Site Plan Review Comments
All Site Plan Review Comments for Case # 16PR0108
Modify comments view for Case # 16PR0108

Go to Case Selection Form or Go to Project List

 
CASE NO: 16PR0108 STATUS: PENDING APPROVAL
PROJECT NAME: TOWNE PLACE AT HUGUE - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: COMMERCIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 04 07/14/17 08/04/17 ******** ********
ENVIR.ENGR.-: 04 07/14/17 08/04/17 ******** 01/29/16 DLD 706-2031
FIRE DEPT.--: 04 07/14/17 08/04/17 COMPLETE 07/17/17 AWB 717-6167
MAPPING/GIS-: 04 07/14/17 08/04/17 COMPLETE 07/27/17 AMJ 768-7549
PLANNING----: 04 07/14/17 08/04/17 ******** 08/25/16 JHL 751-4158
TRANSPORT.--: 04 07/14/17 08/04/17 COMPLETE 07/26/17 SJA 751-4461
UTIL.PLAN.--: 04 07/14/17 08/04/17 ******** ********
UTILITIES---: 04 07/14/17 08/04/17 ******** 02/09/16 M L 748-1338
UTIL.R.O.W.-: 04 07/14/17 08/04/17 ******** ********
VDOT--------: 04 07/14/17 08/04/17 ******** ********
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : RYAN EVANS, P.E./748-1338
NAME OF PLAN : TOWNE PLACE AT HUGUENOT
ADDRESS :
SUBMISSION DATE : 07/09/15
PLAN DATED : 07/01/15
REVIEW DATE : 07/30/15
SITE PLAN NO. : 16PR0108
COMMENTS : 1ST REVIEW-NOT APPROVED
TABLE REVIEW :
PLAT PROCESS :
1. SHOW THE COUNTY UTILITIES PROJECT NUMBER 15-0218 ON TH
LOWER RIGHT HAND CORNER OF EACH SHEET.
2. LABEL WHAT IS PROPOSED TO BE PUBLIC AND WHAT IS PROPOS
AS PRIVATE ON BOTH PLAN AND PROFILE VIEWS. ALSO, SEPARATE
THE UTILITY QUANTITIES SIMILARLY.
3. OBTAIN THE PERTINENT EXISTING WATER AND SEWER AS-
BUILT INFORMATION FROM THE UTILITIES DEPARTMENT. ENSURE TH
THE FIELD SURVEY AND AS-BUILT INFORMATION ACCURATELY REFLE
THE ON-SITE CONDITIONS AND PRESENT SAID INFORMATION
ACCORDINGLY ON THE PLANS. CLEARLY LABEL THE EXISTING SIZE,
MATERIAL TYPE, AND COUNTY PROJECT # ON ALL WATER AND SEWER
LINE WITHIN THE PLAN VIEWPORT. INFORMATION MAY BE OBTAINED
BY EMAILING SWAVAILABILITY@CHESTERFIELD.GOV OR AT THE
UTILITIES DEPARTMENT BUILDING. SPECIFICALLY, SHOW ALL
SANITARY LATERALS AND EXISTING WATER METERS. SHOW THE
UTILITIES ON THE BEST BUY SITE.
4. ON THE DEMO PLAN, SHOW THE EXISTING WATER LINE TO BE
ABANDONED BACK TO THE MAIN WITH THE TEE AND VALVE REMOVED
AND REPLACED WITH A SLEEVE. SHOW THE SANITARY CONNECTIONS
BE ABANDONED AT THE MAIN AS WELL. SHOW NEW HYDRANTS AND
METERS RATHER THAN RELOCATING THE EXISTING MATERIALS.
5. REVISE THE PLAN TO SHOW A MONITORING MANHOLE AND RPZ F
THE PEDIATRICS BUILDING.
6. SHOW THE UTILITIES ON THE TURN LANE PLANS. SPECIFICALL
LOCATE THE EXISTING WATERLINE AND ENSURE IT HAS ADEQUATE
COVER WITH THE NEW GRADES AND ADEQUATE SEPARATION WITH THE
PROPOSED STORM LINE.
7. REVISE THE PROPOSED WATERLINE LOCATION TO BE AT LEAST
FROM ANY EXISTING POWER POLE AND TO MAINTAIN 4' OFF THE FA
OF CURB, GENERALLY.
8. LOCATE AND SHOW ON THE PLANS ALL THE VALVES NECESSARY
SHUT THE WATERLINE DOWN AND INSTALL THE NEW TEE.
9. SUBMIT THE METER SIZING FORMS SEPARATELY IN THE NEXT
SUBMITTAL. REVISE THE PLANS TO SHOW A 1.5" TAP FOR A 1.5"
METER.
10. FIELD LOCATE AND VERIFY THAT THE EXISTING SANITARY
CONNECTIONS CAN BE INTERCEPTED AND STILL MAINTAIN 1.5'
VERTICAL CLEARANCE WITH THE PROPOSED 48" STORM PIPE.
CALCULATE THE CLEARANCES AND LABEL THEM ON THE PLANS.
11. REVISE THE PROPOSED WATERLINE EASEMENTS TO EXCLUDE AN
PRIVATE DOUBLE CHECK FDC CONNECTIONS.
12. REVISE THE LOCATION OF THE METER AND FDC FOR BUILDING
SOUTH OF THE CROSS SO THAT THEY DO NOT CROSS UNDER THE
PARKING STALLS (TYP).
13. REVISE THE NOMENCLATURE OF ANY PUBLIC EASEMENT TO BE
PUBLIC WATER OR PUBLIC SEWER EASEMENT RATHER THAN A PUBLIC
UTILITY EASEMENT.
14. REVISE THE PLANS TO SHOW THE WATERLINE CONNECTING TO
THE DEAD END LINE ON THE BEST BUY PROPERTY. IT APPEARS THA
SOME ADDITIONAL EASEMENT MAY BE NEEDED.
15. BE ADVISED THAT A LICENSE AGREEMENT WILL BE REQUIRED
FOR THE DUMPSTER PAD OVER THE PROPOSED WATERLINE/EASEMENT.
16. REVISE THE SANITARY CONNECTION FOR THE MULTI TENANT
BUILDING SUCH THAT IT DOES NOT CROSS DIRECTLY BETWEEN THE
PROPOSED WATER VALVES.
17. PROVIDE WATERLINE PROFILES AND ENSURE THAT WATERLINE
STATIONING ON THE PLAN REFLECTS THE PROFILE STATIONING.
18. SHOW ON THE PLANS DETAIL DES-2, THE STANDARD UTILITY
NOTES, AND REMOVE ANY NOTES WHICH MAY BE IN CONFLICT.
19. PROVIDE CALCULATIONS TO VERIFY THAT THE FIRE FLOW AND
DOMESTIC FLOWS CAN BE SUSTAINED WITH A RESIDUAL PRESSURE O
20 PSI. SHOW ON THE PLANS DETAILS DES-5 AND DES-6.
20. SUBMIT AN ENGINEER'S CHECKLIST FROM PART 1 OF THE SPEC
21. THE OWNER SHALL BE REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
PRIOR TO THE PREPARATION OF THE UTILITIES CONTRACT,
UTILITIES MUST BE IN RECEIPT OF THE "ACCEPTED" BID PROPOSA
BETWEEN THE DEVELOPER AND THE COUNTY APPROVED UTILITIES
CONTRACTOR AS WELL AS THE PROJECT'S INFORMATIONAL SHEET
FOUND ON THE "DEVELOPER'S CHECKLIST". PLEASE SEND THOSE TW
ITEMS TO THE ATTENTION OF JACQUE HYDEN
(HYDENJ@CHESTERFIELD.GOV OR 804-318-8437). THE BID PROPOSA
MUST BE BASED ON THE APPROVED SITE PLAN. BE ADVISED THAT I
THE SITE PLAN IS REVISED AND REAPPROVED SUBSEQUENT TO THE
PREPARATION OR RECORDATION OF THE UTILITIES CONTRACT, THE
BID PROPOSAL SHALL BE REVISED ACCORDINGLY AND A REVISED
UTILITIES CONTRACT MAY BE NECESSARY.
