All Site Plan Review Comments for Case # 17PR0186
Modify comments view for Case # 17PR0186

Go to Case Selection Form or Go to Project List

 
CASE NO: 17PR0186 STATUS: PENDING APPROVAL
PROJECT NAME: BLUE & GRAY STORAGE - LAST INTERNET UPDATE: 11/21/17
SUBMITTAL TYPE: COMMERCIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 03 10/25/17 11/15/17 ******** ********
ENVIR.ENGR.-: 03 10/25/17 11/15/17 ******** ********
FIRE DEPT.--: 03 10/25/17 11/15/17 COMPLETE 11/01/17 AWB 717-6167
MAPPING/GIS-: 03 10/25/17 11/15/17 COMPLETE 11/13/17 AMJ 768-7549
PLANNING----: 03 10/25/17 11/15/17 COMPLETE 11/15/17 SCP 751-4321
TRANSPORT.--: 03 10/25/17 11/15/17 COMPLETE 11/02/17 SJA 751-4461
UTIL.PLAN.--: 03 10/25/17 11/15/17 ******** ********
UTILITIES---: 03 10/25/17 11/15/17 AMENDED* 10/31/17 M L 748-1338
UTIL.R.O.W.-: 03 10/25/17 11/15/17 ******** ********
VDOT--------: 03 10/25/17 11/15/17 ******** ********
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : BLUE & GRAY STORAGE@ HAMPTON PARK
ADDRESS : 15221 HULL STREET RD
SUBMISSION DATE : 12/7/16
PLAN DATED : 8/31/16
REVIEW DATE : 12/15/16
SITE PLAN NO. : 17PR0186
COMMENTS : 1ST REVIEW-NOT APPROVED
TABLE REVIEW : NO
PLAT PROCESS :
1. PLACE COUNTY PROJECT NUMBER 16-0162 ON THE LOWER RIGHT
CORNER OF EACH SHEET.
2. PLEASE PUT UTILITIES CONTACT MIKE LARSON, P.E. 748-
1338, LARSONM@CHESTERFIELD.GOV ON THE COVER SHEET.
3. UPDATE THE UTILITES MATERIAL QUANTITIES; MUCH OF THE
SANITARY SEWER IS ACTUALLY PRIVATE.
4. DELETE THE FIRST SENTENCE OF GENERAL UTILITY NOTE 17 O
THE COVER SHEET. VANDALPROOF MANHOLE LIDS ARE NOT USED.
5. LABEL THE 8" X 6" TEES AS "HYDRANT TEES".
6. SHOW THE WATER STUBOUT AND BLOW OFF ON THE SUBJECT
PROPERTY.
7. PROVIDE THE D.B AND PAGE NUMBER FOR THE WATER EASEMENT
ON 15301 HULL STREET RD.
8. USE AN 8" X 8" TAPPING SLEEVE AND VALVE FOR THE WATER
CONNECTION. UPDATE THE NOTE ON THE PLAN AND PROFILE.
9. LABEL THE EXISTING PHYSICAL FEATURES THAT WILL BE
IMPACTED (ASPHALT, CURB, ETC AND SHOW THE PROPOSED MEANS O
REPAIR AND REPLACEMENT ON THE PLANS.
10. LABEL THE EXISTING WATER AND SEWER MAINS WITH SIZE,
MATERIAL, AND COUNTY PROJECT NUMBER ON BOTH THE PLAN AND T
PROFILE.
11. SHOW THE EXISTING MANHOLES UPSTREAM AND DOWNSTREAM OF
THE PROPOSED DOGHOUSE MANHOLES ALONG WITH A NOTE SHOWING T
INVERTS ARE FIELD LOCATED AND NOT TAKEN FROM AS-BUILT
DRAWINGS.
12. INSTEAD OF LEAVING A STUBOUT FOR 15211 HULL STREET RD
SET A MANHOLE WITH NO INVERTS ABOUT 4 FT FROM THE PROPERTY
LINE SO THAT A FUTURE EXTENSION CAN BE MADE BY CORE DRILLI
INTO A MANHOLE. A PROFILE IS REQUIRED FOR THIS EXTENSION.
13. WE HAVE RESERVATIONS ABOUT THE CONSTRUCTABILITY OF TH
PROPOSED DOGHOUSE MANHOLE. THE MANHOLE IS OVER 16 FT DEEP
AND ONLY SCALES ABOUT 12-13 FT FROM THE EXISTING WATER LIN
IN TWO LOCATIONS. THE EXCAVATION WILL CREATE A LARGE HOLE
THAT WILL ALMOST CERTAINLY RESULT IN EXPOSURE OF THE WATER
LINE, WHICH IS NOT RESTRAINED. A BETTER SOLUTION WILL BE
EXTEND THE SEWER STRAIGHT DOWN THE EASEMENT LINE SO THAT I
INTERSECTS FURTHER DOWNSTREAM ON THE EXISTING SEWER.
ADDITIONAL EASEMENT WILL BE REQUIRED.
14. LABEL THE WATER AND SEWER LINES ON THE PROFILE AS
EITHER "PUBLIC" OR "PRIVATE".
15. IS THERE A DESIRE FOR AN IRRIGATION METER ON THIS
PROJECT? IF SO, PLEASE SUBMIT A METER SIZING FORM AND SHO
THE METER IN AN EASEMENT ON THE PLANS.
16. A LICENSING AGREEMENT IS REQUIRED FOR PRIVATE STORM
SEWER TO ENCROACH INTO PUBLIC WATER MAIN EASEMENT. PLEASE
CONTACT JOAN COURSON IN OUR RIGHT-OF-WAY DEPARTMENT AT 804
748-1362 TO BEGIN THE PAPERWORK.
16. THE OWNER SHALL BE REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
PRIOR TO THE PREPARATION OF THE UTILITIES CONTRACT,
UTILITIES MUST BE IN RECEIPT OF THE "ACCEPTED" BID PROPOSA
BETWEEN THE DEVELOPER AND THE COUNTY APPROVED UTILITIES
CONTRACTOR AS WELL AS THE PROJECT'S INFORMATIONAL SHEET
FOUND ON THE "DEVELOPER'S CHECKLIST". PLEASE SEND THOSE TW
ITEMS TO THE ATTENTION OF MIKE LARSON
(LARSONM@CHESTERFIELD.GOV). THE BID PROPOSAL MUST BE BASED
ON THE APPROVED SITE PLAN. BE ADVISED THAT IF THE SITE PLA
IS REVISED AND REAPPROVED SUBSEQUENT TO THE PREPARATION OR
RECORDATION OF THE UTILITIES CONTRACT, THE BID PROPOSAL
SHALL BE REVISED ACCORDINGLY AND A REVISED UTILITIES
CONTRACT MAY BE NECESSARY.
