Site Plan Review Comments
All Site Plan Review Comments for Case # 17PR0237
Modify comments view for Case # 17PR0237

Go to Case Selection Form or Go to Project List

 
CASE NO: 17PR0237 STATUS: APPROVED - ADMIN
PROJECT NAME: JOHNSTON-WILLIS MED - LAST INTERNET UPDATE: 11/20/17
SUBMITTAL TYPE: COMMERCIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 00 04/26/17 05/03/17 ******** ********
ENVIR.ENGR.-: 03 07/10/17 07/14/17 ******** ********
FIRE DEPT.--: 03 07/10/17 07/14/17 COMPLETE 07/12/17 AWB 717-6167
MAPPING/GIS-: 03 07/10/17 07/14/17 COMPLETE 07/13/17 AMJ 768-7549
PLANNING----: 03 07/10/17 07/14/17 COMPLETE 07/18/17 CH 717-6042
TRANSPORT.--: 03 07/10/17 07/14/17 COMPLETE 07/17/17 SJA 751-4461
UTIL.PLAN.--: 03 07/10/17 07/14/17 ******** ********
UTILITIES---: 03 07/10/17 07/14/17 AMENDED* 07/14/17 A B 768-7450
UTIL.R.O.W.-: 03 07/10/17 07/14/17 ******** ********
VDOT--------: 03 07/10/17 07/14/17 ******** ********
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : ANDREW BARNES/ 804-768-7450
NAME OF PLAN : JOHNSTON-WILLIS MEDICAL OFFICE BLDG
ADDRESS : 10600 MIDLOTHIAN TURNPIKE
SUBMISSION DATE : 04/26/17
PLAN DATED : 04/24/17
REVIEW DATE : 05/02/17
SITE PLAN NO. : 17PR0237
COMMENTS : 1ST REVIEW-NOT APPROVED
TABLE REVIEW : NO
PLAT PROCESS :
1. UTILITIES PROJECT NUMBER 17-0088 SHALL BE PLACED ON
THE LOWER RIGHT HAND CORNER OF EACH SHEET.
2. PLEASE PUT UTILITIES CONTACT ANDREW BARNES, 804-768-
7450, BARNESAND@CHESTERFIELD.GOV ON THE COVER SHEET.
3. LABEL THE EXISTING WATER AND SEWER MAINS WITH SIZE,
MATERIAL, AND COUNTY PROJECT NUMBER ON ALL APPLICABLE
PLAN AND PROFILE SHEETS THAT DEPICT EXISTING CONDITIONS OR
A CONNECTION. YOU MAY EMAIL SWAVAILABILITY@CHESTERFIELD.GO
TO OBTAIN AS-BUILT INFORMATION.
4. LABEL EACH WATER AND SEWER ITEM ON THE PLANS AS EITHER
"PRIVATE" OR "PUBLIC".
5. INCLUDE PRIVATE ITEMS UNDER A SEPARATE HEADING FOR THE
MATERIAL QUANTITIES LIST.
6. INCLUDE MANHOLE INSERTS IN THE MATERIAL QUANTITY LIST.
7. UPDATE DES-2 ON THE COVER TO INDICATE AN ELEVATION OF
301, BELOW WHICH 80 PSI WILL BE EXCEEDED.
8. AN RPZ BACKFLOW PREVENTER IS REQUIRED. PLEASE INCLUDE
THE RPZ AFTER THE DOMESTIC METER AND LABEL ITS LOCATION ON
THE PLAN.
9. PROVIDE A REFERENCE DISTANCE FOR WL A AND WL B FROM A
FIXED LINE SUCH AS THE BUILDING, FACE OF CURB, ETC.
10. LABEL ALL PROPOSED WATER AND SEWER LINES WITH SIZE AN
MATERIAL.
11. LIST THE BACKFLOW PREVENTER UNDER THE PRIVATE HEADING
IN THE MATERIAL QUANTITY LIST.
12. WILL AN IRRIGATION METER BE NEEDED ON THIS PROJECT?
IF SO PLEASE SHOW THE METER ON THE PLANS AND PROVIDE A
METER SIZING FORM.
13. PROVIDE A 6" VALVE AFTER THE 8" X 6" REDUCER ON WL A.
14. PROVIDE AN 8" VALVE ALONG WL A AFTER THE 8" X 8" TEE
FOR THE DOUBLE CHECK ASSEMBLY.
15. PUBLIC WATER LINES UP TO THE FIRE HYDRANT MUST BE 8".
PLEASE REVISE WL A & B TO 8" PVC.
16. PROVIDE A PLUG AT THE END OF WL A AND EXTEND AN
EASEMENT TO ADJOINING PARCELS 748-709-4670 AND 746-709-
2189.
17. PER THE PLUMBING CODE, CLEAN OUTS ARE NOT PERMITTED O
8" LINES.
18. PROVIDE AN 8" X 2" TEE FOR THE DOMESTIC SERVICE.
19. WE RECOMMEND AN INTERIOR DOUBLE CHECK ASSEMBLY WITH A
BUILDING-MOUNTED FDC, SINCE THE DISTANCE IS LESS THAN 50'.
THIS CONNECTION COULD BE MADE OFF OF WL B.
20. INCLUDE JOINT RESTRAINT CALCULATIONS WITH THE NEXT
SUBMISSION.
21. INCLUDE A COMPLETED SITE UTILIZATION FORM WITH THE
NEXT SUBMISSION.
22. INCLUDE A SEPARATE SIGNED METER SIZING FORM WITH THE
NEXT SUBMISSION FOR PROCESSING.
23. LABEL SANITARY LATERALS WITH SIZE, IN ADDITION TO A
"PRIVATE" LABEL.
24. VERIFY THE EXISTING INVERT OF MANHOLE E2. COUNTY
RECORDS INDICATE AN INVERT OF 326.49.
25. PIPE MUST BE OF THE SAME MATERIAL BETWEEN MANHOLES.
PROVIDE DUCTILE IRON PIPE FROM P1 TO THE CONNECTION POINT.
