Site Plan Review Comments
All Site Plan Review Comments for Case # 16PR0151
Modify comments view for Case # 16PR0151

Go to Case Selection Form or Go to Project List

 
CASE NO: 16PR0151 STATUS: PENDING APPROVAL
PROJECT NAME: IRONBRIDGE BUSINESS - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: COMMERCIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 00 09/30/15 10/21/15 ******** ********
ENVIR.ENGR.-: 03 02/20/17 03/13/17 ******** 06/08/16 DLD 706-2031
FIRE DEPT.--: 03 02/20/17 03/13/17 COMPLETE 03/03/17 AWB 717-6167
MAPPING/GIS-: 03 02/20/17 03/13/17 COMPLETE 03/10/17 AMJ 768-7549
PLANNING----: 03 02/20/17 03/13/17 COMPLETE 03/02/17 WST 768-7566
TRANSPORT.--: 03 02/20/17 03/13/17 COMPLETE 02/22/17 SJA 751-4461
UTIL.PLAN.--: 03 02/20/17 03/13/17 ******** ********
UTILITIES---: 03 02/20/17 03/13/17 AMENDED* 02/28/17 M L 748-1338
UTIL.R.O.W.-: 03 02/20/17 03/13/17 ******** ********
VDOT--------: 03 02/20/17 03/13/17 ******** ********
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : RACHAEL LUMPKIN, P.E./751-4778
NAME OF PLAN : IRONBRIDGE BUSINESS CENTER
ADDRESS :
SUBMISSION DATE : 09/30/15
PLAN DATED : 09/25/15
REVIEW DATE : 10/23/15
SITE PLAN NO. : 16PR0151
COMMENTS : 1ST REVIEW-NOT APPROVED
TABLE REVIEW :
PLAT PROCESS :
1. INCLUDE THE UTILITIES PROJECT NO. 15-0297 IN THE LOWER
RIGHT CORNER OF EACH PLAN SHEET.
2. THERE IS AN EXISTING SANITARY SEWER LINE WITHIN THE
LIMITS OF THE RIGHT-OF-WAY PARALLEL TO THE 30-INCH
WATERLINE. OBTAIN THE PERTINENT EXISTING WATER AND SEWER
AS-BUILT INFORMATION FROM THE UTILITIES DEPARTMENT. CLEARL
LABEL THE EXISTING SIZE, MATERIAL TYPE, AND COUNTY PROJECT
# ON ALL WATER AND SEWER LINE WITHIN THE PLAN VIEWPORT.
INFORMATION MAY BE OBTAINED BY EMAILING
SWAVAILABILITY@CHESTERFIELD.GOV OR AT THE UTILITIES
DEPARTMENT BUILDING.
3. PROVIDE CONTINUITY IN WATERLINE MATERIAL. RATHER THAN
CHANGING MATERIAL TYPE FROM DUCTILE IRON TO PVC FOR THE
SHORT DISTANCES THAT ARE NOT IN FILL, KEEP THE WATERLINE
DUCTILE IRON THROUGHOUT THE SITE. LABEL AS SUCH.
4. SHOW THE LIMITS OF RESTRAINED PIPE IN THE PROFILE VIEW
FOR THE WATERLINE AT ALL FITTINGS AND PROVIDE CALCULATIONS
TO SHOW THE LENGTH OF RESTRAINED PIPE WAS DETERMINED.
5. CONSIDER KEEPING THE WATERLINE IN THE FILL FROM STATIO
14+60± TO STATION 16+30± AND GOING OVER THE STORM AND
SANITARY SEWER PIPES.
6. LABEL ALL PIPE CROSSINGS IN THE WATER AND SEWER
PROFILES. SHOW THE EXISTING SEWER CROSSING IN THE WATERLIN
PROFILE.
7. LABEL ALL FITTINGS IN BOTH THE PLAN AND PROFILE VIEWS.
8. SHOW THE 8-INCH TAP AT 90° TO THE 30-INCH WATERLINE AT
THE SPRING LINE OF THE PIPE. EXTEND THE CASING PIPE TO THE
RIGHT-OF-WAY LINE ON THE WEST SIDE (RECEIVING PIT) WHERE
THERE IS THE POTENTIAL FOR ROAD WIDENING.
9. CASING PIPE CANNOT DEFLECT. SHOW THE WATERLINE AND
CASING TO BE INSTALLED AT A CONSTANT SLOPE UNDER ROUTE 10
WITH NO BENDS OR DEFLECTIONS.
10. PROVIDE A WATERLINE STUB IN AN EASEMENT FOR FUTURE US
BY THE JONES PROPERTY.
11. THE QUANTITY OF SANITARY SEWER PIPE ON THE COVER SHEE
DOES NOT APPEAR TO MATCH WHAT IS SHOWN ON THE PLAN AND
PROFILE. PLEASE REVISE ALL QUANTITIES AS NEEDED.
12. WILL THERE BE IRRIGATION ON THIS SITE? IF SO, PLEASE
SUBMIT A METER SIZING FORM FOR THE IRRIGATION METER AND
SHOW THE LOCATION OF THE PLAN VIEW.
13. THE OWNER SHALL BE REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
PRIOR TO THE PREPARATION OF THE UTILITIES CONTRACT,
UTILITIES MUST BE IN RECEIPT OF THE "ACCEPTED" BID PROPOSA
BETWEEN THE DEVELOPER AND THE COUNTY APPROVED UTILITIES
CONTRACTOR AS WELL AS THE PROJECT'S INFORMATIONAL SHEET
FOUND ON THE "DEVELOPER'S CHECKLIST". PLEASE SEND THOSE TW
ITEMS TO THE ATTENTION OF JACQUE HYDEN
(HYDENJ@CHESTERFIELD.GOV OR 804-318-8437). THE BID PROPOSA
MUST BE BASED ON THE APPROVED SITE PLAN. BE ADVISED THAT I
THE SITE PLAN IS REVISED AND REAPPROVED SUBSEQUENT TO THE
PREPARATION OR RECORDATION OF THE UTILITIES CONTRACT, THE
BID PROPOSAL SHALL BE REVISED ACCORDINGLY AND A REVISED
UTILITIES CONTRACT MAY BE NECESSARY.
14. AFTER FINAL SITE PLAN APPROVAL, SUBMIT THREE SETS OF
THE APPROVED PLANS DIRECTLY TO THE UTILITIES DEPARTMENT FO
OUR USE DURING CONSTRUCTION INSPECTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : IRONBRIDGE BUSINESS CENTER
ADDRESS :
SUBMISSION DATE : 12/31/15
PLAN DATED : 12/23/15
REVIEW DATE : 1/5/16
SITE PLAN NO. : 16PR0151
COMMENTS : 2ND REVIEW-NOT APPROVED
TABLE REVIEW :
PLAT PROCESS :
1. ON THE PREVIOUS COMMENT NUMBER 8 REGARDING THE TAP OF
THE EXITING 30" WATER MAIN AT THE SPRING LINE, WHAT WAS
INTENDED WAS TO SHOW THE NEW WATERLINE COMING IT AT 90
DEGREES CENTERED ON THE EXISTING PIPE ON THE PROFILE.
2. ON PREVIOUSLY COMMENT NUMBER 11, IT WAS NOTED THAT THE
QUANTITY ON THE MATERIALS LIST WAS TO HAVE BEEN UPDATED.
THE QUANTITY ON THE REVISED SUBMITTAL IS STILL 1897 LF OF
8" SEWER WHILE THE PLANS SHOW ABOUT 558 LF. THE CASING
PIPE QUANTITY ALSO DOES NOT MATCH THE PLANS. PLEASE REVIEW
ALL QUANTITIES AND ADJUST AS NEEDED. ADDITIONALLY, PLEASE
LABEL SEPARATELY THE MATERIALS THAT ARE PRIVATE VS PUBLIC
ON THE LIST OF MATERIALS.
3. LABEL THE PROPOSED EASEMENT AT "PERMANENT VARIABLE
WIDTH WATER AND SEWER EASEMENT".
4. PLEASE SHOW A THRUST BLOCK ON THE BACK SIDE OF THE 30"
TAPPING SLEEVE AND VALVE ON BOTH THE PLAN AND PROFILE VIEW
5. LABEL THE INVERTS OF THE EXISTING SANITARY SEWER ON
THE WEST SIDE OF IRON BRIDGE. THE CORRECT FORMAT FOR THE
COUNTY PROJECT NUMBER IS "97-0272".
6. 20" STEEL CASING PIPE COMES IN 10 FT INCREMENTS. WE
SUGGEST EXTENDING TO A WHOLE NUMBER TO AVOID THE CONTRACTO
HAVING TO FIELD CUT THE PIPE.
7. SHOW THE UNDERGROUND TELEPHONE ON IRON BRIDGE RD ON
THE PROFILE.
8. THE ENTIRE SECTION OF DUCTILE IRON WATER LINE MUST BE
CALLED OUT AS RESTRAINED JOINT PIPE. THIS IS A REQUIREMEN
BOTH FOR 3 JOINTS OF PIPE ON EITHER SIDE OF THE CASING AND
ALSO WATER MAIN THAT IS INSTALLED IN FILL.
9. THE LOCATION OF THE METER FOR THE RESTAURANT WILL
REQUIRE PRIVATE WATER LINE TO CROSS PUBLIC WATER LINE,
WHICH IS NOT DESIRABLE. TWO POTENTIAL SOLUTIONS ARE TO
RELOCATE THE METER TO APPROXIMATELY STA 17+90, OR SHIFT TH
WATER LINE NEAR THE CURRENT WATER METER LOCATION TO THE
WEST SO THAT THE TAP CAN BE ON THE EAST SIDE OF THE PUBLIC
MAIN.
10. UPSIZE THE CORPORATION STOP AND WATER LINE FROM THE
MAIN TO THE METERS TO 2" AND 1-1/2" RESPECTIVELY TO ALLOW
FOR ANY FUTURE METER UPSIZING.
11. PLEASE LABEL 10" MINIMUM SEPARATION BETWEEN THE PUBLIC
WATER LINE AND PRIVATE SANITARY SEWER.
12. PLEASE LABEL ALL WATER AND SEWER LINES AS EITHER
"PUBLIC" OR "PRIVATE" ON BOTH THE PLAN AND PROFILE SHEETS.
13. THE FUTURE WATER EXTENSION TO THE JONES PROPERTY AT
APPROXIMATELY STA 14+75 SHOULD EXTEND BEYOND THE LIMITS OF
THE PROPOSED RIP RAP SPILLWAY TO AVOID ANY PERMITTING
ISSUES WITH ENVIRONMENTAL ENGINEERING IN THE FUTURE SHOULD
THIS CONNECTION BE REQUIRED. PLEASE INCLUDE A LABEL OF TH
NUMBER OF FEET OF PIPE TO BE PROVIDED. ADDITIONALLY, A 2"
FLUSHING HYDRANT ASSEMBLY IS REQUIRED AT THE PLUG.
14. LABEL THE COUNTY PROJECT NUMBER FOR THE WATER AND
SEWER MAINS AT THE WAWA AS 99-0134 ON THE PLAN VIEW AND TH
SEWER PROFILE.
15. PROVIDE AN ADDITIONAL VALVE AT THE WEST SIDE OF THE
TEE AT STA 11+00. A 6" VALVE IS ACCEPTABLE.
16. INSTEAD OF A PLUG AT THE END OF THE 6" WATER LINE,
THIS CAN SIMPLY BE A 90 DEGREE BEND INTO THE HYDRANT SINCE
IT IS UNLIKELY THIS LINE CAN BE EXTENDED IN THE FUTURE.
17. WE SUGGEST INSTALLING THE 6" WATER LINE AT THE FIRE
LANE OUTSIDE OF THE PAVEMENT AND ADJUST THE EASEMENT AS
NECESSARY.
18. PLEASE CALL OUT THE VALVE TO CLOSE TO MAKE THE
CONNECTION TO THE EXISTING WATER LINE ON THE PLANS.
19. SHOW ANGLES ON THE SANITARY MANHOLES SO THAT THE BASE
SECTIONS CAN BE ORDERED CORRECTLY.
20. LABEL THE INVERT IN ON THE MONITORING MANHOLE AND
ENSURE THAT THE 6-INCH LATERAL MATCHES CROWNS WITH THE
OUTGOING 8-INCH MAIN.
21. ALTHOUGH IT IS PRIVATE AND NOT REQUIRED, WE NOTICED
THAT THE DETAIL FOR THE GREASE TRAP SHOWS A 4" OUTLET, YOU
MAY CONSIDER UPSIZING TO 6" TO MATCH THE COUNTY CONNECTION
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : IRONBRIDGE BUSINESS CENTER
ADDRESS :
SUBMISSION DATE : 5/16/16
PLAN DATED : 5/16/16
REVIEW DATE : 5/20/16
SITE PLAN NO. : 16PR0151
COMMENTS : 3RD REVIEW-NOT APPROVED
TABLE REVIEW : YES
PLAT PROCESS :
1. A REDUCED PRESSURE BACKFLOW PREVENTER IS REQUIRED FOR
THE POPEYES. THIS MAY BE EITHER IN A HEATED EXTERIOR
ENCLOSURE OR INSIDE THE BUILDING. IF INSIDE, THE PLANS
MUST HAVE A NOTE TO INDICATE THE BACKFLOW PREVENTER IS
INSIDE.
2. THE METERS WERE NOT SUPPOSED TO BE UPSIZED, ONLY THE
SERVICE LINE TWO THE METERS. THE ACTUAL METER SIZE NEEDS
TO REFLECT THE METER SIZING FORMS.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
.