17. AFTER FINAL SITE PLAN APPROVAL, SUBMIT THREE SETS OF
THE APPROVED PLANS DIRECTLY TO THE UTILITIES DEPARTMENT FO
OUR USE DURING CONSTRUCTION INSPECTION. THIS IS IN
ADDITION TO THE ONE APPROVED SET FROM PLANNING (4 TOTAL
SETS).
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
.
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : BLUE & GRAY STORAGE@ HAMPTON PARK
ADDRESS : 15221 HULL STREET RD
SUBMISSION DATE : 4/10/17
PLAN DATED : 3/17/17
REVIEW DATE : 4/13/17
SITE PLAN NO. : 17PR0186
COMMENTS : 1ST REVIEW-NOT APPROVED
TABLE REVIEW : YES
PLAT PROCESS :
*SANITARY SEWER LISTED AS PUBLIC IS ACTUALLY PRIVATE. ALSO
SEWER PIPE IS SHOWN ON THE PROFILE AS PVC, NOT DI.
2. LABEL THE 8" X 6" TEES AS "HYDRANT TEES" ON THE PLAN
VIEW AND MATERIALS LIST.
3. AN OFFSITE EASEMENT IS REQUIRED FROM 15211 HULL STREET
RD. FOR THE WATER STUBOUT AND BLOW OFF
4. THE WATER EASEMENT ON 15301 HULL STREET RD IS LABELED
EXISTING, WE DO NOT HAVE RECORD OF THIS EASEMENT BEING
SIGNED.
5. USE AN 8" X 8" TAPPING SLEEVE AND VALVE FOR THE WATER
CONNECTION. UPDATE THE NOTE ON THE PLAN AND PROFILE AND
MATERIALS LIST.
6. LABEL THE EXISTING WATER AND SEWER MAINS WITH SIZE,
MATERIAL, AND COUNTY PROJECT NUMBER ON BOTH THE PLAN AND T
PROFILE. NONE OF THESE ARE SHOWN ON THE PROFILE AND THE
SIZE AND MATERIAL ARE NOT SHOWN ON THE PLAN VIEW.
7. PROVIDE A NOTE ON THE PLAN SHET SHOWING THE INVERTS AR
FIELD LOCATED AND NOT TAKEN FROM AS-BUILT DRAWINGS.
8. SHOW THE LOCATION OF ALL WATER LINE BENDS, TEES, AND
HYDRANTS ON THE PROFILE.
9. FOR SECTIONS OF SANITARY SEWER IN THE VICINITY OF MH 2
C, AND G THAT HAVE 14 OR MORE FT OF COVER, SHOW 1 FT OF
STONE OVER THE TOP OF THE PIPE ON THE PROFILE SHEETS.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : BLUE & GRAY STORAGE@ HAMPTON PARK
ADDRESS : 15221 HULL STREET RD
SUBMISSION DATE : 7/24/17
PLAN DATED : 7/6/17
REVIEW DATE : 7/27/17
SITE PLAN NO. : 17PR0186
COMMENTS : 3RD REVIEW-APPROVED
TABLE REVIEW : YES
PLAT PROCESS :
1. ONCE ALL OTHER APPROVALS HAVE BEEN OBTAINED, SUBMIT 3
COPIES OF THE APPROVED PLANS TO THE UTILITIES DEPARTMENT F
USE DURING CONSTRUCTION
2. AS DISCUSSED, IF THERE ARE ANY CHANGES TO EXTEND SEWER
ERVICE TO THE PARCEL FRONTING HULL STREET RD, PLEASE RESUB
T REVISED PLANS.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : BLUE & GRAY STORAGE@ HAMPTON PARK
ADDRESS : 15221 HULL STREET RD
SUBMISSION DATE : 10/25/17
PLAN DATED : 10/9/17
REVIEW DATE : 10/31/17
SITE PLAN NO. : 17PR0186
COMMENTS : 4TH REVIEW-APPROVED
TABLE REVIEW : YES
PLAT PROCESS :
ONCE ALL OTHER APPROVALS HAVE BEEN OBTAINED, SUBMIT 3 COPI
* APPROVED PLANS TO THE UTILITIES DEPARTMENT FOR USE
2. AS A REMINDER, THE WATER EASEMENT ON 15211 HULL STREET
D MUST BE SIGNED PRIOR TO THIS PROJECT BEING RELEASED TO
NSTRUCTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: BLUE & GRAY STORAGE HAMPTON PARK
SITE PLAN NUMBER: 17PR0186
LATEST PLAN DATE: 12/06/16
DEPT. REC'D. DATE: 12/12/16
SUBMITTAL NUMBER: ONE
REVIEW DATE: 12/13/16
RECOMMENDATION: NOT APPROVED
1. PRIOR TO FINAL SITE PLAN APPROVAL, PROVIDE THE FOLLOWIN
IN ACCORDANCE WITH ZONING CASE 99SN0125:
A. DEDICATE 100' OF RIGHT OF WAY ON THE SOUTH SIDE OF 360
ALONG ENTIRE PROPERTY FRONTAGE (PROF COND 7).
B. ACCESS EASEMENT, ACCEPTABLE TO CDOT, SHALL BE RECORDED
ACROSS THE PROPERTY TO ENSURE SHARED USE OF THE 360 ACCESS
THE PROPOSED ACCESS EASEMENT ON THE PLANS.COND 8). SHOW
2. PROVIDE THE ADDITIONAL LANE OF PAVEMENT ALONG THE ENTIR
PROPERTY FRONTAGE TO 360 (PROF COND 9). LANE SHOULD EXTEND
ABOUT 60' FURTHER WEST THEN TRANSITION BACK INTO 360.