26. DUE TO THE NATURE OF THE FACILITY, A SAMPLING MANHOLE
IS REQUIRED. PROVIDE THE SAMPLING MANHOLE OUTSIDE OF THE
EASEMENT. MH P1 MAY BE USED AS THE SAMPLING MANHOLE IF TH
SANITARY EASEMENT IS TERMINATED JUST BEFORE THE MANHOLE AN
THE TERMINATION OF COUNTY MAINTENANCE IS CALLED OUT ON THE
PLAN.
27. INCLUDE STANDARD DETAIL MAN-17 ON THE DETAIL SHEET.
28. REMOVE STANDARD DETAILS FOR THRUST BLOCKS FROM C-11.
29. PROVIDE A SUMMARY OF FIRE FLOW CALCULATIONS IN
ACCORDANCE WITH DES-05 AND INCLUDE THE RESULTS ON C-15.
30. WILL A LANDSCAPE/LIGHTING PLAN BE PROVIDED? IF SO,
PLEASE ENSURE THAT ALL PROPOSED WATER AND SEWER UTILITIES
ARE SHOWN. THIS INCLUDES WATER SERVICE LINES AND
WATERMAINS AS WELL AS SEWER LATERALS. LANDSCAPING TREES
MUST BE LOCATED AT LEAST 10 FEET FROM SERVICE
LINES/WATERMAINS AND LATERALS/CLEANOUTS AND MAY NOT BE
LOCATED WITHIN PUBLIC EASEMENTS.
31. INCLUDE A NOTE ON THE PLAN THAT THE CONTRACTOR SHALL
VERIFY THAT THE EXISTING SANITARY SEWER IS CLEAR OF
DEBRIS AND OF SOUND CONDITION PRIOR TO MAKING THE
CONNECTION.
32. AS A RESULT OF ANY CHANGES TO THE PROPOSED UTILITIES
RESULTING FROM THESE COMMENTS, PLEASE UPDATE THE MATERIAL
QUANTITIES ON THE COVER SHEET ACCORDINGLY.
33. THE OWNER SHALL BE REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
PRIOR TO THE PREPARATION OF THE UTILITIES CONTRACT,
UTILITIES MUST BE IN RECEIPT OF THE "ACCEPTED" BID PROPOSA
BETWEEN THE DEVELOPER AND THE COUNTY APPROVED UTILITIES
CONTRACTOR AS WELL AS THE PROJECT'S INFORMATIONAL SHEET
FOUND ON THE "DEVELOPER'S CHECKLIST". PLEASE SEND THOSE TW
ITEMS TO THE ATTENTION OF ANDREW BARNES
(BARNESAND@CHESTERFIELD.GOV). THE BID PROPOSAL MUST BE
BASED ON THE APPROVED SITE PLAN. BE ADVISED THAT IF THE
SITE PLAN IS REVISED AND REAPPROVED SUBSEQUENT TO THE
PREPARATION OR RECORDATION OF THE UTILITIES CONTRACT, THE
BID PROPOSAL SHALL BE REVISED ACCORDINGLY AND A REVISED
UTILITIES CONTRACT MAY BE NECESSARY.
34. AFTER FINAL SITE PLAN APPROVAL, SUBMIT THREE SETS OF
THE APPROVED PLANS DIRECTLY TO THE UTILITIES DEPARTMENT FO
OUR USE DURING CONSTRUCTION INSPECTION. THIS IS IN
ADDITION TO THE ONE APPROVED SET FROM PLANNING (4 TOTAL
SETS). ONE ADDITIONAL ROLLED SET WILL BE REQUESTED AFTER
THE PROJECT IS RELEASED TO CONSTRUCTION TO BE USED FOR AS-
BUILTS.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : ANDREW BARNES/ 804-768-7450
NAME OF PLAN : JOHNSTON-WILLIS MEDICAL OFFICE BLDG
ADDRESS : 10600 MIDLOTHIAN TURNPIKE
SUBMISSION DATE : 05/15/17
PLAN DATED : 05/15/17
REVIEW DATE : 05/19/17
SITE PLAN NO. : 17PR0237
COMMENTS : 2ND REVIEW-NOT APPROVED
TABLE REVIEW : NO
PLAT PROCESS :
1. LABEL THE PROPOSED 8" DIP SANITARY SEWER IN PLAN VIEW.
2. PROVIDE SEPARATE HARD COPIES OF THE SIGNED DOMESTIC AN
IRRIGATION METER SIZING FORM WITH THE NEXT SUBMISSION.
3. THE MATERIAL QUANTITIES LIST STILL IDENTIFIES THE
PRIVATE SANITARY LATERAL AS 8"
4. PROVIDE JOINT RESTRAINT CALCULATIONS FOR THE VERTICAL
BENDS AND DEAD ENDS.
6. THE SITE UTILIZATION FORM MUST BE RESUBMITTED WITH A
COMPLETED HEADING AND CERTIFICATION SECTION.
7. ON THE EASEMENT PLAN, SHEET C-14, IDENTIFY/LABEL THE
PROPOSED SANITARY EASEMENT.
8. PROVIDE AN 8" VALVE AT THE END OF WL "A", AFTER THE
TEE, TO FACILITATE FUTURE EXTENSION.
9. INDICATE THE LOCATION OF THE 6" SANITARY LATERAL
CROSSING IN THE PROFILE FOR WL "A". PROVIDE/IDENTIFY THE
NECESSARY MINIMUM CLEARANCE OF 18".
