Site Plan Review Comments
All Site Plan Review Comments for Case # 17PR0163
Modify comments view for Case # 17PR0163

Go to Case Selection Form or Go to Project List

 
CASE NO: 17PR0163 STATUS: PENDING APPROVAL
PROJECT NAME: BRECKENRIDGE SHOP CE - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: COMMERCIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 04 09/14/17 10/05/17 ******** ********
ENVIR.ENGR.-: 04 09/14/17 10/05/17 ******** 12/06/16 CBH 776-7836
FIRE DEPT.--: 04 09/14/17 10/05/17 COMPLETE 09/22/17 AWB 717-6167
MAPPING/GIS-: 04 09/14/17 10/05/17 COMPLETE 10/05/17 AMJ 768-7549
PLANNING----: 04 09/14/17 10/05/17 ******** 12/06/16 JHL 751-4158
TRANSPORT.--: 04 09/14/17 10/05/17 COMPLETE 09/19/17 SJA 751-4461
UTIL.PLAN.--: 04 09/14/17 10/05/17 ******** ********
UTILITIES---: 04 09/14/17 10/05/17 AMENDED* 10/06/17 M L 748-1338
UTIL.R.O.W.-: 04 09/14/17 10/05/17 ******** ********
VDOT--------: 04 09/14/17 10/05/17 ******** ********
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : BRECKENRIDGE SHOPPING CENTER
ADDRESS : 12810 JEFFERSON DAVIS HWY
SUBMISSION DATE : 11/3/16
PLAN DATED : 3/29/16
REVIEW DATE : 11/8/16
SITE PLAN NO. : 17PR0163
COMMENTS : 1ST REVIEW-NOT APPROVED
TABLE REVIEW : NO
PLAT PROCESS :
1. PLACE COUNTY PROJECT NUMBER 16-0293 ON THE LOWER RIGHT
CORNER OF EACH SHEET.
2. PLEASE PROVIDE A MORE ADEQUATE TITLE FOR THE PROJECT
SUCH AS "BRECKENRIDGE SHOPPING CENTER RENOVATION" SO THAT
IS DIFFERENT FROM PREVIOUS PLAN SUBMITTALS.
3. PLEASE PUT UTILITIES CONTACT MIKE LARSON, P.E. 748-
1338, LARSONM@CHESTERFIELD.GOV ON THE COVER SHEET.
4. THE STANDARD UTILITIES NOTES ON THE COVER SHEET SHOULD
BE MOVED OUT OF THE APPROXIMATE MATERIALS QUANTITIES TABLE
AND LABELED SEPARATELY.
5. ON THE VICINITY MAP, "IRONBRIDGE RD" SHOULD BE CORRECT
TO "W. HUNDRED RD" WITH THE ROUTE NUMBER AS "10", NOT "100
AS SHOWN.
6. PLEASE BREAK DOWN THE WATER AND SEWER ITEMS ON THE COV
SHEET INTO SEPARATE TABLES FOR PRIVATE AND PUBLIC ITEMS.
7. IDENTIFY EACH PROPOSED WATER OR SEWER ITEM ON THE PLAN
AS EITHER "PRIVATE" OR "PUBLIC" ON BOTH THE PLAN AND PROFI
VIEWS.
8. LABEL ALL EXISTING WATER AND SEWER LINES ON THE EXISTI
CONDITIONS, DEMOLITION, AND UTILITY PLAN AND PROFILE SHEET
WITH THE SIZE, MATERIAL, AND COUNTY PROJECT NUMBER.
9. THE WATER LINES ON JEFFERSON DAVIS HIGHWAY ARE
INCORRECTLY SHOWN. PLEASE EMAIL
SWAVAILABILITY@CHESTERFIELD.GOV TO OBTAIN AS-BUILT
INFORMATION ON EXISTING WATER LINES IN THE AREA.
10. THE OUTPUT FROM THE COMPUTER WATER MODEL INFORMATION
INCLUDED IN THE SITE PLAN PACKAGE MUST BE SHOWN ON THE
PLANS.
11. WE NOTICED THAT THE PROPOSED RETAINING WALL ON THE
SOUTH PROPERTY LINE IS THE TYPE THAT REQUIRE EXCAVATION BA
SEVERAL FEET TO SET ON THE FABRIC. THERE IS NO EASEMENT O
EXCAVATION SHOWN ON THE ADJACENT PROPERTY THAT WOULD ALLOW
CONSTRUCTION OF THIS WALL AS SHOWN. IF THE RETAINING WALL
IS PUSHED BACK AWAY FROM THE PROPERTY LINE, IT WILL ENCROA
IN TO THE PROPOSED WATER EASEMENT, WHICH IS NOT ALLOWED.
12. PER OUR PHONE CONVERSATION, PLEASE RE-EVALUATE IF A
12" PARALLEL WATER LINE IS NECESSARY. THE CONFIGURATION O
LOOPED 8" LINES ON THE SITE WITH CONNECTIONS ON BOTH ROUTE
10 AND ROUTE 1 ALLOWS OVER 3,000 GPM FIRE FLOW TO THE SITE
IF POSSIBLE, THE WATER LINE ON THE REAR OF THE SITE SHOUL
BE RELOCATED AND TIED BACK INTO THE 8" LINE THAT LOOPS
AROUND THE FRONT OF THE BUILDING USING A TEE, TWO SLEEVES
AND TWO VALVES.
13. THE PROPOSED LOCATIONS OF THE FIRE HYDRANTS AT STA
10+24 AND 13+96 ARE NOT ACCEPTABLE AS THEY ARE DEPICTED TO
BE SET UP INTO A SIDE SLOPE.
14. THE UTILITIES DEPARTMENT HAS HAD DISCUSSIONS REGARDIN
THE CO-LOCATION OF OTHER UTILITIES WITHIN THE WATER
EASEMENT; HOWEVER, WE DO NOT SEE THIS SHOWN ON THE PLANS.
PLEASE SHOW THE PROPOSED LOCATION OF THE GAS LINES AND
ELECTRIC AS DISCUSSED. NOTE THAT A LICENSE AGREEMENT WILL
BE REQUIRED THROUGH OUR RIGHT-OF-WAY DEPARTMENT FOR THESE
CO-LOCATIONS.
15. LABEL THE EXISTING ADJACENT PROPERTY OWNERS, JEFFERSO
DAVIS HIGHWAY WITH ROUTE NUMBER AND RIGHT OF WAY WIDTH, AN
PROVIDE A NORTH ARROW ON SHEET 10.
16. THE PLANS MUST IDENTIFY ALL THE VALVE CLOSURES
NECESSARY TO TEMPORARILY SHUT DOWN THE WATER LINES TO MAKE
THE PROPOSED TIE-INS.
17. AS DICUSSED, IT IS PREFERABLE IN THIS SITUATION TO US
INTERIOR DOUBLE CHECK VALVES FOR THE BUILDING SINCE THE
WATER MAIN IS ONLY 50 FT FROM THE BUILDING. PLEASE DISCUS
WITH THE FIRE DEPARTMENT THE NUMBER OF FDC VALVES AND
CONNECTIONS REQUIRED.
18. A 1-1/2" METER IS ADEQUATE TO SERVE ALL THREE TENANTS
BASED ON THE FIXTURE COUNT PROVIDED. THE OWNER MAY CONSIDE
CONSOLIDATING TO A SINGLE ACCOUNT AND INSTALLING PRIVATE
METERS ON TENANTS 1 AND 3 IN ORDER TO SPLIT THE UTILITY
BILL.
19. REPLACE DETAIL MET-7 ON SHEET 15 WITH THE CURRENT
VERSION THAT USES AN HDPE METER BOX. THE KNOCK-DOWN BOX I
NO LONGER ALLOWED.
20. SHOW THE EXISTING AND PROPOSED WATER AND SEWER
EASEMENTS ON SHEET 9. THE EXISTING EASEMENTS MUST BE
LABELED WITH WIDTH, DEED BOOK AND PAGE NUMBER.
21. PROVIDE JOINT RESTRAINT CALCULATIONS. MAKE SURE TO U
A TEST PRESSURE OF 150 PSI WITH 1.5 SAFETY FACTOR
22. PART OF THE SEWER LINE NORTH OF THE BUILDING IS
OBSCURED BY TEXT.
23. CONNECT ALL TENANTS INTO THE EXISTING PRIVATE SANITARY
SEWER IN THE REAR RATHER THAN CORING INTO AN EXISTING
MANHOLE AND INSTALLING A DROP CONNECTION.
24. IT IS OUR UNDERSTANDING THAT ONE OF THE TENANT
PROSPECTS WILL BE A CHAIN PET STORE, WHICH OFTEN INCLUDES
VETERINARY CLINIC INSIDE THE STORE. PLEASE NOTE THAT A
VETERINARY CLINIC WILL REQUIRE THE USE OF A REDUCED PRESSU
PRINCIPLE BACKFLOW PREVENTER AND MONITORING MANHOLE ON THE
LATERAL FOR THAT TENANT.