22. AFTER FINAL SITE PLAN APPROVAL, SUBMIT THREE SETS OF T
APPROVED PLANS DIRECTLY TO THE UTILITIES DEPARTMENT FOR OU
USE DURING CONSTRUCTION INSPECTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : RYAN EVANS, P.E./748-1338
NAME OF PLAN : TOWNE PLACE AT HUGUENOT
ADDRESS :
SUBMISSION DATE : 09/01/15
PLAN DATED : 08/28/15
REVIEW DATE : 09/15/15
SITE PLAN NO. : 16PR0108
COMMENTS : 2ND REVIEW-NOT APPROVED
TABLE REVIEW :
PLAT PROCESS :
PREVIOUS COMMENTS NOT ADEQUATELY ADDRESSED
4. ON THE DEMO PLAN, SHOW THE EXISTING WATER LINE TO BE
ABANDONED BACK TO THE MAIN WITH THE TEE AND VALVE REMOVED
AND REPLACED WITH A SLEEVE. SHOW THE SANITARY CONNECTIONS
BE ABANDONED AT THE MAIN AS WELL. SHOW NEW HYDRANTS AND
METERS RATHER THAN RELOCATING THE EXISTING MATERIALS.**A F
PLACES STILL CALL FOR "COUNTY FORCES TO RELOCATE WATER
METER"
6. SHOW THE UTILITIES ON THE TURN LANE PLANS. SPECIFICALL
LOCATE THE EXISTING WATERLINE AND ENSURE IT HAS ADEQUATE
COVER WITH THE NEW GRADES AND ADEQUATE SEPARATION WITH THE
PROPOSED STORM LINE.**CLARIFY WHY THE PROPOSED ALIGNMENT I
SO FAR OUT IN THE TURN LANE/TRAVEL LANE RATHER THAN
MAINTAINING 4' FROM THE FACE OF CURB.**
7. REVISE THE PROPOSED WATERLINE LOCATION TO BE AT LEAST
FROM ANY EXISTING POWER POLE AND TO MAINTAIN 4' OFF THE FA
OF CURB, GENERALLY.**THROUGHOUT THE SITE, THE WATERLINE IS
PROPOSED IN THE MIDDLE OF THE DRIVE AISLE.**
10. FIELD LOCATE AND VERIFY THAT THE EXISTING SANITARY
CONNECTIONS CAN BE INTERCEPTED AND STILL MAINTAIN 1.5'
VERTICAL CLEARANCE WITH THE PROPOSED 48" STORM PIPE.
CALCULATE THE CLEARANCES AND LABEL THEM ON THE PLANS. **NO
CLEARANCES WERE LABELED ON THE PLANS. REVISE THE MATERIAL
TYPE FOR THE SANITARY LATERAL FROM THE PEDIATRICS BUILDING
TO WATERTIGHT DUCTILE IRON PIPE AND SHOW THE STANDARD
CONCRETE ENCASEMENT DETAIL FOR THE 48" RCP CROSSING.**
14. REVISE THE PLANS TO SHOW THE WATERLINE CONNECTING TO
THE DEAD END LINE ON THE BEST BUY PROPERTY. IT APPEARS THA
SOME ADDITIONAL EASEMENT MAY BE NEEDED.**THE CURRENTLY
PROPOSED ALIGNMENT CANNOT BE CONSTRUCTED. THERE IS NOT
ENOUGH ROOM BETWEEN THE VALVE AND REDUCER FOR A NEW TEE AN
IT IS NOT A POTABLE CONNECTION. REVISE THE PLAN TO REMOVE
THE FIRE HYDRANT AND REDUCER AND CONNECT THE PROPOSED 8"
ONTO THE EXISTING 8" DOWNSTREAM OF THE VALVE. INSTALL A
STANDARD FIR-4 CONFIGURATION WITH A FH TEE AND 6" GV FOR T
HYDRANT.**
NEW COMMENTS
1. EITHER SHOW EXTERIOR RPZ'S FOR BUILDINGS A AND B OR
PROVIDE A NOTE WITHIN THE BUILDING FOOTPRINT STATING THAT
THE RPZ WILL BE INTERNAL TO THE BUILDING.
2. REVISE THE SANITARY SEWER CONNECTIONS FOR EACH NEW
BUILDING TO SHOW THE DOMESTIC SANITARY DISCHARGING
DOWNSTREAM OF THE PROPOSED GREASE TRAPS AND MONITORING
MANHOLES PER PLUMBING CODE.
3. REVISE ANY PROPOSED FIRE HYDRANT TO BE DESIGNED IN
ACCORDANCE WITH THE FIR-4 DETAIL.
4. ENSURE THAT ALL SANITARY AND STORM CROSSINGS ARE SHOWN
ON THE WATER PROFILE AND THAT ALL WATER AND STORM CROSSING
ARE SHOWN ON THE SANITARY PROFILES. THERE ARE A FEW
INSTANCES WHERE THEY ARE MISSING.
5. IT APPEARS THAT WATERLINE 1B CAN BE ELIMINATED FROM IT
0+00 TO 2+50 NOW THAT THE WATER CONNECTION TO BEST BUY HAS
BEEN PROPOSED. I DO NOT BELIEVE THE LOOP WILL SERVE ANY
APPRECIABLE BENEFIT AND THE COST OF DEVELOPMENT CAN BE
LOWERED. IN ADDITION, THE WATER CONNECTION POINT FOR THE
PEDIATRICS BUILDING CAN BE RAISED FROM 10' IN THE GROUND T
THE NORMAL 3.5" FOR EASE OF FUTURE MAINTENANCE. SHOW A PLU
ON THE END OF THE WATERLINE AND PROPOSE A BLOW OFF TO BE
INSTALLED NEXT TO THE WATER METER.
6. AT THE MOST UPSTREAM RUN OF SANITARY SEWER, ENSURE THA
0.52% SLOPE HAS BEEN PROPOSED RATHER THAN 0.40%. REVISE
ACCORDINGLY.
7. FOR BUILDING A, THE METER AND FDC CAN BE REVISED TO CO
OFF WATERLINE 1B EITHER AT ~3+40 IN THE CONCRETE AREA OR
~2+50 IN THE LANDSCAPE ISLAND ADJACENT TO THE PROPOSED
PARCEL LINE. IT IS PREFERABLE TO SHOW THEM CLOSER TO THE
PEDIATRICS BUILDING TO HELP FACILITATE WATER TURNOVER ONCE
THE LOOP HAS BEEN REMOVED.
8. REVERSE THE ALIGNMENTS OF THE WATER AND SEWER IN THE
DRIVE AISLE FRONTING BUILDING B. THE SEWER WOULD BE EASIER
TO CONNECT AND THE WATER WOULD BE CLOSER TO THE LANDSCAPE
AREA WHERE THE HYDRANT AND FDC ARE PROPOSED. THERE ARE FEW
OVERALL CROSSINGS, SHORTER PIPE RUNS, AND EASIER FUTURE
MAINTENANCE.
9. SHOW THE METER FOR BUILDING B DIRECTLY IN FRONT OF
BUILDING B RATHER THAN IN THE LANDSCAPE ISLAND NEXT TO THE
FDC.
10. REVISE THE TAP LOCATION FOR THE HYDRANT AT THE ENTRAN
TO COME OFF WATERLINE 1A AT 1+05 FOR A SHORTER RUN WITH NO
CROSSINGS.
11. REMOVE SANITARY MANHOLE 1. THERE IS NO REASON FOR IT
SINCE THE SLOPES ARE CONSTANT AND THE TOTAL LENGTH OF PIPE
BETWEEN 2 AND THE MMH IS LESS THAN 400'. SHOW IT AT 0.52%
SLOPE.
12. EITHER REVISE THE PROPOSED PARCEL LINE CONFIGURATION
FOR THE PEDIATRICS BUILDING TO ENCOMPASS THE PRIVATE
SANITARY LATERAL, REVISE THE LOCATION OF THE PRIVATE SEWER
TO BE CLOSER TO THE BUILDING, OR REVISE THE PRIVATE SANITA
LATERAL TO BE A PUBLIC LINE WITH MANHOLES RATHER THAN
CLEANOUTS AND 8" MINIMUM SIZE SINCE PRIVATE UTILITIES CANN
CROSS PARCEL LINES.
13. FULL APPROVAL OF THIS SITE PLAN CANNOT BE GIVEN UNTIL
ANY/ALL OFF-SITE UTILITY EASEMENTS ARE ACQUIRED, ALTHOUGH
SUBSTANTIAL APPROVAL CAN BE GIVEN.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : MIKE LARSON/(804)748-1338
NAME OF PLAN : TOWNE PLACE AT HUGUENOT
ADDRESS :
SUBMISSION DATE : 12/30/15
PLAN DATED : 12/30/15
REVIEW DATE : 2/9/15
SITE PLAN NO. : 16PR0108
COMMENTS : 3ND REVIEW-NOT APPROVED
TABLE REVIEW : NO
PLAT PROCESS :
1. AS DISCUSSED IN OUR MEETING, THE EXISTING WATER MAIN
ON HUGUENOT ROAD IS NOT SHOWN CORRECTLY. PLEASE UPDATE
BASED ON THE AS-BUILT THAT HAS BEEN EMAILED TO TIMMONS.
2. PLEASE CALL OUT THE VALVES THAT ARE TO BE CLOSED IN
ORDER TO MAKE THE PROPOSED CONNECTIONS TO THE EXISTING
WATER MAIN.
3. CALL OUT THE METER SIZE FOR ALL PROPOSED NEW WATER
METERS ON THE PLANS.