10. AS A RESULT OF ANY CHANGES TO THE PROPOSED UTILITIES
RESULTING FROM THESE COMMENTS, PLEASE UPDATE THE MATERIAL
QUANTITIES ON THE COVER SHEET ACCORDINGLY.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : ANDREW BARNES/ 804-768-7450
NAME OF PLAN : JOHNSTON-WILLIS MEDICAL OFFICE BLDG
ADDRESS : 10600 MIDLOTHIAN TURNPIKE
SUBMISSION DATE : 06/14/17
PLAN DATED : 06/13/17
REVIEW DATE : 06/14/17
SITE PLAN NO. : 17PR0237
COMMENTS : 3RD REVIEW- APPROVED
TABLE REVIEW : N/A
PLAT PROCESS :
THE PLANS FOR JOHNSTON-WILLIS MOB WITH THE LATEST REVISION
DATE OF JUNE 13, 2017 ARE APPROVED. THIS REVIEW IS
EFFECTIVE UNTIL JUNE 14, 2022.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : ANDREW BARNES/ 804-768-7450
NAME OF PLAN : JOHNSTON-WILLIS MEDICAL OFFICE BLDG
ADDRESS : 10600 MIDLOTHIAN TURNPIKE
SUBMISSION DATE : 07/10/17
PLAN DATED : 07/07/17
REVIEW DATE : 07/13/17
SITE PLAN NO. : 17PR0237
COMMENTS : 4TH REVIEW- APPROVED
TABLE REVIEW : N/A
PLAT PROCESS :
THE PLANS FOR JOHNSTON-WILLIS MOB WITH THE LATEST REVISION
DATE OF JULY 7, 2017 ARE APPROVED. THIS REVIEW IS
EFFECTIVE UNTIL JULY 14, 2022. ONCE ALL OTHER DEPARTMENTS
HAVE APPROVED THE PLANS, PLEASE SUBMIT 3 ADDITIONAL COPIES
(4 TOTAL) DIRECTLY TO THE UTILITIES DEPARTMENT FOR USE
DURING CONSTRUCTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: JOHNSTON WILLIS MED OFFICE BLDG
SITE PLAN NUMBER: 17PR0237
LATEST PLAN DATE: 04/24/17
DEPT. REC'D. DATE: 04/27/17
SUBMITTAL NUMBER: ONE
REVIEW DATE: 04/28/17
RECOMMENDATION: NOT APPROVED
.
1. PRIOR TO FINAL SITE PLAN APPROVAL, DEDICATE JOHNSTON
WILLIS DR RIGHT-OF-WAY TO THE COUNTY, FREE & UNRESTRICTED.
.
2. PROVIDE A PRIVATE SIDEWALK ALONG THE DEVELOPMENT'S
FRONTAGE TO JOHNSTON WILLIS DR AND PROVIDE SIDEWALK
EXTENSION TO ROUTE 60 PER CDOT SKETCH EMAILED TO ENGINEER
ON 4/28/17.
.
3. JOHNSTON WILLIS DR IS ON THE COUNTY'S BIKEWAYS & TRAILS
PLAN; THEREFORE, PROVIDE "SHARE THE ROAD" SIGNAGE ALONG
ROAD FRONTAGE RIGHT-OF-WAY. PLEASE COORDINATE THIS REQUEST
WITH VDOT.
.
4. NOTE THE COUNTY CLASSIFICATION FOR JOHNSTON WILLIS DR
(COLLECTOR).
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: JOHNSTON WILLIS MED OFFICE BLDG
SITE PLAN NUMBER: 17PR0237
LATEST PLAN DATE: 05/15/17
DEPT. REC'D. DATE: 05/16/17
SUBMITTAL NUMBER: TWO (FAST TRACK - CH)
REVIEW DATE: 05/18/17
RECOMMENDATION: SUBSTANTIAL APPROVAL
.
1. FINAL SITE PLAN APPROVAL IS PENDING RIGHT-OF-WAY
DEDICATION ALONG JOHNSTON WILLIS DRIVE.
.
2. REMOVE "COLLECTOR" REFERENCE FOR JOHNSTON WILLIS DR.
CDOT WAS IN ERROR ON PREVIOUS COMMENT. THIS CAN BE
REDLINED ON PLAN TO EXPEDITE SUBSTANTIAL APPROVAL.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: JOHNSTON WILLIS MED OFFICE BLDG
SITE PLAN NUMBER: 17PR0237
LATEST PLAN DATE: 06/02/17
DEPT. REC'D. DATE: 06/06/17
SUBMITTAL NUMBER: THREE (FAST TRACK - CH)
REVIEW DATE: 06/09/17
RECOMMENDATION: SUBSTANTIAL APPROVAL
.
FINAL SITE PLAN APPROVAL IS PENDING RIGHT-OF-WAY DEDICATIO
ALONG JOHNSTON WILLIS DRIVE.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: JOHNSTON WILLIS MED OFFICE BLDG
SITE PLAN NUMBER: 17PR0237
LATEST PLAN DATE: 07/07/17
DEPT. REC'D. DATE: 07/11/17
SUBMITTAL NUMBER: FOUR (FAST TRACK - CH)
REVIEW DATE: 07/S17/17
RECOMMENDATION: SUBSTANTIAL APPROVAL
.
FINAL SITE PLAN APPROVAL IS PENDING RIGHT-OF-WAY DEDICATIO
ALONG JOHNSTON WILLIS DRIVE.
==========================================================
==========================================================
**********************************************************
REVIEW DEPARTMENT---------PLANNING
REVIEWER / PHONE #--------CHRIS HALE / (804) 717-6042
NAME OF PLAN--------------JOHNSTON WILLIS MOB
SITE PLAN NUMBER----------17PR0237
ADDRESS-------------------10600 MIDLOTHIAN TNPK
LATEST PLAN DATE----------04/24/17
DEPT. REC'D. DATE---------04/24/17
SUBMITTAL NUMBER----------1 (FAST TRACK)
REVIEW DATE---------------05/01/17
RECOMMENDATION------------REVISION REQUIRED
TABLE REVIEW--------------NO
PLAT PROCESSING-----------YES
LANDSCAPE PLAN STATUS-----NOT SUBMITTED
ARCHITECTURAL ELEVATIONS--NOT SUBMITTED
LIGHTING PLAN/CUTSHEETS---REVISION REQUIRED
IRRIGATION/HOSEBIB PLAN---NOT SUBMITTED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS.
RESUBMIT 10 FULL SETS AND ONE COPY OF THE SITE PLAN
SHEET TO THEPLANNING DEPARTMENT FOR YOUR NEXT REVIEW.
PROVIDE A COMPLETE RESPONSE TO COMMENTS FOR ALL
DEPARTMENTS TO THE PLANNING DEPARTMENT. BELOW EACH
COMMENT DESCRIBE HOW YOU HAVE ADDRESSED EACH REVIEW
PROVIDE A COMPLETE RESPONSE TO COMMENTS FOR ALL
DEPARTMENTS TO THE PLANNING DEPARTMENT. BELOW EACH
COMMENT DESCRIBE HOW YOU HAVE ADDRESSED EACH REVIEW
COMMENT. INDICATE WHICH SHEETS SHOW THE REQUIRED
CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE ANY
CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
2. PUT THE CHESTERFIELD COUNTY SITE PLAN NUMBER IN THE
LOWER RIGHT CORNER OF EACH SHEET: 17PR0237
3. SHOW ON THE PLANS ALL PARCELS, SUBJECT AND ADJACENT,
WITH OWNER NAMES, ZONING, AND CURRENT USES, INCLUDING
VACANT. 19.1-27.F
4. PROVIDE PARCEL INFORMATION FOR 10520 MIDLOTHIAN TNPK,
PARCEL 7467093466 ON SHEET C-2.