25. PROVIDE NUMBERING FOR THE EXISTING SANITARY MANHOLES
BASED UPON THE NUMBERS USED ON THE AS-BUILT PLANS, FOR
EXAMPLE MH-EX1, MH-EX2, ETC.
26. IF A DROP CONNECTION MUST BE MADE INTO AN EXISTING
MANHOLE, IT SHALL BE CALLED OUT AS AN INSIDE DROP CONNECTI
PER DETAIL MAN-16. THIS DETAIL ALSO MUST BE PROVIDED ON T
PLANS.
27. THE OWNER SHALL BE REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
PRIOR TO THE PREPARATION OF THE UTILITIES CONTRACT,
UTILITIES MUST BE IN RECEIPT OF THE "ACCEPTED" BID PROPOSA
BETWEEN THE DEVELOPER AND THE COUNTY APPROVED UTILITIES
CONTRACTOR AS WELL AS THE PROJECT'S INFORMATIONAL SHEET
FOUND ON THE "DEVELOPER'S CHECKLIST". PLEASE SEND THOSE TW
ITEMS TO THE ATTENTION OF MIKE LARSON
(LARSONM@CHESTERFIELD.GOV). THE BID PROPOSAL MUST BE BASED
ON THE APPROVED SITE PLAN. BE ADVISED THAT IF THE SITE PLA
IS REVISED AND REAPPROVED SUBSEQUENT TO THE PREPARATION OR
RECORDATION OF THE UTILITIES CONTRACT, THE BID PROPOSAL
SHALL BE REVISED ACCORDINGLY AND A REVISED UTILITIES
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : BRECKENRIDGE SHOPPING CENTER
ADDRESS : 12810 JEFFERSON DAVIS HWY
SUBMISSION DATE : 2/8/17
PLAN DATED : 1/13/17
REVIEW DATE : 1/27/17
SITE PLAN NO. : 17PR0163
COMMENTS : 2ND REVIEW-NOT APPROVED
TABLE REVIEW : NO
PLAT PROCESS :
1. ON THE MATERIALS LIST, CORPORATION STOPS, WATER SERVIC
LINES UP TO AND INCLUDING THE METER ARE PUBLIC. WATER
SERVICE LINES PAST THE METER ARE PRIVATE. BACKFLOW
PREVENTERS ARE PRIVATE.
2. SHEET 5 REFERS TO INSTALLATION OF A 12 INCH WATER LINE
WHICH IS NO LONGER APPLICABLE.
3. ON SHEET 5, SHOW AND CALL OUT THE SPECIFIC VALVES TO B
CLOSED IN ORDER TO PLUG THE WATER LINES.
4. ON SHEET 5, REFER TO THE SHEET NUMBER WHERE THE
CONSTRUCTION SEQUENCE IS WRITTEN.
5. INDICATE THE SIZE, TYPE, AND COUNTY PROJECT NUMBER FOR
THE EXISTING WATER LINE PROFILE ON SHEET 13. ADDITIONALLY
THE LABEL FOR THIS INFORMATION ON THE PLAN VIEW IS OBSCURE
BY TEXT
6. JOINT RESTRAINT CALCULATIONS HAVE NOT YET BEEN RECEIVE
PLEASE SEND VIA EMAIL TO LARSONM@CHESTERFIELD.GOV
7. A STANDARD BURIED VALVE IS REQUIRED AT THE EASEMENT LI
AS A POINT OF DEMARCATION BETWEEN PRIVATE AND PUBLIC WATER
LINE FOR EACH FIRE SERVICE LINE.
8. MOVE THE CLEAN OUT SHOWN ON THE SOUTHERNMOST TENANT FR
THE WATER SERVICE TO THE SANITARY SERVICE.
9. THE TWO NEW WATER METERS SHOULD BE LOCATED IN BETWEEN
THE WATER LINE AND BUILDING. BACK TAPPING AS SHOWN IS NOT
DESIRED BY OPERATIONS.
10. REVISE THE NOTES THAT CALL FOR "DOUBLE DETECTOR
CHECK", "DETECTOR CHECK" OR "DD" IN THE MATERIALS LIST AND
CALL OUTS. DETECTOR CHECKS ARE ONLY REQUIRED WHEN THE FIR
LINE SERVES PRIVATE HYDRANTS OR ARE VERY LONG. THE CORREC
DESIGNATION SHOULD BE A "DOUBLE CHECK".
11. PROVIDE A NOTE THAT EACH FIRE HYDRANT IS SET SO THAT
HAS A LEAST 3 FT OF CLEAR FLAT SPACE BETWEEN THE HYDRANT A
TOE OF SLOPE.
12. EACH OF THE TWO FIRE SERVICE LINES ON THE WEST SIDE O
THE BUILDING ARE TO BE CUT-IN TEES WITH TWO SHORT PIECES O
PIPE AND TWO APPROVED COUPLINGS.
13. THE CONNECTION TO THE EXISTING WATER LINE AT STA 9+96
SHOULD BE WITH A 45 DEGREE BEND AT THE END OF THE LINE
RATHER THAN A TAPPING SLEEVE AND VALVE.
14. THE CONNECTION AT ST 14+52 SHOULD BE IN A CUT-IN TEE
WITH 2 VALVES AND 2 COUPLINGS. THIS IS THE LOCATION WHERE
IT MAKES THE MOST SENSE FOR THE "JUMPER" (DETAIL WAT-06) T
BE INSTALLED.
15. AS INDICATED ON THE PDF I SENT 1/27/17, A TEMPORARY
FLUSHING HYDRANT WILL BE NEEDED PRIOR TO THE TIE IN AS WEL
AS A THRUST BLOCK AS THE EXISTING WATER MAIN IS NOT
RESTRAINED.
16. PLEASE MAKE SURE TO RECORD THE COUNTY WATER EASEMENT
FIRST SO THAT WE HAVE PRIOR RIGHTS FOR THE OVERLAPPING
EASEMENTS.
17. IT IS UNCLEAR ON SHEET 13 IF THE POWER LINE WILL
ENCROACH INTO THE WATER EASEMENT. IF IT DOES, THEN A
LICENSE AGREEMENT WILL BE REQUIRED PRIOR TO RELEASE TO
CONSTRUCTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : BRECKENRIDGE SHOPPING CENTER
ADDRESS : 12810 JEFFERSON DAVIS HWY
SUBMISSION DATE : 4/5/17
PLAN DATED : 3/17/17
REVIEW DATE : 4/11/17
SITE PLAN NO. : 17PR0163
COMMENTS : 3RD REVIEW-NOT APPROVED
TABLE REVIEW : YES, CONDITIONALLY
PLAT PROCESS :
.
1. ON SHEET 5, SHOW AND CALL OUT THE SPECIFIC VALVES TO B
CLOSED IN ORDER TO PLUG THE WATER LINES.
2. THE CONNECTION AT STA 13+58 SHOULD INCLUDE A VALVE ON
E WEST SIDE OF THE TEE AND REFERENCE A JUMPER PER DETAIL W
-6.
.
.
SO THAT THE LINE BEHIND THE BUILDING CAN BE PUT BACK INTO
RVICE QUICKLY. THIS PLUG WILL REQUIRE A THRUST BLOCK AS T
EXISTING LINE IS NOT RESTRAINED.
4. A TEMPORARY FLUSHING HYDRANT IS NEEDED AT STA 10+41.
5. PLEASE REVISIT THE SEQUENCE OF CONSTRUCTION NOTES ON S
ET 7. SEVERAL OF THE NOTES UNDER PHASE II E&S STILL REFER
CE CONSTRUCTION OF A RETAINING WALL, WHICH HAS BEEN ELIMIN
ED. FROM A UTILITY STANDPOINT, THE WATER LINE WILL
FIRST NEED TO BE SHUT DOWN USING THE VALVES THAT ARE TO BE
LEARLY LABELED ON SHEET 5. THE PIPE WILL THEN BE CUT AND
PPED AT THE LOCATIONS NECESSARY, AND WATER TURNED BACK ON.
WATER WILL THEN HAVE TO BE CUT OFF USING THE EXISTING
VALVES ON THE EAST OF THE BUILDING TO CUT IN THE TEE. A J
PER WILL BE INSTALLED ON THIS TEE PER WAT-6,AND FROM THERE
HE CONTRACTOR CAN LAY PIPE UP TO STA 10+41. AT THE SAME T
E, THE CONTRACTOR CAN CUT IN THE TEES ON THE WEST WATER LI
FOR FIRE CONNECTIONS. THE CONTRACTOR WILL THEN USE THE T
PORARY FLUSHING HYDRANT TO FLUSH THE MAIN DURING TESTING,
D ONCE IT PASSES THE BAC-T AND PRESSURE TEST THE
FLUSHING HYDRANT AND CAP CAN BE REMOVED AND THE PIPE JOINE
THE CONTRACTOR CAN THEN REMOVE THE JUMPER. THIS SEQUENC
OF CONSTRUCTION WILL REQUIRE A LOT OF UP FRONT SCHEDULING
THE TIE INS SO MAKE SURE THAT THE CONTRACTOR FACTORS THIS
NTO THEIR OVERALL SCHEDULE.