4. AS DISCUSSED IN OUR MEETING, PLEASE REVISE THE
CONNECTION TO THE PIPE ON THE EAST SIDE OF THE SITE TO
INCLUDE A TAPPING SLEEVE AND VALVE ON THE UPSTREAM SIDE OF
THE HYDRANT. THIS IS SO THAT THE WATER SERVICE TO BEST BU
WILL NOT BE DISRUPTED AND THE PIPE WILL NOT PULL APART WHE
THE THRUST BLOCK ON THE EXISTING HYDRANT IS REMOVED.
5. AS DISCUSSED IN OUR MEETING, PLEASE CONSIDER REVISING
THE ALIGNMENT OF THE WATER MAIN INSIDE THE ISLAND, WHICH
WILL MINIMIZE CROSSING OF PRIVATE MAINS WITH PUBLIC MAINS.
6. CONSIDER RELOCATION OF THE PROPOSED GREASE TRAPS TO
AVOID MULTIPLE BENDS ON THE SEWER LATERAL. IF BENDS CANNO
BE AVOIDED, WE SUGGEST THAT PRIVATE TRAFFIC RATED CLEAN
OUTS BE PROVIDED.
7. THE DOMESTIC CONNECTION TO THE SANITARY SEWER MUST BE
UPSTREAM OF THE SAMPLING MANHOLE.
8. CONSIDER RELOCATING THE DDCA TO 1409 WEST HUGUENOT
ROAD AS DISCUSSED TO AVOID PRIVATE WATER MAINS CROSSING
PUBLIC WATER MAINS.
9. THE NORMAL MINIMUM SLOPE FOR A 6" SEWER LATERAL IS
2.08%. WE UNDERSTAND THE DIFFICULTY OF CROSSING THE LARGE
DRAIN PIPE NEAR 1409 WEST HUGUENOT. IT IS OUR
UNDERSTANDING THAT THE ENGINEER IS INVESTIGATING OPTIONS T
IMPROVE THIS SLOPE.
10. AS DISCUSSED, PLEASE INCLUDE A DETAIL FOR A CUT-IN
MANHOLE. WE REQUEST THE PRINCE WILLIAM COUNTY SERVICE
AUTHORITY DETAIL 5.08.07.01.
11. INCLUDE THE COUNTY PROJECT NUMBER FOR THE CONNECTION
TO THE EXISTING SEWER ON SAN PROFILE 2.
12. PLEASE SHOW ANGLES ON THE PROPOSED MANHOLES.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: TOWNE PLACE AT HUGUENOT
SITE PLAN NUMBER: 16PR0108
LATEST PLAN DATE: 07/01/15
DEPT. REC'D. DATE: 07/10/15
SUBMITTAL NUMBER: ONE
REVIEW DATE: 07/30/15
RECOMMENDATION: NOT APPROVED
PLAT PROCESSING: R/W DEDICATION?, SIDEWALK ESMT?
1. PROVIDE SIDEWALK ALONG HUGUENOT ROAD AND KOGER CENTER
BLVD. PROVIDE RIGHT-OF-WAY DEDICATION AND/OR SIDEWALK
EASEMENT TO ACCOMMODATE THIS IMPROVEMENT.
2. DIMENSION THE EXISTING RIGHT-OF-WAY WIDTH FROM THE
CENTERLINE ALONG HUGUENOT ROAD. PER ZONING CASE,
ADDITIONAL RIGHT-OF-WAY DEDICATION IS REQUIRED ALONG
HUGUENOT RD TO ENSURE A 60' WIDE R/W FROM THE CENTERLINE I
IT DOES NOT EXIST.
3. NOTE THE COUNTY CLASSIFICATONS FOR HUGUENOT ROAD AND
KOGER CENTER BLVD ON THE PLANS PER THE THOROUGHFARE PLAN
(BOTH ARE MAJOR ARTERIALS).
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: TOWNE PLACE AT HUGUENOT
SITE PLAN NUMBER: 16PR0108
LATEST PLAN DATE: 08/28/15
DEPT. REC'D. DATE: 09/02/15
SUBMITTAL NUMBER: TWO
REVIEW DATE: 09/17/15
RECOMMENDATION: NOT APPROVED
PLAT PROCESSING: NO
EXTEND THE PROPOSED SIDEWALK TO PROVIDE A CONNECTION FROM
HUGUENOT RD TO KOGER CENTER BLVD.
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: TOWNE PLACE AT HUGUENOT
SITE PLAN NUMBER: 16PR0108
LATEST PLAN DATE: 12/30/15
DEPT. REC'D. DATE: 01/04/16
SUBMITTAL NUMBER: THREE
REVIEW DATE: 01/28/16
RECOMMENDATION: APPROVED
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: TOWNE PLACE AT HUGUENOT
SITE PLAN NUMBER: 16PR0108
LATEST PLAN DATE: 04/12/17
DEPT. REC'D. DATE: 04/19/17
SUBMITTAL NUMBER: FOUR
REVIEW DATE: 04/28/17
RECOMMENDATION: APPROVED
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
NAME OF PLAN: TOWNE PLACE AT HUGUENOT
SITE PLAN NUMBER: 16PR0108
LATEST PLAN DATE: 07/13/17
DEPT. REC'D. DATE: 07/18/17
SUBMITTAL NUMBER: FIVE (LAMSON)
REVIEW DATE: 07/26/17
RECOMMENDATION: APPROVED
==========================================================
==========================================================
**********************************************************
REVIEW DEPARTMENT------PLANNING
REVIEWER / PHONE #-----JEFF LAMSON/ 804-751-4158
NAME OF PLAN-----------TOWNE CENTER AT HUGUENOT PLACE
SITE PLAN NUMBER-------16PR0108
ADDRESS----------------HUGUENOT/KOGER CENTER BLVD NE QUAD
LATEST PLAN DATE-------7-1-15
DEPT. REC'D. DATE------7-1-15 . ACCEPTED FOR REIVEW: 7-9-1
SUBMITTAL NUMBER-------1
REVIEW DATE------------8-4-15
RECOMMENDATION---------NOT APPROVED
TABLE REVIEW-----------NO
PLAT PROCESSING--------
LANDSCAPE PLAN STATUS-----NOT YET SUBMITTED
ARCHITECTURAL ELEVATIONS--NOT YET SUBMITTED
LIGHTING PLAN/CUTSHEETS---NOT YET SUBMITTED
IRRIGATION/HOSEBIB PLAN---NOT YET SUBMITTED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT
10 FULL SETS AND ONE COPY OF THE SITE PLAN SHEET TO THE
PLANNING DEPARTMENT FOR YOUR NEXT REVIEW. PROVIDE A COMPLE
RESPONSE TO COMMENTS FOR ALL DEPARTMENTS TO THE PLANNING
DEPARTMENT.
BELOW EACH COMMENT TO DESCRIBE HOW YOU HAVE ADDRESSED EACH
REVIEW COMMENT. BE SURE TO INDICATE WHICH SHEETS SHOW THE
REQUIRED CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE
ANY CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
(CL X.X REPRESENTS CHECKLIST ITEM NUMBER)
==========================================================
==========================================================
REVIEW DEPARTMENT: IST / GIS
REVIEWER : NANCY PARKER 751-4319
NAME OF PLAN : TOWNE PLACE
PLAN NO. : 16PR0108
ADDRESS :
LATEST PLAN DATE : 7/1/15
RECEIVED DATE : 7/10/15
SUBMITTAL NUMBER : 1
REVIEW DATE : 7/28/15
RECOMMENDATION : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. COORDINATE POINTS BASED ON THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, NORTH AMERICAN DATUM
1983 ARE NOT PRESENT. TWO POINTS MUST BE SHOWN ON THE
SITE BOUNDARY.
2. THE SITE BOUNDARY SURVEY IS INCOMPLETE. PLEASE
SUPPLY METES AND BOUNDS FOR EVERY SEGMENT ALONG THE
TRAVERSE TO INCLUDE CHORD BEARING AND DISTANCE FOR ALL
NON-TANGENT CURVES.
==========================================================
==========================================================
REVIEW DEPARTMENT: IST / GIS
REVIEWER : NANCY PARKER 751-4319
NAME OF PLAN : TOWNE PLACE AT HUGUENOT
PLAN NO. : 16PR0108
ADDRESS :
LATEST PLAN DATE : 8/28/15
RECEIVED DATE : 9/1/15
SUBMITTAL NUMBER : 2
REVIEW DATE : 9/8/15
RECOMMENDATION : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. COORDINATE POINTS BASED ON THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, NORTH AMERICAN DATUM
1983 ARE NOT PRESENT. TWO POINTS MUST BE SHOWN ON THE
SITE BOUNDARY. COMMENTS INDICATE THE POINTS ARE SHOWN
ON SHEET C2.0 BUT I DO NOT SEE THEM. PERHAPS THEY
WERE NOT TURNED ON WHEN THE SHEET WAS PRINTED?