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON, P.E./748-1338
NAME OF PLAN : IRONBRIDGE BUSINESS CENTER
ADDRESS :
SUBMISSION DATE : 2/20/17
PLAN DATED : 2/16/17
REVIEW DATE : 2/27/17
SITE PLAN NO. : 16PR0151
COMMENTS : 4TH REVIEW-APPROVED
TABLE REVIEW : YES
PLAT PROCESS :
.
1. UPON APPROVAL FROM ALL OTHER DEPARTMENTS, PLEASE SUBMIT
COPIES OF THE APPROVED PLANS DIRECTLY TO THE UTILITIES DE
RTMENT FOR USE DURING CONSTRUCTION.
.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER: 16PR0151
LATEST PLAN DATE: 09/25/15
DEPT. REC'D. DATE: 10/01/15
SUBMITTAL NUMBER: ONE
REVIEW DATE: 10/21/15
RECOMMENDATION: NOT APPROVED
PLAT PROCESSING: R/W DEDICATION
1. PRIOR TO SITE PLAN APPROVAL, OWNER/DEVELOPER SHALL
DEDICATE 100' FROM THE EXISTING CENTERLINE ALONG THE
PROPERTY'S FRONTAGE TO ROUTE 10. THIS DEDICATION SHALL
BE MADE FREE AND UNRESTRICTED, TO AND FOR THE BENEFIT, OF
COUNTY. (PROFFERED CONDITION 4 OF CASE 12SN0217)
2. PROVIDE A SEPARATE RIGHT TURN LANE ALONG ROUTE 10 INTO
THE EXISTING SHARED ACCESS. (PROFFERED CONDITION 6B)
3. PROVIDE VDOT STANDARD SIDEWALK ALONG THE DEVELOPMENT'S
FRONTAGE TO ROUTE 10 (EXISTING SHARED ACCESS TO RT 1690).
4. NOTE COUNTY CLASSIFICATION OF ROUTE 10 ON THE PLANS
(MAJOR ARTERIAL PER COUNTY'S THOROUGHFARE PLAN).
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER: 16PR0151
LATEST PLAN DATE: 12/23/15
DEPT. REC'D. DATE: 01/04/16
SUBMITTAL NUMBER: TWO
REVIEW DATE: 01/28/16
RECOMMENDATION: NOT APPROVED
PLAT PROCESSING: R/W DEDICATION
1. PRIOR TO SITE PLAN APPROVAL, OWNER/DEVELOPER SHALL
DEDICATE 100' FROM THE EXISTING CENTERLINE ALONG THE
PROPERTY'S FRONTAGE TO ROUTE 10. DEDICATION SHALL BE MADE
FREE AND UNRESTRICTED, TO AND FOR THE BENEFIT, OF COUNTY.
(CONDITION 4 OF CASE 12SN0217)
2. IS THE SEPARATE RIGHT TURN LANE INTO THE SHARED ACCESS
BEING PROVIDED WITH THIS SITE PLAN? IF SO, IT NEEDS TO BE
FULLY SHOWN IN PLAN VIEW WITH THIS SUBMITTAL. IF NOT BEIN
CONSTRUCTED WITH THIS PLAN, THEN NOTE AS SUCH AND REFERENC
OTHER SITE PLAN OR REMOVE COMPLETELY. REGARDLESS, THE
RIGHT TURN LANE INTO THE SHARED ACCESS WILL NEED TO BE
COMPLETED PRIOR TO ISSUANCE OF ANY CERTIFICATE OF OCCUPANC
AND WILL BE SO NOTED ON ANY APPROVAL LETTER FOR THIS SITE
PLAN.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER: 16PR0151
LATEST PLAN DATE: 05/12/16
DEPT. REC'D. DATE: 05/19/16
SUBMITTAL NUMBER: THREE
REVIEW DATE: 05/20/16
RECOMMENDATION: NOT APPROVED
PLAT PROCESSING: R/W DEDICATION
FINAL SITE PLAN APPROVAL IS PENDING RIGHT-OF-WAY DEDICATIO
100' FROM THE EXISTING CENTERLINE ALONG THE PROPERTY'S
FRONTAGE TO ROUTE 10. (CONDITION 4 OF CASE 12SN0217)
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER: 16PR0151
LATEST PLAN DATE: 02/16/17
DEPT. REC'D. DATE: 02/22/17
SUBMITTAL NUMBER: FOUR
REVIEW DATE: 02/22/17
RECOMMENDATION: SUBSTANTIAL APPROVAL
PLAT PROCESSING: R/W DEDICATION
.
1. FINAL SITE PLAN APPROVAL IS PENDING RIGHT-OF-WAY
DEDICATION 100' FROM THE CENTERLINE ALONG THE PROPERTY'S
FRONTAGE TO RT 10. (CONDITION 4 OF CASE 12SN0217)
.
2. SHEET C-3: PROVIDE INSET TO SHOW FULL EXTENT OF PAVEMEN
WORK FOR RIGHT TURN LANE. ALSO, REVISE NOTE TO REFERENCE
SHEET C-20 FOR CONSTRUCTION.
==========================================================
==========================================================
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #-----BETH SYKES/717-6836
EMAIL------------------SYKESB@CHESTERFIELD.GOV
NAME OF PLAN----------- IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER-------16PR0151
ADDRESS----------------10801 IRONBRIDGE ROAD
LATEST PLAN DATE-------9/25/15
DEPT. REC'D. DATE------9/25/15
ACCEPTED FOR REVIEW----9/30/15
SUBMITTAL NUMBER-------ONE
REVIEW DATE------------10/26/15
RECOMMENDATION---------REVISIONS REQUESTED
TABLE REVIEW-----------NO
LANDSCAPE PLAN STATUS--MUST BE INCLUDED WITH 2ND SUBMISSIO
ARCHITECTURAL ELEVATIONS--REQUESTED
LIGHTING PLAN/CUTSHEETS---REQUESTED
IRRIGATION/HOSEBIB PLAN---REQUESTED
REVIEW COMMENTS:
1. INTERIOR PARKING LOT LANDSCAPING REQUIREMENTS ARE BASED
N PARKING SPACES PROVIDED (NOT SPACES REQUIRED).
2. ADD NOTE TO COVER SHEET: "PER PROFFERED CONDITION 3 FRO
ZONING CASE 15SN0606, NO USE SHALL BE OPEN TO THE PUBLIC B
WEEN THE HOURS OF 11 P.M. AND 6 A.M."
3. THE ADJACENT PROPERTY TO THE NORTHEAST IS GPIN 774-658-
88.
4. SHOW THE 20 FOOT YARD WITH PERIMETER LANDSCAPING B ALON
THE SOUTHERN BOUNDARY.
5. LABEL ON THE PLAN ANY SETBACK EXCEPTIONS ALLOWED BY ZON
G CASE.
6. LABEL FRONT AND CORNER SIDE SETBACKS AS TREE SAVE AREAS
ND SHOW TREE PROTECTION FENCING ON EROSION CONTROL PLANS.
7. LANDSCAPE PLAN MUST BE SUBMITTED WITH NEXT SUBMITTAL.
8. LANDSCAPE PLAN MUST BE PREPARED BY A STATE REGISTERED L
DSCAPE ARCHITECT, NURSERYMAN, OR LANDSCAPE DESIGNER.
9. REMOVAL OF EXISTING TREES WITHIN THE SETBACK WITHOUT WR
TEN APPROVAL FROM THE PLANNING DEPARTMENT SHALL RESULT IN
O TREES BEING PLANTING FOR EACH TREE REMOVAL.
10. ALL JUNCTION BOXES MUST BE SCREENED ON AT LEAST THREE
DES WITH SHRUBBERY OR LATTICE.
11. ALL LANDSCAPED AREAS SHALL BE PROVIDED WITH A READILY
AILABLE WATER SUPPLY; YARD HYDRANTS AND OR HOSE BIBS WITHI
100 FEEL OF ALL NEW PLANTINGS OR IRRIGATION. SHOW IRRIGATI
SLEEVES, HYDRANTS AND/OR HOSE BIBS ON LANDSCAPE PLAN.
12. SHOW LIGHT POLES ON LANDSCAPE PLAN AND KEY THEM TO CUT
HEETS FOR EACH LIGHT FIXTURE.
13. SUBMIT DOCUMENTS THAT DEFINE THE OVERALL ARCHITECTURAL
HEME DESCRIBING HOW EXTERIOR MATERIALS, COLORS, ARCHITECTU
L STYLE AND BUILDING SCALE SHALL BE USED TO DEVELOP A CONS
TENT ARCHITECTURAL TREATMENT FOR THE PROJECT.
14. SUBMIT TWO COPIES OF THE ELEVATIONS OF BOTH BUILDINGS
TH NEXT SUBMITTAL. IDENTIFY ALL MATERIALS AND COLORS, JUNC
ON AND ACCESS BOXES, ROOF ACCESS, AND ROOF TOP MECHANICAL
UIPMENT. SHOW ALL RTUS IN RELIEF BEHIND THE PARAPETS TO I
URE UNITS ARE FULLY SCREENED.
15. JUNCTION AND ACCESS BOXES MUST BE SCREENED OR PAINTED
MATCH THE BUILDING.
16. SHOW THE LOCATION OF THE ROOF ACCESS. EXTERIOR LADDER
CESS AND PARAPET OPENINGS SHALL NOT BE VISIBLE FROM ADJACE
PROPERTIES AND PUBLIC RIGHTS OF WAY, AND ANY EXTERIOR ACC
S MUST BE DESIGNED IN A MANNER INTEGRAL TO THE ARCHITECTUR
CHARACTER OF THE BUILDING. PROVIDE INTERIOR ACCESS THROU
YOUR SPACE, OR A COMMON CONTROL ROOM.
17. PUT THE CHESTERFIELD COUNTY SITE PLAN NUMBER 16PR0151
THE LOWER RIGHT CORNER OF EACH SHEET.
18. SHOW SIGNS ON DUMPSTERS STATING NO SERVICE BETWEEN 9PM
ND 6AM.
19. PROVIDE DETAIL FOR DUMPSTER, NOTING MATERIALS AND COLO
TO MATCH BUILDING. SCREEN SHOULD BE BRICK, NOT CMU.
20. PROVIDE A SIGN PACKAGE FOR TYPICAL BUILDING AND FREEST
DING SIGNS WITHIN A NONRESIDENTIAL COMMUNITY (IE - SHOPPIN
CENTER, OFFICE PARK, OR OTHER MULTI-TENANT PROJECT). THE
GN PACKAGE SHALL PROVIDE RENDERINGS FOR ALL SIGNS INCLUDIN
SIZES, LIGHTING AND GENERAL LOCATION. THE DEVELOPER SHALL
ETERMINE THE FOLLOWING: (1) GENERAL LETTER STYLE TO BE USE
(2) NOTE THAT ACCESSORY SIGNS TO THE PRIMARY TENANT SIGN
ALL BE A SINGLE COLOR FROM THE PRIMARY SIGN, (3) CHOOSE EI
ER SIGN BOXES OR INDIVIDUALLY MOUNTED LETTERS.
21. PRIOR TO RECEIVING A TEMPORARY OCCUPANCY PERMIT, THE A
LICANT SHALL PROVIDE A LETTER OF GUARANTEE (COUNTY FORMAT)
O REPLACE ALL UNHEALTHY OR DEAD PLANTS OR POLLARDED TREES
ENTIFIED BY THE ONE YEAR INSPECTION BY THE PLANNING DEPART
NT.
ADDITIONALLY, A FORM OF SURETY (BOND OR LETTER OF CREDIT)
AN AMOUNT EQUAL TO THE COST OF COMPLETING THE REQUIRED LA
SCAPING SHALL BE PROVIDED TO THE PLANNING DEPARTMENT.
22. RETAINING WALL SHALL BE CONSTRUCTED SO THAT IT IS COMP
IBLE IN APPEARANCE WITH THE PRINCIPAL STRUCTURE IN THE DEV
OPMENT. COMPATIBILITY SHALL BE ACCOMPLISHED THROUGH THE
E OF INTEGRATED COLOR BLOCK THAT IS SIMILAR IN APPEARANCE
THE PRIMARY STRUCTURES OR IS AN EARTH TONE ACCEPTABLE TO
E DIRECTOR OF PLANNING.
24. DELETE NOT ON SHEET C-13 REFERENCING ALTERNATIVE WALL.
THIS COMPLETES THE FIRST REVIEW
**********************************************************
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #-----BETH SYKES/717-6836
EMAIL------------------SYKESB@CHESTERFIELD.GOV
NAME OF PLAN----------- IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER-------16PR0151
ADDRESS----------------10801 IRONBRIDGE ROAD
LATEST PLAN DATE-------12/23/15
DEPT. REC'D. DATE------12/31/15
SUBMITTAL NUMBER-------TWO
REVIEW DATE------------2/8/16
RECOMMENDATION---------REVISIONS REQUESTED
TABLE REVIEW-----------NO
LANDSCAPE PLAN STATUS-REVISIONS REQUESTED
ARCHITECTURAL ELEVATIONS-MUST BE SUBMITTED WITH NET SUBMIT
LIGHTING PLAN/CUTSHEETS---LABEL ON PLANS
IRRIGATION/HOSEBIB PLAN---HOSEBIBS
REVIEW COMMENTS:
PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT 10
ULL SETS AND ONE COPY OF THE SITE PLAN SHEET TO THE PLANNI
DEPARTMENT FOR YOUR NEXT REVIEW. PROVIDE A RESPONSE TO C
MENTS, USING THE SPACE BELOW (NOT ON A SEPARATE SHEET) EAC
REVIEW COMMENT TO DESCRIBE HOW YOU HAVE ADDRESSED EACH COM
NT. BE SURE TO INDICATE WHICH SHEETS SHOW THE REQUIRED CH
GES. PROVIDE ONE COMPLETE RESPONSE TO ALL DEPARTMENT COMM
TS TO THE PLANNING DEPARTMENT. PROVIDE A TRANSMITTAL LETT
TO DESCRIBE ANY CHANGES TO THE PLANS NOT CAUSED BY STAFF
VIEW COMMENTS. CLEARLY LABEL TO WHICH DEPARTMENT SUPPLEMEN
L INFORMATION SHOULD BE ROUTED.