3. PROVIDE PAVEMENT SECTION DESIGN FOR 360 ADDITIONAL LANE
THAT WILL ACCOMMODATE THRU TRAFFIC VOLUME. LANE WILL SERV
AS A RIGHT TURN LANE TO THE SITE UNTIL 360 IS WIDENED.
4. PROVIDE HANDICAP RAMP ON EAST SIDE OF ROUTE 360 ACCESS.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: BLUE & GRAY STORAGE HAMPTON PARK
SITE PLAN NUMBER: 17PR0186
LATEST PLAN DATE: 04/17/17
DEPT. REC'D. DATE: 04/11/17
SUBMITTAL NUMBER: TWO
REVIEW DATE: 04/28/17
RECOMMENDATION: NOT APPROVED
.
FOLLOWING COMMENTS ARE REPEATED FROM FIRST REVIEW:
.
1. PRIOR TO FINAL SITE PLAN APPROVAL, PROVIDE THE FOLLOWIN
IN ACCORDANCE WITH ZONING CASE 99SN0125:
A. DEDICATE 100' OF RIGHT OF WAY ON THE SOUTH SIDE OF 360
ALONG ENTIRE PROPERTY FRONTAGE (P.C. 7).
B. ACCESS EASEMENT, ACCEPTABLE TO CDOT, SHALL BE RECORDED
ACROSS THE PROPERTY TO ENSURE SHARED USE OF THE 360 ACCESS
WITH ADJACENT PROPERTIES TO THE EAST (P.C. 8). AGREEMENT
NEEDS TO PROVIDE NON-EXCLUSIVE ACCESS TO ADJACENT PROPERTY
.
2. SHOW THE PROPOSED PRIVATE ACCESS EASEMENT ON THE PLANS.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: BLUE & GRAY STORAGE HAMPTON PARK
SITE PLAN NUMBER: 17PR0186
LATEST PLAN DATE: 07/14/17
DEPT. REC'D. DATE: 07/26/17
SUBMITTAL NUMBER: THREE (PRUSIK)
REVIEW DATE: 07/26/17
RECOMMENDATION: SUBSTANTIAL APPROVAL
.
FINAL SITE PLAN APPROVAL IS PENDING ZONING CASE 99SN0125:
.
A. DEDICATE 100' OF RIGHT OF WAY ON THE SOUTH SIDE OF 360
ALONG ENTIRE PROPERTY FRONTAGE (P.C. 7 OF 99SN0125).
.
B. ACCESS EASEMENT, ACCEPTABLE TO CDOT, SHALL BE RECORDED
ACROSS THE PROPERTY TO ENSURE SHARED USE OF THE 360 ACCESS
WITH ADJACENT PROPERTIES TO THE EAST (P.C. 8 OF CASE
99SN0125). AGREEMENT NEEDS TO PROVIDE NON-EXCLUSIVE ACCESS
TO ADJACENT PROPERTY.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: BLUE & GRAY STORAGE HAMPTON PARK
SITE PLAN NUMBER: 17PR0186
LATEST PLAN DATE: 10/17/17
DEPT. REC'D. DATE: 10/27/17
SUBMITTAL NUMBER: FOUR (PRUSIK)
REVIEW DATE: 11/02/17
RECOMMENDATION: SUBSTANTIAL APPROVAL
.
FINAL SITE PLAN APPROVAL IS PENDING:
A. DEDICATE 100' OF RIGHT-OF-WAY FOR ROUTE 360 ALONG
PROPERTY FRONTAGE (PC 7 OF CASE 99SN0125).
B. ACCESS EASEMENT, ACCEPTABLE TO CDOT, SHALL BE RECORDED
ACROSS THE PROPERTY TO ENSURE SHARED USE OF ACCESS WITH
ADJACENT PROPERTY TO THE EAST (PC 8 OF CASE 99SN0125).
==========================================================
==========================================================
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: STEVE PRUSIK/ 751-4321
PLAN NAME: BLUE & GRAY STORAGE
PLAN NUMBER: 17PR0186
ORIGINAL PLAN DATE: 08/31/16
REVIEW DATE: 01/05/17
LATEST SUBMISSION DATE: 08/31/16
SUBMITTAL NUMBER: 1
STATUS: NOT APPROVED
TABLE REVIEW: NO
COMMENTS:
ARCHITECTURAL ELEVATIONS: SUBMITTED
LANDSCAPE PLAN: SUBMITTED
LIGHTING PLAN: SUBMITTED
1. PROVIDE AN AUTOCAD FILE DEPICTING THE BOUNDARY
OF THE SELF STORAGE SITE. THE DWG FILE CAN BE SENT
VIA EMAIL.
2. PLEASE PLACE THE CHESTERFIELD COUNTY SITE PLAN
NUMBER (17PR0186) ON THE LOWER RIGHT CORNER OF
EACH SHEET.
3. PLEASE INCLUDE IN THE GENERAL NOTES ON THE
COVER SHEET THAT THE PROJECT IS LOCATED IN THE
ROUTE 360 WEST DESIGN DISTRICT.
4. IN ACCORDANCE WITH ZONING CASE 99SN0125, DEDICATE
100' OF RIGHT OF WAY ON THE SOUTH SIDE OF HULL STREET
ROAD ALONG ENTIRE PROPERTY FRONTAGE (PROF COND 7).
LABEL THE EXISTING RIGHT OF WAY AND THE ULTIMATE
RIGHT OF WAY FOR RTE. 360 EVEN IF THEY ARE THE SAME.
5. PER SEC. 19.1-262 AND 263, SHOW THE REQUIRED BUFFERS
THAT APPLY ON SITES ZONED I (INDUSTRIAL) ADJACENT TO
R, R-TH, R-MF, AND MH DISTRICTS AND ANY A DISTRICT
THAT HAS A RESIDENTIAL USE ON IT OR THE PROPERTY
IS VACANT AND THE COMPREHENSIVE PLAN DESIGNATES
THE PROPERTY FOR A RESIDENTIAL USE. THE COUNTY
COMPREHENSIVE LAND USE PLAN INDICATES THAT THE
PROPERTY TO THE EAST CURRENTLY ZONED "A" IS DEEMED
MEDIUM-HIGH DENSITY RESIDENTIAL REQUIRING A 100 FT
BUFFER WHEN ADJACENT TO PROPERTY ZONED I-1.