==========================================================
==========================================================
REVIEW DEPARTMENT: IST / GIS
REVIEWER : NANCY PARKER 751-4319
NAME OF PLAN : TOWNE PLACE AT HUGUENOT
PLAN NO. : 16PR0108
ADDRESS :
LATEST PLAN DATE : 12/30/15
RECEIVED DATE : 1/5/16
SUBMITTAL NUMBER : 3
REVIEW DATE : 1/21/16
RECOMMENDATION : APPROVED
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : TOWNE PLACE AT HUGUENOT
CASE NUMBER : 16PR0108
LATEST PLAN DATE : 4/12/17
RECEIVED DATE : 4/20/17
SUBMITTAL NUMBER : 4
REVIEW DATE : 4/28/17
ADDRESS : SEE BELOW
STATUS : APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. THE PARCEL BOUNDARY SURVEY IS INCOMPLETE. N10-29-10W
0.82' IS MISSING AT THE NORTHWEST CORNER OF THE BOUNDARY
SURVEY.
2. ADDRESSING FOR THIS DEVELOPMENT IS AS FOLLOWS:
BUILDING A IS 1409 HUGUENOT RD MIDLOTHIAN VA 23113.
BUILDING B IS 1403 HUGUENOT RD MIDLOTHIAN VA 23113.
WITHIN BUILDING B: TENANT SPACE A IS STE A, TENANT SPACE
C IS STE C, TENANT SPACE D IS STE D, TENANT SPACE E IS
STE E, TENANT SPACE F IS STE F.
==========================================================
==========================================================
REVIEW DEPARTMENT: GIS + HOUSE NUMBERING
REVIEWER : AMY JOHANSON 768-7549
PROJECT NAME : TOWNE PLACE AT HUGUENOT
CASE NUMBER : 16PR0108
LATEST PLAN DATE : 7/12/17
RECEIVED DATE : 7/17/17
SUBMITTAL NUMBER : 5
REVIEW DATE : 7/27/17
ADDRESS : SEE BELOW
STATUS : APPROVED
==========================================================
==========================================================
DEPARTMENT REVIEW: IST / HOUSE NUMBERING SECTION
REVIEWER: NANCY PARKER
PHONE NUMBER: 751-4319
CASE NUMBER: 16PR0108
NAME OF PLAN:TOWNE PLACE AT HUGUENOT
ADDRESS: SEE BELOW
DATE OF REVIEW:7/28/15 REVIEW # 1
STATUS: HOUSE NUMBERING NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS
CONCERNING THE COMMENTS BELOW.
1) SHOW THE LOCATION OF THE MAIL BOX KIOSKS OR CLUSTER
BOXES ON THE PLAN SHEET.
2) ADDRESSING FOR THIS DEVELOPMENT IS AS FOLLOWS:
BUILDING A IS 1409 WEST HUGUENOT RD MIDLOTHIAN VA 23113
BUILDING B IS 1403 WEST HUGUENOT RD MIDLOTHIAN VA 23113
WITHIN BUILDING B, TENANT SPACE 1 IS STE A, TENANT SPACE 2
IS STE B, AND TENANT SPACE 3 IS STE C.
3) LOCATION OF STREET ADDRESS SIGN IS NOT SHOWN.
(THE ADDRESS CAN BE PART OF YOUR MONUMENT SIGN.
THIS DOES NOT COUNT AS PART OF THE SQUARE FOOTAGE OF THE
SIGN. IF YOU ARE USING THE MONUMENT
SIGN FOR THE ADDRESS, A DETAIL OF THE MONUMENT SIGN
NEEDS TO BE ON THE SITE PLAN.)
4) SPECIFY THE MATERIAL THAT THE ADDRESS SIGN IS TO BE
MADE OF. (MATERIAL TO BE MORE DURABLE THAN WOOD).
==========================================================
==========================================================
DEPARTMENT REVIEW: IST / HOUSE NUMBERING SECTION
REVIEWER: NANCY PARKER
CASE NUMBER: 16PR01089
NAME OF PLAN:TOWNE PLACE AT HUGUENOT
ADDRESS: SEE BELOW
DATE OF REVIEW:9/8/15 REVIEW # 2
STATUS: HOUSE NUMBERING NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS
CONCERNING THE COMMENTS BELOW.
1) SHOW THE LOCATION OF THE MAIL BOX KIOSKS OR CLUSTER
BOXES ON THE PLAN SHEET. COMMENTS INDICATE THE KIOSKS
ARE SHOWN ON SHEET C3.0 BUT I DON'T SEE THEM. PERHAPS THE
WERE NOT TURNED ON WHEN THE SHEET WAS PRINTED?
==========================================================
==========================================================
DEPARTMENT REVIEW: IST / HOUSE NUMBERING SECTION
REVIEWER: NANCY PARKER
PHONE NUMBER: 751-4319
CASE NUMBER: 16PR0108
NAME OF PLAN:TOWNE PLACE AT HUGUENOT
ADDRESS: SEE BELOW
DATE OF REVIEW:1/21/16 REVIEW # 3
STATUS: HOUSE NUMBERING APPROVED
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: TOWNE PLACE AT HUGUENOT
SITE PLAN NUMBER: 16PR0108
ADDRESS: 1409 HUGUENOT ROAD
LATEST PLAN DATE: 7/1/15
DEPT. REC'D. DATE: 7/10/15
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 7/10/15
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. CALL OUT THE EXISTING HYDRANT NEAR BUILDING #1401 ON TH
UTILITY PLAN.
2. PROVIDE THE CHESTERFIELD COUNTY STANDARD FIRE LANE
DETAIL ON THE PLAN.
3. FIRE LANE SIGNS SHALL BE PLACED 75 - 100 FT. APART.
4. PROVIDE COMPUTER GENERATED WATER FLOW TEST DATA,
PROVIDED BY THE CHESTERFIELD COUNTY UTILITIES
DEPARTMENT, VERIFYING THE REQUIRED WATER FLOW FOR FIRE
PROTECTION IS AVAILABLE AT THE SITE. THE WATERFLOW TEST
RESULTS AND GRAPH SHALL BE SHOWN ON THE SUBMITTED PLAN.
THE MINIMUM REQUIRED FIRE FLOW FOR ALL BUILDINGS, WITH
THE EXCEPTION OF ONE AND TWO-FAMILY DWELLINGS, IS 1500
GPM (SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED) IN
ACCORDANCE WITH THE INTERNATIONAL FIRE CODE (2012) -
SECTION B105.2 AND TABLE B105.1.
5. SHOW THE NODE MAP AND RESULTS TABLE FOR THE PROPOSED
OR EXISTING HYDRANTS ON SITE SHOWING THE MAXIMUM FIRE
FLOW CAN BE ACHIEVED. WHEN MULTIPLE FIRE HYDRANTS ARE
USED THE COMBINED FLOW MUST BE SIMULTANEOUS.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: TOWNE PLACE AT HUGUENOT
SITE PLAN NUMBER: 16PR0108
ADDRESS: 1409 HUGUENOT ROAD
LATEST PLAN DATE: 8/28/15
DEPT. REC'D. DATE: 9/1/15
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 9/1/15
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED PLAN IS APPROVED AS SUBMITTED
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: TOWNE PLACE AT HUGUENOT
SITE PLAN NUMBER: 16PR0108
ADDRESS: 1409 HUGUENOT ROAD
LATEST PLAN DATE: 8/28/15
DEPT. REC'D. DATE: 1/05/16
SUBMITTAL NUMBER: 3RD REVIEW
REVIEW DATE: 1/05/16
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED PLAN IS APPROVED AS SUBMITTED
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: TOWNE PLACE AT HUGUENOT
SITE PLAN NUMBER: 16PR0108
ADDRESS: 1409 HUGUENOT ROAD
LATEST PLAN DATE: 4/12/17
DEPT. REC'D. DATE: 4/25/17
SUBMITTAL NUMBER: 4TH REVIEW
REVIEW DATE: 4/25/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED PLAN IS APPROVED AS SUBMITTED
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: TOWNE PLACE AT HUGUENOT
SITE PLAN NUMBER: 16PR0108
ADDRESS: 1409 HUGUENOT ROAD
LATEST PLAN DATE: 7/12/17
DEPT. REC'D. DATE: 7/17/17
SUBMITTAL NUMBER: 5TH REVIEW
REVIEW DATE: 7/17/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED PLAN IS APPROVED AS SUBMITTED
==========================================================
==========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : DUSTIN DUNNAGAN / 706-2061
NAME OF PLAN : TOWNE PLACE AT HUGUENOT
ADDRESS : 1409 HUGUENOT ROAD
SITE PLAN NO. : 16PR0108
LATEST PLAN DATE : JULY 01, 2015
DEPT. REC'D DATE : JULY 09, 2015
SUBMITTAL NUMBER : 1
REVIEW DATE : JULY 30, 2015
RECOMMENDATION : NOT APPROVED
TABLE REVISION : NO
PLAT PROCESSING : NO
01. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND / OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURE
INCLUDING BUT NOT LIMITED TO WETLANDS, SURFACE WATERS
(E.G. VSMP PERMIT FOR CONSTRUCTION SITES, GROUND WATER
AND AIR QUALITY) FINAL APPROVAL OF THESE PLANS WILL NO
RELIEVE YOU OF YOUR RESPONSIBILITY.