(CL X.X REPRESENTS CHECKLIST ITEM #)
1. SHOW THE TREE SAVE AREAS ON THE GRADING PLAN TO INSURE
ADING DOES NOT ENCROACH INTO THE TREE SAVE AREAS.
2. REMOVAL OF EXISTING TREES WITHIN THE SETBACK WITHOUT WR
TEN APPROVAL FROM THE PLANNING DEPARTMENT SHALL RESULT IN
O TREES BEING PLANTING FOR EACH TREE REMOVAL.
3. ALL GROUND LEVEL JUNCTION BOXES MUST BE SCREENED ON AT
AST THREE SIDES WITH SHRUBBERY OR LATTICE.
4. ALL WALL MOUNTED JUNCTION AND ACCESS BOXES MUST BE SCRE
ED OR PAINTED TO MATCH THE BUILDING.
5. FIRE HYDRANTS AND LIGHT POLES MUST BE LABELED ON PLANS.
6. SUBMIT DOCUMENTS THAT DEFINE THE OVERALL ARCHITECTURAL
EME DESCRIBING HOW EXTERIOR MATERIALS, COLORS, ARCHITECTUR
STYLE AND BUILDING SCALE SHALL BE USED TO DEVELOP A CONSI
ENT ARCHITECTURAL TREATMENT FOR THE PROJECT.
7. SUBMIT TWO COPIES OF THE ELEVATIONS OF BOTH BUILDINGS W
H NEXT SUBMITTAL. IDENTIFY ALL MATERIALS AND COLORS, JUNCT
N AND ACCESS BOXES, ROOF ACCESS, AND ROOF TOP MECHANICAL E
IPMENT. SHOW ALL RTUS IN RELIEF BEHIND THE PARAPETS TO IN
RE UNITS ARE FULLY SCREENED.
8. SHOW THE LOCATION OF THE ROOF ACCESS. EXTERIOR LADDER A
ESS AND PARAPET OPENINGS SHALL NOT BE VISIBLE FROM ADJACEN
PROPERTIES AND PUBLIC RIGHTS OF WAY, AND ANY EXTERIOR ACCE
MUST BE DESIGNED IN A MANNER INTEGRAL TO THE ARCHITECTURA
CHARACTER OF THE BUILDING. PROVIDE INTERIOR ACCESS THROUG
YOUR SPACE, OR A COMMON CONTROL ROOM.
9. SHEET 13: DUMPSTER GATE COLOR SHOULD BE LABELED "TO MAT
BUILDING."
10. MINIMUM SIZE AT TIME OF PLANTING FOR ORNAMENTAL TREES
2 ½" CALIPER (OR 8 FEET TALL FOR MULTISTEMMED TREES).
11. PROVIDE THE SQUARE FOOTAGE OF ANY ISLAND COUNTED TOWAR
THE REQUIREMENTS TO INSURE THE MINIMUM HAS BEEN MET.
12. PROVIDE A SIGN PACKAGE FOR TYPICAL BUILDING AND FREEST
DING SIGNS WITHIN A NONRESIDENTIAL COMMUNITY (IE - SHOPPIN
CENTER, OFFICE PARK, OR OTHER MULTI-TENANT PROJECT). THE
GN PACKAGE SHALL PROVIDE RENDERINGS FOR ALL SIGNS INCLUDIN
SIZES, LIGHTING AND GENERAL LOCATION. THE DEVELOPER SHALL
ETERMINE THE FOLLOWING: (1) GENERAL LETTER STYLE TO BE USE
(2) NOTE THAT ACCESSORY SIGNS TO THE PRIMARY TENANT SIGN
ALL BE A SINGLE COLOR FROM THE PRIMARY SIGN, (3) CHOOSE EI
ER SIGN BOXES OR INDIVIDUALLY MOUNTED LETTERS.
13. PRIOR TO RECEIVING A TEMPORARY OCCUPANCY PERMIT, THE A
LICANT SHALL PROVIDE A LETTER OF GUARANTEE (COUNTY FORMAT)
O REPLACE ALL UNHEALTHY OR DEAD PLANTS OR POLLARDED TREES
ENTIFIED BY THE ONE YEAR INSPECTION BY THE PLANNING DEPART
NT.
ADDITIONALLY, A FORM OF SURETY (BOND OR LETTER OF CREDIT)
AN AMOUNT EQUAL TO THE COST OF COMPLETING THE REQUIRED LA
SCAPING SHALL BE PROVIDED TO THE PLANNING DEPARTMENT.
THIS COMPLETES THE SECOND REVIEW
*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=*=
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #-----STEVE TUGWELL/768-7566
EMAIL------------------TUGWELLW@CHESTERFIELD.GOV
NAME OF PLAN-----------IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER-------16PR0151
ADDRESS----------------10801 IRON BRIDGE RD
LATEST PLAN DATE-------5/12/16
DEPT. REC'D. DATE------5/13/16
SUBMITTAL NUMBER-------THREE
REVIEW DATE------------6/6/16
RECOMMENDATION---------REVISIONS REQUESTED
TABLE REVIEW-----------NO
LANDSCAPE PLAN STATUS-- REVISIONS REQUESTED
ARCHITECTURAL ELEVATIONS-PROVIDE BRICK SAMPLE
LIGHTING PLAN/CUTSHEETS--- REVISIONS REQUESTED
IRRIGATION/HOSEBIB PLAN--- REVISIONS REQUESTED
REVIEW COMMENTS:
PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT 10
FULL SETS AND ONE COPY OF THE SITE PLAN SHEET TO THE
PLANNING DEPARTMENT FOR YOUR NEXT REVIEW. PROVIDE A
RESPONSE TO COMMENTS, USING THE SPACE BELOW (NOT ON A
SEPARATE SHEET) EACH REVIEW COMMENT TO DESCRIBE HOW YOU
HAVE ADDRESSED EACH COMMENT. BE SURE TO INDICATE WHICH
SHEETS SHOW THE REQUIRED CHANGES. PROVIDE ONE COMPLETE
RESPONSE TO ALL DEPARTMENT COMMENTS TO THE PLANNING
DEPARTMENT. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE ANY
CHANGES TO THE PLANS NOT CAUSED BY STAFF REVIEW COMMENTS.
CLEARLY LABEL TO WHICH DEPARTMENT SUPPLEMENTAL INFORMATIO
SHOULD BE ROUTED.
(
1. THE BUILDING FOOTPRINT SHOWN ON THE SITE PLAN DATED
5/12/16 DOES NOT APPEAR TO MATCH THE FOOTPRINT ON
THE ELEVATION SUBMITTED VIA EMAIL ON 6/6/16. PLEASE
RESUBMIT TWO COPIES OF THE ELEVATIONS OF BOTH
BUILDINGS WITH NEXT SUBMITTAL. IDENTIFY ALL MATERIALS
AND COLORS, JUNCTION AND ACCESS BOXES, ROOF ACCESS
AND ROOF TOP MECHANICAL EQUIPMENT.
SHOW ALL RTUS IN RELIEF BEHIND THE PARAPETS TO INSURE
UNITS ARE FULLY SCREENED.
2. SHOW THE LOCATION OF THE ROOF ACCESS. EXTERIOR LADDER
ESS AND PARAPET OPENINGS SHALL NOT BE VISIBLE FROM ADJAC
PROPERTIES AND PUBLIC RIGHTS OF WAY, AND ANY EXTERIOR AC
MUST BE DESIGNED IN A MANNER INTEGRAL TO THE ARCHITECTUR
CHARACTER OF THE BUILDING. PROVIDE INTERIOR ACCESS THROU
YOUR SPACE, OR A COMMON CONTROL ROOM.
3. IS THE OVERSIZE BRICK AN APPROPRIATE MATERIAL FOR
FEDERAL AND COLONIAL STYLE ARCHITECTURE?
4. PROVIDE A SIGN PACKAGE FOR TYPICAL BUILDING AND FREES
DING SIGNS WITHIN A NONRESIDENTIAL COMMUNITY (IE - SHOPP
CENTER, OFFICE PARK, OR OTHER MULTI-TENANT PROJECT). THE
GN PACKAGE SHALL PROVIDE RENDERINGS FOR ALL SIGNS INCLUD
SIZES, LIGHTING AND GENERAL LOCATION. THE DEVELOPER SHAL
ETERMINE THE FOLLOWING: (1) GENERAL LETTER STYLE TO BE U
(2) NOTE THAT ACCESSORY SIGNS TO THE PRIMARY TENANT SIGN
ALL BE A SINGLE COLOR FROM THE PRIMARY SIGN, (3) CHOOSE
EITHER SIGN BOXES OR INDIVIDUALLY MOUNTED LETTERS.
5. PRIOR TO RECEIVING A TEMPORARY OCCUPANCY PERMIT, THE
APPLICANT SHALL PROVIDE A LETTER OF GUARANTEE (COUNTY
FORMAT) TO REPLACE ALL UNHEALTHY OR DEAD PLANTS OR
POLLARDED TREES IDENTIFIED BY THE ONE YEAR INSPECTION B
THE PLANNING DEPARTMENT.
ADDITIONALLY, A FORM OF SURETY (BOND OR LETTER OF CREDIT
AN AMOUNT EQUAL TO THE COST OF COMPLETING THE REQUIRED L
D SCAPING SHALL BE PROVIDED TO THE PLANNING DEPARTMENT.
THIS COMPLETES THE THIRD REVIEW
**********************************************************
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #-----STEVE TUGWELL/768-7566
EMAIL------------------TUGWELLS@CHESTERFIELD.GOV
NAME OF PLAN-----------IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER-------16PR0151
ADDRESS----------------10801 IRON BRIDGE RD
LATEST PLAN DATE-------2/16/17
DEPT. REC'D. DATE------2/20/17
SUBMITTAL NUMBER-------4
REVIEW DATE------------2/24/17
RECOMMENDATION---------REVISIONS REQUESTED
TABLE REVIEW-----------NO
LANDSCAPE PLAN STATUS-- REVISIONS REQUESTED
ARCHITECTURAL ELEVATIONS- REVISIONS REQUESTED + PROVIDE A
BRICK SAMPLE
LIGHTING PLAN/CUTSHEETS--- REVISIONS REQUESTED
IRRIGATION/HOSEBIB PLAN--- REVISIONS REQUESTED
REVIEW COMMENTS:
PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT 10
FULL SETS AND ONE COPY OF THE SITE PLAN SHEET TO THE
PLANNING DEPARTMENT FOR YOUR NEXT REVIEW. PROVIDE A
RESPONSE TO COMMENTS, USING THE SPACE BELOW (NOT ON A
SEPARATE SHEET) EACH REVIEW COMMENT TO DESCRIBE HOW YOU
HAVE ADDRESSED EACH COMMENT. BE SURE TO INDICATE WHICH
SHEETS SHOW THE REQUIRED CHANGES. PROVIDE ONE COMPLETE
RESPONSE TO ALL DEPARTMENT COMMENTS TO THE PLANNING
DEPARTMENT. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE ANY
CHANGES TO THE PLANS NOT CAUSED BY STAFF REVIEW COMMENTS.
1. THE BUILDING FOOTPRINT SHOWN ON THE SITE PLAN DATED
2/16/17 DOES NOT APPEAR TO MATCH THE FOOTPRINT ON
THE ELEVATION SUBMITTED VIA EMAIL ON 6/6/16 OR THE
ELEVATIONS SUBMITTED WITH THIS CURRENT PLAN. PLEASE
RESUBMIT TWO COPIES OF THE ELEVATIONS OF BOTH
BUILDINGS (INCLUDING THE RESTAURANT) WITH NEXT SUBMITTAL.
IDENTIFY ALL MATERIALS AND COLORS, JUNCTION AND ACCESS
BOXES, ROOF ACCESS AND ROOF TOP MECHANICAL EQUIPMENT. SHOW
ALL ROOFTOP MECHANICAL UNITS IN RELIEF BEHIND THE PARAPETS
TO INSURE UNITS ARE FULLY SCREENED.
2. SHOW THE LOCATION OF THE ROOF ACCESS. EXTERIOR LADDER A
ESS AND PARAPET OPENINGS SHALL NOT BE VISIBLE FROM ADJACEN
PROPERTIES AND PUBLIC RIGHTS OF WAY, AND ANY EXTERIOR ACCE
MUST BE DESIGNED IN A MANNER INTEGRAL TO THE ARCHITECTURAL
CHARACTER OF THE BUILDING. PROVIDE INTERIOR ACCESS THROUGH
YOUR SPACE, OR A COMMON CONTROL ROOM.