6. PLEASE CLEARLY LABEL ALL PROPERTY LINES ON THE
ADJOINING PROPERTIES TO THE EAST, WEST AND SOUTH.
7. PER SEC. 19.1-262(B), USES IN BUFFERS ARE LIMITED TO
LANDSCAPING AND SCREENING, SIGNS, SECURITY
FENCING, UTILITIES THAT RUN PERPENDICULAR THROUGH
THE BUFFER, PEDESTRIAN WALKWAYS, AND SIMILAR
USES AS APPROVED THROUGH SITE OR SCHEMATIC PLAN
REVIEW. A BMP IS NOT A PERMITTED USE.
8. ALL TREES WITHIN THE SETBACK FROM A PUBLIC
RIGHT OF WAY SHALL BE RETAINED UNLESS REMOVAL
IS NECESSARY TO ACCOMMODATE VEHICULAR ACCESS
AND/OR UTILITIES THAT RUN GENERALLY
PERPENDICULAR THROUGH THE SETBACK. THESE TREE
SAVE AREAS SHALL BE SHOWN ON THE EROSION
CONTROL, GRADING AND LANDSCAPE PLANS.
9. REMOVAL OF EXISTING TREES WITHIN THE SETBACK
OR BUFFER WITHOUT WRITTEN APPROVAL FROM THE
PLANNING DEPARTMENT SHALL RESULT IN TWO TREES
BEING PLANTING FOR EACH TREE REMOVED.
10. ANY EXISTING TREES IN SETBACKS THAT ARE APPROVED
FOR REMOVAL SHALL BE SHOWN AS SUCH ON THE EROSION
CONTROL, GRADING AND LANDSCAPE PLANS.
11. PER SEC'S. 19.1-235-236, SHOW YOUR CALCULATION FOR
THE REQUIRED NUMBER OF PARKING SPACES FOR THE SITE.
12. SHOW THE TOTAL REQUIRED AND TOTAL PROVIDED
HANDICAP PARKING SPACES.
13. PER SEC. 19.1-253, PARKING LOTS MUST BE DESIGNED
TO INCLUDE 30 S.F. OF INTERIOR PARKING LOT LANDSCAPING
FOR EACH PARKING SPACE. PROVIDE A CALCULATION FOR
THE TOTAL NUMBER OF PARKING SPACES TIMES 30 S.F. TO
DETERMINE TOTAL LANDSCAPE AREA WITHIN PARKING LOT.
(EXAMPLE: 100 PARKING SPACES X 30 S.F. = 3000 S.F.
LANDSCAPE AREA IN PARKING LOT)
14. PER SEC. 19.1-253, THE TOTAL NUMBER OF TREES IN A
PARKING LOT SHALL BE 1 PER 200 S.F. OF LANDSCAPE AREA
IN THE PARKING LOT. SHOW THE CALCULATION FOR TOTAL
NUMBER OF TREES. (EXAMPLE: 3000 S.F. LANDSCAPE AREA
DIVIDED BY 200 S.F. PER TREE = 15 TREES)
15. PER SEC. 19.1-253, AT LEAST 50% OF THE TREES SHALL
BE LARGE MATURING TREES THAT ARE IN ISLANDS WITH
A MINIMUM WIDTH OF 15 FEET AND 250 SF IN SIZE. SMALL
MATURING TREES SHALL BE IN ISLANDS WITH A MINIMUM
WIDTH OF 9 FEET AND BE 150 SF IN SIZE.
16. PLEASE LABEL THE SURFACE PARKING LANDSCAPE
CALCULATION AREA(S) SQ FT ON THE LANDSCAPE PLAN.
THIS CAN BE SHOWN USING LIGHT HATCHING.
17. PER SEC. 19.1-249, ALL LANDSCAPED AREAS SHALL BE
PROVIDED WITH A READILY AVAILABLE WATER SUPPLY.
THE COUNTY ACCEPTS EITHER YARD HYDRANTS AND/OR
HOSE BIBS WITHIN 100 FEET OF ALL NEW PLANTINGS OR
AN IRRIGATION SYSTEM FOR ALL AREAS OF NEW PLANTINGS.
18. PER SEC. 19.1-205, SHOW ON THE LANDSCAPE PLAN
THE LOCATION OF ALL EXTERIOR SITE LIGHTING MOUNTED
ON POLES TO INSURE THEY DO NOT INTERFERE WITH
PROPOSED LANDSCAPE TREES.
19. PER SEC. 19.1-205, CLEARLY SHOW ON THE LIGHTING
PLAN THE LOCATION OF ALL EXTERIOR SITE LIGHTING
FIXTURES AND HAVE THEM KEYED TO CUT SHEETS FOR
EACH LIGHT FIXTURE SHOWN ON THE PLAN.
20. PER SEC. 19.1-317(C), SHOW THAT JUNCTION AND
ACCESS BOXES ARE EITHER SCREENED OR PAINTED
TO MATCH THE BUILDING EXCEPT AS ALLOWED IN I-2
AND I-3 DISTRICTS.
21. PROVIDE A DUMPSTER ENCLOSURE DETAIL THAT
SPECIFIES MATERIALS AND COLORS. SHOW SIGN LOCATION
ON ENCLOSURE DOOR THAT STATES "NO SERVICE
BETWEEN 9 PM - 6 AM"
22. PLEASE PROVIDE MORE DETAILED INFORMATION
REGARDING THE COLORS AND MATERIALS FOR THE
BUILDING(S) AND ACCESSORIES. IF POSSIBLE, SEND 2
COPIES OF COLOR RENDERINGS/ELEVATIONS
OF THE BUILDINGS WITH ALL BUILDING MATERIALS AND
COLORS IDENTIFIED. ELEVATIONS CAN BE SENT AS A PDF
VIA EMAIL. ELEVATIONS MUST BE APPROVED PRIOR TO
ISSUANCE OF A BUILDING PERMIT.
NOTES:
1. ANY CHANGE IN THE CURRENT PLAN, WHETHER IT
STEMS FROM DEPARTMENT COMMENTS OR AN
ENGINEERING CHANGE REQUESTED BY THE APPLICANT,
MAY GENERATE ADDITIONAL COMMENTS FROM THE
REVIEWING DEPARTMENTS, RESULTING IN REQUIRED
REVISIONS.