5. CLEARLY SHOW ALL EXISTING PARCEL LINES ON SHEET C-2.
6. ADJUST THE ANNOTATION FOR THE ADJACENT PARCEL 746709618
FOR LEGIBILITY. THE EXISTING TOPO LINES OBSCURE THE TEXT A
CURRENTLY SHOWN.
7. SHOW THE ZONING DISTRICT BOUNDARY LINES MORE CLEARLY ON
ALL PARCELS.
8. ADD ZONING CASE 86SN0159 TO THE SITE DATA ON THE COVER.
9. PER ZONING CASE 86SN0159 CONDITION 6, A 50 FOOT PARKING
SETBACK IS REQUIRED AT THE MIDLOTHIAN TNPK FRONTAGE ON
PARCEL 7467093466. THIS WAS DISCUSSED AT THE PRELIMINARY
SITE PLAN MEETING. SETBACK RELIEF WOULD REQUIRE A VARIANCE
THROUGH ZONING AND PLANNING COMMISSION APPROVAL.
10. LABEL ALL SETBACKS DETERMINED THOUGH CONDITIONS OF
ZONING CASES, SPECIFICALLY 86SN0159.
11. THE SETBACK LOCATED AT THE EASTERN-MOST PROPERTY LINE
OF 7467096180 IS THE REAR YARD SETBACK. PER POST-
DEVELOPMENT DESIGN DISTRICT STANDARDS, THERE IS A 0 FOOT
PARKING SETBACK. REVISE ON ALL SHEETS WHERE SHOWN.
12. A FUTURE BIKEWAY PER THE COMPREHENSIVE PLAN IS PROPOSE
ALONG JOHNSTON WILLIS DRIVE. THE FRONT SETBACK ON JOHNSTON
WILLIS DRIVE WHERE THE BIKEWAY IS PLANNED IS ALLOWED TO BE
MEASURED FROM THE EXISTING, NOT THE ULTIMATE RIGHT-OF-WAY
PER 19.1-209.B. THIS IS CORRECTLY SHOWN. ADD A NOTE TO THE
PLAN INDICATING THE BIKEWAY ALLOWANCE AT THIS SETBACK.
13. ADD A SIDEWALK ALONG JOHNSTON WILLIS DRIVE AND AN
INTERNAL CONNECTOR SIDEWALK OUT TO MIDLOTHIAN TNPK PER
COUNTY TRANSPORTATION REQUIREMENTS. LIST THE LINEAR FOOTAG
OF SIDEWALKS PROVIDED IN THE SITE DATA ON THE COVER SHEET.
14. PROVIDE A MINIMUM 6 FOOT WIDE PLANTING STRIP TO
ACCOMMODATE TREES ALONG THE JOHNSTON WILLIS DRIVE SETBACK
EITHER BETWEEN THE SIDEWALK AND PARKING OR BETWEEN THE
SIDEWALK AND THE ROAD. IF THIS AMOUNT OF SPACE CANNOT BE
ACHIEVED GIVEN THE SIDEWALK REQUIREMENTS, PROVIDE AT LEAST
TWO PARKING LOT ISLANDS ADJACENT TO THIS SETBACK AT A
MINIMUM WIDTH OF 13.5 FEET TO ACCOMMODATE LARGE TREES.
SPACE THE ISLANDS AT AN ADEQUATE DISTANCE TO CREATE A
STREET TREE EFFECT ALONG JOHNSTON WILLIS DRIVE.
15. SHOW ALL SETBACKS ON THE GRADING PLAN.
16. 237 PARKING SPACES ARE SHOWN IN THE CALCULATIONS. 235
WERE COUNTED. VERIFY AND UPDATE THE PARKING AND INTERIOR
LANDSCAPE CALCULATIONS.
17. LABEL PROVIDED INTERIOR PARKING LOT LANDSCAPE AREAS ON
18. INTERIOR PARKING LOT LANDSCAPING CALCULATIONS REQUIRE
18 LARGE TREES WITHIN THE PARKING LOT. LARGE TREES ARE TO
BE LOCATED WITHIN ISLANDS WITH 250 SQ FT MIN AREA AND 15 F
MIN DIMENSION OR A CONTINUOUS 600 SQ FT AND 9 FT MIN
DIMENSION LANDSCAPE STRIP WITHIN THE PARKING LOT (19.1-
253.B). VERIFY THAT THIS CAN BE ACHIEVED AND ADJUST THE
PARKING LAYOUT AS NEEDED.
19. PROVIDE A LANDSCAPE PLAN MEETING THE REQUIREMENTS OF
DIVISION 5 OF THE COUNTY ZONING ORDINANCE.
20. ON THE LANDSCAPE PLAN TO BE PROVIDED SHOW THE LOCATION
OF ALL PROPOSED SITE LIGHTING FIXTURES.
21. PROVIDE 2 COPIES OF COLOR ELEVATIONS OF THE BUILDINGS
WITH ALL BUILDING MATERIALS AND COLORS IDENTIFIED,
LOCATIONS OF JUNCTION AND ACCESS BOXES SHOWN, AND HOW ALL
MECHANICAL EQUIPMENT IS SCREENED WHETHER IT IS MOUNTED ON
THE ROOF OR ON THE GROUND. 19.1-27.F
22. PER ZONING CASE 92SN0118 CONDITION 2, THE ARCHITECTURA
STYLE OF THE PROPOSED OFFICE BUILDING SHALL BE COMPATIBLE
WITH THE EXISTING JOHNSTON WILLIS HOSPITAL FACILITY.
23. ON THE DUMPSTER GATE DETAIL CHANGE THE 'NO SERVICE'
TIMES TO 9 PM - 6 AM. 19.1-206.B
24. IF NEW SIGNAGE IS PROPOSED, SIGN PERMIT APPROVAL
IS SEPARATE FROM SITE PLAN APPROVAL.