6. REMOVE THE NOTE THAT SAYS "TEMPORARY BAC-T TESTING" AT
NE OF THE FIRE SERVICE LINES. THESE LINES WILL BE TREATED
S TIE-INS WHERE THEY WILL BE SWABBED WITH BLEACH SOLUTION.
7. ON THE SOUTHERN TENANT, THERE IS A NOTE THAT SAYS "SAN
ARY LATERAL 6" PVC AT 2" MIN W/INTERNAL REDUCED PRESSURE Z
E BACKFLOW PREVENTER". THE REFERENCE TO THE BACKFLOW PREV
TER BELONGS WITH THE WATER SERVICE LINE.
8. THERE IS A NOTE ON SHEET 12 NEAR THE SOUTHEAST CORNER
THE BUILDING THAT REFERS TO AN EXISTING GATE VALVE POTENT
L
LOCATION PROPOSED PER ORIG PLAN. THERE IS NO EXISTING OR
OPOSED GATE VALVE AT THIS LOCATION. PLEASE CLARIFY THE
INTENT OF THIS NOTE
9. THERE IS A NOTE ON SHEET 12 REFERRING TO SHEET 21 FOR
E LOCATION OF THE SHUT OFF VALVES. SHEET 21 DOES NOT SHOW
NY VALVE LOCATIONS, PLEASE CLARIFY.
10. THE FITTING WHERE THE WATER LINE IS DISCONNECTED NEAR
TA 13+58 SHOULD BE AN M.J. CAP, NOT PLUG.
11. SHOW THE PROPOSED GRADING ON THE REVISED WATERLINE PR
ILE.
12. THE PRIVATE FIRE LINE COMING OFF THE EXISTING 8" DOUB
CHECK AT THE SOUTHWEST CORNER OF THE BUILDING IS SHOWN DI
ERENTLY ON SHEET 12 AND SHEET 13. ONE SHEET SHOWS A 90
DEGREE BEND, THE OTHER SHOWS A TEE. PLEASE RESOLVE SO THE
SHEETS ARE IN AGREEMENT.
13. PLEASE LABEL THE FIRE SERVICE LINES SO THAT IT IS CLE
*THE GATE VALVE AT THE EASEMENT LINE IS PUBLIC AND THE SER
CE LINE FROM THE VALVE TO THE BUILDING IS PRIVATE.
14. THE SOUTHWEST 1-1/2" WATER METER TAP LOCATION SHOULD C
E OFF THE NEW LINE AT APPROXIMATELY STA 10+60. THE LATERA
SHOULD EXTEND PERPENDICULAR FROM THE LINE AND SET
THE METER BOX 3 FT FROM THE EDGE OF THE BUILDING. FOR THI
SPECIFIC APPLICATION, SPECIFY AND OLDCASTLE ENCLOSURE SOLU
ONS H-SERIES POLYMER CONCRETE BOX, SIZE 17 X 30 TO INCLUDE
CAST IRON READER LID. ENSURE THE EASEMENT
INCLUDES THE METER AND LATERAL
15. SEVERAL OF THE EXISTING WATER LINES BEHIND THE KROGER
D SMALL SHOPS (DON PAPA, TROPICAL SMOOTHIE, AVAIL) ARE NOT
HOWN ACCURATELY. PLEASE UPDATE PER THE AS-BUILT DRAWINGS
AILED TO CHRIS MULLIGAN AND BILL JOHNS ON APRIL 11, 2017.
APPEARS THAT A 1" WATER LINE SERVES THE SMALL SHOPS AND T
T THERE IS A DOUBLE CHECK VALVE VAULT BEHIND THE SMALL SHO
THAT MAY STILL BE PROVIDING FIRE PROTECTION. PLEASE CLAR
Y IF THIS VAULT IS TO BE ABANDONED ON THE SITE PLAN.
16. THE PLANS SHOW TWO 1-1/2" METERS AND TWO 5/8" METER.
HE METER SIZING FORMS ON SHEET 20 SHOW A 1-1/2" METER, A 1
METER, AND A 5/8" METER, AND THE BOTTOM SECTION WHERE THE
UNTY SIGNS THE FORM IS CUT OFF ON TWO OF THE FORMS.
PLEASE UPDATE THE METER SIZING FORMS TO MATCH THE PLANS.
MAY BE SIMPLER TO DELETE THE FORMS OFF THE PLANS AND SEND
PDF DIRECTLY TO MIKE LARSON.
17. WE HAVE NOT YET RECEIVED THRUST RESTRAINT CALCULATION
*PLEASE SUBMIT BY EMAIL TO MIKE LARSON.
18. AS A CONDITION OF A TABLE REVIEW, A PDF OF EACH REVIS
SHEET AND A COMMENT RESPONSE MUST BE SENT TO MIKE LARSON
DAY PRIOR TO THE TABLE REVIEW DATE.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : BRECKENRIDGE SHOPPING CENTER
ADDRESS : 12810 JEFFERSON DAVIS HWY
SUBMISSION DATE : 5/5/17
PLAN DATED : 5/1/17
REVIEW DATE : 5/18/17
SITE PLAN NO. : 17PR0163
COMMENTS : 4TH REVIEW-NOT APPROVED
TABLE REVIEW : YES
PLAT PROCESS :
1. PLEASE REFER TO THE PDF MARK UPS OF SHEET 12 AND 13 SE
TO BILL JOHNS AND CHRIS MULLIGAN ON 5/18/17, WHICH ARE MO
LY CLARIFICATIONS OF PREVIOUS COMMENTS AND SOME MINOR CORR
TIONS.
2. PRIOR TO A TABLE REVIEW, PLEASE SUBMIT REVISED PDFS FO
*E TO CHECK AT LEAST 2 DAYS AHEAD OF TIME.
3. SUBMIT REVISED METER SIZING FORMS. A SEPARATE FORM IS
EEDED FOR EACH TENANT AND MUST CORRELATE TO THE METERS SHO
ON THE PLANS. ENSURE THAT PART C WHERE THE COUNTY SIGNS
NOT CUT OFF.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : BRECKENRIDGE SHOPPING CENTER
ADDRESS : 12810 JEFFERSON DAVIS HWY
SUBMISSION DATE : 9/14/17
PLAN DATED : 9/12/17
REVIEW DATE : 10/5/17
SITE PLAN NO. : 17PR0163
COMMENTS : 5TH REVIEW-NOT APPROVED
TABLE REVIEW : YES
PLAT PROCESS :
1. PLEASE PUT REVISION DATES ON THE PLAN SHEETS SO THAT TH
*CAN EASILY BE DIFFERENTIATED FROM PREVIOUS SUBMISSIONS.
2. WE UNDERSTAND THAT THE WATER/FIRE SYSTEM WILL BE
REVISED, THEREFORE WE WILL HOLD ANY COMMENTS RELATED TO TH
* REVISIONS UNTIL PRESENTED.
3. THE EXISTING SANITARY SEWER AND ALSO THE WATER SERVICE
THAT SERVES D6 AND D7 SHOULD BE SHOWN TO BE CAPPED AND ABA
*NED.
4. THE PRIVATE WATER SERVICE LINES TO TENANTS 5, 6, AND 7
E LONG, PLEASE MAKE SURE THAT THE SIZE OF THE LINE COMPLIE
WITH THE PLUMBING CODE REQUIREMENTS FOR THAT LENGTH OF RUN
5. AS DISCUSSED IN A MEETING WITH BILL JOHNS, THE MONITORI
*MANHOLES ARE NORMALLY PRIVATE. ANY SEWER LINE THAT DOES
6. UPDATE THE QUANTITIES ON THE COVER PAGE ONCE THE REVISI
S ARE MADE. CURRENTLY, THE NUMBER OF METERS CALLED OUT IS
OT CORRECT AND THE NEW PUBLIC SEWER ITEMS ARE MISSING, PLE
E CHECK THE OTHER QUANTITIES.