2. THE FIRST SUBMITTAL SHALL INCLUDE A PLAN DATE
(MONTH, DAY & YEAR), AND EACH REVISED SET OF PLANS
SHALL SHOW A REVISION DATE.
3. PER SEC. 19.1-246, THE CONCEPTUAL LANDSCAPE PLAN
SHALL BE APPROVED PRIOR TO RELEASE OF FINAL SITE
PLAN APPROVAL. THE PLAN SHALL MEET ALL
REQUIREMENTS OF SEC. 19.1-246.
4. EACH REVIEW OF DETAILED LANDSCAPE PLANS AFTER
APPROVAL OF THE SITE PLAN INCURS A RESUBMITTAL FEE
AND IS TRACKED AS A SITE PLAN REVIEW UNTIL APPROVED.
APPROVAL MUST BE OBTAINED PRIOR TO TEMPORARY
OCCUPANCY OF THE BUILDING.
*************************************************
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: STEVE PRUSIK/ 751-4321
PLAN NAME: BLUE & GRAY STORAGE
PLAN NUMBER: 17PR0186
ORIGINAL PLAN DATE: 08/31/16
REVIEW DATE: 05/01/17
LATEST SUBMISSION DATE: 03/17/17
SUBMITTAL NUMBER: 2
STATUS: NOT APPROVED
TABLE REVIEW: NO
COMMENTS:
ARCHITECTURAL ELEVATIONS: SUBMITTED
LANDSCAPE PLAN: SUBMITTED
LIGHTING PLAN: SUBMITTED
1. PROVIDE AN AUTOCAD FILE DEPICTING THE BOUNDARY
OF THE SELF STORAGE SITE. THE DWG FILE CAN BE SENT
VIA EMAIL.
2. PLEASE PLACE THE CHESTERFIELD COUNTY SITE PLAN
NUMBER (17PR0186) ON THE LOWER RIGHT CORNER OF
THE LANDSCAPE SHEETS.
3. PLEASE LABEL THE ZONNG AND USE FOR ALL THE
ADJOINING PROPERTIES TO THE EAST, WEST AND SOUTH.
4. FOR THE INTERIOR PARKING CALCULATION WHERE
YOU HAVE INDICATED HATCHING AS PART OF THE
GRAPHIC KEY, PLEASE SHOW WHERE THAT
HATCHING APPREARS ON THE PLAN. ALSO, YOU HAVE
INDICATED (3) ARA AND (2) BPW TO SATISFY THE
PARKING PLANTING REQUIREMENTS. THE BPW DO NOT
APPEAR IN THE PLANT SCHEDULE OR ON THE PLAN.
PLEASE ADD OR CORRECT THE LABEL.
5. PLEASE INCLUDE THE CULTIVAR FOR THE PROPOSED
CRAPE MYRTLES.
6. PER SEC. 19.1-317(C), PLACE A NOTE ON THE PLANS THAT
STATES "ALL JUNCTION AND ACCESS BOXES MUST BE
SCREENED OR PAINTED TO MATCH THE BUILDING".
7. PER SEC. 19.1-317.C, PLACE A NOTE ON THE PLANS THAT
STATES "ALL ROOF VENTS AND EXHAUST FANS MUST BE
EITHER SCREENED OR PAINTED TO MATCH THE ROOF
PRIOR TO THE BUILDING PERMIT BEING ISSUED".
8. PER THE PROFFERED CONDITIONS OF ZONING CASE
99SN0125, THE ARCHITECTURE STYLE, MATERIALS
AND COLORS SHALL BE COMPATIBLE TO THE ALTA
STERLING APARTMENT COMPLEX ON THE ADJACENT
PROPERTIES SOUTH AND WEST. AT THIS TIME, THE
ELEVATIONS SUBMITTED CAN NOT BE APPROVED.
PLANNING WOULD LIKE TO SCHEDULE A MEETING TO
DISCUSS THE ARCHITETURE IN MORE DETAIL PRIOR TO
SITE PLAN APPROVAL.
9. PLANNING WOULD LIKE TO SEE THE BUFFER ALONG
HULL STREET (EXCLUDING THE IMMEDIATE ENTRANCE
PLANTINGS) PLANTED WITH A MIX OF NATIVE PLANT
MATERIAL TO RESTORE THIS AREA TO A MORE NATURAL
STATE. RECOMMNEDED SPECIES INCLUDE A MIX OF
REDBUD AND LOBLLOY PINE ALONG THE ROAD
FRONTAGE AND IN FRONT OF THE BMP.
10. DUE TO THE CONCESSION PLANNING HAS GRANTED
TO REDUCE THE 100 FT BUFFER ALONG THE EASTERN
PROPERTY LINE TO 30 FT, PLANNING IS REQUESTING
THAT THE PLANTINGS ALONG THE EASTERN AND
WESTERN PROPERTY LINES BE PLANTED AS 1 & 1/2
LANDSCAPE TYPE C USING AS MANY NATIVE SPECIES
AS POSSIBLE INTERSPERSED ALONG BOTH BUFFERS.
11. THE PLANTINGS ALONG THE WESTERN PROPERTY
LINE SHOULD FILL THE BUFFER UNIFORMILY VERSUS
THREE SMALLER POCKETS OF PLANTINGS.
12. THIS PROJECT IS IN THE 360 WEST DESIGN DISTRICT.
PLEASE REVISE IN THE MAIN TITLE OF COVER SHEET.
13. PLEASE PROVIDE THE ZONING OF THE PROPERTY (I-1) IN
THE NOTES
14. PLEASE PROVIDE THE EXISTING USE OF THE PROPERTY
IN THE NOTES, EVEN IF IT IS VACANT.
15. FOR THE DUMPSTER ENCLOSURE, PLEASE PROVIDE
A DUMPSTER ENCLOSURE DETAIL THAT INDICATES ALL
MATERIALS AND COLORS TO BE USED. ALSO, SHOW THE
SIGN LOCATION ON ENCLOSURE DOOR THAT STATES
"NO SERVICE BETWEEN 9 PM - 6 AM"
16. PLEASE PUT A NOTE ON THE LIGHTING PLAN THAT STATES:
"ALL LIGHT FIXTURES SHALL BE OF A DIRECTIONAL TYPE THAT
SHIELDS THE LIGHT SOURCE FROM DIRECT VIEW FROM ANY
ADJOINING, A, R, R-TH, MH, TND, OR R-MF DISTRICT OR PUBLIC
RIGHT OF WAY". THERE IS CONCERN THAT THE WALL PACKS WILL
NEGATIVELY IMPACT THE ADJOINING APARTMENT COMPLEX.