(CL-XX #) REPRESENTS A SUBMITTAL CHECKLIST COMMENT -
SECTION AND COMMENT NUMBER
02. EFFECTIVE JULY 1, 2014, ENFORCEMENT OF THE VIRGINIA
STORMWATER REGULATIONS BECAME THE RESPONSIBILITY OF TH
COUNTY FOR DEVELOPMENT PROJECTS WITHIN CHESTERFIELD
COUNTY. ADDITIONALLY, NEW STATE STORMWATER REGULATION
ALSO BECAME EFFECTIVE ON JULY 1, 2014. LAND DISTURBING
ACTIVITIES THAT OBTAINED A VSMP PERMIT PRIOR TO JULY 1
2014 MAY USE THE STORMWATER MANAGEMENT CRITERIA
SPECIFIED IN PART II C (9VAC25-870-93 ET SEQ) FOR TWO
PERMIT CYCLES. PROJECTS GRANDFATHERED UNDER THE
PROVISIONS OF 9VAC25-870-48 MAY FOLLOW THE REQUIREMENT
LISTED UNDER PART IIC FOR ONE PERMIT CYCLE. ALL OTHER
NEW DEVELOPMENT WILL BE SUBJECT TO THE REQUIREMENTS OF
PART IIB (9VAC25-870-62 TO 9VAC25-870-92).
03. PROVIDE THE FOLLOWING INFORMATION ON THE COVER SHEET:
A. LATITUDE AND LONGITUDE FOR THE PROJECT SITE (IN
DEGREES, MINUTES, SECONDS, TO THE NEAREST 15 SECONDS)
B. NAME OF RECEIVING CHANNEL/WATERS
C. VAHU6 FOUR DIGIT WATERSHED CODE
04. ALL ROOF WATER AND DOWNDRAINS MUST BE COLLECTED AND
DISCHARGED IN A NON-ERODIBLE MANNER. (CL-G&D 6)
05. INLET SHAPING IS RESTRICTED TO PIPE DIAMETERS OF 30"
OR LESS AND TO SITUATIONS WHERE ONE PIPE ENTERS THE
CHAMBER AND ONE PIPE EXITS THE CHAMBER. STORM SEWERS
WITH PIPE DIAMETERS OF 30" AND ABOVE SHALL QUALIFY FOR
THE 50 PERCENT REDUCTION IN JUNCTION LOSSES ONLY WHEN
PRE-CAST TEES AND ELBOWS ARE USED. (CL-G&D 18)
06. A DETAIL MUST BE SHOWN ON THE PLANS FOR INLET SHAPING
STD. IS-1. IF INLET SHAPING CANNOT BE ACCOMPLISHED
WITHIN THE STANDARD STRUCTURE, THEN DETAILS MUST BE
PROVIDED FOR THE MODIFICATIONS NECESSARY TO THE
STRUCTURE TO ACCOMPLISH INLET SHAPING. (CL-G&D 19)
07. BOOT CONNECTORS MUST BE SPECIFIED IN THE TABULAR
DRAINAGE DESCRIPTION FOR ALL PLASTIC PIPES THAT TIE
INTO A CONCRETE STRUCTURE. (CL-G&D 21)
08. ALL EXISTING AND PROPOSED DRAINAGE EASEMENTS MUST BE
SHOWN. (CL-G&D 27)
09. THE DEED BOOK AND PAGE NUMBER OF ALL EXISTING DRAINAGE
EASEMENTS MUST BE SHOWN ON THE PLAN. (CL-G&D 28)
10. DRAINAGE EASEMENTS MUST BE SHOWN ALONG ANY STORMWATER
CONVEYANCE SYSTEM WHICH RECEIVES RUNOFF FROM OFFSITE,
FROM A PUBLIC RIGHT OF WAY OR REQUIRES IMPROVEMENTS ON
A DOWNSTREAM PROPERTY OWNER. (CL-G&D 29)
11. A SEPARATE PLAN SHEET MUST BE ADDED WHICH ONLY SHOWS
ALL PROPOSED EASEMENTS AND RIGHT OF WAY TO BE
DEDICATED. METES AND BOUNDS MUST BE PROVIDED.
(CL-G&D 30)
12. APPROVAL OF THE SITE PLAN BY THE PRIVATE UTILITY
COMPANY IN RELATION TO ITS EASEMENT AND FACILITIES
THEREIN MUST BE PROVIDED PRIOR TO SITE PLAN APPROVAL.
13. ANY AREAS LABELED AS FUTURE ARE NOT REVIEWED NOR ARE
THEY APPROVED WITH THIS PROJECT.
14. ON SHEET C3.0, SPECIFY CURB TYPE USED WITHIN THE SITE
AND CLARIFY WHERE THE CURB CUTS ARE TO BE USED
(DETAIL IS SHOWN ON C3.2).
15. PROVIDE DETAIL FOR STANDARD CG-6 TO BE USED WITHIN
RIGHT-OF-WAY.
16. SHEET C5.0
A) CLARIFY HOW THE PROPOSED BUILDINGS ARE TO DRAIN AND
ENTER THE STORM SEWER SYSTEM.
B) PROVIDE LABEL FOR STRUCTURE UPSTREAM FROM STRUCTURE
9.
C) THE FLOW ARROWS FOR THE EXISTING STORM SEWER TO THE
NORTH OF THE SITE APPEAR TO BE FACING THE WRONG
DIRECTION.
17. SHEET C5.1:
A) THE LIMITS OF DISTURBANCE DO NOT MATCH THE SITE
AREA. VERIFY SITE AREA.
B) ENSURE DISTURBANCE WITHIN THE RIGHT-OF-WAY AND
REDEVELOPMENT WITHIN THE ROW IS BEING ACCOUNTED FOR
WITHIN THE WATER QUALITY CALCULATIONS.
C) PROVIDE DATA MAP FOR THE EXISTING AND PROPOSED SITE
INCLUDE HATCHING OF THE IMPERVIOUS AREA AND
DELINEATION OF THE SITE AREA.
18. SHEET C5.2:
A) IN THE PROFILE FOR STM1:
1) VERIFY WITH THE UTILITIES DEPARTMENT THAT THE
MINIMUM SEPARATION BETWEEN THE WATERLINE AND THE
STORM SEWER IS ACCEPTABLE. CONCRETE ENCASEMENT
OR OTHER REQUIREMENTS MAY BE STIPULATED BY THE
UTILITIES DEPARTMENT.
2) SHOW THE SANITARY SEWER CROSSING OF PIPE 8 AND
LABEL THE REQUIRED MINIMUM SEPARATION.
B) THE COVER FOR PIPE 10 DOES NOT APPEAR TO MEET
MINIMUM REQUIREMENTS. VERIFY COVER, INCREASE IN
PIPE CLASS MAY BE WARRANTED.
C) ENSURE FLOWS USED WITHIN THE PIPES ARE INCLUSIVE OF
UPSTREAM FLOWS AND CALCULATIONS. REFERENCES TO
PREVIOUS PERFORMED CALCULATIONS CAN BE USED IF IT
ADEQUATELY PORTRAYS DEVELOPMENT IN THE UPSTREAM
WATERSHED.
D) PROVIDE HGL TO A NATURAL CHANNEL OR PROVIDE
REFERENCES TO APPROVED PLANS THAT CONTAIN
CALCULATIONS FOR THE CAPACITY OF THE SYSTEM TO A
NATURAL CHANNEL.
E) ENSURE ROOF DRAINS/DISCHARGES ARE INCLUDED WITHIN
THE STORM SEWER AND HGL COMPUTATIONS.
F) PROVIDE SPREAD CALCULATIONS.
G) NOTE 2 INDICATES ALL STRUCTURES ARE TO HAVE IS-1.
HOWEVER, NOT ALL STRUCTURES ARE ACCOUNTING FOR IS-
IN THE CALCULATIONS. VERIFY IS-1 IS NEEDED ON ALL
STRUCTURES (CLARIFY IF THE EXISTING STRUCTURES ARE
TO BE MODIFIED FOR IS-1) AND UPDATE NOTE OR
CALCULATIONS AS REQUIRED.
H) STRUCTURE 15 APPEARS TO NOT MEET THE MINIMUM DEPTH
REQUIRED. VERIFY THE DEPTH AND PROVIDE DETAILS FOR
MODIFICATION IF NEEDED.
