOWER RIGHT CORNER OF EACH SHEET.
[SEC. 19.1-27.F.]
.
11. PUT NOTE ON PLANS, "ALL PROPOSED UTILITIES ARE TO BE
INSTALLED UNDERGROUND INCLUDING ELECTRIC,
TELEPHONE AND CATV." [SEC. 19.1-27.F.]
***********************************************
REVIEW DEPARTMENT: PLANNING
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: BRAD MORRISON / 717-6143
PLAN NAME: RESIDENCE INN
PLAN NUMBER : 17PR0264
ORIGINAL PLAN DATE: 6/22/17
REVISION DATE:
LATEST SUBMISSION DATE: 11/16/17
REVIEW DATE: 12/7/17
SUBMITTAL NUMBER : 2
STATUS: REVISIONS REQUIRED
.
1. INCLUDE ZONING CASE #84SN0109 IN GENERAL NOTES.
[19.1-27F]- CHECK TYPO
.
2. LABEL PARKING SPACES OCCUPIED BY OFF-SITE-USE.
MUST DELINEATE ON SITE PLAN. SPECIFY THE ZONING
OF THE OFF-SITE USE OCCUPYING ONSITE PARKING.
[19.1-235B].
USE OF OFF SITE PARKING SHOULD BE LEASED AND
RECORDEDWITH CLERK OF THE CIRCUIT COURT.
.
3. PARKING TABULATION MUST INCLUDE THE NUMBER
REQUIRED AND PROVIDED SPACES FOR EACH SITE.
SPACES OCCUPIED BY ATHLETIC CLUB CANNOT
BE COUNTED IN SPACES PROVIDED FOR EITHER
HOTEL.
.
4. BIKEWAYS MUST BE CONSISTENT WITH THE
RECOMMENDATIONS OF THE BIKEWAY AND
TRAILS CHAPTER OF THE COMPREHENSIVE PLAN.
[19.1-27], [19.1-208]. THE PROPOSED FACILITIES
ARE NOT CONSISTENT WITH RECOMMENDATIONS.
ADDITIONALLY, THERE MUST BE A SEAMLESS
TRANSITION BETWEEN JOHNSTON WILLES AND
CENTERVIEW DRIVE.
.
PLEASE NOTE PER ZONING ORDINANCE SECTION 19.1-209.B,
SETBACKS SHALL BE MEASURED WITHOUT INCLUDING
THE EXPANDED RIGHT-OF-WAY, EXCEPT THAT THE
SETBACK SHALL NOT BE LESS THAN ONE (1) FOOT
FROM THE EXPANDED RIGHT-OF-WAY.
.
5. PER SEC. 19.1-317 A, B, PROVIDE 2 COPIES OF
RENDERINGS/ELEVATIONS OF THE BUILDINGS WITH
ALL BUILDING MATERIALS AND COLORS IDENTIFIED,
LOCATIONS OF JUNCTION AND ACCESS BOXES SHOWN,
AND HOW ALL MECHANICAL EQUIPMENT IS SCREENED
WHETHER IT IS MOUNTED ON THE ROOF
OR ON THE GROUND.
.
6. PER SEC.19.1-317 A, B , OR ANY PROJECT WITH MORE
THAN ONE BUILDING, THE DEVELOPER SHALL SUBMIT
DOCUMENTS THAT DEFINE THE OVERALL ARCHITECTURAL
THEME. THE THEME SHALL DESCRIBE HOW EXTERIOR
MATERIALS, COLORS, ARCHITECTURAL STYLE AND
BUILDING SCALE SHALL BE USED TO DEVELOP A
CONSISTENT ARCHITECTURAL TREATMENT. COMPATIBILITY
IS REQUIRED BETWEEN BUILDINGS WITHIN THE PROJECT.
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : RESIDENCE INN HOTEL
CASE NUMBER : 17PR0264
LATEST PLAN DATE : 6/22/17
RECEIVED DATE : 7/3/17
SUBMITTAL NUMBER : 1
REVIEW DATE : 7/18/17
ADDRESS : PENDING
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. COORDINATE POINTS BASED ON THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, NORTH AMERICAN DATUM
1983 ARE NOT PRESENT. TWO POINTS MUST BE SHOWN ON THE
PARCEL BOUNDARY.
2. FYI: WHEN THE ADDRESS FOR THE HOTEL IS ASSIGNED, IT
WILL BE ADDRESSED OFF OF JOHNSTON WILLIS DR.
==========================================================
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : RESIDENCE INN HOTEL
CASE NUMBER : 17PR0264
LATEST PLAN DATE : 11/16/17
RECEIVED DATE : 11/18/17
SUBMITTAL NUMBER : 2
REVIEW DATE : 11/30/17
ADDRESS : 1350 JOHNSTON WILLIS DR 23235
STATUS : APPROVED
==========================================================
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: RESIDENCE INN HOTEL
SITE PLAN NUMBER: 17PR0264
ADDRESS: 10701 CENTER VIEW DRIVE
LATEST PLAN DATE: 6/22/1
DEPT. REC'D. DATE: 6/30/17
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 7/6/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. RELOCATE THE FDC TO AN AREA NEAR THE HYDRANT ON
THE SOUTHWEST CORNER OF THE PROPERTY.
2. THE MINIMUM REQUIRED FIRE FLOW FOR PROTECTION PURPOSES
SHALL BE SHOWN ON THE SUBMITTED DRAWINGS. REFER TO THE
INTERNATIONAL FIRE CODE (2012), SECTION B105 AND THE
COUNTY CODE OF CHESTERFIELD FOR EXCEPTIONS ALLOWED FOR
SPRINKLER PROTECTED BUILDINGS
REFER TO THE INTERNATIONAL FIRE CODE (2012) -
SECTION B104, B104.1, B104.2 AND B104.3 FOR THE CALCULATIO
PROCESS AND ALLOWANCES. THE CORRECT FORMAT AND CALCULATION
SHEET CAN BE OBTAINED VIA THE INTERNET AT
CHESTERFIELD COUNTY- CHESTERFIELD FIRE AND EMS - DIVISION
OF FIRE AND LIFE SAFETY
HTTP://WWW.CHESTERFIELD.GOV/PUBLICSAFETY/FIRE/PLANS.ASP
3. ON THE UTILITY PLAN, SHOW THE GATE VALVE AND BOX AT THE
END OF THE UTILITY EASEMENT SERVING THE FIRE PROTECTION
UNDERGROUND WITH INTERIOR BACKFLOW PREVENTER.
4. PROVIDE THE DETAILS FOR THE AUTOMATIC SPRINKLER SYSTEM
RUN-IN AND STUB UP, INCLUDING ALL APPLICABLE NOTES. SEE:
HTTP://WWW.CHESTERFIELD.GOV/PUBLICSAFETY/FIRE/PLANS.ASP
FOR A COPY OF THE DETAILS.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: RESIDENCE INN HOTEL
SITE PLAN NUMBER: 17PR0264
ADDRESS: 10701 CENTER VIEW DRIVE
LATEST PLAN DATE: 11/16/17
DEPT. REC'D. DATE: 11/27/17
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 11/27/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. . PROVIDE THE DETAILS FOR THE AUTOMATIC SPRINKLER SYSTE
RUN-IN AND STUB UP, INCLUDING ALL APPLICABLE NOTES. SEE:
HTTP://WWW.CHESTERFIELD.GOV/PUBLICSAFETY/FIRE/PLANS.ASP
FOR A COPY OF THE DETAILS.