3. THE ELEVATIONS SUBMITTED WITH THE CURRENT PLAN ARE STIL
SHOWING OVERSIZE BRICK. THIS IS NOT AN APPROPRIATE MATERIA
FOR FEDERAL AND COLONIAL STYLE ARCHITECTURE OF THIS SCALE.
16PLEASE CHANGE TO STANDARD BRICK AND REVISE ON THE NEXT
ELEVATION.
4. PLEASE NOTE THAT THE EXISTING LANDSCAPE
MATERIAL SHOWN TO REMAIN WITHIN THE 50-FOOT
SETBACK MAY BE CREDITED TOWARDS LANDSCAPE "C"
LANDSCAPE REQUIREMENTS, PENDING AN INSPECTION BY
THE PLANNING DEPT. PRIOR TO FINAL APPROVAL,
LANDSCAPE ARCHITECT OR DESIGNEE TO PLEASE CALL
STEVE TUGWELL AT 768-7566 TO SCHEDULE AN ON-SITE
INSPECTION TO DETERMINE WHETHER OR NOT EXISTING
PLANT MATERIAL WILL FULLY COMPLY WITH LANDSCAPE C
STANDARDS, AND THAT IT IS REASONABLY DISTRIBUTED
THROUGHOUT THE SETBACK, I.E. IF EXISTING TREES MEET
ALL THE REQUIREMENTS BUT ARE LOCATED AT ONE END OF
THE SITE, THEN IT IS NOT REASONABLY DISTRIBUTED.
[SEC. 19.1-247.2.]
5. WITHIN THE 50-FOOT SETBACK TREE PRESERVATION
AREA, INSTALL TREE PROTECTION FENCING SO THAT LARGE
TRUCKS AND HEAVY MACHINERY DO NOT DAMAGE THE ROOT
STRUCTURE OF THESE EXISTING TREES DURING SITE
PREPARATIONS AND/OR SITE CONSTRUCTION PHASES. ADD
THIS DETAIL TO THE LANDSCAPE AND SITE PLANS. [SEC.
19.1-247.3.]
6. PROVIDE A READILY AVAILABLE WATER SOURCE FOR REQUIRED
LANDSCAPED AREAS. PROVIDE NOTES ALONG WITH IRRIGATION
SLEEVES OR HOSEBIB LOCATIONS TO SATISFY THIS REQUIREMENT.
[SEC. 19.1-249.B.]
7. PROVIDE NOTES REGARDING THE DETAILS, MATERIALS, AND
SETBACKS OF ALL RETAINING WALLS PROPOSED FOR THIS SITE.
[SEC. 19.1-320.A.]
8. PROVIDE A SIDEWALK FOR SAFE AND CONVENIENT PEDESTRIAN
ACCESS THAT CONNECTS TO THE SITE FROM THE PROPOSED SIDEWA
SHOWN PARALLEL TO ROUTE 10.
REVIEW NOTES:
1. LANDSCAPING SURETY REQUIREMENTS AND MAINTENANCE
SHALL BE FORMED IN ACCORDANCE WITH SEC. 19.1-248.A
& B. OF THE ZONING ORDINANCE.
2. MAINTENANCE GUARANTEE: PRIOR TO RECEIVING AN
OCCUPANCY PERMIT. THE APPLICANT SHALL PROVIDE A
LETTER OF GUARANTEE (COUNTY FORMAT) TO INSURE
REPLACEMENT OF UNHEALTHY, DYING, DEAD OR POLLARDED
LANDSCAPING WITHIN THE FIRST YEAR OF INSTALLATION,
PER SEC. 19.1-248.B.
3. LANDSCAPE REPLACEMENT SHALL BE REGULATED PER
SEC. 19.1-249.1., 2., & 3. OF THE ZONING ORDINANCE.
**************************************************
END OF THE 4TH SUBMITTAL PLANNING COMMENTS
==========================================================
==========================================================
REVIEW DEPARTMENT: IST / GIS
REVIEWER : NANCY PARKER 751-4319
NAME OF PLAN : IRON BRIDGE BUSINESS CENTER
PLAN NO. : 16PR0151
ADDRESS :
LATEST PLAN DATE : 9/25/15
RECEIVED DATE : 10/1/15
SUBMITTAL NUMBER : 1
REVIEW DATE : 10/16/15
RECOMMENDATION : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. COORDINATE POINTS BASED ON THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, NORTH AMERICAN DATUM
1983 ARE NOT PRESENT. TWO POINTS MUST BE SHOWN ON THE
SITE BOUNDARY.
2. THERE ARE FOUR PROPERTIES BEING USED FOR THIS SITE.
THE FOURTH TAX-ID IS: 774-658-1727-00000.
3. WILL THE ORIGINAL ROADWAY ULTIMATELY BECOME PART OF
THE IRON BRIDGE ROAD RIGHT OF WAY?
4. BECAUSE THE ROAD NAME IS IRON BRIDGE ROAD (TWO WORDS)
PLEASE CHANGE THE SPELLING OF THIS BUSINESS CENTER TO
IRON BRIDGE BUSINESS CENTER (TWO WORDS).
==========================================================
==========================================================
REVIEW DEPARTMENT: IST / GIS
REVIEWER : NANCY PARKER 751-4319
NAME OF PLAN : IRON BRIDGE BUSINESS CENTER
PLAN NO. : 16PR0151
ADDRESS :
LATEST PLAN DATE : 12/23/15
RECEIVED DATE : 1/3/16
SUBMITTAL NUMBER : 2
REVIEW DATE : 2/1/16
RECOMMENDATION : APPROVED
==========================================================
==========================================================
REVIEW DEPARTMENT: IST / GIS
REVIEWER : AMY JOHANSON 768-7549
NAME OF PLAN : IRON BRIDGE BUSINESS CENTER
PLAN NO. : 16PR0151
LATEST PLAN DATE : 5/12/16
RECEIVED DATE : 5/17/16
SUBMITTAL NUMBER : 3
REVIEW DATE : 6/3/16
RECOMMENDATION : APPROVED
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : IRON BRIDGE BUSINESS CENTER
CASE NUMBER : 16PR0151
LATEST PLAN DATE : 2/16/17
RECEIVED DATE : 2/21/17
SUBMITTAL NUMBER : 4
REVIEW DATE : 3/10/17
ADDRESS : PENDING
STATUS : APPROVED
==========================================================
==========================================================
DEPARTMENT REVIEW: IST / HOUSE NUMBERING SECTION
REVIEWER: NANCY PARKER
PHONE NUMBER: 751-4319
CASE NUMBER: 16PR0151
NAME OF PLAN:IRON BRIDGE BUSINESS CENTER
ADDRESS: NO ADDRESSES ASSIGNED YET
DATE OF REVIEW:10/16/15 REVIEW # 1
STATUS: HOUSE NUMBERING NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS
CONCERNING THE COMMENTS BELOW.
1) SHOW THE LOCATION OF THE MAIL BOX KIOSKS OR CLUSTER
BOXES ON THE PLAN SHEETS.
2) WILL THE ORIGINAL ROADBED BECOME PART OF IRON BRIDGE
ROAD RIGHT-OF-WAY, WILL IT BE RENAMED OR WILL IT REMAIN
AS SIMPLY AN ACCESS?
3) LOCATION OF STREET ADDRESS SIGN IS NOT SHOWN.
(THE ADDRESS CAN BE PART OF YOUR MONUMENT SIGN.
THIS DOES NOT COUNT AS PART OF THE SQUARE FOOTAGE OF THE
SIGN. IF YOU ARE USING THE MONUMENT
SIGN FOR THE ADDRESS, A DETAIL OF THE MONUMENT SIGN
NEEDS TO BE ON THE SITE PLAN.)
4) SPECIFY THE MATERIAL THAT THE ADDRESS SIGN IS TO BE
MADE OF. (MATERIAL TO BE MORE DURABLE THAN WOOD).
==========================================================
==========================================================
DEPARTMENT REVIEW: IST / HOUSE NUMBERING SECTION
REVIEWER: NANCY PARKER
PHONE NUMBER: 751-4319
CASE NUMBER: 16PR0151
NAME OF PLAN:IRON BRIDGE BUSINESS CENTER
ADDRESS: NO ADDRESSES ASSIGNED YET
DATE OF REVIEW: 2/1/16 REVIEW # 2
STATUS: HOUSE NUMBERING NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS
CONCERNING THE COMMENTS BELOW.
1) SHOW THE LOCATION OF THE MAIL BOX KIOSKS OR CLUSTER
BOXES ON THE PLAN SHEETS.
2) LOCATION OF STREET ADDRESS SIGN IS NOT SHOWN.
(THE ADDRESS CAN BE PART OF YOUR MONUMENT SIGN.
THIS DOES NOT COUNT AS PART OF THE SQUARE FOOTAGE OF THE
SIGN. IF YOU ARE USING THE MONUMENT
SIGN FOR THE ADDRESS, A DETAIL OF THE MONUMENT SIGN
NEEDS TO BE ON THE SITE PLAN.)
==========================================================
==========================================================
DEPARTMENT REVIEW: IST / HOUSE NUMBERING SECTION
REVIEWER: AMY JOHANSON
PHONE NUMBER: 768-7549
CASE NUMBER: 16PR0151
NAME OF PLAN:IRON BRIDGE BUSINESS CENTER
ADDRESS: NO ADDRESSES ASSIGNED YET
DATE OF REVIEW: 6/3/16 REVIEW # 3
STATUS: HOUSE NUMBERING NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS
CONCERNING THE COMMENTS BELOW.
1) I CAN'T LOCATE THE MONUMENT SIGN. CAN YOU PLEASE
PROVIDE THE PAGE IT'S ON.
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER: 16PR0151
ADDRESS: 10801 IRONBRIDGE ROAD
LATEST PLAN DATE: 9/25/15
DEPT. REC'D. DATE: 10/1/15
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 10/2/15
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. REVIEW DOES NOT INDICATE PROPER NUMBER AND OR LOCATION
OF FIRE HYDRANTS. THE NUMBER OF FIRE HYDRANTS REQUIRED
SHALL BE BASED ON THE INTERNATIONAL FIRE CODE - SECTION
C105 AND TABLE C105.1 FOR AVERAGE SPACING BETWEEN FIRE
HYDRANTS AND MAXIMUM DISTANCE FROM ANY POINT ON A STREET
OR ROAD FRONTAGE TO A FIRE HYDRANT. A MINIMUM DISTANCE OF
40 FEET SHALL BE PROVIDED BETWEEN FIRE HYDRANTS AND
BUILDING EXTERIOR WALL AND FIRE HYDRANTS SHALL BE
LOCATED AT A MAXIMUM DISTANCE OF 50 FEET BETWEEN HYDRANT
AND FIRE DEPARTMENT CONNECTION FOR ANY PROPOSED FIRE
SPRINKLER SYSTEM OR STANDPIPE SYSTEM.
CALL OUT THE THIRD HYDRANT LOCATED IN THE
ISLAND AT THE WAWA.
2. THE MINIMUM TURNING RADIUS TO BE PROVIDED FOR
EMERGENCY FIRE APPARATUS TO TRAVEL, INCLUDING CUL-DE-SACS,
SHALL BE AT LEAST 42' (OUTSIDE). THE TURNING RADIUS SHALL
BE DEMONSTRATED ON THE PLAN BY TEMPLATE.
ENSURE THE EXIT AT BOJANGLES CAN MEET THIS REQUIREMENT.
3. PROVIDE DETAILS AS TO THE METHOD TO BE USED TO PROVIDE
ACCESS TO ALL EXTERIOR POINTS OF THE BUILDING FROM
WITHIN 150 FEET OF AN APPROVED EMERGENCY FIRE APPARATUS
ACCESS ROADWAY. SEE THE 2012 INTERNATIONAL FIRE CODE,
SECTION 503.1.1 FOR CODE INFORMATION AND EXCEPTIONS.
IN ACCORDANCE WITH THE PROVISIONS OF THE INTERNATIONAL
FIRE CODE, SECTION 503, 503.1 THROUGH 503.1.3, FIRE LANES
BE PROVIDED. THE MINIMUM UNOBSTRUCTED CLEAR WIDTH SHALL
BE TWENTY FEET. THE MINIMUM REQUIRED VERTICAL CLEARANCE
SHALL BE THIRTEEN-FEET SIX-INCHES.
4. THE APPROXIMATE LOCATION OF ALL REQUIRED FIRE LANE
SIGNS AND CURB / STREET MARKING SHALL BE INDICATED ON
THE PLAN. FIRE LANES THAT ARE BETWEEN TWENTY AND
TWENTY-SIX FEET IN WIDTH SHALL BE POSTED AND MARKED ON
BOTH SIDES OF THE ROADWAY. FIRE LANES IN EXCESS OF
TWENTY-SIX FEET IN WIDTH UP TO THIRTY-TWO FEET IN WIDTH
SHALL BE POSTED AND MARKED ON ONE SIDE OF THE
ROADWAY. THE LOCATION OF AND METHOD OF MARKING FIRE
LANES SHALL BE CLEARLY INDICATED ON THE SUBMITTED SITE
PLAN. ALL FIRE LANE SIGNS SHALL BE DOUBLE FACED AND
INSTALLED PERPENDICULAR TO THE CURB.