19. SHEET C6.0:
A) PROVIDE DRAINAGE AREA TO SWALE AND CULVERT ON THE
SOUTHWEST SIDE OF THE SITE.
B) SHOW OFFSITE CONTOURS TO VERIFY DRAINAGE AREAS SHOW
ENCOMPASS THE FULL CONTRIBUTING DRAINAGE AREAS.
C) VERIFY THE DRAINAGE FROM #1407 AND #1401 DO NOT
ENTER DRAINAGE AREAS 2 AND 1, RESPECTIVELY.
20. SHEET C6.1:
A) CLARIFY IF PROPOSED DRAINAGE AREAS INCLUDE ROOF
DRAINS.
21. A NOTE MUST BE ADDED TO THE SEQUENCE OF CONSTRUCTION
STATING THAT THE VSMP CONSTRUCTION ACTIVITY OPERATOR
AND THE ENVIRONMENTAL INSPECTOR (OR AUTHORIZED
REPRESENTATIVE) MUST ATTEND THE PRE-CONSTRUCTION
MEETING.
22. STEPS MUST BE INCLUDED IN THE SEQUENCE OF CONSTRUCTION
EVENTS FOR BUILDING CONSTRUCTION. (CL-EC 6)
23. THE CONSTRUCTION ENTRANCE MUST BE GRAPHICALLY SHOWN ON
THE PLANS AND CONSTRUCTED AS WIDE AS THE PROPOSED
PERMANENT ENTRANCE. (CL-EC 9)
24. THE MOST RECENT VERSION OF EROSION CONTROL MINIMUM
STANDARD # 1, (SEE THE VIRGINIA EROSION AND SEDIMENT
CONTROL LAW AND REGULATIONS FOR FY 2013) MUST BE ADDED
TO THE PLANS AND ALL OTHER NOTES WHICH ARE IN CONFLICT
MUST BE ADJUSTED OR REMOVED. (CL-EC 25)
25. AN MS-19 ANALYSIS MUST BE PERFORMED AT EACH POINT OF
CONCENTRATED DISCHARGE AND AT THE DOWNSTREAM PROPERTY
LINE. THE LOCATION OF EACH ANALYSIS MUST BE SHOWN AND
LABELED ON THE EROSION CONTROL PLAN SHEETS. (CL-EC 28)
26. ANY SOIL STOCKPILE AREA MUST BE LOCATED ON THE PLANS.
SILT FENCE MUST BE PROVIDED AROUND THE PERIMETER.
(CL-EC 39)
27. THE FOLLOWING NOTE(S) MUST BE ADDED TO OR ADJACENT TO
THE SEQUENCE OF CONSTRUCTION: (CL-EC 42)
1. ALL OFFSITE DRAINAGE EASEMENTS MUST BE RECORDED PRIOR
TO ISSUANCE OF A LAND DISTURBANCE PERMIT FOR THIS
PROJECT. (CL-EC 42A)
2. A VDOT LAND USE PERMIT IS REQUIRED FOR THIS PROJECT
PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT.
(CL-EC 42D)
3. AT THE TIME OF THE PRE-CONSTRUCTION MEETING, TWO
STANDARD SIGNS MUST BE INSTALLED ON EACH SIDE OF THE
CONSTRUCTION ACCESS. THESE SIGNS SHOULD STATE EITHER
"CONSTRUCTION ENTRANCE AHEAD" OR "TRUCKS ENTERING
HIGHWAY". (CL-EC 42E)
28. SHEET C2.0:
A) PROVIDE SAFETY FENCE AROUND THE SITE.
B) CLARIFY THE PHASE I LIMITS OF DISTURBANCE, AS SHOWN
IT APPEARS DIFFICULT FOR CONSTRUCTION EQUIPMENT TO
MOVE AROUND THE SITE WITHIN THE LIMITS SHOWN TO
INSTALL THE PHASE 1 MEASURES, IN PARTICULAR THE US
OF THE CONSTRUCTION ENTRANCE.
C) CLARIFY IF THE PAVEMENT FOR THE CONSTRUCTION
ENTRANCE IS TO BE DEMOLISHED PRIOR TO INSTALLING TH
CONSTRUCTION ENTRANCE. CONSTRUCTION ENTRANCE CANNO
BE INSTALLED ON TOP OF PAVEMENT.
D) IN THE NARRATIVE:
1) NOTE 1, ACCORDING TO THE COVER SHEET THERE IS A
VSMP ALREADY IN PLACE FOR THE SITE. CLARIFY IF
THE PERMIT IS TO BE TRANSFERRED.
2) NOTE 3, UPDATE THE ESC REGULATIONS TO THE CURREN
REGULATIONS.
3) NOTE 4, INCLUDE TREE PROTECTION.
29. SHEET C2.1:
A) PROVIDE PERMANENT SEEDING AND MULCHING WITHIN THE
CURB ISLANDS.
B) NOTE 4 OF THE NARRATIVE SHALL BE UPDATED TO BE
WITHIN 14 DAYS INSTEAD OF 30.
30. SHEET C2.2:
A) PROVIDE A DETAIL FOR INSTALLING THE TREE PROTECTION
B) IN THE EROSION CONTROL NOTES, UPDATE THE REGULATION
TO MOST RECENT.
31. ON SHEET C2.3, USE THE MOST RECENT MINIMUM STANDARDS.
32. PRIOR TO PLAN APPROVAL, DOCUMENTATION OF THE OWNER'S
ACQUISITION OF THE NONPOINT NUTRIENT OFFSETS MUST BE
PROVIDED IN A CERTIFICATION FROM THE OFFSET BROKER
DOCUMENTING THE NUMBER OF PHOSPHOROUS NONPOINT NUTRIEN
OFFSETS ACQUIRED AND THE ASSOCIATED RATIO OF NITROGEN
NONPOINT NUTRIENT OFFSETS AT THE OFFSET GENERATING
FACILITY.
33. NOTE THAT THE NONPOINT NUTRIENT OFFSETS USED FOR WATER
QUALITY COMPLIANCE MUST BE GENERATED IN THE SAME OR
ADJACENT EIGHT DIGIT HYDROLOGIC UNIT CODE AS DEFINED B
THE UNITED STATES GEOLOGICAL SURVEY AS THE SITE.
NONPOINT NUTRIENT OFFSETS OUTSIDE THE SAME OR ADJACENT
EIGHT DIGIT HYDROLOGIC UNIT CODE MAY ONLY BE USED IF I
IS DETERMINED THAT NO NONPOINT NUTRIENT OFFSETS ARE
AVAILABLE WITHIN THE SAME OR ADJACENT EIGHT DIGIT
HYDROLOGIC UNIT CODE. IN SUCH CASES, THE NONPOINT
NUTRIENT OFFSETS MUST BE GENERATED WITHIN THE SAME
TRIBUTARY. PROVIDE A HYDROLOGIC UNIT MAP SHOWING THE
LOCATION OF THE PROJECT AND THE OFFSET GENERATING
FACILITY.
34. IT IS THE RESPONSIBILITY OF THE OWNER TO PROVIDE ONE
ADDITIONAL SET OF PLANS TO THE ENVIRONMENTAL
ENGINEERING DEPARTMENT AND OBTAIN AN "APPROVED FOR
CONSTRUCTION" STAMP ON TWO ADDITIONAL SETS FOR THE
OWNER TO KEEP ON-SITE.
35. PERMISSION MUST BE OBTAINED FROM THE ADJACENT PROPERTY
OWNER(S) ALLOWING FOR GRADING ON THE PROPERTY AS
PROPOSED PRIOR TO ISSUANCE OF A LAND DISTURBANCE
PERMIT.
36. ALL OFFSITE DRAINAGE EASEMENTS MUST BE RECORDED PRIOR
TO ISSUANCE OF A LAND DISTURBANCE PERMIT FOR THIS
PROJECT.
37. ALL ONSITE DRAINAGE EASEMENTS INCLUDING STORMWATER /
BMP DRAINAGE EASEMENTS MUST BE RECORDED PRIOR TO
ISSUANCE OF A BUILDING PERMIT FOR THIS PROJECT.
38. THE POLLUTION PREVENTION PLAN MUST BE PROVIDED TO THE
ENVIRONMENTAL ENGINEERING INSPECTOR PRIOR TO ISSUANCE
OF A LAND DISTURBANCE PERMIT. THE CHESTERFIELD COUNTY
POLLUTION PREVENTION PLAN SHEET MAY BE PROVIDED IN THE
CONSTRUCTION PLANS (THIS IS AVAILABLE ON THE
ENVIRONMENTAL ENGINEERING DOCUMENTS AND FORMS WEBPAGE)
39. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A COPY
OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD
FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD VERSIO
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINI
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE SITE
PLAN NAME, SITE PLAN NUMBER, ENGINEERING FIRM AND CAD
FILE PREPARER'S NAME AND PHONE NUMBER. THE FILE MUST
CONTAIN THE FOLLOWING, EACH CLEARLY LABELED IN SEPARAT
LAYERS:
A. PROPOSED BUILDING FOOTPRINT;
B. PARKING LOTS AND DRIVEWAYS;
C. ROADS;
D. SIDEWALKS;
E. ALL JURISDICTIONAL WETLAND AREAS AND/OR WATERS OF THE
U.S./STATE; AND
F. FLOODPLAINS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
40. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND SUBSTANTIAL OR FULL SITE PLAN APPROVAL IS REQUIRED
PRIOR TO ITS ISSUANCE. A LAND DISTURBANCE PERMIT IS
A PREREQUISITE TO A BUILDING PERMIT.
41. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND THE FOLLOWING ARE REQUIRED PRIOR TO ITS ISSUANCE:
A. SUBSTANTIAL OR FULL SITE PLAN APPROVAL
B. A VDOT LAND USE PERMIT
C. COPIES OF THE VIRGINIA STORMWATER MANAGEMENT PERMIT
(VSMP) REGISTRATION STATEMENT AND FEE PAID RECEIPT
E. COPY OF THE STORMWATER POLLUTION PREVENTION PLAN
(SWPPP) TO BE REVIEWED FOR COMPLETENESS.
F. POSTING OF AN EROSION AND SEDIMENT CONTROL SURETY
(AMOUNT TO BE APPROVED BY EE)
==========================================================
==========================================================
==========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : DUSTIN DUNNAGAN / 706-2061
NAME OF PLAN : TOWNE PLACE AT HUGUENOT
ADDRESS : 1409 HUGUENOT ROAD
SITE PLAN NO. : 16PR0108
LATEST PLAN DATE : AUGUST 28, 2015
DEPT. REC'D DATE : SEPTEMBER 01, 2015
SUBMITTAL NUMBER : 2
REVIEW DATE : SEPTEMBER 17, 2015
RECOMMENDATION : NOT APPROVED
TABLE REVISION : YES, SEE NOTE 03 AND 12. PROVIDE PDF
PLAT PROCESSING : NO
01. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND / OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURE
INCLUDING BUT NOT LIMITED TO WETLANDS, SURFACE WATERS
(E.G. VSMP PERMIT FOR CONSTRUCTION SITES, GROUND WATER
AND AIR QUALITY) FINAL APPROVAL OF THESE PLANS WILL NO
RELIEVE YOU OF YOUR RESPONSIBILITY.
(CL-XX #) REPRESENTS A SUBMITTAL CHECKLIST COMMENT -
SECTION AND COMMENT NUMBER
02. EFFECTIVE JULY 1, 2014, ENFORCEMENT OF THE VIRGINIA
STORMWATER REGULATIONS BECAME THE RESPONSIBILITY OF TH
COUNTY FOR DEVELOPMENT PROJECTS WITHIN CHESTERFIELD
COUNTY. ADDITIONALLY, NEW STATE STORMWATER REGULATION
ALSO BECAME EFFECTIVE ON JULY 1, 2014. LAND DISTURBING
ACTIVITIES THAT OBTAINED A VSMP PERMIT PRIOR TO JULY 1
2014 MAY USE THE STORMWATER MANAGEMENT CRITERIA
SPECIFIED IN PART II C (9VAC25-870-93 ET SEQ) FOR TWO
PERMIT CYCLES. PROJECTS GRANDFATHERED UNDER THE
PROVISIONS OF 9VAC25-870-48 MAY FOLLOW THE REQUIREMENT
LISTED UNDER PART IIC FOR ONE PERMIT CYCLE. ALL OTHER
NEW DEVELOPMENT WILL BE SUBJECT TO THE REQUIREMENTS OF
PART IIB (9VAC25-870-62 TO 9VAC25-870-92).
03. APPROVAL OF THE SITE PLAN BY THE PRIVATE UTILITY
COMPANY IN RELATION TO ITS EASEMENT AND FACILITIES
THEREIN MUST BE PROVIDED PRIOR TO SITE PLAN APPROVAL.
04. ANY AREAS LABELED AS FUTURE ARE NOT REVIEWED NOR ARE
THEY APPROVED WITH THIS PROJECT.
05. ON SHEET C2.1, INCLUDE AN MS-19 ANALYSIS POINT AT THE
STORM SEWER OUTFALL TO A NATURAL CHANNEL. INCLUDE THE
MS-19 TABLE AS WELL.
06. ON SHEET C2.2, ESC NOTE 14 SHALL BE UPDATED TO BE
TEMPORARY SEEDED WITHIN 14 DAYS.
07. SHEET C5.2:
A) PROVIDE HGL TO A NATURAL CHANNEL OR PROVIDE
REFERENCES TO APPROVED PLANS THAT CONTAIN
CALCULATIONS FOR THE CAPACITY OF THE SYSTEM TO A
NATURAL CHANNEL.
B) ENSURE ROOF DRAINS/DISCHARGES ARE INCLUDED WITHIN
THE STORM SEWER AND HGL COMPUTATIONS.
C) PROVIDE SPREAD CALCULATIONS FOR ONSITE INLETS.
D) ADD A NOTE IN THE STORM SEWER COMPUTATIONS FOR EX2
INDICATING THE INFORMATION RELIES UPON PREVIOUSLY
APPROVED PLAN FOR THE BEST BUY AND STATE THE
PLANNING PROJECT NUMBER.
08. SHEET C6.0:
A) SHOW OFFSITE CONTOURS (TOWARD THE BEST BUY LOT) TO
VERIFY DRAINAGE AREAS SHOWN ENCOMPASS THE FULL
CONTRIBUTING DRAINAGE AREAS.
09. ON SHEET C6.1, REMOVE THE 60/147 CALCULATION. THIS
DISTRICT IS CLOSED AND NO LONGER REQUIRES A FEE.
10. ON SHEET C6.3, INCLUDE THE WORK REQUIRED FOR PIPE 10
AND STRUCTURE 9 WITHIN THE SITE AREA AND IMPERVIOUS
AREAS.
11. ON SHEET L1.0, IT IS RECOMMENDED TO ADJUST THE LOCATIO
OF THE ELM TREE NEAR PIPE 6 TO HELP PREVENT ROOT
INTERFERENCE WITH THE PIPE.
12. PRIOR TO PLAN APPROVAL, DOCUMENTATION OF THE OWNER'S
ACQUISITION OF THE NONPOINT NUTRIENT OFFSETS MUST BE
PROVIDED IN A CERTIFICATION FROM THE OFFSET BROKER
DOCUMENTING THE NUMBER OF PHOSPHOROUS NONPOINT NUTRIEN
OFFSETS ACQUIRED AND THE ASSOCIATED RATIO OF NITROGEN
NONPOINT NUTRIENT OFFSETS AT THE OFFSET GENERATING
FACILITY.
13. NOTE THAT THE NONPOINT NUTRIENT OFFSETS USED FOR WATER
QUALITY COMPLIANCE MUST BE GENERATED IN THE SAME OR
ADJACENT EIGHT DIGIT HYDROLOGIC UNIT CODE AS DEFINED B
THE UNITED STATES GEOLOGICAL SURVEY AS THE SITE.
NONPOINT NUTRIENT OFFSETS OUTSIDE THE SAME OR ADJACENT
EIGHT DIGIT HYDROLOGIC UNIT CODE MAY ONLY BE USED IF I
IS DETERMINED THAT NO NONPOINT NUTRIENT OFFSETS ARE
AVAILABLE WITHIN THE SAME OR ADJACENT EIGHT DIGIT
HYDROLOGIC UNIT CODE. IN SUCH CASES, THE NONPOINT
NUTRIENT OFFSETS MUST BE GENERATED WITHIN THE SAME
TRIBUTARY. PROVIDE A HYDROLOGIC UNIT MAP SHOWING THE
LOCATION OF THE PROJECT AND THE OFFSET GENERATING
FACILITY.
14. IT IS THE RESPONSIBILITY OF THE OWNER TO PROVIDE ONE
ADDITIONAL SET OF PLANS TO THE ENVIRONMENTAL
ENGINEERING DEPARTMENT AND OBTAIN AN "APPROVED FOR
CONSTRUCTION" STAMP ON TWO ADDITIONAL SETS FOR THE
OWNER TO KEEP ON-SITE.
15. PERMISSION MUST BE OBTAINED FROM THE ADJACENT PROPERTY
OWNER(S) ALLOWING FOR GRADING ON THE PROPERTY AS
PROPOSED PRIOR TO ISSUANCE OF A LAND DISTURBANCE
PERMIT.
16. ALL OFFSITE DRAINAGE EASEMENTS MUST BE RECORDED PRIOR
TO ISSUANCE OF A LAND DISTURBANCE PERMIT FOR THIS
PROJECT.