NOTES:
1. ANY CHANGE IN THE CURRENT PLAN, WHETHER IT
STEMS FROM DEPARTMENT COMMENTS OR AN
ENGINEERING CHANGE REQUESTED BY THE APPLICANT,
MAY GENERATE ADDITIONAL COMMENTS FROM THE
REVIEWING DEPARTMENTS, RESULTING IN REQUIRED
REVISIONS.
2. THE FIRST SUBMITTAL SHALL INCLUDE A PLAN DATE
(MONTH, DAY & YEAR), AND EACH REVISED SET OF PLANS
SHALL SHOW A REVISION DATE.
3. PER SEC. 19.1-246, THE CONCEPTUAL LANDSCAPE PLAN
SHALL BE APPROVED PRIOR TO RELEASE OF FINAL SITE
PLAN APPROVAL. THE PLAN SHALL MEET ALL
REQUIREMENTS OF SEC. 19.1-246.
4. EACH REVIEW OF DETAILED LANDSCAPE PLANS AFTER
APPROVAL OF THE SITE PLAN INCURS A RESUBMITTAL FEE
AND IS TRACKED AS A SITE PLAN REVIEW UNTIL APPROVED.
APPROVAL MUST BE OBTAINED PRIOR TO TEMPORARY
OCCUPANCY OF THE BUILDING.
.
**************************************************
.
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: STEVE PRUSIK/ 751-4321
PLAN NAME: BLUE & GRAY STORAGE
PLAN NUMBER: 17PR0186
ORIGINAL PLAN DATE: 08/31/16
REVIEW DATE: 08/14/17
LATEST SUBMISSION DATE: 07/06/17
SUBMITTAL NUMBER: 3
STATUS: NOT APPROVED
TABLE REVIEW: YES
.
COMMENTS:
.
ARCHITECTURAL ELEVATIONS: SUBMITTED
LANDSCAPE PLAN: SUBMITTED
LIGHTING PLAN: SUBMITTED
.
01. PROVIDE AN AUTOCAD FILE DEPICTING THE BOUNDARY
OF THE SITE. THE DWG FILE CAN BE SENT VIA EMAIL.
.
02. FOR THE INTERIOR PARKING CALCULATION WHERE
YOU HAVE INDICATED HATCHING AS PART OF THE
GRAPHIC KEY, PLEASE SHOW WHERE THAT
HATCHING APPREARS ON THE PLAN (THE HATCHING
SHOULD INDICATE WHERE THE ACTUAL PLANTS ARE
LOCATED - NOT THE 5 PARKING SPACES/PAVEMENT).
.
03. THIS PROJECT IS LOCATED IN THE 360 WEST DESIGN
DISTRICT, NOT THE EMERGING GROWTH AREA. PLEASE
REVISE IN THE MAIN TITLE OF COVER SHEET
(UPPER/MIDDLE OF THE COVER SHEET).
.
04. PLEASE PROVIDE THE CURRENT ZONING OF THE
PROPERTY (I-1) IN THE NOTES. THE ZONING CASE
NUMBER SHOULD BE LISTED AS A SEPARATE LINE.
.
05. PLEASE PROVIDE THE EXISTING USE OF THE PROPERTY
(VACANT) IN THE NOTES, JUST ABOVE THE PROPOSED
USE NOTE.
.
06. PLEASE PUT A NOTE ON THE LIGHTING PLAN THAT STATES:
"ALL LIGHT FIXTURES SHALL BE OF A DIRECTIONAL TYPE THAT
SHIELDS THE LIGHT SOURCE FROM DIRECT VIEW FROM ANY
ADJOINING, A, R, R-TH, MH, TND, OR R-MF DISTRICT OR PUBLIC
RIGHT OF WAY". THERE IS CONCERN THAT THE WALL PACKS WILL
NEGATIVELY IMPACT THE ADJOINING APARTMENT COMPLEX.
.
NOTES:
.
01. ANY CHANGE IN THE CURRENT PLAN, WHETHER IT
STEMS FROM DEPARTMENT COMMENTS OR AN
ENGINEERING CHANGE REQUESTED BY THE APPLICANT,
MAY GENERATE ADDITIONAL COMMENTS FROM THE
REVIEWING DEPARTMENTS, RESULTING IN REQUIRED
REVISIONS.
.
02. PER SEC. 19.1-246, THE CONCEPTUAL LANDSCAPE PLAN
SHALL BE APPROVED PRIOR TO RELEASE OF FINAL SITE
PLAN APPROVAL. THE PLAN SHALL MEET ALL
REQUIREMENTS OF SEC. 19.1-246.
.
03. EACH REVIEW OF DETAILED LANDSCAPE PLANS AFTER
APPROVAL OF THE SITE PLAN INCURS A RESUBMITTAL FEE
AND IS TRACKED AS A SITE PLAN REVIEW UNTIL APPROVED.
APPROVAL MUST BE OBTAINED PRIOR TO TEMPORARY
OCCUPANCY OF THE BUILDING.
.
*************************************************
.
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: STEVE PRUSIK/ 751-4321
PLAN NAME: BLUE & GRAY STORAGE
PLAN NUMBER: 17PR0186
ORIGINAL PLAN DATE: 08/31/16
REVIEW DATE: 11/15/17
LATEST SUBMISSION DATE: 10/09/17
SUBMITTAL NUMBER: 4
STATUS: APPROVED
TABLE REVIEW: YES
.
COMMENTS:
.
ARCHITECTURAL ELEVATIONS: SUBMITTED
LANDSCAPE PLAN: SUBMITTED
LIGHTING PLAN: SUBMITTED
.
NOTES:
.
01. ANY CHANGE IN THE CURRENT PLAN, WHETHER IT
STEMS FROM DEPARTMENT COMMENTS OR AN
ENGINEERING CHANGE REQUESTED BY THE APPLICANT,
MAY GENERATE ADDITIONAL COMMENTS FROM THE
REVIEWING DEPARTMENTS, RESULTING IN REQUIRED
REVISIONS.