5. PROVIDE THE CHESTERFIELD COUNTY STANDARD FIRE LANE
DETAIL ON THE PLAN.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER: 16PR0151
ADDRESS: 10801 IRONBRIDGE ROAD
LATEST PLAN DATE: 12/23/15
DEPT. REC'D. DATE: 01/05/16
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 01/05/16
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. MOVE LOCATION OF HYDRANT FROM THE END OF THE DEAD-END
ROAD TO THE INTERSECTION AT THE BEGINNING OF THE DEAD-END
ROAD.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER: 16PR0151
ADDRESS: 10801 IRONBRIDGE ROAD
LATEST PLAN DATE: 5/12/16
DEPT. REC'D. DATE: 5/19/16
SUBMITTAL NUMBER: 3RD REVIEW
REVIEW DATE: 5/20/16
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED PLAN IS APPROVED AS SUBMITTED.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: IRONBRIDGE BUSINESS CENTER
SITE PLAN NUMBER: 16PR0151
ADDRESS: 10801 IRONBRIDGE ROAD
LATEST PLAN DATE: 2/16/17
DEPT. REC'D. DATE: 3/23/17
SUBMITTAL NUMBER: 4TH REVIEW
REVIEW DATE: 3/3/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED PLAN IS APPROVED AS SUBMITTED.
==========================================================
==========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : DUSTIN DUNNAGAN / 706-2061
NAME OF PLAN : IRONBRIDGE BUSINESS CENTER
ADDRESS : 10911 IRONBRIDGE BLVD
SITE PLAN NO. : 16PR0151
LATEST PLAN DATE : SEPTEMBER 25, 2015
DEPT. REC'D DATE : OCTOBER 1, 2015
SUBMITTAL NUMBER : 1
REVIEW DATE : OCTOBER 20, 2015
RECOMMENDATION : NOT APPROVED
TABLE REVISION : NO
PLAT PROCESSING : NO
01. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND / OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURE
INCLUDING BUT NOT LIMITED TO WETLANDS, SURFACE WATERS
(E.G. VSMP PERMIT FOR CONSTRUCTION SITES, GROUND WATER
AND AIR QUALITY) FINAL APPROVAL OF THESE PLANS WILL NO
RELIEVE YOU OF YOUR RESPONSIBILITY. WETLANDS
DOCUMENTATION MUST BE RECEIVED BY THIS DEPARTMENT PRIO
TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
(CL-XX #) REPRESENTS A SUBMITTAL CHECKLIST COMMENT -
SECTION AND COMMENT NUMBER
02. EFFECTIVE JULY 1, 2014, ENFORCEMENT OF THE VIRGINIA
STORMWATER REGULATIONS BECAME THE RESPONSIBILITY OF TH
COUNTY FOR DEVELOPMENT PROJECTS WITHIN CHESTERFIELD
COUNTY. ADDITIONALLY, NEW STATE STORMWATER REGULATION
ALSO BECAME EFFECTIVE ON JULY 1, 2014. LAND DISTURBING
ACTIVITIES THAT OBTAINED A VSMP PERMIT PRIOR TO JULY 1
2014 MAY USE THE STORMWATER MANAGEMENT CRITERIA
SPECIFIED IN PART II C (9VAC25-870-93 ET SEQ) FOR TWO
PERMIT CYCLES. PROJECTS GRANDFATHERED UNDER THE
PROVISIONS OF 9VAC25-870-48 MAY FOLLOW THE REQUIREMENT
LISTED UNDER PART IIC FOR ONE PERMIT CYCLE. ALL OTHER
NEW DEVELOPMENT WILL BE SUBJECT TO THE REQUIREMENTS OF
PART IIB (9VAC25-870-62 TO 9VAC25-870-92).
03. A DETAIL MUST BE SHOWN ON THE PLANS WHICH DEMONSTRATES
THE ABILITY TO OBTAIN A MINIMUM OF 2' OF HORIZONTAL
BACKFILL BEHIND THE CURBING AND DROP INLETS PRIOR TO
BEGINNING A BACKSLOPE WHICH CANNOT EXCEED 1.5 : 1
WITHOUT ENCROACHING ONTO ANY ADJACENT PROPERTY. THE
DETAIL MUST BE TO SCALE. (CL-G&D 25)
04. APPROVAL OF THE SITE PLAN BY THE PRIVATE UTILITY
COMPANY IN RELATION TO ITS EASEMENT AND FACILITIES
THEREIN MUST BE PROVIDED PRIOR TO SITE PLAN APPROVAL.
05. SHEET C-3:
A) PROVIDE GUARDRAIL OR OTHER ACCEPTABLE VEHICULAR
PROTECTION MEASURES ALONG THE TOP OF THE RETAINING
WALL.
06. SHEET C-4:
A) SHOW THE ROOF DRAINS.
B) PROVIDE MORE OFFSITE CONTOUR DATA IN ORDER TO VERIF
CONDITIONS ON THE DOWNSTREAM PROPERTY.
C) PROVIDE CULVERT CALCULATION FOR CULVERT 23.
D) SHOW THE UNDERGROUND STORAGE.
E) THE CALLOUT FOR THE DETAILS OF THE UNDERGROUND
STORAGE APPEAR TO BE REFERENCING THE COVER PAGE.
F) THE TOP ELEVATION FOR STRUCTURE 1 DOES NOT APPEAR T
MATCH THE CURB ELEVATION SHOWN IN PLAN VIEW.
G) IN PLAN VIEW LABEL THE PIPE UPSTREAM OF STRUCTURE 1
H) PROVIDE A CULVERT ENTRANCE CALCULATION FOR THE
STRUCTURE UPSTREAM OF STRUCTURE 1.
07. CALCULATIONS:
A) THE I-VALUES PRESENTED IN THE DRAINAGE AREA
CALCULATIONS ARE HIGHER THAN WHAT IS CALCULATED
USING THE BDE VALUES. THIS IS A CONSERVATIVE
APPROACH.
B) ENSURE A 1.25 SATURATION FACTOR IS USED IN
CALCULATION THE 100-YEAR DISCHARGE.
C) THERE ARE THREE DIFFERENT DRAINAGE AREAS LABELED AS
BYPASS. CLARIFY THESE AREAS.
D) PROVIDE HYDROGRAPHS FOR THE UNATTENUATED SITE FLOW.
E) PROVIDE ANALYSIS, METHODOLOGY, AND APPROACH FOR THE
DEVELOPMENT OF THE 1-YEAR RATIONAL METHODOLOGY BDE
VALUES. VDOT AND DEQ DO NOT HAVE PUBLISHED VALUES
AND METHODOLOGY FOR THE 1-YEAR RATIONAL METHOD.
F) IN THE UNATTENUATED FLOW, THE BYPASS AREA DOES NOT
GO TOWARD THE OUTFALL LOCATION AND SHOULD NOT BE
CONSIDERED IN THE ANALYSIS.
G) IN THE ROUTING CALCULATIONS, FOR POND NO. 2, THE
OUTFALL ORIFICE DOES NOT MATCH THE 15" OUTFALL PIPE
VERIFY OUTFALL SIZE.
H) IN THE ROUTING CALCULATIONS, PROVIDE A STARTING
WATER SURFACE ELEVATION FOR THE UNDERGROUND
DETENTION.
08. A NOTE MUST BE ADDED TO THE SEQUENCE OF CONSTRUCTION
STATING THAT THE VSMP CONSTRUCTION ACTIVITY OPERATOR
AND THE ENVIRONMENTAL INSPECTOR (OR AUTHORIZED
REPRESENTATIVE) MUST ATTEND THE PRE-CONSTRUCTION
MEETING.
09. STEPS MUST BE INCLUDED IN THE SEQUENCE OF CONSTRUCTION
EVENTS FOR BUILDING CONSTRUCTION. (CL-EC 6)
10. A DETAIL MUST BE SHOWN WHICH PROVIDES FOR PLACEMENT OF
EXCAVATED TRENCH MATERIAL ON THE UPHILL SIDE OF THE
TRENCH WHILE SILT FENCE AND STOCKPILED MATERIALS ARE
PLACED ON THE DOWNSTREAM SIDE. (CL-EC 37)
11. THE OFF-SITE UTILITY LINE(S) MUST BE SHOWN ON THE
EROSION CONTROL PLAN SHEETS WITH SILT FENCE ON THE
DOWNSTREAM SIDE. (CL-EC 38)
12. THE FOLLOWING NOTE(S) MUST BE ADDED TO OR ADJACENT TO
THE SEQUENCE OF CONSTRUCTION: (CL-EC 42)
A. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
SURETY FOR THE CONSTRUCTION OF THE PERMANENT BMP MUST
BE POSTED WITH ENVIRONMENTAL ENGINEERING. (COUNTY CODE
PART II, CHAPTER 8, SEC. 8-16)
B. THE BMP MUST BE CERTIFIED PRIOR TO RELEASE OF THE BMP
PERFORMANCE BOND AND CERTIFICATE OF OCCUPANCY.
C. THE LIMITS OF THE WETLANDS MUST BE FLAGGED IN THE FIEL
(SURVEY LOCATED) WITH OPTIC ORANGE SAFETY FENCE PRIOR
TO ISSUANCE OF A LAND DISTURBANCE PERMIT. (CL-EC 42G)
13. SHEET C-6:
A) SHOW AND LABEL THE DRAINAGE AREAS FOR THE PROPOSED
SEDIMENT TRAPS.
B) SHOW THE LOCATIONS OF THE SILT FENCE OUTFALLS.
C) CLARIFY HOW THE PROPOSED CONSTRUCTION ENTRANCE TO
THE NORTH IS TO BE INSTALLED OVER EXISTING PAVEMENT
DEMO OF THE EXISTING PAVEMENT MAY NEED TO OCCUR
PRIOR TO INSTALLATION OF THE CONSTRUCTION ENTRANCE.
D) SHOW THE MINIMUM CONSTRUCTION LIMITS REQUIRED TO
INSTALL THE BOUNDARY CONTROL DEVICES.
E) PROVIDE TEMPORARY SEEDING FOR THE DIVERSION DIKES
AND SEDIMENT TRAPS.
F) IT APPEARS SOME OF THE DIVERSION DIKES ARE RUNNING
UPHILL. ENSURE THE DIVERSION DIKES HAVE POSITIVE
DRAINAGE.
G) THE OUTFALL AREA FOR THE SEDIMENT TRAPS APPEARS TO
BE ENCUMBERED WITH DIVERSION DIKES TRAPPING THE
WATER BETWEEN THE TWO FACILITIES. PROVIDE AN OUTLE
FOR THE WATER LEAVING THE TRAPS.
H) IT IS PREFERRED TO ONLY HAVE ONE CONSTRUCTION
ENTRANCE ON SITE.
I) IN THE CRITICAL AREAS SECTION OF THE ESC NARRATIVE,
IT STATES THE DISCHARGE WILL BE THROUGH SHEET FLOW;
HOWEVER, CHANNELIZED OUTFALLS WITH OUTLET PROTECTIO
IS SHOWN. VERIFY DISCHARGE METHODOLOGY FROM THE
SITE.
J) IN THE CRITICAL AREAS SECTION OF THE ESC NARRATIVE,
IT STATES THERE ARE NO WETLANDS ON SITE; HOWEVER,
THE SITE IS SHOWN IN EXISTING CONDITIONS HEAVILY
ENCUMBERED WITH WETLANDS. CLARIFY NOTE.
K) IN THE ESC SEQUENCE CLARIFY WHEN THE SUPER SILT
FENCE IS TO BE INSTALLED.
14. SHEET C-7:
A) PROVIDE BLANKET AND MATTING ON ALL EXPOSED SLOPES
3:1 OR GREATER.
B) CLARIFY HOW THE SEDIMENT TRAPS ARE TO FUNCTION
DURING GRADING OPERATIONS AND INSTALLATION OF THE
STORM SEWER PIPING.
C) UPDATE THE NOTE ABOVE VEGETATIVE AND EROSION CONTRO
TO THE MOST RECENT ESC REGULATIONS.
15. SHEET C-8:
A) IN THE OUTLET PROTECTION DETAIL SHOW A MINIMUM OF 2
OF CLASS 1 RIP-RAP.
16. SHEET C-9:
A) SHOW ALL UTILITY CROSSINGS AND LABEL THE REQUIRED
SEPARATION.
B) SHOW AND LABEL OUTLET PROTECTION AT 0% GRADE WITH
FILTER FABRIC.
C) THE PIPE UPSTREAM OF STRUCTURE 1 IS SHOWN AS A 12"
PIPE. A 15" PIPE IS REQUIRED. 12" CAN ONLY BE USE
FOR THE FIRST 50' OF ENTRANCE PIPE.
D) IT APPEARS THAT THE UNDERGROUND STORAGE SETS BELOW
THE OUTFALL PIPES. THIS RESULTS IN A PERMANENT
POOL. IF INFILTRATION IS TO BE USED, INFILTRATION
TESTING WILL BE REQUIRED SHOWING THE INFILTRATION
AREA HAS AT LEAST 0.5 IN/HR OF INFILTRATION. IN
ADDITION, CONSTRUCTION PRACTICES WILL NEED TO BE
NOTED AND REQUIRED TO ENSURE THAT THE HEAVY
CONSTRUCTION EQUIPMENT AND TRAFFIC WILL NOT COMPACT
THE SOIL AND RESTRICT INFILTRATION.
E) PIPE 24 IS SHOWN AS AN 18" PIPE; HOWEVER, IN THE
STRUCTURE TABLE IT IS LISTED AS 15". VERIFY PIPE
SIZE.
F) THE ELEVATIONS AND STORAGE VOLUMES FOR UNDERGROUND
STORAGE 2 IS TRUNCATED ON THE PAGE.
17. SHEET C-10:
A) PROVIDE AN EXISTING DRAINAGE AREA MAP.