7. THERE IS A NOTE STATING TO RELOCATE THE EXISTING 1-1/2"
METER FOR TENANTS D3 AND D4, WHICH WE THINK IS SUPPOSED TO
E D2 AND D3. THIS METER WILL NOT ACTUALLY BE RELOCATED, I
WILL BE ABANDONED AND A NEW METER AND BOX WILL BE SET FOR
THOSE TENANTS. PLEASE NOTE THAT THE CREDIT FOR THIS EXIST
* METER WILL HAVE TO STAY WITH THE NEW PARCEL THAT IS SET
8. THERE IS AN ENCROACHMENT OF A CONCRETE LOADING DOCK IN
E PROPOSED SEWER EASEMENT BETWEEN MH B AND MH C. PLEASE R
LIGN THE SEWER TO ELIMINATE THIS ENCROACHMENT.
9. LABEL THE SEWER LINES ON THE PROFILES AS EITHER "PUBLIC
OR "PRIVATE" AS APPLICABLE.
10. THE MINIMUM COVER FOR PVC SANITARY SEWER UNDER PAVED
F
* THE RUN FROM MONITORING MANHOLE C1 TO MH C HAS AT LEAST
11. THE SERVICE LINES FOR TENANTS D3, D4, AND D5 SHOULD BE
*OWN AS PRIVATE 6" LATERALS. IT IS ACCEPTABLE TO PUT A PR
12. THE SERVICE FOR TENANTS D6 AND D7 IS REQUIRED TO BE PU
IC SINCE IT CROSSES A PROPERTY LINE. 8" PUBLIC CONNECTION
ARE REQUIRED TO CONNECT AT A MANHOLE, NOT A 8" X 8" TEE.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: BRECKENRIDGE SHOPPING CENTER RENO
SITE PLAN NUMBER: 17PR0163
LATEST PLAN DATE: 11/01/16
DEPT. REC'D. DATE: 11/04/16
SUBMITTAL NUMBER: ONE
REVIEW DATE: 11/29/16
RECOMMENDATION: NOT APPROVED
1. CDOT HAS EVALUATED THE USE OF THE EXISTING ACCESS
EASEMENT TO THE BIG LOTS PROPERTY AND TOPOGRAPHY WILL
PRECLUDE THIS CONNECTION. CDOT WOULD RECOMMEND EVALUATING
IF A PEDESTRIAN WAY (CONCRETE/ASPHALT) COULD BE PROVIDED T
PROVIDE A SAFE WALKWAY BETWEEN SHOPPING CENTERS. THERE IS
A DEFINED TRAIL BETWEEN CENTERS TODAY BUT IS UNSAFE.
2. UPON APPROVAL OF THIS SITE PLAN, THERE WILL BE NO
REMAINING DENSITY ON THE PARCELS ZONED AS PART OF CASE
86SN0156.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: BRECKENRIDGE SHOPPING CENTER RENO
SITE PLAN NUMBER: 17PR0163
LATEST PLAN DATE: 01/17/17
DEPT. REC'D. DATE: 01/23/17
SUBMITTAL NUMBER: TWO
REVIEW DATE: 01/30/17
RECOMMENDATION: APPROVED
.
UPON APPROVAL OF THIS SITE PLAN, THERE WILL BE NO REMAININ
DENSITY ON THE PARCELS ZONED AS PART OF CASE 86SN0156.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: BRECKENRIDGE SHOPPING CENTER RENO
SITE PLAN NUMBER: 17PR0163
LATEST PLAN DATE: 04/04/17
DEPT. REC'D. DATE: 04/11/17
SUBMITTAL NUMBER: THREE
REVIEW DATE: 04/19/17
RECOMMENDATION: APPROVED
.
UPON APPROVAL OF THIS SITE PLAN, THERE WILL BE NO REMAININ
DENSITY ON THE PARCELS ZONED AS PART OF CASE 86SN0156.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: BRECKENRIDGE SHOPPING CENTER RENO
SITE PLAN NUMBER: 17PR0163
LATEST PLAN DATE: 05/12/17
DEPT. REC'D. DATE: 05/16/17
SUBMITTAL NUMBER: FOUR (FAST TRACK - JHL)
REVIEW DATE: 05/18/17
RECOMMENDATION: APPROVED
.
UPON APPROVAL OF THIS SITE PLAN, THERE WILL BE NO REMAININ
DENSITY ON THE PARCELS ZONED AS PART OF CASE 86SN0156.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: BRECKENRIDGE SHOPPING CENTER RENO
SITE PLAN NUMBER: 17PR0163
LATEST PLAN DATE: 09/12/17
DEPT. REC'D. DATE: 09/15/17
SUBMITTAL NUMBER: FIVE (FAST TRACK - JHL)
REVIEW DATE: 09/19/17
RECOMMENDATION: APPROVED
.
ADVISORY COMMENT: UPON APPROVAL OF THIS SITE PLAN, THERE
WILL BE NO REMAINING DENSITY ON THE PARCELS ZONED AS PART
OF CASE 86SN0156.
==========================================================
==========================================================
**********************************************************
REVIEW DEPARTMENT------PLANNING
REVIEWER / PHONE #-----JEFF LAMSON
NAME OF PLAN-----------BRECKENRIDGE SHP CTR RENOVATION
SITE PLAN NUMBER-------17PR0163
ADDRESS----------------12810 JEFFERSON DAVIS HWY
LATEST PLAN DATE-------11-1-16
DEPT. REC'D. DATE------11-1-16
SUBMITTAL NUMBER-------ONE
REVIEW DATE------------12-6-16
RECOMMENDATION---------REVISION REQUESTED
TABLE REVIEW-----------NO
PLAT PROCESSING--------
LANDSCAPE PLAN STATUS-- NOT YET SUBMITTED
ARCHITECTURAL ELEVATIONS--SEE COMMENTS
LIGHTING PLAN/CUTSHEETS---NOT YET SUBMITTED
IRRIGATION/HOSEBIB PLAN---NOT YET SUBMITTED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT
10 FULL SETS AND ONE COPY OF THE SITE PLAN SHEET TO THE
PLANNING DEPARTMENT FOR YOUR NEXT REVIEW. PROVIDE A COMPLE
RESPONSE TO COMMENTS FOR ALL DEPARTMENTS TO THE PLANNING
DEPARTMENT.
BELOW EACH COMMENT TO DESCRIBE HOW YOU HAVE ADDRESSED EACH
REVIEW COMMENT. BE SURE TO INDICATE WHICH SHEETS SHOW THE
REQUIRED CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE
ANY CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
2. SPECIFY THE ZONING CASE(S) THAT ESTABLISHED THE ZONING
FOR THE SITE. [SEC. 19.1-27.F] 92SN0169
.
3. ON THE TITLE SHEET, CONFIRM SPELLING OF THE APPLICANT A
OWNERS NAME.
.
4. LABEL THE 75 FOOT BUFFER ON ALL PLAN SHEETS
.
5. PER SEC. 19.1-262.B, USES IN BUFFERS ARE LIMITED TO
LANDSCAPING AND SCREENING, SIGNS, SECURITY FENCING,
UTILITIES THAT RUN PERPENDICULAR THROUGH THE BUFFER,
PEDESTRIAN WALKWAYS, AND SIMILAR USES AS APPROVED THROUGH
SITE OR SCHEMATIC PLAN REVIEW.
WORK IN THE BUFFER AREA:
MINIMIZE DISTURBANCE IN THE BUFFER AREA. ROUTING OF SEWER
AND STORMWATER LINES SHOULD BE ALIGNED PERPENDICULAR TO TH
BUFFER. CAN THE SEWER CONECTION BE MADE AT THE EXISTING MH
NEAR THE CURB?
.
6. MAINTAIN ACCESS TO THE BUILDING LOCATED AT 12900
JEFFERSON DAVIS HWY. CONTACT OWNER PRIOR TO STARTING WORK
ADJACENT TO THIS PROPERTY.
.
7. PER SEC'S. 19.1-235 & 236, SHOW YOUR CALCULATION FOR
THE REQUIRED NUMBER OF PARKING SPACES FOR ALL USES ON THE
SITE.
.
SHOW THE TOTAL NUMBER OF PARKING SPACES PROVIDED ON
THE SITE PLAN PER TABLE 19.1-236.A.
.
==========================================================
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : BRECKENRIDGE SHOPPING CENTER
CASE NUMBER : 17PR0163
LATEST PLAN DATE : 11/1/16
RECEIVED DATE : 11/7/16
SUBMITTAL NUMBER : 1
REVIEW DATE : 11/23/16
ADDRESS : NOT ASSIGNED YET
STATUS : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. COORDINATE POINTS BASED ON THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, NORTH AMERICAN DATUM 1983
ARE NOT PRESENT. TWO POINTS MUST BE SHOWN ON THE PARCEL
BOUNDARY.
2. THE PARCEL BOUNDARY SURVEY IS INCOMPLETE. PLEASE
SUPPLY THE METES AND BOUNDS FOR EVERY SEGMENT ALONG THE
TRAVERSE TO INCLUDE CHORD BEARING AND DISTANCE FOR ALL
NON-TANGENT CURVES. IF THE PARCEL IS TOO LARGE TO
CONVENIENTLY FIT ON ONE SHEET, A LARGER SCALE DRAWING
OF THE BOUNDARY IS ACCEPTABLE.