==========================================================
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : BLUE + GRAY STORAGE HAMPTON PK
CASE NUMBER : 17PR0186
LATEST PLAN DATE : 12/6/16
RECEIVED DATE : 12/13/16
SUBMITTAL NUMBER : 1
REVIEW DATE : 1/3/17
ADDRESS : 15221, 15223 AND 15231 HULL STREET RD
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. MORE THAN ONE DIRECTION OF TRAVERSE IS SHOWN.
PLEASE REVISE THE SURVEY TO SHOW ONLY ONE PATH OF
TRAVERSE.
2. COORDINATE POINTS BASED ON THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, NORTH AMERICAN DATUM
1983 ARE NOT PRESENT. TWO POINTS MUST BE SHOWN ON THE
PARCEL BOUNDARY.
3. THE PARCEL BOUNDARY SURVEY DOESN'T CLOSE. PLEASE
SUPPLY THE METES AND BOUNDS FOR EVERY SEGMENT ALONG THE
TRAVERSE TO INCLUDE CHORD BEARING AND DISTANCE FOR ALL
NON-TANGENT CURVES. IF THE PARCEL IS TOO LARGE TO
CONVENIENTLY FIT ON ONE SHEET, A LARGER SCALE DRAWING
OF THE BOUNDARY IS ACCEPTABLE.
4. STREET ADDRESS LOCATION IS NOT SHOWN. IT CAN BE
LOCATED ON THE BUILDING, ON A SIGN OR AS A PART OF A
MONUMENT SIGN. LOCATION AND MATERIAL USED MUST BE NOTED
ON THE SITE PLAN. IF YOU ARE USING A MONUMENT SIGN, A
DETAIL OF THE MONUMENT SIGN MUST BE ON THE SITE PLAN.
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : BLUE + GRAY STORAGE HAMPTON PK
CASE NUMBER : 17PR0186
LATEST PLAN DATE : 3/17/17
RECEIVED DATE : 4/12/17
SUBMITTAL NUMBER : 2
REVIEW DATE : 4/28/17
ADDRESS : 15221 HULL STREET RD
STATUS : APPROVED
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : BLUE + GRAY STORAGE HAMPTON PK
CASE NUMBER : 17PR0186
LATEST PLAN DATE : 7/24/17
RECEIVED DATE : 7/27//17
SUBMITTAL NUMBER : 3
REVIEW DATE : 7/27/17
ADDRESS : 15221 HULL STREET RD
STATUS : APPROVED
==========================================================
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : BLUE + GRAY STORAGE HAMPTON PK
CASE NUMBER : 17PR0186
LATEST PLAN DATE : 10/9/17
RECEIVED DATE : 10/27//17
SUBMITTAL NUMBER : 4
REVIEW DATE : 11/13/17
ADDRESS : 15221 HULL STREET RD
STATUS : APPROVED
==========================================================
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: BLUE & GRAY STORAGE HAMPTON PARK
SITE PLAN NUMBER: 17PR0186
ADDRESS: 15221 HULL STREET ROAD
LATEST PLAN DATE: 12/6/16
DEPT. REC'D. DATE: 12/12/16
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 12/15/16
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. ADD A NOTE TO THE UTILITY PLAN STATING:
"THE 4.5 INCH DISCHARGE OF THE FIRE HYDRANT SHALL FACE
IN THE DIRECTION INDICATED BY THE ARROW ON THE PLAN."
2. ADD AN ARROW TO THE FIRE HYDRANT INDICATING WHICH
DIRECTION IT SHALL FACE.
3. THE MINIMUM REQUIRED FIRE FLOW FOR PROTECTION PURPOSES
SHALL BE SHOWN ON THE SUBMITTED DRAWINGS. REFER TO THE
INTERNATIONAL FIRE CODE (2012), SECTION B105 AND THE
COUNTY CODE OF CHESTERFIELD FOR EXCEPTIONS ALLOWED FOR
SPRINKLER PROTECTED BUILDINGS
REFER TO THE INTERNATIONAL FIRE CODE (2012) -
SECTION B104, B104.1, B104.2 AND B104.3 FOR THE CALCULATIO
PROCESS AND ALLOWANCES. THE CORRECT FORMAT AND CALCULATION
SHEET CAN BE OBTAINED VIA THE INTERNET AT
CHESTERFIELD COUNTY- CHESTERFIELD FIRE AND EMS - DIVISION
OF FIRE AND LIFE SAFETY
HTTP://WWW.CHESTERFIELD.GOV/PUBLICSAFETY/FIRE/PLANS.ASP
4. PROVIDE COMPUTER GENERATED WATER FLOW TEST DATA,
PROVIDED BY THE CHESTERFIELD COUNTY UTILITIES
DEPARTMENT, VERIFYING THE REQUIRED WATER FLOW FOR FIRE
PROTECTION IS AVAILABLE AT THE SITE. THE WATERFLOW TEST
RESULTS AND GRAPH SHALL BE SHOWN ON THE SUBMITTED PLAN.
THE MINIMUM REQUIRED FIRE FLOW FOR ALL BUILDINGS, WITH
THE EXCEPTION OF ONE AND TWO-FAMILY DWELLINGS, IS 1500
GPM (SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED) IN
ACCORDANCE WITH THE INTERNATIONAL FIRE CODE (2012) -
SECTION B105.2 AND TABLE B105.1.
5. SHOW THE NODE MAP AND RESULTS TABLE FOR THE PROPOSED
OR EXISTING HYDRANTS ON SITE SHOWING THE MAXIMUM FIRE
FLOW CAN BE ACHIEVED. WHEN MULTIPLE FIRE HYDRANTS ARE
USED THE COMBINED FLOW MUST BE SIMULTANEOUS.
6. BUILDING "E" IS OVER THE 12, 000 SQUARE FOOT THRESHOLD
DOES NOT REQUIRE A SPRINKLER SYSTEM. BUILDING "E" NEEDS TO
EITHER HAVE A SPRINKLER SYSTEM, OR A REDUCTION IN THE SQUA
FOOTAGE OF THE BUILDING. A REDUCTION IN THE SQUARE FOOTAGE
CAN BE ACCOMPLISHED BY INSTALLING A FIRE WALL.
6. PROVIDE THE CHESTERFIELD COUNTY STANDARD FIRE LANE
DETAIL ON THE PLAN.