B) CLARIFY WHERE THE WATER TO THE NORTH SECTION OF THE
PLANS DISCHARGES.
C) SHOW AND LABEL ALL FLOW PATHS ABOVE A 5 MINUTE TIME
OF-CONCENTRATION.
18. A STORMWATER COMPLIANCE SHEET(S) IS REQUIRED FOR
PROJECTS UTILIZING PART IIB OF THE CURRENT VSMP
REGULATIONS. THE FOLLOWING INFORMATION IS REQUIRED TO
BE SHOWN ON THE SHEET(S):
A. NATURAL VEGETATED AREA EASEMENTS FOR AREAS CLAIMED AS
FORESTED/OPEN SPACE IN THE VRRM SPREADSHEET THAT IS NO
ENCOMPASSED BY A BMP EASEMENT, RPA, OR WITHIN A
PLANNING BUFFER/TREE SAVE AREA.
B. INCREMENTAL DRAINAGE AREAS TO EACH BMP AND THE LAND
COVER TYPES WITHIN EACH BMP DRAINAGE AREA.
C. DRAINAGE AREA MAP SHOWING:
A) THE DRAINAGE AREA(S) TO WHERE THE SITE OUTFALL(S)
MEET ENERGY BALANCE FOR THE CHANNEL PROTECTION
ANALYSIS AND WHERE THE SITE MEETS 10-YEAR POST TO
10-YEAR PRE FOR FLOOD PROTECTION.
B) WHERE THE SITE IS 1% OR LESS THAN THE ENTIRE
DRAINAGE AREA OR;
C) WHERE THE UNATTENUATED FLOW IS 1% OR LESS THAN THE
FLOW AT THAT POINT OR;
D) WHERE THE FLOW FROM THE SITE AND ITS DOWNSTREAM ARE
REACHES A NATURAL STORMWATER CONVEYANCE SYSTEM FOR
THE 1-YEAR STORM, AND WHERE THE FLOW FROM THE SITE
AND ITS DOWNSTREAM AREA REACHES A DOCUMENTED
FLOODPLAIN (COUNTY OR FEMA) FOR THE 10-YEAR STORM.
D. PROVIDE CHANNEL AND FLOOD PROTECTION CALCULATIONS.
E. PROPOSED EASEMENT LOCATIONS.
19. THE ENTIRE BASIN MUST BE ENCLOSED WITHIN AN SWM/BMP
EASEMENT WHICH EXTENDS 8 FT. BEYOND THE 100-YEAR WSE.
OR DOWNSTREAM TOE OF DAM, WHICHEVER APPLIES.
(CL-CBPA 14)
20. A MINIMUM 20' WIDE ACCESS EASEMENT MUST BE PROVIDED
FROM THE SWM/BMP EASEMENT TO A PUBLIC RIGHT-0F-WAY FOR
FUTURE MAINTENANCE. (CL-CBPA 15)
21. PROVISIONS MUST BE MADE IN THE EROSION CONTROL
NARRATIVE FOR THE SWM/BMP FACILITY TO BE OBSERVED
BY A PROFESSIONAL ENGINEER DURING CONSTRUCTION. "AS
BUILT" INFORMATION WILL BE REQUIRED FOR FUTURE
CERTIFICATION OF THE FACILITY. (CL-CBPA 42)
22. RCP IS REQUIRED WITHIN ALL COUNTY DRAINAGE EASEMENTS.
AN EXCEPTION REQUEST WILL BE REQUIRED IF RCP IS TO NOT
BE USED.
23. SHEET C-11:
A) RENAME TO STORMWATER COMPLIANCE SHEET.
B) THE FORESTED/OPEN SPACE HATCH DOES NOT SHOW UP ON
THE PLANS. USE AN ALTERNATE HATCHING PATTERN THAT
WILL SHOW UP WHEN PRINTED AND SCANNED.
C) SHOW AND LABEL THE SITE AREA.
D) ENERGY BALANCE IS USED FOR THE CHANNEL PROTECTION
CRITERIA. IT IS NOT APPLICABLE TOWARD THE FLOOD
PROTECTION CRITERIA. CLARIFY THE COMPLIANCE
METHODOLOGY FOR FLOOD PROTECTION.
E) THE COMPLIANCE METHOD SHOWN FOR CHANNEL PROTECTION
FOR OUTFALL 1 IS ENERGY BALANCE. ENERGY BALANCE IS
ONLY TO BE USED WHEN DISCHARGING TO A MAN-MADE STOR
SEWER SYSTEM OR A NATURAL CHANNEL. A NATURALLY FLA
WETLAND AREA DOES NOT MEET THE REQUIREMENTS OF A
NATURAL CHANNEL AND THEREFORE ENERGY BALANCE DOES
NOT APPLY AT THIS LOCATION. PROVIDE AN ANALYSIS
BASED ON THE PREVIOUS COMMENTS LIMITS OF ANALYSIS O
PROVIDE ENERGY DISSIPATION METHODS THAT ENCOURAGE
SHEET FLOW AT THIS LOCATION.
F) IN THE COMPLIANCE TABLE, THE DRAINAGE AREAS FOR
BASIN 1 DO NOT MATCH THE VRRM SPREADSHEET. VERIFY
DA.
24. PRIOR TO PLAN APPROVAL, DOCUMENTATION OF THE OWNER'S
ACQUISITION OF THE NONPOINT NUTRIENT OFFSETS MUST BE
PROVIDED IN A CERTIFICATION FROM THE OFFSET BROKER
DOCUMENTING THE NUMBER OF PHOSPHOROUS NONPOINT NUTRIEN
OFFSETS ACQUIRED AND THE ASSOCIATED RATIO OF NITROGEN
NONPOINT NUTRIENT OFFSETS AT THE OFFSET GENERATING
FACILITY.
25. NOTE THAT THE NONPOINT NUTRIENT OFFSETS USED FOR WATER
QUALITY COMPLIANCE MUST BE GENERATED IN THE SAME OR
ADJACENT EIGHT DIGIT HYDROLOGIC UNIT CODE AS DEFINED B
THE UNITED STATES GEOLOGICAL SURVEY AS THE SITE.
NONPOINT NUTRIENT OFFSETS OUTSIDE THE SAME OR ADJACENT
EIGHT DIGIT HYDROLOGIC UNIT CODE MAY ONLY BE USED IF I
IS DETERMINED THAT NO NONPOINT NUTRIENT OFFSETS ARE
AVAILABLE WITHIN THE SAME OR ADJACENT EIGHT DIGIT
HYDROLOGIC UNIT CODE. IN SUCH CASES, THE NONPOINT
NUTRIENT OFFSETS MUST BE GENERATED WITHIN THE SAME
TRIBUTARY. PROVIDE A HYDROLOGIC UNIT MAP SHOWING THE
LOCATION OF THE PROJECT AND THE OFFSET GENERATING
FACILITY.
26. THE CBPA COMPLIANCE NOTE MUST SPECIFY THE NUMBER OF
PHOSPHOROUS NONPOINT NUTRIENT OFFSETS ACQUIRED
AND THE NAME OF THE OFFSET GENERATING FACILITY.
27. IT IS THE RESPONSIBILITY OF THE OWNER TO PROVIDE ONE
ADDITIONAL SET OF PLANS TO THE ENVIRONMENTAL
ENGINEERING DEPARTMENT AND OBTAIN AN "APPROVED FOR
CONSTRUCTION" STAMP ON TWO ADDITIONAL SETS FOR THE
OWNER TO KEEP ON-SITE.
28. PERMISSION MUST BE OBTAINED FROM THE ADJACENT PROPERTY
OWNER(S) ALLOWING FOR GRADING ON THE PROPERTY AS
PROPOSED PRIOR TO ISSUANCE OF A LAND DISTURBANCE
PERMIT.
29. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, THE
NAME, "WALK-IN" ADDRESS, AND TELEPHONE NUMBER OF
A LOCAL REGISTERED AGENT REPRESENTING THE OWNER FOR
SERVICE OF PROCESS MUST BE PROVIDED ON THE "APPOINTMEN
OF AGENT FOR SERVICE OF PROCESS" FORM FOUND ON THE
CHESTERFIELD COUNTY ENVIRONMENTAL ENGINEERING WEBPAGE.
(CL-GENERAL 12)
30. ALL ONSITE DRAINAGE EASEMENTS INCLUDING STORMWATER /
BMP DRAINAGE EASEMENTS MUST BE RECORDED PRIOR TO
ISSUANCE OF A BUILDING PERMIT FOR THIS PROJECT.
31. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
SURETY FOR THE CONSTRUCTION OF THE PERMANENT BMP MUST
BE POSTED WITH ENVIRONMENTAL ENGINEERING. (COUNTY CODE
PART II, CHAPTER 8, SEC. 8-16)
32. THE BMP MUST BE CERTIFIED PRIOR TO RELEASE OF THE BMP
PERFORMANCE BOND AND CERTIFICATE OF OCCUPANCY.
33. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A COPY
OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD
FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD VERSIO
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINI
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE SITE
PLAN NAME, SITE PLAN NUMBER, ENGINEERING FIRM AND CAD
FILE PREPARER'S NAME AND PHONE NUMBER. THE FILE MUST
CONTAIN THE FOLLOWING, EACH CLEARLY LABELED IN SEPARAT
LAYERS:
A. PROPOSED BUILDING FOOTPRINT;
B. PARKING LOTS AND DRIVEWAYS;
C. ROADS;
D. SIDEWALKS;
E. ALL JURISDICTIONAL WETLAND AREAS AND/OR WATERS OF THE
U.S./STATE; AND
F. FLOODPLAINS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
34. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND SUBSTANTIAL OR FULL SITE PLAN APPROVAL IS REQUIRED
PRIOR TO ITS ISSUANCE. A LAND DISTURBANCE PERMIT IS
A PREREQUISITE TO A BUILDING PERMIT.
35. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND THE FOLLOWING ARE REQUIRED PRIOR TO ITS ISSUANCE:
A. SUBSTANTIAL OR FULL SITE PLAN APPROVAL
B. A VDOT LAND USE PERMIT
C. A LETTER MUST BE RECEIVED FROM A QUALIFIED WETLANDS
EXPERT STATING:
1.THERE ARE NO WETLANDS IMPACTED ON THIS PROJECT, OR
2.ALL APPLICABLE FEDERAL AND STATE WETLAND PERMITS HAVE
BEEN ACQUIRED (COPIES OF THE PERMITS MUST BE SUBMITTED
D. THE VIRGINIA STORMWATER MANAGEMENT PERMIT (VSMP)
REGISTRATION STATEMENT AND FEE OF $2,700
E. THE STORMWATER POLLUTION PREVENTION PLAN (SWPPP) BOOK
F. POSTING OF AN EROSION AND SEDIMENT CONTROL SURETY
(AMOUNT TO BE APPROVED BY EE)
==========================================================
==========================================================
==========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : DUSTIN DUNNAGAN / 706-2061
NAME OF PLAN : IRONBRIDGE BUSINESS CENTER
ADDRESS : 10911 IRONBRIDGE BLVD
SITE PLAN NO. : 16PR0151
LATEST PLAN DATE : DECEMBER 23, 2015
DEPT. REC'D DATE : JANUARY 04, 2016
SUBMITTAL NUMBER : 2
REVIEW DATE : FEBRUARY 5, 2016
RECOMMENDATION : NOT APPROVED
TABLE REVISION : NO
PLAT PROCESSING : NO
01. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND / OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURE
INCLUDING BUT NOT LIMITED TO WETLANDS, SURFACE WATERS
(E.G. VSMP PERMIT FOR CONSTRUCTION SITES, GROUND WATER
AND AIR QUALITY) FINAL APPROVAL OF THESE PLANS WILL NO
RELIEVE YOU OF YOUR RESPONSIBILITY. WETLANDS
DOCUMENTATION MUST BE RECEIVED BY THIS DEPARTMENT PRIO
TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
(CL-XX #) REPRESENTS A SUBMITTAL CHECKLIST COMMENT -
SECTION AND COMMENT NUMBER
02. EFFECTIVE JULY 1, 2014, ENFORCEMENT OF THE VIRGINIA
STORMWATER REGULATIONS BECAME THE RESPONSIBILITY OF TH
COUNTY FOR DEVELOPMENT PROJECTS WITHIN CHESTERFIELD
COUNTY. ADDITIONALLY, NEW STATE STORMWATER REGULATION
ALSO BECAME EFFECTIVE ON JULY 1, 2014. LAND DISTURBING
ACTIVITIES THAT OBTAINED A VSMP PERMIT PRIOR TO JULY 1
2014 MAY USE THE STORMWATER MANAGEMENT CRITERIA
SPECIFIED IN PART II C (9VAC25-870-93 ET SEQ) FOR TWO
PERMIT CYCLES. PROJECTS GRANDFATHERED UNDER THE
PROVISIONS OF 9VAC25-870-48 MAY FOLLOW THE REQUIREMENT
LISTED UNDER PART IIC FOR ONE PERMIT CYCLE. ALL OTHER
NEW DEVELOPMENT WILL BE SUBJECT TO THE REQUIREMENTS OF
PART IIB (9VAC25-870-62 TO 9VAC25-870-92).
03. APPROVAL OF THE SITE PLAN BY THE PRIVATE UTILITY
COMPANY IN RELATION TO ITS EASEMENT AND FACILITIES
THEREIN MUST BE PROVIDED PRIOR TO SITE PLAN APPROVAL.