3. LOCATION OF STREET ADDRESS SIGN IS NOT SHOWN. THE
ADDRESS CAN BE PART OF YOUR MONUMENT SIGN. THIS DOES
NOT COUNT AS PART OF THE SQUARE FOOTAGE OF THE SIGN.
IF YOU ARE USING THE MONUMENT SIGN FOR THE ADDRESS, A
DETAIL OF THE MONUMENT SIGN NEEDS TO BE ON THE SITE
PLAN.
4. SPECIFY THE MATERIAL THAT THE ADDRESS SIGN IS TO BE
MADE OF. THE MATERIAL USED MUST BE MORE DURABLE THAN
WOOD.
5. HOW MANY RETAIL SHOPS WILL BE IN THE BUILDING? WE
NEED TO KNOW THIS SO WE CAN ASSIGN THE RIGHT NUMBER OF
ADDRESSES.
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : BRECKENRIDGE SHOPPING CENTER
CASE NUMBER : 17PR0163
LATEST PLAN DATE : 1/13/17
RECEIVED DATE : 1/23/16
SUBMITTAL NUMBER : 2
REVIEW DATE : 2/3/17
ADDRESS : NOT ASSIGNED YET
STATUS : APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. HOW MANY RETAIL SHOPS WILL BE IN THE BUILDING? WE
NEED TO KNOW THIS SO WE CAN ASSIGN THE RIGHT NUMBER OF
ADDRESSES.
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : BRECKENRIDGE SHOPPING CENTER
CASE NUMBER : 17PR0163
LATEST PLAN DATE : 4/4/17
RECEIVED DATE : 4/10/17
SUBMITTAL NUMBER : 3
REVIEW DATE : 4/25/17
ADDRESS : NOT ASSIGNED YET
STATUS : APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. ADDRESSES WILL NOT BE ASSIGNED UNTIL THE NUMBER OF
RETAIL SHOPS HAVE BEEN DETERMINED.
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : BRECKENRIDGE SHOPPING CENTER
CASE NUMBER : 17PR0163
LATEST PLAN DATE : 5/1/17
RECEIVED DATE : 5/22/17
SUBMITTAL NUMBER : 4
REVIEW DATE : 5/24/17
ADDRESS : NOT ASSIGNED YET
STATUS : APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. ADDRESSES WILL NOT BE ASSIGNED UNTIL THE NUMBER OF
RETAIL SHOPS HAVE BEEN DETERMINED.
==========================================================
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON (N) 768-7549
PROJECT NAME : BRECKENRIDGE SHOPPING CENTER
CASE NUMBER : 17PR0163
LATEST PLAN DATE : 9/6/17
RECEIVED DATE : 9/15/17
SUBMITTAL NUMBER : 5
REVIEW DATE : 10/5/17
ADDRESS : NOT ASSIGNED YET
STATUS : APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. ADDRESSES WILL NOT BE ASSIGNED UNTIL THE NUMBER OF
RETAIL SHOPS HAVE BEEN DETERMINED.
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: BRECKENRIDGE SH. CENTER RENO
SITE PLAN NUMBER: 17PR0163
ADDRESS: 12810 JEFFERSON DAVIS HIGHWAY
LATEST PLAN DATE: 11/1/16
DEPT. REC'D. DATE: 11/7/16
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 12/5/16
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. PROVIDE DETAILS AS TO THE METHOD TO BE USED TO PROVIDE
ACCESS TO ALL EXTERIOR POINTS OF THE BUILDING FROM
WITHIN 150 FEET OF AN APPROVED EMERGENCY FIRE APPARATUS
ACCESS ROADWAY. SEE THE 2012 INTERNATIONAL FIRE CODE,
SECTION 503.1.1 FOR CODE INFORMATION AND EXCEPTIONS.
IN ACCORDANCE WITH THE PROVISIONS OF THE INTERNATIONAL
FIRE CODE, SECTION 503, 503.1 THROUGH 503.1.3, FIRE LANES
BE PROVIDED. THE MINIMUM UNOBSTRUCTED CLEAR WIDTH SHALL
BE TWENTY FEET. THE MINIMUM REQUIRED VERTICAL CLEARANCE
SHALL BE THIRTEEN-FEET SIX-INCHES.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: BRECKENRIDGE SH. CENTER RENO
SITE PLAN NUMBER: 17PR0163
ADDRESS: 12810 JEFFERSON DAVIS HIGHWAY
LATEST PLAN DATE: 1/17/17
DEPT. REC'D. DATE: 1/20/17
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 1/26/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. SHOW THE LOCATION 0F THE FDC FOR THE SECTION OF BUILDIN
LOCATED TO THE NORTH OF THE FIRE WALL.
2. HYDRANTS SHALL BE LOCATED AT A MAXIMUM DISTANCE OF 50
FEET BETWEEN HYDRANT AND FIRE DEPARTMENT CONNECTION
FOR ANY PROPOSED FIRE SPRINKLER SYSTEM.
3. PROVIDE THE DETAILS FOR THE AUTOMATIC SPRINKLER SYSTEM
RUN-IN AND STUB UP, INCLUDING ALL APPLICABLE NOTES. SEE:
HTTP://WWW.CHESTERFIELD.GOV/PUBLICSAFETY/FIRE/PLANS.ASP
FOR A COPY OF THE DETAILS
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: BRECKENRIDGE SH. CENTER RENO
SITE PLAN NUMBER: 17PR0163
ADDRESS: 12810 JEFFERSON DAVIS HIGHWAY
LATEST PLAN DATE: 4/4/17
DEPT. REC'D. DATE: 4/10/17
SUBMITTAL NUMBER: 3RD REVIEW
REVIEW DATE: 4/24/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED SITE PLAN IS APPROVED AS SUBMITTED.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: BRECKENRIDGE SH. CENTER RENO
SITE PLAN NUMBER: 17PR0163
ADDRESS: 12810 JEFFERSON DAVIS HIGHWAY
LATEST PLAN DATE: 5/12/17
DEPT. REC'D. DATE: 5/22/17
SUBMITTAL NUMBER: 4TH REVIEW
REVIEW DATE: 5/25/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED SITE PLAN IS APPROVED AS SUBMITTED.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: BRECKENRIDGE SH. CENTER RENO
SITE PLAN NUMBER: 17PR0163
ADDRESS: 12810 JEFFERSON DAVIS HIGHWAY
LATEST PLAN DATE: 9/12/17
DEPT. REC'D. DATE: 9/19/17
SUBMITTAL NUMBER: 5TH REVIEW
REVIEW DATE: 9/22/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. REVIEW DOES NOT INDICATE PROPER NUMBER AND OR LOCATION
OF FIRE HYDRANTS. THE NUMBER OF FIRE HYDRANTS REQUIRED
SHALL BE BASED ON THE INTERNATIONAL FIRE CODE - SECTION
C105 AND TABLE C105.1 FOR AVERAGE SPACING BETWEEN FIRE
HYDRANTS AND MAXIMUM DISTANCE FROM ANY POINT ON A STREET
OR ROAD FRONTAGE TO A FIRE HYDRANT. A MINIMUM DISTANCE OF
40 FEET SHALL BE PROVIDED BETWEEN FIRE HYDRANTS AND
BUILDING EXTERIOR WALL AND FIRE HYDRANTS SHALL BE
LOCATED AT A MAXIMUM DISTANCE OF 50 FEET BETWEEN HYDRANT
AND FIRE DEPARTMENT CONNECTION FOR ANY PROPOSED FIRE
SPRINKLER SYSTEM OR STANDPIPE SYSTEM.
2. THE FIRE DEPARTMENT SUGGEST HAVING 1 FDC SUPPLY THE ENT
BUILDING AND RELOCATING A HYDRANT TO MEET DISTANCE
REQUIREMENTS BETWEEN THE FIRE HYDRANT AND THE FDC.
==========================================================
==========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : CATHY HILL, P.E. / 768-7836
NAME OF PLAN : BRECKENRIDGE SHOPPING CENTER
ADDRESS : 12810 JEFFERSON DAVIS HWY
SITE PLAN NO. : 17PR0163
LATEST PLAN DATE : 11/1/2016
DEPT. REC'D DATE : 11/3/2016
SUBMITTAL NUMBER : 1
REVIEW DATE : 12/1/2016
RECOMMENDATION : NOT APPROVED
TABLE REVISION : NO
PLAT PROCESSING : NOT APPROVED
01. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL
FEATURES INCLUDING BUT NOT LIMITED TO WETLANDS,
SURFACE WATERS (E.G. VSMP PERMIT FOR CONSTRUCTION
SITES, GROUND WATER AND AIR QUALITY) FINAL APPROVAL
OF THESE PLANS WILL NOT RELIEVE YOU OF YOUR
RESPONSIBILITY. WETLANDS DOCUMENTATION MUST BE
RECEIVED BY THIS DEPARTMENT PRIOR TO ISSUANCE OF THE
LAND DISTURBANCE PERMIT.