17. ALL ONSITE DRAINAGE EASEMENTS INCLUDING STORMWATER /
BMP DRAINAGE EASEMENTS MUST BE RECORDED PRIOR TO
ISSUANCE OF A BUILDING PERMIT FOR THIS PROJECT.
18. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A COPY
OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD
FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD VERSIO
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINI
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE SITE
PLAN NAME, SITE PLAN NUMBER, ENGINEERING FIRM AND CAD
FILE PREPARER'S NAME AND PHONE NUMBER. THE FILE MUST
CONTAIN THE FOLLOWING, EACH CLEARLY LABELED IN SEPARAT
LAYERS:
A. PROPOSED BUILDING FOOTPRINT;
B. PARKING LOTS AND DRIVEWAYS;
C. ROADS;
D. SIDEWALKS;
E. ALL JURISDICTIONAL WETLAND AREAS AND/OR WATERS OF THE
U.S./STATE; AND
F. FLOODPLAINS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
19. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND SUBSTANTIAL OR FULL SITE PLAN APPROVAL IS REQUIRED
PRIOR TO ITS ISSUANCE. A LAND DISTURBANCE PERMIT IS
A PREREQUISITE TO A BUILDING PERMIT.
20. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND THE FOLLOWING ARE REQUIRED PRIOR TO ITS ISSUANCE:
A. SUBSTANTIAL OR FULL SITE PLAN APPROVAL
B. A VDOT LAND USE PERMIT
C. COPIES OF THE VIRGINIA STORMWATER MANAGEMENT PERMIT
(VSMP) REGISTRATION STATEMENT AND FEE PAID RECEIPT
E. COPY OF THE STORMWATER POLLUTION PREVENTION PLAN
(SWPPP) TO BE REVIEWED FOR COMPLETENESS.
F. POSTING OF AN EROSION AND SEDIMENT CONTROL SURETY
(AMOUNT TO BE APPROVED BY EE)
==========================================================
==========================================================
==========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : DUSTIN DUNNAGAN / 706-2061
NAME OF PLAN : TOWNE PLACE AT HUGUENOT
ADDRESS : 1409 HUGUENOT ROAD
SITE PLAN NO. : 16PR0108
LATEST PLAN DATE : DECEMBER 30, 2015
DEPT. REC'D DATE : JANUARY 04, 2016
SUBMITTAL NUMBER : 3
REVIEW DATE : JANUARY 29, 2016
RECOMMENDATION : APPROVED
TABLE REVISION : YES
PLAT PROCESSING : YES
01. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND / OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURE
INCLUDING BUT NOT LIMITED TO WETLANDS, SURFACE WATERS
(E.G. VSMP PERMIT FOR CONSTRUCTION SITES, GROUND WATER
AND AIR QUALITY) FINAL APPROVAL OF THESE PLANS WILL NO
RELIEVE YOU OF YOUR RESPONSIBILITY.
(CL-XX #) REPRESENTS A SUBMITTAL CHECKLIST COMMENT -
SECTION AND COMMENT NUMBER
02. EFFECTIVE JULY 1, 2014, ENFORCEMENT OF THE VIRGINIA
STORMWATER REGULATIONS BECAME THE RESPONSIBILITY OF TH
COUNTY FOR DEVELOPMENT PROJECTS WITHIN CHESTERFIELD
COUNTY. ADDITIONALLY, NEW STATE STORMWATER REGULATION
ALSO BECAME EFFECTIVE ON JULY 1, 2014. LAND DISTURBING
ACTIVITIES THAT OBTAINED A VSMP PERMIT PRIOR TO JULY 1
2014 MAY USE THE STORMWATER MANAGEMENT CRITERIA
SPECIFIED IN PART II C (9VAC25-870-93 ET SEQ) FOR TWO
PERMIT CYCLES. PROJECTS GRANDFATHERED UNDER THE
PROVISIONS OF 9VAC25-870-48 MAY FOLLOW THE REQUIREMENT
LISTED UNDER PART IIC FOR ONE PERMIT CYCLE. ALL OTHER
NEW DEVELOPMENT WILL BE SUBJECT TO THE REQUIREMENTS OF
PART IIB (9VAC25-870-62 TO 9VAC25-870-92).
03. ANY AREAS LABELED AS FUTURE ARE NOT REVIEWED NOR ARE
THEY APPROVED WITH THIS PROJECT.
04. PRIOR TO LAND DISTURBANCE PERMIT, PROVIDE SLIP SHEET
FOR SHEET C2.3 AND CHANGE THE MS-19 SITUATIONS TO
INCLUDE SITUATION D.
05. PRIOR TO LAND DISTURBANCE PERMIT, DOCUMENTATION OF THE
OWNER'S ACQUISITION OF THE NONPOINT NUTRIENT OFFSETS
MUST BE PROVIDED IN A CERTIFICATION FROM THE OFFSET
BROKER DOCUMENTING THE NUMBER OF PHOSPHOROUS NONPOINT
NUTRIENT OFFSETS ACQUIRED AND THE ASSOCIATED RATIO OF
NITROGEN NONPOINT NUTRIENT OFFSETS AT THE OFFSET
GENERATING FACILITY.
06. NOTE THAT THE NONPOINT NUTRIENT OFFSETS USED FOR WATER
QUALITY COMPLIANCE MUST BE GENERATED IN THE SAME OR
ADJACENT EIGHT DIGIT HYDROLOGIC UNIT CODE AS DEFINED B
THE UNITED STATES GEOLOGICAL SURVEY AS THE SITE.
NONPOINT NUTRIENT OFFSETS OUTSIDE THE SAME OR ADJACENT
EIGHT DIGIT HYDROLOGIC UNIT CODE MAY ONLY BE USED IF I
IS DETERMINED THAT NO NONPOINT NUTRIENT OFFSETS ARE
AVAILABLE WITHIN THE SAME OR ADJACENT EIGHT DIGIT
HYDROLOGIC UNIT CODE. IN SUCH CASES, THE NONPOINT
NUTRIENT OFFSETS MUST BE GENERATED WITHIN THE SAME
TRIBUTARY. PROVIDE A HYDROLOGIC UNIT MAP SHOWING THE
LOCATION OF THE PROJECT AND THE OFFSET GENERATING
FACILITY.
07. IT IS THE RESPONSIBILITY OF THE OWNER TO PROVIDE ONE
ADDITIONAL SET OF PLANS TO THE ENVIRONMENTAL
ENGINEERING DEPARTMENT AND OBTAIN AN "APPROVED FOR
CONSTRUCTION" STAMP ON TWO ADDITIONAL SETS FOR THE
OWNER TO KEEP ON-SITE.
08. PERMISSION MUST BE OBTAINED FROM THE ADJACENT PROPERTY
OWNER(S) ALLOWING FOR GRADING ON THE PROPERTY AS
PROPOSED PRIOR TO ISSUANCE OF A LAND DISTURBANCE
PERMIT.
09. ALL OFFSITE DRAINAGE EASEMENTS MUST BE RECORDED PRIOR
TO ISSUANCE OF A LAND DISTURBANCE PERMIT FOR THIS
PROJECT.
10. ALL ONSITE DRAINAGE EASEMENTS INCLUDING STORMWATER /
BMP DRAINAGE EASEMENTS MUST BE RECORDED PRIOR TO
ISSUANCE OF A BUILDING PERMIT FOR THIS PROJECT.
11. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A COPY
OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD
FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD VERSIO
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINI
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE SITE
PLAN NAME, SITE PLAN NUMBER, ENGINEERING FIRM AND CAD
FILE PREPARER'S NAME AND PHONE NUMBER. THE FILE MUST
CONTAIN THE FOLLOWING, EACH CLEARLY LABELED IN SEPARAT
LAYERS:
A. PROPOSED BUILDING FOOTPRINT;
B. PARKING LOTS AND DRIVEWAYS;
C. ROADS;
D. SIDEWALKS;
E. ALL JURISDICTIONAL WETLAND AREAS AND/OR WATERS OF THE
U.S./STATE; AND
F. FLOODPLAINS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
12. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND SUBSTANTIAL OR FULL SITE PLAN APPROVAL IS REQUIRED
PRIOR TO ITS ISSUANCE. A LAND DISTURBANCE PERMIT IS
A PREREQUISITE TO A BUILDING PERMIT.
13. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND THE FOLLOWING ARE REQUIRED PRIOR TO ITS ISSUANCE:
A. SUBSTANTIAL OR FULL SITE PLAN APPROVAL
B. A VDOT LAND USE PERMIT
C. COPIES OF THE VIRGINIA STORMWATER MANAGEMENT PERMIT
(VSMP) REGISTRATION STATEMENT AND FEE PAID RECEIPT
E. COPY OF THE STORMWATER POLLUTION PREVENTION PLAN
(SWPPP) TO BE REVIEWED FOR COMPLETENESS.
F. POSTING OF AN EROSION AND SEDIMENT CONTROL SURETY
(AMOUNT TO BE APPROVED BY EE)
==========================================================