04. IN GENERAL IT IS RECOMMENDED THAT THE TURN LANE AND
OTHER WORK THAT IS SUBJECT TO PART IIC CRITERIA BE
RELOCATED TOWARD THE BACK OF THE PLAN SET. IT SHOULD
INCLUDE ANY NECESSARY CALCULATIONS FOR THE STORMWATER
QUALITY AND QUANTITY. THIS WILL HELP TO EASE REVIEW
AND FUTURE REVIEW OF THE WORK AND PROVIDE CLARITY AS T
WHY THIS AREA IS NOT USING PART IIC.
05. SHEET C-3:
A) PROVIDE EASEMENTS FOR THE DRY SWALE AND SHEET FLOW
TO OPEN SPACE.
B) PROVIDE ACCESS EASEMENTS TO THE BMP EASEMENTS.
06. SHEET C-4:
A) PROVIDE MORE OFFSITE CONTOUR DATA IN ORDER TO VERIF
CONDITIONS ON THE DOWNSTREAM PROPERTY.
B) IT IS SUGGESTED TO DISCHARGE THE ROOF DRAINS TOWARD
THE WETLANDS.
C) PROVIDE CURB ELEVATIONS FOR THE POPEYE'S PARKING TO
THE NORTHWEST FOR THE RADII.
D) THE INVERT OUT FOR PIPE 8 DOES NOT MATCH
CALCULATIONS.
E) CLARIFY HOW THE DRAINAGE FROM THE CG-6 ALONG IRON
BRIDGE ROAD WILL BE CONVEYED DOWN THE SLOPE BANK
TOWARD THE WETLANDS AS IT EXITS OFF OF ROUTE 1690.
AS SHOWN IT WILL LIKELY BE CONCENTRATED FLOW THAT
COULD LEAD TO EROSION. THIS AREA MAY WARRANT A PG-
2A WITH OUTLET PROTECTION/LEVEL SPREADER PRIOR TO
ENTERING THE WETLANDS.
07. SHEET C-6:
A) IT APPEARS SOME OF THE DIVERSION DIKES ARE RUNNING
UPHILL. ENSURE THE DIVERSION DIKES HAVE POSITIVE
DRAINAGE.
B) PROVIDE SAFETY FENCE AROUND THE CONSERVED OPEN SPAC
AND DRY SWALE TO PREVENT CONSTRUCTION TRAFFIC AND
OVER COMPACTION OF SOIL.
08. SHEET C-7:
A) UPDATE REFERENCES TO THE CURRENT ESC REGULATIONS.
09. SHEET C-10:
A) CLARIFY WHERE THE AREA LABELED AS RETAIL DISCHARGES
B) IN THE DRY SWALE DRAINAGE AREA THE CURB ISLAND
APPEARS TO HAVE TWO DIFFERENT SET OF CURB LINES.
CLARIFY THE CURB LINES.
C) CLARIFY IF THE COS-1 DA IS INCLUDED IN THE WETLANDS
TO CULVERT DRAINAGE AREA.
10. SHEET C-11:
A) ENERGY BALANCE IS USED FOR THE CHANNEL PROTECTION
CRITERIA. IT IS NOT APPLICABLE TOWARD THE FLOOD
PROTECTION CRITERIA. CLARIFY THE COMPLIANCE
METHODOLOGY FOR FLOOD PROTECTION. (SHEET FLOW OR
POST TO PRE)
B) THE CHANNEL PROTECTION METHOD FOR COMPLIANCE FOR
OUTFALL 1 SHOULD BE SHEET FLOW.
C) THE IMPROVEMENT FACTORS FOR THE OUTFALLS SHALL BE
0.8 SINCE THE SITE DISTURBANCE IS OVER 1 ACRE.
D) IT DOES NOT APPEAR THAT THE OPEN SPACE FROM THE DRY
SWALE IS COUNTED AS SUCH IN THE BMP DRAINAGE AREA
BREAKDOWN. CLARIFY DRAINAGE AREA LAND USE.
11. IRON BRIDGE ROAD CROSS-SECTIONS, VERIFY THAT 0% SLOPE
IS ACCEPTABLE BY VDOT. 2% CROSS-SLOPE IS TYPICALLY
REQUIRED TO MEET ADA STANDARDS.
12. ON SHEET C-19, CLARIFY IF A SEPARATE STOCKPILE IS
NEEDED FOR THE ROADWORK.
13. LANDSCAPE PLAN:
A) SHOW STORM SEWER.
B) REPLACE RED MAPLES WITHIN 10' OF THE STORM SEWER
WITH TREES WITH LESS AGGRESSIVE ROOT SYSTEMS.
C) KOREAN FEATHER REED GRASS IS NOT TO BE USED WITHIN
THE DRY SWALE. USE NORTHERN SEA OATS, INDIAN GRASS
WOOL GRASS, OR OTHER NATIVE PLANTS.
D) USE COMMON WINTERBERRY INSTEAD OF INKBERRY.
COMMON WINTERBERRY IS BETTER SUITED FOR THE PIEDMON
REGION.
14. BMP DESIGN:
A) THE INFILTRATION TESTING WILL NEED TO BE DONE PRIOR
TO PLAN APPROVAL; OTHERWISE, PROVIDE UNDERDRAINS.
B) SHOW THE TV, 2-YEAR, AND 10-YEAR ELEVATIONS FOR THE
DRY SWALE.
C) THE ADJACENT WETLANDS ARE SHOWN AT AN ELEVATION OF
196. THE DRY SWALE WILL HAVE A SURFACE ELEVATION O
196 AND THE BOTTOM OF THE MEDIA AND GRAVEL WILL BE
AT AN ELEVATION OF 193. IT IS HIGHLY LIKELY THIS
WILL BE BENEATH THE SEASONAL HIGH GROUNDWATER
ELEVATION. PROVIDE GEOENVIRONMENTAL TESTING THAT
SHOWS THIS PRACTICE WILL HAVE AT LEAST 2' OF
VERTICAL SEPARATION FROM THE SEASONAL HIGH
GROUNDWATER ELEVATION AND THE BOTTOM OF THE
PRACTICE. IF THIS IS NOT ACHIEVED THE DRY SWALE
WILL NEED TO BE REDESIGNED TO MEET THE
SPECIFICATIONS OR A PRACTICE PROVIDED THAT CAN BE
PLACED WITHIN THE GROUNDWATER TABLE.
D) PROVIDE SPOT SHOT GRADING OF THE DRY SWALE.
E) PROVIDE PROFILE AND CROSS-SECTION OF THE DRY SWALE
SHOWING ALL INFORMATION REQUIRED TO BUILD THE DRY
SWALE INCLUDING MEDIA DEPTHS AND ELEVATIONS.
F) PROVIDE CONVEYANCE CALCULATIONS FOR THE DRY SWALE.
G) A LEVEL 2 DRY SWALE DESIGN IS REQUIRED IN THE
SPECIFICATIONS TO EITHER BE OFF-LINE OR PROVIDE
MULTI-CELL DESIGN. PROVIDE A DESIGN THAT MEETS
THESE SPECIFICATIONS.
H) PROVIDE MEDIA SPECIFICATIONS FOR THE DRY SWALE.
I) IT APPEARS THAT THE D SOILS FOR THE DRY SWALE WERE
NOT INCLUDED IN THE DESIGN CALCULATIONS OR THE BMP
TABLE. VERIFY THE DRAINAGE AREA AND CONTRIBUTING
LAND USES ARE CORRECT.
J) SPECIFY FILTER FABRIC UNDERNEATH THE GRAVEL
DIAPHRAGMS.
K) CLARIFY THAT THE INFILTRATION TESTING MUST BE AT
LEAST EVERY 200' AND SHOULD INCLUDE A MINIMUM OF TW
TEST LOCATIONS WITHIN THE INFILTRATION/DRY SWALE
PRACTICE.
L) PROVIDE NOTES THAT THE DRY SWALE AND GRAVEL
DIAPHRAGMS ARE NOT TO BE INSTALLED UNTIL THE
CONTRIBUTING DRAINAGE AREAS ARE STABILIZED.
M) THE SHEET FLOW TO OPEN SPACE MUST HAVE 2% SLOPE FOR
THE FIRST 10' OF SHEET FLOW. AS SHOWN IT IS AGAINS
A 3:1 SIDE SLOPE AND DOES NOT APPEAR TO MEET THIS
CRITERIA.
N) PROVIDE SIGNAGE FOR THE BMPS TO PREVENT OVER MOWING
AND TO NOTIFY OF THE CONSERVED OPEN SPACE. THESE
SIGNS SHOULD BE SIMILAR TO THE RPA SIGNS.
15. CALCULATIONS:
A) ENSURE A 1.25 SATURATION FACTOR IS USED IN
CALCULATION THE 100-YEAR DISCHARGE.
B) CULVERT CALCULATIONS FOR CULVERT 8 ARE LABELED AS
CULVERT 6.
C) THE LEVEL SPREADER FOR SHEET FLOW FROM THE PIPE
SHOULD BE BASED ON 40 LF PER CFS SINCE IT IS GOING
INTO A FORESTED AREA.
D) PROVIDE FULL ROUTING CALCULATIONS. THE SUMMARY DOE
NOT ALLOW ENOUGH REVIEW DETAIL TO DETERMINE IF
CORRECT ASSUMPTIONS AND PARAMETERS WERE USED IN THE
ANALYSIS.
E) CLARIFY HOW A ONE-YEAR RATIONAL METHOD STORM WAS
DETERMINED. DEQ AND VDOT DOES NOT HAVE PARAMETERS
FOR THE 1-YEAR RATIONAL STORM.
F) THE DRY SWALE MAY NOT BE ABLE TO USE THE DOWNSTREAM
WETLANDS AS A CONSERVATION AREA UNLESS AN EASEMENT
IS USED TO PROTECT THE WETLANDS FROM FUTURE
DEVELOPMENT.
16. PROVISIONS MUST BE MADE IN THE EROSION CONTROL
NARRATIVE FOR THE SWM/BMP FACILITY TO BE OBSERVED
BY A PROFESSIONAL ENGINEER DURING CONSTRUCTION. "AS
BUILT" INFORMATION WILL BE REQUIRED FOR FUTURE
CERTIFICATION OF THE FACILITY. (CL-CBPA 42)
17. A DETAIL MUST BE SHOWN WHICH PROVIDES FOR PLACEMENT OF
EXCAVATED TRENCH MATERIAL ON THE UPHILL SIDE OF THE
TRENCH WHILE SILT FENCE AND STOCKPILED MATERIALS ARE
PLACED ON THE DOWNSTREAM SIDE. (CL-EC 37)
18. PRIOR TO PLAN APPROVAL, DOCUMENTATION OF THE OWNER'S
ACQUISITION OF THE NONPOINT NUTRIENT OFFSETS MUST BE
PROVIDED IN A CERTIFICATION FROM THE OFFSET BROKER
DOCUMENTING THE NUMBER OF PHOSPHOROUS NONPOINT NUTRIEN
OFFSETS ACQUIRED AND THE ASSOCIATED RATIO OF NITROGEN
NONPOINT NUTRIENT OFFSETS AT THE OFFSET GENERATING
FACILITY.
19. NOTE THAT THE NONPOINT NUTRIENT OFFSETS USED FOR WATER
QUALITY COMPLIANCE MUST BE GENERATED IN THE SAME OR
ADJACENT EIGHT DIGIT HYDROLOGIC UNIT CODE AS DEFINED B
THE UNITED STATES GEOLOGICAL SURVEY AS THE SITE.
NONPOINT NUTRIENT OFFSETS OUTSIDE THE SAME OR ADJACENT
EIGHT DIGIT HYDROLOGIC UNIT CODE MAY ONLY BE USED IF I
IS DETERMINED THAT NO NONPOINT NUTRIENT OFFSETS ARE
AVAILABLE WITHIN THE SAME OR ADJACENT EIGHT DIGIT
HYDROLOGIC UNIT CODE. IN SUCH CASES, THE NONPOINT
NUTRIENT OFFSETS MUST BE GENERATED WITHIN THE SAME
TRIBUTARY. PROVIDE A HYDROLOGIC UNIT MAP SHOWING THE
LOCATION OF THE PROJECT AND THE OFFSET GENERATING
FACILITY.
20. THE CBPA COMPLIANCE NOTE MUST SPECIFY THE NUMBER OF
PHOSPHOROUS NONPOINT NUTRIENT OFFSETS ACQUIRED
AND THE NAME OF THE OFFSET GENERATING FACILITY.
21. IT IS THE RESPONSIBILITY OF THE OWNER TO PROVIDE ONE
ADDITIONAL SET OF PLANS TO THE ENVIRONMENTAL
ENGINEERING DEPARTMENT AND OBTAIN AN "APPROVED FOR
CONSTRUCTION" STAMP ON TWO ADDITIONAL SETS FOR THE
OWNER TO KEEP ON-SITE.
22. PERMISSION MUST BE OBTAINED FROM THE ADJACENT PROPERTY
OWNER(S) ALLOWING FOR GRADING ON THE PROPERTY AS
PROPOSED PRIOR TO ISSUANCE OF A LAND DISTURBANCE
PERMIT.
23. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, THE
NAME, "WALK-IN" ADDRESS, AND TELEPHONE NUMBER OF
A LOCAL REGISTERED AGENT REPRESENTING THE OWNER FOR
SERVICE OF PROCESS MUST BE PROVIDED ON THE "APPOINTMEN
OF AGENT FOR SERVICE OF PROCESS" FORM FOUND ON THE
CHESTERFIELD COUNTY ENVIRONMENTAL ENGINEERING WEBPAGE.