(CL-XX #) REPRESENTS A SUBMITTAL CHECKLIST COMMENT -
SECTION AND COMMENT NUMBER
02. EFFECTIVE JULY 1, 2014, ENFORCEMENT OF THE VIRGINIA
STORMWATER REGULATIONS BECAME THE RESPONSIBILITY OF
THE COUNTY FOR DEVELOPMENT PROJECTS WITHIN
CHESTERFIELD COUNTY. ADDITIONALLY, NEW STATE
STORMWATER REGULATIONS ALSO BECAME EFFECTIVE ON
JULY 1, 2014. LAND DISTURBING ACTIVITIES THAT
OBTAINED A VSMP PERMIT PRIOR TO JULY 1, 2014 MAY
USE THE STORMWATER MANAGEMENT CRITERIA SPECIFIED
IN PART II C (9VAC25-870-93 ET SEQ) FOR TWO PERMIT
CYCLES. PROJECTS GRANDFATHERED UNDER THE PROVISIONS
OF 9VAC25-870-48 MAY FOLLOW THE REQUIREMENTS LISTED
UNDER PART IIC FOR ONE PERMIT CYCLE. ALL OTHER NEW
DEVELOPMENT WILL BE SUBJECT TO THE REQUIREMENTS OF
PART IIB (9VAC25-870-62 TO 9VAC25-870-92).
03. PROVIDE THE FOLLOWING INFORMATION ON THE COVER SHEET:
A. LATITUDE AND LONGITUDE FOR THE PROJECT SITE (IN DECIMA
DEGREES TO 4 DECIMAL PLACES)
B. TOTAL ON-SITE IMPERVIOUS COVER IN SQUARE FEET
(EXCLUDING VDOT RIGHTS-OF-WAY AND GRAVELED AREAS)
BROKEN UP BY PHASES AND PARCELS.
04. A BENCHMARK MUST BE SHOWN WITH REFERENCE TO
MEAN SEA LEVEL. (CL-GENERAL 11)
05. PROVIDE A PRE-DEVELOPED DRAINAGE AREA MAP TO VERIFY
PRE- AND POST-DEVELOPED DISCHARGES.
06. CLARIFY HOW RUNOFF WILL BE CONVEYED FROM THE SOUTH
SIDE OF THE PROPOSED RETAINING WALL TO STRUCTURE 2.
07. IN THE ABSENCE OF A DETAILED SOILS REPORT, THE
MAXIMUM VELOCITY ALLOWABLE ON BARE EARTH IS 3.5 FPS.
VELOCITIES BETWEEN 3.5 FPS AND 4.0 FPS REQUIRE A
JUTE LINING AND ANY VELOCITIES GREATER THAN 4.0 FPS
REQUIRE A STRUCTURAL LINING OF EITHER RIP RAP OR
CONCRETE. (CL-G&D 5) THIS APPLIES TO THE EXISTING
DRAINGE DITCH (WITHIN THE SHADY ACRES SUBDIVISION)
RECEIVING THE POND DISCHARGE.
08. WHAT TYPE OF BUSINESS WILL BE USING THE BUILDINGS
WITH THE DEPRESSED LOADING DOCK? AN ADDITIONAL DRY
WELL MAY BE REQUIRED BETWEEN THE TRENCH DRAIN AND THE
STORM SEWER TO CATCH SPILLS PRIOR TO ENTERING THE
STORM SYSTEM.
09. CALCULATIONS MUST BE SUBMITTED TO SUPPORT THE DESIGN O
ALL PROPOSED CULVERTS, OPEN DITCHES, DROP INLETS, AND
STORM SEWERS ON VDOT STANDARD CALCULATION SHEETS.
(CL-G&D 11) PRE- AND POST-DEVELOPMENT CALCULATIONS FOR
THE EXISTING 24" RCP (BEHIND THE PROPOSED RENOVATION)
MUST BE SUBMITTED.
10. CLARIFY IF THE EXISTING 24" RCP IS CONVEYING THE STORM
SEWER RUNOFF (FROM EXISTING STORM STRUCTURE 118/119, A
LABELED ON THE BRECKENRIDGE PHASE I AND PHASE II PLANS
INTO THE DITCH WITHIN THE SHADY ACRES SUBDIVISION. IF
THE PIPE IS CONVEYING STORMWATER, CAN THE PIPE BE
REMOVED AND STORM REROUTED TO THE EXISTING BASIN? THE
ORIGINAL BRECKENRIDGE PHASE I AND PHASE II PLANS SHOW
THAT THE BASIN IS DESIGNED TO HANDLE THE RUNOFF FROM
THE ENTIRE SHOPPING CENTER.
11. PROVIDE A DETAIL SHOWING THE PROPOSED MASONRY WALL AND
EXISTING 24" DIAMETER RCP PIPE TO ENSURE NO CONFLICTS
OCCUR.
12. ALL EXISTING AND PROPOSED STORM SEWERS, CULVERTS, DROP
INLETS AND APPURTENANCES MUST BE ASSIGNED A STRUCTURE
NUMBER AND LISTED IN TABULAR FORM ON THE PLAN SHEET ON
WHICH THEY ARE LOCATED. (CL-G&D 14)
13. STEPS STD. ST-1 MUST BE SPECIFIED IN THE TABULAR
DRAINAGE DESCRIPTION OF ANY STRUCTURE OVER 4 FEET IN
HEIGHT. (CL-G&D 20)
14. BOOT CONNECTORS MUST BE SPECIFIED IN THE TABULAR
DRAINAGE DESCRIPTION FOR ALL PLASTIC PIPES THAT TIE
INTO A CONCRETE STRUCTURE. (CL-G&D 21) THIS APPLIES TO
THE HDPE PIPE CONNECTING INTO STORM STRUCTURE 3.
15. STORM PIPES MUST CONNECT AT A STORM STRUCTURE (DROP
INLET, MANHOLE, JUNCTION BOX) AND CANNOT TIE INTO THE
SIDE OF A PIPE. REVISE FOR STORM PIPE 4 - 5.
16. WITH REGARD TO THE PREVIOUS COMMENT, CLARIFY HOW/IF TH
EXISTING ROOF DRAINS TIE INTO EXISTING STORM PIPES 119
AND 121 (AS LABELED ON THE BRECKENRIDGE SHOPPING CENTE
PHASE I AND PHASE II PLANS). IF THE EXISTING STORM
PIPE IS IN DISREPAIR DUE TO THE MULTIPLE TIE-INS, IT
MAY NEED TO BE REPLACED. A NEW ROOF DRAIN CONNECTION
FROM THE BUILDING TO A STORM STRUCTURE IS PREFERRED.
17. TOP OF CURB ELEVATIONS MUST BE SHOWN AT THE NOSE OF AL
RADIAL CURB AND AT ALL APPRECIABLE BREAKS IN HORIZONTA
OR VERTICAL ALIGNMENT. (CL-G&D 22)
18. DRY GUTTER IS REQUIRED WHERE RUNOFF FLOWS AWAY FROM TH
FACE OF CURB. THESE AREAS MUST BE CROSS-HATCHED AND A
DETAIL PROVIDED ON THE PLAN FOR CONSTRUCTION OF DRY
GUTTER. (CL-G&D 23)
19. THE SYMBOL USED FOR DRY GUTTER ON THE PLAN VIEW MUST B
SHOWN ADJACENT TO THE DETAIL FOR ITS CONSTRUCTION.
(CL-G&D 24)
20. ALL EXISTING AND PROPOSED DRAINAGE EASEMENTS MUST BE
SHOWN. (CL-G&D 27)
21. THE DEED BOOK AND PAGE NUMBER OF ALL EXISTING DRAINAGE
EASEMENTS MUST BE SHOWN ON THE PLAN. (CL-G&D 28)
22. COUNTY GIS SHOWS AN EXISTING DRAINAGE EASEMENT ALONG
THE SOUTH WEST PORTION OF THE EXISTING BUILDING, WHERE
THE PROPOSED DEPRESSED LOADING AREA IS TO BE LOCATED.
A. IF STORM SEWER EXISTS WITHIN THIS EASEMENT, SHOW THE
STORM PIPES/STRUCTURES ON THE DEMOLITION PLAN.
B. THE PORTION OF THE EASEMENT NO LONGER NEEDED MUST BE
VACATED PRIOR TO ISSUANCE OF A BUILDING PERMIT FOR THI
PROJECT.