**********************************************************
REVIEW DEPARTMENT---------PLANNING
REVIEWER / PHONE #--------CHRIS HALE / (804) 717-6042
NAME OF PLAN--------------JOHNSTON WILLIS MOB
SITE PLAN NUMBER----------17PR0237
ADDRESS-------------------10600 MIDLOTHIAN TNPK
LATEST PLAN DATE----------05/15/17
DEPT. REC'D. DATE---------05/15/17
SUBMITTAL NUMBER----------2 (FAST TRACK)
REVIEW DATE---------------05/22/17
RECOMMENDATION------------REVISION REQUIRED
TABLE REVIEW--------------NO
PLAT PROCESSING-----------YES
LANDSCAPE PLAN STATUS-----SUBMITTED
ARCHITECTURAL ELEVATIONS--NOT SUBMITTED
LIGHTING PLAN/CUTSHEETS---REVISION REQUIRED
IRRIGATION/HOSEBIB PLAN---NOT SUBMITTED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS.
RESUBMIT 10 FULL SETS AND ONE COPY OF THE SITE PLAN
SHEET TO THEPLANNING DEPARTMENT FOR YOUR NEXT REVIEW.
PROVIDE A COMPLETE RESPONSE TO COMMENTS FOR ALL
DEPARTMENTS TO THE PLANNING DEPARTMENT. BELOW EACH
COMMENT DESCRIBE HOW YOU HAVE ADDRESSED EACH REVIEW
COMMENT. INDICATE WHICH SHEETS SHOW THE REQUIRED
CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE ANY
CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
2. LIST THE LINEAR FOOTAGE OF SIDEWALKS PROVIDED IN THE
SITE DATA ON THE COVER SHEET.
3. SHOW A FUTURE SIDEWALK CONNECTION WITH DASHED LINES OUT
TO THE MIDLOTHIAN TNPK RIGHT-OF-WAY LINE FROM THE INTERNAL
SIDEWALK. SHOW THE FUTURE WALK ON THE LAYOUT, GRADING,
LANDSCAPE, AND OTHER APPLICABLE SHEETS.
4. 242 PARKING SPACES ARE SHOWN IN THE CALCULATIONS. 240
WERE COUNTED. VERIFY AND UPDATE THE PARKING AND INTERIOR
LANDSCAPE CALCULATIONS. THE PARKING BAY WITH 36 SPACES
LABELED IS INCORRECT.
5. LABEL ALL PROVIDED INTERIOR PARKING LOT LANDSCAPE AREAS
ON THE SITE LAYOUT, SHEET C-3. INTERIOR AREAS THAT DO NOT
RECEIVE TREES SHOULD ALSO BE COUNTED. THE 1751 SQUARE FOOT
STRIP ALONG THE EDGE OF THE PARKING WOULD NOT COUNT TOWARD
INTERIOR PARKING LOT LANDSCAPING. USE THE REQUIRED INTERIO
AREA, NOT THE PROVIDED, TO DETERMINE THE TREE QUANTITY
REQUIREMENT. WITH 240 PARKING SPACES, 7200 SQ FT IS
REQUIRED WITH 36 TREES, 18 OF WHICH ARE TO BE LARGE
DECIDUOUS.
6. PROVIDE ADDITIONAL LARGE DECIDUOUS TREES TO MEET THE
INTERIOR PARKING LOT LANDSCAPE REQUIREMENT. INTERIOR
PARKING LOT LANDSCAPING CALCULATIONS REQUIRE 18 LARGE TREE
WITHIN THE PARKING LOT. LARGE TREES ARE TO BE LOCATED
WITHIN ISLANDS WITH 250 SQ FT MIN AREA AND 15 FT MIN
DIMENSION.
7. PER SECTION 19.1-27(E), LANDSCAPE PLANS SHALL BE
CERTIFIED BY A STATE OF VIRGINIA REGISTERED LANDSCAPE
ARCHITECT, NURSERYMAN OR LANDSCAPE DESIGNER.
8. REFER TO SECTION 19.1-250.D FOR LANDSCAPE MATERIAL SIZE
REQUIREMENTS. UPDATE THE PLANTING SCHEDULE TO MEET MINIMUM
SIZE REQUIREMENTS.
9. MAINTAIN A MINIMUM OF 8 FEET CLEAR BETWEEN LARGE
DECIDUOUS TREES AND STORM DRAIN LINES. THE MAPLE AT THE
NORTH EAST CORNER OF THE PARKING LOT IS TOO CLOSE.
10. LIGHT POLES HAVE BEEN SHOWN ON THE LANDSCAPE PLAN.
MAINTAIN 15 FEET CLEAR BETWEEN LIGHT POLES AND LARGE
DECIDUOUS TREES.
11. PERIMETER LANDSCAPE TREATMENT J IS REQUIRED IN THE 15
FOOT FRONT SETBACK ALONG JOHNSTON WILLIS DRIVE. PROVIDE AT
MINIMUM 1 LARGE DECIDUOUS TREE PER 35 FEET GENERALLY SPACE
ON-CENTER AND AN EVERGREEN HEDGE ALONG THE PARKING, WITH 3
FEET CLEAR BETWEEN MATURE SHRUBS AND THE BACK OF CURB. THE
SETBACK LENGTH IS 207 FEET. LABEL THE LANDSCAPE REQUIREMEN
ON THE LAYOUT AND LANDSCAPE PLANS AND ADD TO THE
CALCULATIONS.
12. CORRECT THE 'PERIMETER LANDSCAPE J' TITLE IN THE
CALCULATIONS FOR THE MIDLOTHIAN TNPK SETBACK.
13. DUE TO HEAT INTOLERANCE AND ROOT ISSUES NEAR PAVING, D
NOT SPECIFY RED MAPLES ADJACENT TO SIDEWALKS, BETWEEN WALK
AND PARKING AREAS, OR WITHIN INTERIOR PARKING LOT ISLANDS.
RED MAPLES PLACED ON THE PERIMETER OF THE PARKING LOT ARE
ACCEPTABLE.
14. THE FUTURE SIDEWALK CONNECTION TO THE MIDLOTHIAN TNPK
RIGHT-OF-WAY SHOULD BE SHOWN ON THE LANDSCAPE PLAN. ADJUST
PLANTINGS IN THE SETBACK TO ACCOMMODATE THE WALK LOCATION.