7. PROVIDE THE GATE DETAIL FOR THE GATE SECURING THE FIRE
APPARATUS ACCESS ROAD. THE DETAILS SHALL COMPLY WITH
THE 2012 INTERNATIONAL FIRE CODE, APPENDIX D,
SECTION D103.5
8. THE APPROXIMATE LOCATION OF ALL REQUIRED FIRE LANE
SIGNS AND CURB / STREET MARKING SHALL BE INDICATED ON
THE PLAN. FIRE LANES THAT ARE BETWEEN TWENTY AND
TWENTY-SIX FEET IN WIDTH SHALL BE POSTED AND MARKED ON
BOTH SIDES OF THE ROADWAY. FIRE LANES IN EXCESS OF
TWENTY-SIX FEET IN WIDTH UP TO THIRTY-TWO FEET IN WIDTH
SHALL BE POSTED AND MARKED ON ONE SIDE OF THE
ROADWAY. THE LOCATION OF AND METHOD OF MARKING FIRE
LANES SHALL BE CLEARLY INDICATED ON THE SUBMITTED SITE
PLAN. ALL FIRE LANE SIGNS SHALL BE DOUBLE FACED AND
INSTALLED PERPENDICULAR TO THE CURB.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: BLUE & GRAY STORAGE HAMPTON PARK
SITE PLAN NUMBER: 17PR0186
ADDRESS: 15221 HULL STREET ROAD
LATEST PLAN DATE: 4/7/17
DEPT. REC'D. DATE: 4/17/17
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 4/18/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. CONFIRM THE BUILDING CONSTRUCTION TYPE AND PROVIDE
THE APPROPRIATE NUMBER OF HYDRANTS TO MEET FIRE
FLOW REQUIREMENTS.
2. PROVIDE COMPUTER GENERATED WATER FLOW TEST DATA,
PROVIDED BY THE CHESTERFIELD COUNTY UTILITIES
DEPARTMENT, VERIFYING THE REQUIRED WATER FLOW FOR FIRE
PROTECTION IS AVAILABLE AT THE SITE. THE WATERFLOW TEST
RESULTS AND GRAPH SHALL BE SHOWN ON THE SUBMITTED PLAN.
THE MINIMUM REQUIRED FIRE FLOW FOR ALL BUILDINGS, WITH
THE EXCEPTION OF ONE AND TWO-FAMILY DWELLINGS, IS 1500
GPM (SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED) IN
ACCORDANCE WITH THE INTERNATIONAL FIRE CODE (2012) -
SECTION B105.2 AND TABLE B105.1.
3. SHOW THE NODE MAP AND RESULTS TABLE FOR THE PROPOSED
OR EXISTING HYDRANTS ON SITE SHOWING THE MAXIMUM FIRE
FLOW CAN BE ACHIEVED. WHEN MULTIPLE FIRE HYDRANTS ARE
USED THE COMBINED FLOW MUST BE SIMULTANEOUS.
4. PROVIDE THE GATE DETAIL FOR THE GATE SECURING THE FIRE
APPARATUS ACCESS ROAD. THE DETAILS SHALL COMPLY WITH
THE 2012 INTERNATIONAL FIRE CODE, APPENDIX D,
SECTION D103.5
5. THE APPROXIMATE LOCATION OF ALL REQUIRED FIRE LANE
SIGNS AND CURB / STREET MARKING SHALL BE INDICATED ON
THE PLAN. FIRE LANES THAT ARE BETWEEN TWENTY AND
TWENTY-SIX FEET IN WIDTH SHALL BE POSTED AND MARKED ON
BOTH SIDES OF THE ROADWAY. FIRE LANES IN EXCESS OF
TWENTY-SIX FEET IN WIDTH UP TO THIRTY-TWO FEET IN WIDTH
SHALL BE POSTED AND MARKED ON ONE SIDE OF THE
ROADWAY. THE LOCATION OF AND METHOD OF MARKING FIRE
LANES SHALL BE CLEARLY INDICATED ON THE SUBMITTED SITE
PLAN. ALL FIRE LANE SIGNS SHALL BE DOUBLE FACED AND
INSTALLED PERPENDICULAR TO THE CURB.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: BLUE & GRAY STORAGE HAMPTON PARK
SITE PLAN NUMBER: 17PR0186
ADDRESS: 15221 HULL STREET ROAD
LATEST PLAN DATE: 7/14/17
DEPT. REC'D. DATE: 7/27/17
SUBMITTAL NUMBER: 3RD REVIEW
REVIEW DATE: 7/31/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. CORRECT THE DATA PROVIDED ON THE FIRE-FLOW
ESTIMATE FORM.
2. PROVIDE COMPUTER GENERATED WATER FLOW TEST DATA,
PROVIDED BY THE CHESTERFIELD COUNTY UTILITIES
DEPARTMENT, VERIFYING THE REQUIRED WATER FLOW FOR FIRE
PROTECTION IS AVAILABLE AT THE SITE. THE WATERFLOW TEST
RESULTS AND GRAPH SHALL BE SHOWN ON THE SUBMITTED PLAN.
THE MINIMUM REQUIRED FIRE FLOW FOR ALL BUILDINGS, WITH
THE EXCEPTION OF ONE AND TWO-FAMILY DWELLINGS, IS 1500
GPM (SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED) IN
ACCORDANCE WITH THE INTERNATIONAL FIRE CODE (2012) -
SECTION B105.2 AND TABLE B105.1.
3. SHOW THE NODE MAP AND RESULTS TABLE FOR THE PROPOSED
OR EXISTING HYDRANTS ON SITE SHOWING THE MAXIMUM FIRE
FLOW CAN BE ACHIEVED. WHEN MULTIPLE FIRE HYDRANTS ARE
USED THE COMBINED FLOW MUST BE SIMULTANEOUS.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: BLUE & GRAY STORAGE HAMPTON PARK
SITE PLAN NUMBER: 17PR0186
ADDRESS: 15221 HULL STREET ROAD
LATEST PLAN DATE: 10/17/17
DEPT. REC'D. DATE: 10/31/17
SUBMITTAL NUMBER: 4TH REVIEW
REVIEW DATE: 11/1/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED SITE PLAN IS APPROVED AS SUBMITTED.