23. DRAINAGE EASEMENTS MUST BE SHOWN ALONG ANY STORMWATER
CONVEYANCE SYSTEM WHICH RECEIVES RUNOFF FROM OFFSITE,
FROM A PUBLIC RIGHT OF WAY OR REQUIRES IMPROVEMENTS ON
A DOWNSTREAM PROPERTY OWNER. (CL-G&D 29)
24. A SEPARATE PLAN SHEET MUST BE ADDED WHICH ONLY SHOWS
ALL PROPOSED EASEMENTS AND RIGHT OF WAY TO BE
DEDICATED. METES AND BOUNDS MUST BE PROVIDED.
(CL-G&D 30)
25. A PAVEMENT DESIGN IS REQUIRED FOR ALL PAVED AREAS.
(CL-G&D 34)
26. THE RADIUS OF ALL RADIAL CURBING MUST BE SHOWN.
(CL-G&D 35)
===================== EROSION CONTROL ===================
27. THE EROSION CONTROL PLAN AND SEQUENCE/NARRATIVE MUST B
DIVIDED INTO A MINIMUM OF TWO PHASES.
PHASE I SHALL SHOW THE MINIMAL AMOUNT OF CLEARING TO
INCLUDE DIMENSIONS FOR CONSTRUCTION OF ALL PERIMETER-
CONTROL DEVICES, AND STRATEGICALLY PLACED SEDIMENT
TRAPS AND BASINS, ASSOCIATED DIVERSIONS AND DIVERSION
DIKES, AND SPOIL AND BORROW AREAS FOR THE INSTALLATION
OF EROSION CONTROL MEASURES.
PHASE II WILL INCLUDE ALL REMAINING CLEARING, GRADING,
AND INSTALLATION OF REMAINING EROSION CONTROL DEVICES,
INSTALLATION OF TEMPORARY AND PERMANENT IMPROVEMENTS,
AND TEMPORARY AND PERMANENT SEEDING AND STABILIZATION.
(CL-EC 1)
28. A DETAILED SEQUENCE OF CONSTRUCTION IS REQUIRED WHICH
COORDINATES THE INSTALLATION AND REMOVAL OF THE
EROSION AND SEDIMENT CONTROL MEASURES WITH CONSTRUCTIO
OF THE REMAINDER OF THE PROJECT. (CL-EC 3)
29. A NOTE MUST BE ADDED TO THE CONSTRUCTION SEQUENCE WHIC
REQUIRES THE OWNER TO GIVE THE COUNTY INSPECTOR 48
HOURS NOTIFICATION TO SCHEDULE AN ON-SITE PRE-
CONSTRUCTION MEETING FOR THE ISSUANCE OF A LAND
DISTURBANCE PERMIT. THIS NOTE SHOULD BE THE FIRST STE
IN THE EROSION CONTROL NARRATIVE/SEQUENCE OF
CONSTRUCTION. (CL-EC 4)
30. A NOTE MUST BE ADDED TO THE SEQUENCE OF CONSTRUCTION
STATING THAT THE CERTIFIED RESPONSIBLE LAND DISTURBER
(CRLD) MUST ATTEND THE PRE-CONSTRUCTION MEETING.
(CL-EC 5)
31. A NOTE MUST BE ADDED TO THE SEQUENCE OF CONSTRUCTION
STATING THAT THE VSMP CONSTRUCTION ACTIVITY OPERATOR
AND THE ENVIRONMENTAL INSPECTOR (OR AUTHORIZED
REPRESENTATIVE) MUST ATTEND THE PRE-CONSTRUCTION
MEETING.
32. THE FOLLOWING NOTES MUST BE ADDED TO THE PLANS:
A. "ALL VEGETATIVE AND STRUCTURAL EROSION AND SEDIMENT
CONTROL PRACTICES WILL BE CONSTRUCTED AND MAINTAINED
ACCORDING TO MINIMUM STANDARDS AND SPECIFICATIONS OF
THE VIRGINIA EROSION AND SEDIMENT CONTROL HANDBOOK AND
VIRGINIA REGULATION 9 VAC 25-840-40." (CL-EC 18)
B. "THE CONTRACTOR SHALL INSPECT ALL EROSION CONTROL
MEASURES PERIODICALLY AND AFTER EACH RUNOFF PRODUCING
RAINFALL EVENT. ANY NECESSARY REPAIRS OR CLEANUP TO
MAINTAIN THE EFFECTIVENESS OF THE EROSION CONTROL
DEVICES SHALL BE MADE IMMEDIATELY. (CL-EC 22)
C. "ALL DISTURBED AREAS ARE TO DRAIN TO APPROVED SEDIMENT
CONTROL MEASURES AT ALL TIMES DURING LAND DISTURBING
ACTIVITIES AND DURING SITE DEVELOPMENT UNTIL FINAL
STABILIZATION IS ACHIEVED." (CL-EC 23)
D. "THE CONTRACTOR IS RESPONSIBLE FOR THE INSTALLATION OF
ANY ADDITIONAL EROSION CONTROL MEASURES NECESSARY TO
PREVENT EROSION AND SEDIMENTATION AS DETERMINED BY THE
ENVIRONMENTAL ENGINEERING DEPARTMENT". (CL-EC 24)
33. THE MOST RECENT VERSION OF EROSION CONTROL MINIMUM
STANDARD # 1, (SEE THE VIRGINIA EROSION AND SEDIMENT
CONTROL LAW AND REGULATIONS FOR FY 2013) MUST BE ADDED
TO THE PLANS AND ALL OTHER NOTES WHICH ARE IN CONFLICT
MUST BE ADJUSTED OR REMOVED. (CL-EC 25)
34. TABLE 3.31-B, FOUND IN THE CURRENT EDITION OF THE
VIRGINIA EROSION AND SEDIMENT CONTROL HANDBOOK, MUST B
PROVIDED ON THE EROSION CONTROL PLAN SHEETS. (CL-EC 26
35. SPECIFY INLET PROTECTION FOR THE GRATE INLETS TO THE
NORTH OF THE PROJECT.
36. REVISE THE UTILITY TRENCH DETAIL ON SHEET 7 TO SHOW
SILT FENCE AND STOCKPILED MATERIALS PLACED ON THE
DOWNSTREAM SIDE OF THE EXCAVATION. (CL-EC 37)
37. PROVIDE CONTOURS FOR THE AREHG, LLC AND BRANCH
BANKING & TRUST PARCELS TO THE EAST OF THIS PROJECT.
THE DISTURBANCE FOR THE WATERLINE CONNECTION MUST BE
SHOWN WITH APPROPRIATE EROSION CONTROL MEASURES ON THE
DOWNSTREAM SIDE.
38. IN THE COMMENTS BELOW MINIMUM STANDARD 2 (SHEET 5),
PROVIDE A NOTE THAT SILT FENCE WILL BE PLACED AROUND
ALL SOIL STOCKPILES ON-SITE.
39. BLANKET AND MATTING MUST BE SPECIFIED ON ALL EXPOSED
SLOPES 3:1 OR GREATER THAT ARE 5 FEET OR GREATER IN
HEIGHT.
40. ALL SILT MUST BE CLEANED FROM THE DETENTION BASIN PRIO
TO RE-CERTIFICATION. A NOTE MUST BE PROVIDED IN THE
EROSION CONTROL NARRATIVE. (CL-EC 41)
41. THE FOLLOWING NOTE(S) MUST BE ADDED TO OR ADJACENT TO
THE SEQUENCE OF CONSTRUCTION: (CL-EC 42)
A. THE PORTION OF THE DRAINAGE EASEMENT TO THE SOUTH OF
THE EXISTING BUILDING THAT IS NO LONGER NEEDED MUST BE
VACATED PRIOR TO ISSUANCE OF A BUILDING PERMIT FOR THI
PROJECT.
B. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
SURETY FOR THE CONSTRUCTION OF THE PERMANENT BMP MUST
BE POSTED WITH ENVIRONMENTAL ENGINEERING. (COUNTY CODE
PART II, CHAPTER 8, SEC. 8-16)
C. THE BMP MUST BE RE-CERTIFIED PRIOR TO RELEASE OF THE
BMP PERFORMANCE BOND.
D. BMP CERTIFICATION DOCUMENTATION MUST INCLUDE THE
FOLLOWING:
I. AS-BUILT SURVEY OF THE FACILITY
II. CERTIFICATION FORM PROVIDING AS-BUILT
ELEVATIONS/DIMENSIONS OF BMP ELEMENTS (INCLUDING,
BUT NOT LIMITED TO: UNDERDRAINS, GRAVEL LAYER,
MEDIA LAYER, MULCH, OUTFALL STRUCTURE, GRAVEL
DIAPHRAGM, UNDERGROUND DETENTION STRUCTURES, ETC.)