15. IF STAR MAGNOLIAS, ROSES, AND CAMELLIAS ARE TO BE USED
GROUP THEM INTO MASSES WITH BED LINES DEFINED. CONSIDER
DESIRABLE POINTS OF VISIBILITY TO THE BUILDING WITH THE
PLACEMENT OF SMALL TREE AND SHRUB GROUPINGS.
16. ALL LANDSCAPED AREAS SHALL BE PROVIDED WITH A READILY
AVAILABLE WATER SUPPLY. THE COUNTY ACCEPTS EITHER YARD
HYDRANTS AND/OR HOSE BIBS WITHIN 100 FEET OF ALL NEW
PLANTINGS OR AN IRRIGATION SYSTEM FOR ALL AREAS OF NEW
PLANTINGS. SHOW LOCATION OF HYDRANTS, BIBS OR IRRIGATION
SLEEVES. THE COUNTY ALSO ACCEPTS A 3-YEAR CONTINUOUS
MAINTENANCE AGREEMENT FROM A REPUTABLE LANDSCAPE COMPANY
WITH DOCUMENTATION PROVIDED TO THE PLANNING DEPARTMENT.
17. PROVIDE LIGHTING CUTSHEETS FOR SPECIFIED LIGHTING
FIXTURES.
18. PROVIDE 2 COPIES OF COLOR ELEVATIONS OF THE BUILDINGS
WITH ALL BUILDING MATERIALS AND COLORS IDENTIFIED,
LOCATIONS OF JUNCTION AND ACCESS BOXES SHOWN, AND HOW ALL
MECHANICAL EQUIPMENT IS SCREENED WHETHER IT IS MOUNTED ON
THE ROOF OR ON THE GROUND. 19.1-27.F
19. PER ZONING CASE 92SN0118 CONDITION 2, THE ARCHITECTURA
STYLE OF THE PROPOSED OFFICE BUILDING SHALL BE COMPATIBLE
WITH THE EXISTING JOHNSTON WILLIS HOSPITAL FACILITY.
20. IF NEW SIGNAGE IS PROPOSED, SIGN PERMIT APPROVAL
IS SEPARATE FROM SITE PLAN APPROVAL.
**********************************************************
REVIEW DEPARTMENT---------PLANNING
REVIEWER / PHONE #--------CHRIS HALE / (804) 717-6042
NAME OF PLAN--------------JOHNSTON WILLIS MOB
SITE PLAN NUMBER----------17PR0237
ADDRESS-------------------10600 MIDLOTHIAN TNPK
LATEST PLAN DATE----------06/02/17
DEPT. REC'D. DATE---------06/02/17
SUBMITTAL NUMBER----------3 (FAST TRACK)
REVIEW DATE---------------06/09/17
RECOMMENDATION------------REVISION REQUIRED
TABLE REVIEW--------------YES
PLAT PROCESSING-----------YES
LANDSCAPE PLAN STATUS-----SUBMITTED
ARCHITECTURAL ELEVATIONS--NOT SUBMITTED (PDF ONLY)
LIGHTING PLAN/CUTSHEETS---SUBMITTED
IRRIGATION/HOSEBIB PLAN---NOT SUBMITTED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS.
RESUBMIT 10 FULL SETS AND ONE COPY OF THE SITE PLAN
SHEET TO THE PLANNING DEPARTMENT FOR YOUR NEXT REVIEW.
PROVIDE A COMPLETE RESPONSE TO COMMENTS FOR ALL
DEPARTMENTS TO THE PLANNING DEPARTMENT. BELOW EACH
COMMENT DESCRIBE HOW YOU HAVE ADDRESSED EACH REVIEW
COMMENT. INDICATE WHICH SHEETS SHOW THE REQUIRED
CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE ANY
CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
2. IF ALL DEPARTMENTS AGREE TO A TABLE REVIEW, THEN YOU
MAY BRING SUBMITTAL PLAN SETS AND THE COMMENT RESPONSE
LETTER (WITH 3 OF THE 10 PLAN SETS HIGHLIGHTED WITH
REVISIONS SINCE THE LAST REVIEW), ALONG WITH THE RECEIPT
FOR THE REVIEW FEE, IF REQUIRED (PAYABLE AT THE FRONT
COUNTER), TO THE TABLE REVIEW MEETING. COORDINATION WITH
DEPARTMENTS NOT APPROVED ON THE LAST REVIEW PRIOR TO THE
TABLE REVIEW IS ADVISABLE.
3. THE FEE FOR THE NEXT (FOURTH) SITE PLAN SUBMITTAL IS
$350. REFER TO SITE PLAN FEES LISTED IN TABLE 19.1-41.C OF
THE ZONING ORDINANCE.
4. WHERE THE SIDEWALK HAS BEEN PROVIDED ALONG JOHNSTON
WILLIS DRIVE, AT THE NORTHERN END OF THE SITE, TERMINATE
THE WALK WITH THE CURB RAMP FARTHER EAST OF THE DRIVE LANE
OF JOHNSTON WILLIS DRIVE. THIS PROVIDES AN ADDED SAFETY
MEASURE ALLOWING VEHICLES TURNING INTO THE ENTRANCE DRIVE
MORE SPACE BEFORE STOPPING AT THE CROSSWALK IF NEEDED, AND
SHORTENS THE LENGTH OF THE CROSSING FOR PEDESTRIANS.
5. PROVIDE ADDITIONAL TREES TO MEET THE INTERIOR PARKING
LOT LANDSCAPE REQUIREMENT. INTERIOR PARKING LOT LANDSCAPIN
CALCULATIONS REQUIRE A MINIMUM OF 18 LARGE TREES AND THE
REMAINDER SMALL TREES TOTALING 36 DECIDUOUS TREES WITHIN
THE BOUNDARY OF THE PARKING LOT. LARGE TREES ARE
TO BE LOCATED WITHIN ISLANDS WITH 250 SQ FT MIN AREA AND 1
FT MIN DIMENSION. PERIMETER LANDSCAPING IN SETBACKS CANNOT
COUNT TOWARD INTERIOR PARKING LOT LANDSCAPING.