(CL-GENERAL 12)
24. ALL ONSITE DRAINAGE EASEMENTS INCLUDING STORMWATER /
BMP DRAINAGE EASEMENTS MUST BE RECORDED PRIOR TO
ISSUANCE OF A BUILDING PERMIT FOR THIS PROJECT.
25. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
SURETY FOR THE CONSTRUCTION OF THE PERMANENT BMP MUST
BE POSTED WITH ENVIRONMENTAL ENGINEERING. (COUNTY CODE
PART II, CHAPTER 8, SEC. 8-16)
26. THE BMP MUST BE CERTIFIED PRIOR TO RELEASE OF THE BMP
PERFORMANCE BOND AND CERTIFICATE OF OCCUPANCY.
27. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A COPY
OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD
FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD VERSIO
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINI
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE SITE
PLAN NAME, SITE PLAN NUMBER, ENGINEERING FIRM AND CAD
FILE PREPARER'S NAME AND PHONE NUMBER. THE FILE MUST
CONTAIN THE FOLLOWING, EACH CLEARLY LABELED IN SEPARAT
LAYERS:
A. PROPOSED BUILDING FOOTPRINT;
B. PARKING LOTS AND DRIVEWAYS;
C. ROADS;
D. SIDEWALKS;
E. ALL JURISDICTIONAL WETLAND AREAS AND/OR WATERS OF THE
U.S./STATE; AND
F. FLOODPLAINS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
28. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND SUBSTANTIAL OR FULL SITE PLAN APPROVAL IS REQUIRED
PRIOR TO ITS ISSUANCE. A LAND DISTURBANCE PERMIT IS
A PREREQUISITE TO A BUILDING PERMIT.
29. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND THE FOLLOWING ARE REQUIRED PRIOR TO ITS ISSUANCE:
A. SUBSTANTIAL OR FULL SITE PLAN APPROVAL
B. A VDOT LAND USE PERMIT
C. A LETTER MUST BE RECEIVED FROM A QUALIFIED WETLANDS
EXPERT STATING:
1.THERE ARE NO WETLANDS IMPACTED ON THIS PROJECT, OR
2.ALL APPLICABLE FEDERAL AND STATE WETLAND PERMITS HAVE
BEEN ACQUIRED (COPIES OF THE PERMITS MUST BE SUBMITTED
D. THE VIRGINIA STORMWATER MANAGEMENT PERMIT (VSMP)
REGISTRATION STATEMENT AND FEE OF $2,700
E. THE STORMWATER POLLUTION PREVENTION PLAN (SWPPP) BOOK
F. POSTING OF AN EROSION AND SEDIMENT CONTROL SURETY
(AMOUNT TO BE APPROVED BY EE)
==========================================================
==========================================================
==========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : DUSTIN DUNNAGAN / 706-2061
NAME OF PLAN : IRONBRIDGE BUSINESS CENTER
ADDRESS : 10911 IRONBRIDGE BLVD
SITE PLAN NO. : 16PR0151
LATEST PLAN DATE : MAY 12, 2016
DEPT. REC'D DATE : MAY 18, 2016
SUBMITTAL NUMBER : 3
REVIEW DATE : JUNE 08, 2016
RECOMMENDATION : NOT APPROVED
TABLE REVISION : NO
PLAT PROCESSING : NO
01. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND / OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURE
INCLUDING BUT NOT LIMITED TO WETLANDS, SURFACE WATERS
(E.G. VSMP PERMIT FOR CONSTRUCTION SITES, GROUND WATER
AND AIR QUALITY) FINAL APPROVAL OF THESE PLANS WILL NO
RELIEVE YOU OF YOUR RESPONSIBILITY. WETLANDS
DOCUMENTATION MUST BE RECEIVED BY THIS DEPARTMENT PRIO
TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
(CL-XX #) REPRESENTS A SUBMITTAL CHECKLIST COMMENT -
SECTION AND COMMENT NUMBER
02. EFFECTIVE JULY 1, 2014, ENFORCEMENT OF THE VIRGINIA
STORMWATER REGULATIONS BECAME THE RESPONSIBILITY OF TH
COUNTY FOR DEVELOPMENT PROJECTS WITHIN CHESTERFIELD
COUNTY. ADDITIONALLY, NEW STATE STORMWATER REGULATION
ALSO BECAME EFFECTIVE ON JULY 1, 2014. LAND DISTURBING
ACTIVITIES THAT OBTAINED A VSMP PERMIT PRIOR TO JULY 1
2014 MAY USE THE STORMWATER MANAGEMENT CRITERIA
SPECIFIED IN PART II C (9VAC25-870-93 ET SEQ) FOR TWO
PERMIT CYCLES. PROJECTS GRANDFATHERED UNDER THE
PROVISIONS OF 9VAC25-870-48 MAY FOLLOW THE REQUIREMENT
LISTED UNDER PART IIC FOR ONE PERMIT CYCLE. ALL OTHER
NEW DEVELOPMENT WILL BE SUBJECT TO THE REQUIREMENTS OF
PART IIB (9VAC25-870-62 TO 9VAC25-870-92).
03. CLARIFY CBPA NOTE ON THE COVER SHEET. IT STILL SHOWS
THE USE OF DRY SWALES.
04. SHEET C-4:
A) PROVIDE MORE OFFSITE CONTOUR DATA IN ORDER TO VERIF
CONDITIONS ON THE DOWNSTREAM PROPERTY.
B) THE DRAINAGE SUMMARY TABLE HAS CELLS WITH "#VALUE"
DELETE OR MARK AS N/A.
C) PROVIDE OUTLET PROTECTION FOR ROOF DRAINS.
D) PROVIDE OFFSITE DRAINAGE EASEMENT FOR THE DRAINAGE
WORK ALONG THE WAWA PROPERTY LINE.
E) PROVIDE LEVEL SPREADING DEVICE AT THE BOTTOM OF THE
ROAD SLOPE TO REDUCE EROSION POTENTIAL IN THE
WETLAND AREA.
05. SHEET C-11:
A) ENSURE ALL AREAS LISTED AS FORESTED/OPEN SPACE ARE
ENCOMPASSED BY VSMP OPEN SPACE EASEMENTS. THIS
INCLUDES WETLANDS.
B) SHOW AND LOCATE OUTFALL 3 FROM THE TABLE.
06. PROVIDE CALCULATIONS FOR CULVERTS AND INLET SPREADS.
07. STATE AND DEMONSTRATE HOW THE TURN LANE IN FRONT OF
WAWA COMPLIES WITH SWM REGULATIONS.
08. BMP DESIGN:
A) THE SHEET FLOW TO OPEN SPACE MUST HAVE 2% SLOPE FOR
THE FIRST 10' OF SHEET FLOW. AS SHOWN IT IS AGAINS
A 3:1 SIDE SLOPE AND DOES NOT APPEAR TO MEET THIS
CRITERIA.
B) PROVIDE EASEMENT FOR WIDTH AND LENGTH REQUIRED FOR
THE SHEET FLOW. NOTE THAT THE LENGTH WILL RUN OFF
PROPERTY AND REQUIRE EASEMENTS.
C) PROVIDE LEVEL SPREADER LENGTH CALCULATIONS USING
RATIONAL METHOD WITH AN INTENSITY OF 1 INCH PER
HOUR.
D) PROVIDE VELOCITY CALCULATIONS SHOWING THE SHEET FLO
IS NON-EROSIVE ON THE DOWNSTREAM PROPERTIES.
09. PRIOR TO PLAN APPROVAL, DOCUMENTATION OF THE OWNER'S
ACQUISITION OF THE NONPOINT NUTRIENT OFFSETS MUST BE
PROVIDED IN A CERTIFICATION FROM THE OFFSET BROKER
DOCUMENTING THE NUMBER OF PHOSPHOROUS NONPOINT NUTRIEN
OFFSETS ACQUIRED AND THE ASSOCIATED RATIO OF NITROGEN
NONPOINT NUTRIENT OFFSETS AT THE OFFSET GENERATING
FACILITY.
10. NOTE THAT THE NONPOINT NUTRIENT OFFSETS USED FOR WATER
QUALITY COMPLIANCE MUST BE GENERATED IN THE SAME OR
ADJACENT EIGHT DIGIT HYDROLOGIC UNIT CODE AS DEFINED B
THE UNITED STATES GEOLOGICAL SURVEY AS THE SITE.
NONPOINT NUTRIENT OFFSETS OUTSIDE THE SAME OR ADJACENT
EIGHT DIGIT HYDROLOGIC UNIT CODE MAY ONLY BE USED IF I
IS DETERMINED THAT NO NONPOINT NUTRIENT OFFSETS ARE
AVAILABLE WITHIN THE SAME OR ADJACENT EIGHT DIGIT
HYDROLOGIC UNIT CODE. IN SUCH CASES, THE NONPOINT
NUTRIENT OFFSETS MUST BE GENERATED WITHIN THE SAME
TRIBUTARY. PROVIDE A HYDROLOGIC UNIT MAP SHOWING THE
LOCATION OF THE PROJECT AND THE OFFSET GENERATING
FACILITY.
11. THE CBPA COMPLIANCE NOTE MUST SPECIFY THE NUMBER OF
PHOSPHOROUS NONPOINT NUTRIENT OFFSETS ACQUIRED
AND THE NAME OF THE OFFSET GENERATING FACILITY.
12. IT IS THE RESPONSIBILITY OF THE OWNER TO PROVIDE ONE
ADDITIONAL SET OF PLANS TO THE ENVIRONMENTAL
ENGINEERING DEPARTMENT AND OBTAIN AN "APPROVED FOR
CONSTRUCTION" STAMP ON TWO ADDITIONAL SETS FOR THE
OWNER TO KEEP ON-SITE.
13. PERMISSION MUST BE OBTAINED FROM THE ADJACENT PROPERTY
OWNER(S) ALLOWING FOR GRADING ON THE PROPERTY AS
PROPOSED PRIOR TO ISSUANCE OF A LAND DISTURBANCE
PERMIT.
14. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, THE
NAME, "WALK-IN" ADDRESS, AND TELEPHONE NUMBER OF
A LOCAL REGISTERED AGENT REPRESENTING THE OWNER FOR
SERVICE OF PROCESS MUST BE PROVIDED ON THE "APPOINTMEN
OF AGENT FOR SERVICE OF PROCESS" FORM FOUND ON THE
CHESTERFIELD COUNTY ENVIRONMENTAL ENGINEERING WEBPAGE.
(CL-GENERAL 12)
15. ALL OFFSITE DRAINAGE EASEMENTS MUST BE RECORDED PRIOR
TO ISSUANCE OF A LAND DISTURBANCE PERMIT FOR THIS
PROJECT.
16. ALL ONSITE DRAINAGE EASEMENTS INCLUDING STORMWATER /
BMP DRAINAGE EASEMENTS MUST BE RECORDED PRIOR TO
ISSUANCE OF A BUILDING PERMIT FOR THIS PROJECT.
17. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
SURETY FOR THE CONSTRUCTION OF THE PERMANENT BMP MUST
BE POSTED WITH ENVIRONMENTAL ENGINEERING. (COUNTY CODE
PART II, CHAPTER 8, SEC. 8-16)
18. THE BMP MUST BE CERTIFIED PRIOR TO RELEASE OF THE BMP
PERFORMANCE BOND AND CERTIFICATE OF OCCUPANCY.
19. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A COPY
OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD
FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD VERSIO
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINI
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE SITE
PLAN NAME, SITE PLAN NUMBER, ENGINEERING FIRM AND CAD
FILE PREPARER'S NAME AND PHONE NUMBER. THE FILE MUST
CONTAIN THE FOLLOWING, EACH CLEARLY LABELED IN SEPARAT
LAYERS:
A. PROPOSED BUILDING FOOTPRINT;
B. PARKING LOTS AND DRIVEWAYS;
C. ROADS;
D. SIDEWALKS;
E. ALL JURISDICTIONAL WETLAND AREAS AND/OR WATERS OF THE
U.S./STATE; AND
F. FLOODPLAINS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
20. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND SUBSTANTIAL OR FULL SITE PLAN APPROVAL IS REQUIRED
PRIOR TO ITS ISSUANCE. A LAND DISTURBANCE PERMIT IS
A PREREQUISITE TO A BUILDING PERMIT.
21. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND THE FOLLOWING ARE REQUIRED PRIOR TO ITS ISSUANCE:
A. SUBSTANTIAL OR FULL SITE PLAN APPROVAL
B. A VDOT LAND USE PERMIT
C. A LETTER MUST BE RECEIVED FROM A QUALIFIED WETLANDS
EXPERT STATING:
1.THERE ARE NO WETLANDS IMPACTED ON THIS PROJECT, OR
2.ALL APPLICABLE FEDERAL AND STATE WETLAND PERMITS HAVE
BEEN ACQUIRED (COPIES OF THE PERMITS MUST BE SUBMITTED
D. THE VIRGINIA STORMWATER MANAGEMENT PERMIT (VSMP)
REGISTRATION STATEMENT AND FEE OF $2,700
E. THE STORMWATER POLLUTION PREVENTION PLAN (SWPPP) BOOK
F. POSTING OF AN EROSION AND SEDIMENT CONTROL SURETY
(AMOUNT TO BE APPROVED BY EE)
==========================================================

Modify comments view for case # 16PR0151



Go to Case Selection Form or Go to Project List