III. CERTIFICATION FORM PROVIDING AS-BUILT VOLUMES FOR
STORMWATER QUALITY AND QUANTITY (1-, 2-, 10-, AND
100-YEAR, AS APPLICABLE)
IV. PHOTOGRAPHIC DOCUMENTATION SHALL BE PROVIDED WHICH
COVERS THE CONSTRUCTION/INSTALLATION PROCESS
V. THE CERTIFICATION DOCUMENTATION MUST BE STAMPED
AND SIGNED BY A PROFESSIONAL ENGINEER, CERTIFIED
LAND SURVEYOR, OR ARCHITECT.
E. AT THE TIME OF THE PRE-CONSTRUCTION MEETING, TWO
STANDARD SIGNS MUST BE INSTALLED ON EACH SIDE OF THE
CONSTRUCTION ACCESS. THESE SIGNS SHOULD STATE EITHER
"CONSTRUCTION ENTRANCE AHEAD" OR "TRUCKS ENTERING
HIGHWAY". (CL-EC 42E)
===============CBPA/STORMWATER MANAGEMENT ================
42. THE VIRGINIA RUNOFF REDUCTION SPREADSHEET MUST BE
SUBMITTED TO VERIFY POLLUTANT REMOVAL REQUIREMENTS.
43. PROVIDE THE FULL ROUTING CALCULATIONS FOR THE BASIN.
44. THE ROUTING CALCULATION SUMMARY ON SHEET 13 FOR THE
FULL POND DOES NOT APPEAR TO ACCOUNT FOR THE ENTIRE
DRAINAGE AREA HANDLED BY THE EXISTING BASIN.
45. THE ENERGY BALANCE CALCULATIONS SHOULD RESULT IN AN
ALLOWABLE POST-DEVELOPED 1 YEAR DISCHARGE OF 11.8 CFS,
NOT 2.53 CFS.
46. PROVIDE A DRAINAGE MAP OF THE TOTAL DRAINAGE AREA TO
THE BASIN. CLEARLY DELINEATE THE 4.25-ACRE SITE AREA
FOR THIS PROJECT.
47. A TRASH RACK MUST BE PROVIDED FOR THE RISER ASSEMBLY.
A DETAIL IS REQUIRED. (CL-CBPA 30)
48. A DETAIL MUST BE PROVIDED ON THE PLAN SHOWING THE
METHOD OF SECURING THE METAL TRASH RACK / ANTI VORTEX
DEVICE TO THE CONCRETE RISER PIPE. (CL-CBPA 31)
49. PROVISIONS MUST BE MADE IN THE EROSION CONTROL
NARRATIVE FOR THE SWM/BMP FACILITY TO BE OBSERVED
BY A PROFESSIONAL ENGINEER DURING CONSTRUCTION. "AS
BUILT" INFORMATION WILL BE REQUIRED FOR FUTURE
CERTIFICATION OF THE FACILITY. CERTIFICATION IS
REQUIRED PRIOR TO RELEASE OF THE SWM/BMP PERFORMANCE
BOND AND ANY CERTIFICATE OF OCCUPANCY. (CL-CBPA 42)
============== NONPOINT NUTRIENT OFFSETS ===============
50. PRIOR TO PLAN APPROVAL, DOCUMENTATION OF THE OWNER'S
ACQUISITION OF THE NONPOINT NUTRIENT OFFSETS MUST BE
PROVIDED IN A CERTIFICATION FROM THE OFFSET BROKER
DOCUMENTING THE NUMBER OF PHOSPHOROUS NONPOINT NUTRIEN
OFFSETS ACQUIRED AND THE ASSOCIATED RATIO OF NITROGEN
NONPOINT NUTRIENT OFFSETS AT THE OFFSET GENERATING
FACILITY.
51. NOTE THAT THE NONPOINT NUTRIENT OFFSETS USED FOR WATER
QUALITY COMPLIANCE MUST BE GENERATED IN THE SAME OR
ADJACENT EIGHT DIGIT HYDROLOGIC UNIT CODE AS DEFINED B
THE UNITED STATES GEOLOGICAL SURVEY AS THE SITE.
NONPOINT NUTRIENT OFFSETS OUTSIDE THE SAME OR ADJACENT
EIGHT DIGIT HYDROLOGIC UNIT CODE MAY ONLY BE USED IF I
IS DETERMINED THAT NO NONPOINT NUTRIENT OFFSETS ARE
AVAILABLE WITHIN THE SAME OR ADJACENT EIGHT DIGIT
HYDROLOGIC UNIT CODE. IN SUCH CASES, THE NONPOINT
NUTRIENT OFFSETS MUST BE GENERATED WITHIN THE SAME
TRIBUTARY. PROVIDE A HYDROLOGIC UNIT MAP SHOWING THE
LOCATION OF THE PROJECT AND THE OFFSET GENERATING
FACILITY.
52. THE CBPA COMPLIANCE NOTE MUST SPECIFY THE NUMBER OF
PHOSPHOROUS NONPOINT NUTRIENT OFFSETS ACQUIRED
AND THE NAME OF THE OFFSET GENERATING FACILITY.
======================= CLOSING ========================
53. IT IS THE RESPONSIBILITY OF THE OWNER TO PROVIDE ONE
ADDITIONAL SET OF PLANS TO THE ENVIRONMENTAL
ENGINEERING DEPARTMENT AND OBTAIN AN "APPROVED FOR
CONSTRUCTION" STAMP ON TWO ADDITIONAL SETS FOR THE
OWNER TO KEEP ON-SITE.
54. PERMISSION MUST BE OBTAINED FROM THE ADJACENT PROPERTY
OWNER(S) ALLOWING FOR GRADING ON THE PROPERTY AS
PROPOSED PRIOR TO ISSUANCE OF A LAND DISTURBANCE
PERMIT.
55. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, THE
NAME, "WALK-IN" ADDRESS, AND TELEPHONE NUMBER OF
A LOCAL REGISTERED AGENT REPRESENTING THE OWNER FOR
SERVICE OF PROCESS MUST BE PROVIDED ON THE "APPOINTMEN
OF AGENT FOR SERVICE OF PROCESS" FORM FOUND ON THE
CHESTERFIELD COUNTY ENVIRONMENTAL ENGINEERING WEBPAGE.
(CL-GENERAL 12)
56. THE POLLUTION PREVENTION PLAN MUST BE PROVIDED TO THE
ENVIRONMENTAL ENGINEERING INSPECTOR PRIOR TO ISSUANCE
OF A LAND DISTURBANCE PERMIT. THE CHESTERFIELD COUNTY
POLLUTION PREVENTION PLAN SHEET MAY BE PROVIDED IN THE
CONSTRUCTION PLANS (THIS IS AVAILABLE ON THE
ENVIRONMENTAL ENGINEERING DOCUMENTS AND FORMS WEBPAGE)
57. AS-BUILT BMP INFORMATION WILL BE REQUIRED FOR EACH
BMP FACILITY AS PART OF ITS FUTURE CERTIFICATION.
58. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
SURETY FOR THE CONSTRUCTION OF THE PERMANENT BMP MUST
BE POSTED WITH ENVIRONMENTAL ENGINEERING. (COUNTY CODE
PART II, CHAPTER 8, SEC. 8-16)
59. THE BMP MUST BE CERTIFIED PRIOR TO RELEASE OF THE BMP
PERFORMANCE BOND.
60. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A COPY
OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD
FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD VERSIO
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINI
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE SITE
PLAN NAME, SITE PLAN NUMBER, ENGINEERING FIRM AND CAD
FILE PREPARER'S NAME AND PHONE NUMBER. THE FILE MUST
CONTAIN THE FOLLOWING, EACH CLEARLY LABELED IN SEPARAT
LAYERS:
A. PROPOSED BUILDING FOOTPRINT;
B. PARKING LOTS AND DRIVEWAYS;
C. ROADS;
D. SIDEWALKS;
E. ALL JURISDICTIONAL WETLAND AREAS AND/OR WATERS OF THE
U.S./STATE; AND
F. FLOODPLAINS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
61. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND SUBSTANTIAL OR FULL SITE PLAN APPROVAL IS REQUIRED
PRIOR TO ITS ISSUANCE. A LAND DISTURBANCE PERMIT IS
A PREREQUISITE TO A BUILDING PERMIT.
62. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND THE FOLLOWING ARE REQUIRED PRIOR TO ITS ISSUANCE:
A. SUBSTANTIAL OR FULL SITE PLAN APPROVAL
B. THE VIRGINIA STORMWATER MANAGEMENT PERMIT (VSMP)
REGISTRATION STATEMENT AND FEE OF $2700
C. THE STORMWATER POLLUTION PREVENTION PLAN (SWPPP) BOOK
D. POSTING OF AN EROSION AND SEDIMENT CONTROL SURETY
(AMOUNT TO BE APPROVED BY EE)
==========================================================