6. ADDITIONAL TREES CAN BE PROVIDED IN THESE LOCATIONS:
IN THE TWO NORTHEASTERN MOST PARKING LOT ISLANDS CONTAININ
CRAPE MYRTLES, ENLARGE THE WESTERN HALF OF EACH ISLAND
TO ACCOMMODATE WILLOW OAKS WHERE CRAPE MYRTLES ARE SHOWN.
THIS WOULD REQUIRE THE REMOVAL OF TWO PARKING SPACES, ONE
AT EACH ISLAND LOCATION. AN EXCESS OF 26 SPACES OVER THE
REQUIRED AMOUNT WOULD STILL BE PROVIDED AFTER REMOVING THE
TWO SPACES.
REPLACE THE ONE CRAPE MYRTLE WITH A RED MAPLE BETWEEN THE
OTHER TWO MAPLES LOCATED OFF THE NORTHERN EDGE OF THE
PARKING LOT, EAST OF THE BUILDING.
ADD A CRAPE MYRTLE SOUTH OF THE SIDEWALK IN THE ISLAND AT
THE NORTHWEST CORNER OF THE BUILDING.
ADD TWO CRAPE MYRTLES IN THE BUMP-OUTS ON EACH SIDE OF THE
DUMPSTER, IN FRONT OF THE STORM PIPE. MAINTAIN A MINIMUM 5
FEET CLEAR BETWEEN THE CENTER OF THE TREE AND THE PIPE.
7. MAINTAIN 15 FEET CLEAR BETWEEN LIGHT POLES AND LARGE
DECIDUOUS TREES. ONE WILLOW OAK IN THE SETBACK ALONG
JOHNSTON WILLIS DRIVE IS SHOWN ONLY 10 FEET FROM A LIGHT
POLE.
8. ALL LANDSCAPED AREAS SHALL BE PROVIDED WITH A READILY
AVAILABLE WATER SUPPLY. THE COUNTY ACCEPTS EITHER YARD
HYDRANTS AND/OR HOSE BIBS WITHIN 100 FEET OF ALL NEW
PLANTINGS OR AN IRRIGATION SYSTEM FOR ALL AREAS OF NEW
PLANTINGS. SHOW LOCATION OF HYDRANTS, BIBS OR IRRIGATION
SLEEVES. THE COUNTY ALSO ACCEPTS A 3-YEAR CONTINUOUS
MAINTENANCE AGREEMENT FROM A REPUTABLE LANDSCAPE COMPANY
WITH DOCUMENTATION PROVIDED TO THE PLANNING DEPARTMENT.
IF AN IRRIGATION SYSTEM IS TO BE PROVIDED, ADD A NOTE TO
THE PLAN: ALL LANDSCAPED AREAS ARE TO BE IRRIGATED WITH AN
AUTOMATIC IRRIGATION SYSTEM.
9. PROVIDE 2 COPIES OF COLOR ELEVATIONS OF THE BUILDINGS
WITH ALL BUILDING MATERIALS AND COLORS IDENTIFIED,
LOCATIONS OF JUNCTION AND ACCESS BOXES SHOWN, AND HOW ALL
MECHANICAL EQUIPMENT IS SCREENED WHETHER IT IS MOUNTED ON
THE ROOF OR ON THE GROUND. 19.1-27.F
10. ON THE ARCHITECTURAL ELEVATIONS, SHOW IN RELIEF USING
DASHED LINE THE LOCATION OF ROOF TOP MECHANICAL UNITS IN
RELATION TO THE PARAPET WALL. IF THE PLANNING DEPARTMENT
DETERMINES THAT UNITS ARE VISIBLE TO THE PUBLIC, THE
PARAPETS SHALL BE EXTENDED UNTIL THE SCREENING IS
ACCOMPLISHED, BUT NO HIGHER THAN THE TOP OF THE RTU'S. THI
SHALL BE REQUIRED PRIOR TO THE RELEASE OF A TEMPORARY
CERTIFICATE OF OCCUPANCY, OR A BOND PLACED WITH THE COUNTY
FOR THE COST OF THE ADDITIONAL BUILDING. 19.1-317.D
11. BUILDING ARCHITECTURE IS TO BE COMPATIBLE WITH OTHER
BUILDINGS WITHIN THE HOSPITAL COMPLEX AS DISCUSSED WITH TH
PLANNING DEPARTMENT.
12. IF NEW SIGNAGE IS PROPOSED, SIGN PERMIT APPROVAL
IS SEPARATE FROM SITE PLAN APPROVAL.
13. IF NO NEW MONUMENT SIGN IS PROPOSED, ADD A NOTE TO
THE LAYOUT PLAN THAT THE STREET ADDRESS WILL BE POSTED
ON THE BUILDING WITH 10 INCH LETTERS CLEARLY VISIBLE
FROM THE PUBLIC ROAD.
**********************************************************
REVIEW DEPARTMENT---------PLANNING
REVIEWER / PHONE #--------CHRIS HALE / (804) 717-6042
NAME OF PLAN--------------JOHNSTON WILLIS MOB
SITE PLAN NUMBER----------17PR0237
ADDRESS-------------------10600 MIDLOTHIAN TNPK
LATEST PLAN DATE----------07/07/17
DEPT. REC'D. DATE---------07/07/17
SUBMITTAL NUMBER----------5 (FAST TRACK)
REVIEW DATE---------------076/17/17
RECOMMENDATION------------SUBSTANTIAL RE-APPROVAL
TABLE REVIEW--------------YES
PLAT PROCESSING-----------YES
LANDSCAPE PLAN STATUS-----APPROVED
ARCHITECTURAL ELEVATIONS--SUBMITTED, NOT APPROVED
LIGHTING PLAN/CUTSHEETS---APPROVED
IRRIGATION/HOSEBIB PLAN---NOTE PROVIDED
THE SITE PLAN (SUBSTANTIALLY APPROVED ON JUNE 14, 2017) WA
RESUBMITTED TO ADDRESS ITEMS RELATED TO STORM WATER
MANAGEMENT ONLY. THIS CHANGE WAS INITIATED BY THE APPLICAN
FULL SITE PLAN APPROVAL IS PENDING:
1. RIGHT-OF-WAY DEDICATION AS REQUIRED BY TRANSPORTATION
2. BUILDING ELEVATION APPROVAL BY PLANNING
**********************************************************
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : JOHNSTON-WILLIS MED OFF BLDG
CASE NUMBER : 17PR0237
LATEST PLAN DATE : 4/24/17
RECEIVED DATE : 4/28/17
SUBMITTAL NUMBER : 1
REVIEW DATE : 4/28/17
ADDRESS : PENDING
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. THE PARCEL BOUNDARY SURVEY ISN'T SHOWN. PLEASE
SUPPLY THE METES AND BOUNDS FOR EVERY SEGMENT ALONG THE
TRAVERSE TO INCLUDE CHORD BEARING AND DISTANCE FOR ALL
NON-TANGENT CURVES. IF THE PARCEL IS TOO LARGE TO
CONVENIENTLY FIT ON ONE SHEET, A LARGER SCALE DRAWING
OF THE BOUNDARY IS ACCEPTABLE.
2. PLEASE SHOW WHERE THE MONUMENT SIGN WILL BE LOCATED
AND WHAT IT WILL BE MADE OUT OF (VINYL, ALUMINUM, ETC).
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : JOHNSTON-WILLIS MED OFF BLDG
CASE NUMBER : 17PR0237
LATEST PLAN DATE : 5/15/17
RECEIVED DATE : 5/23/17
SUBMITTAL NUMBER : 2
REVIEW DATE : 5/23/17
ADDRESS : PENDING
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. SHEET C-11 SHOWS A DETAIL OF THE ADDRESS SIGN AND A
NOTE THAT IT WILL BE A PART OF THE MONUMENT SIGN. PLEASE
SHOW WHERE THE MONUMENT SIGN WILL BE LOCATED AND WHAT IT
WILL BE MADE OUT OF (VINYL, ALUMINUM, ETC).
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : JOHNSTON-WILLIS MED OFF BLDG
CASE NUMBER : 17PR0237
LATEST PLAN DATE : 6/2/17
RECEIVED DATE : 6/9/17
SUBMITTAL NUMBER : 3
REVIEW DATE : 6/12/17
ADDRESS : PENDING
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. SHEET C-11 SHOWS A DETAIL OF THE ADDRESS SIGN AND A
NOTE THAT IT WILL BE A PART OF THE MONUMENT SIGN. PLEASE
SHOW WHERE THE MONUMENT SIGN WILL BE LOCATED AND WHAT IT
WILL BE MADE OUT OF (VINYL, ALUMINUM, ETC).
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : JOHNSTON-WILLIS MED OFF BLDG
CASE NUMBER : 17PR0237
LATEST PLAN DATE : 7/7/17
RECEIVED DATE : 7/12/17
SUBMITTAL NUMBER : 4
REVIEW DATE : 7/13/17
ADDRESS : 1011 JOHNSTON WILLIS DR
STATUS : APPROVED
==========================================================
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: JOHNSTON-WILLIS MED. OFF. BLDG
SITE PLAN NUMBER: 17PR0237
ADDRESS: 10600 MIDLOTHIAN TURNPIKE
LATEST PLAN DATE: 4/24/17
DEPT. REC'D. DATE: 5/1/17
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 5/1/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. REPLACE THE FIR-3 DETAIL ON PAGE C-11 WITH THE 2012 VE
2. ADD A NOTE TO THE UTILITY PLAN STATING:
"THE 4.5 INCH DISCHARGE OF THE FIRE HYDRANT SHALL FACE
IN THE DIRECTION INDICATED BY THE ARROW ON THE PLAN."
3. ADD AN ARROW TO THE FIRE HYDRANT INDICATING WHICH
DIRECTION IT SHALL FACE.
4. SHOW THE NODE MAP AND RESULTS TABLE FOR THE PROPOSED
OR EXISTING HYDRANTS ON SITE SHOWING THE MAXIMUM FIRE
FLOW CAN BE ACHIEVED. WHEN MULTIPLE FIRE HYDRANTS ARE
USED THE COMBINED FLOW MUST BE SIMULTANEOUS.
5. PROVIDE THE DETAILS FOR THE AUTOMATIC SPRINKLER SYSTEM
RUN-IN AND STUB UP, INCLUDING ALL APPLICABLE NOTES. SEE:
HTTP://WWW.CHESTERFIELD.GOV/PUBLICSAFETY/FIRE/PLANS.ASP
FOR A COPY OF THE DETAILS
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: JOHNSTON-WILLIS MED. OFF. BLDG
SITE PLAN NUMBER: 17PR0237
ADDRESS: 10600 MIDLOTHIAN TURNPIKE
LATEST PLAN DATE: 5/15/17
DEPT. REC'D. DATE: 5/22/17
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 5/25/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. A DEDICATED FIRE HYDRANT MUST BE WITHIN 50 FEET OF
THE FDC.
2. NO PARKING STALLS CAN BE IN FRONT OF THE FDC OR HYDRANT
3. PROVIDE THE DETAILS FOR THE AUTOMATIC SPRINKLER SYSTEM
RUN-IN AND STUB UP, INCLUDING ALL APPLICABLE NOTES. SEE:
HTTP://WWW.CHESTERFIELD.GOV/PUBLICSAFETY/FIRE/PLANS.ASP
FOR A COPY OF THE DETAILS
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: JOHNSTON-WILLIS MED. OFF. BLDG
SITE PLAN NUMBER: 17PR0237
ADDRESS: 10600 MIDLOTHIAN TURNPIKE
LATEST PLAN DATE: 6/2/17
DEPT. REC'D. DATE: 6/5/17
SUBMITTAL NUMBER: 3RD REVIEW
REVIEW DATE: 6/6/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. A DEDICATED FIRE HYDRANT MUST BE WITHIN 50 FEET OF
THE FDC.
2. NO PARKING STALLS CAN BE IN FRONT OF THE FDC OR HYDRANT
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: JOHNSTON-WILLIS MED. OFF. BLDG
SITE PLAN NUMBER: 17PR0237
ADDRESS: 10600 MIDLOTHIAN TURNPIKE
LATEST PLAN DATE: 7/7/17
DEPT. REC'D. DATE: 7/12/17
SUBMITTAL NUMBER: 4TH REVIEW
REVIEW DATE: 7/12/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED SITE PLAN IS APPROVED AS SUBMITTED.