Site Plan Review Comments
All Site Plan Review Comments for Case # 13PR0177
Modify comments view for Case # 13PR0177

Go to Case Selection Form or Go to Project List

 
CASE NO: 13PR0177 STATUS: APPROVED - ADMIN
PROJECT NAME: BRANDERMILL WOODS HC - LAST INTERNET UPDATE: 08/01/14
SUBMITTAL TYPE: COMMERCIAL
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 02 10/31/13 11/19/13 COMPLETE 11/19/13 SCD 748-1035
FIRE DEPT.--: 02 10/31/13 11/19/13 COMPLETE 11/14/13 GDS 706-2012
HOUSE NUMBER: 02 10/31/13 11/19/13 COMPLETE 11/19/13 NCP 751-4319
MAPPING/GIS-: 02 10/31/13 11/19/13 COMPLETE 11/19/13 NCP 751-4319
POLICE DEPT.: 02 10/31/13 11/19/13 ******** ********
PLANNING----: 02 10/31/13 11/19/13 COMPLETE 11/25/13 AGC 717-6042
TRANSPORT.--: 02 10/31/13 11/19/13 COMPLETE 11/15/13 SJA 751-4461
UTILITIES---: 02 10/31/13 11/19/13 AMENDED* 11/14/13 RME 748-1338
UTIL.R.O.W.-: 02 10/31/13 11/19/13 ******** ********
VDOT--------: 02 10/31/13 11/19/13 ******** ********
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : RYAN EVANS, P.E./748-1338
NAME OF PLAN : BRANDERMILL WOODS HEALTHCARE CENTER
ADDITION
ADDRESS :
SUBMISSION DATE : 01/31/13
PLAN DATED : 01/26/13
REVIEW DATE : 02/11/13
SITE PLAN NO. : 13PR0177
COMMENTS : 1ST REVIEW-NOT APPROVED
TABLE REVIEW :
PLAT PROCESS :
1. SHOW THE COUNTY PROJECT NUMBER 13-0021 ON THE LOWER
RIGHT HAND CORNER OF EACH SHEET.
2. LABEL WHAT IS PROPOSED TO BE PUBLIC AND WHAT IS PROPOS
AS PRIVATE ON BOTH PLAN AND PROFILE VIEWS. ALSO, SEPARATE
THE UTILITY QUANTITIES SIMILARLY.
3. ADD A NOTE THAT BEYOND THE WATER METER IT IS THE
PLUMBER'S RESPONSIBILITY TO INSTALL THE WATER SERVICE AND
THE WATER SERVICE WILL BE INSPECTED BY THE BUILDING
INSPECTION OFFICE. MARK THE WATER SERVICE BEHIND THE METE
"PRIVATE".
4. PLEASE REFER TO THE EXISTING AS-BUILT RECORDS TO
ACCURATELY SHOW THE EXISTING UTILITIES.
5. ACCORDING TO RECORDS, THERE IS ONE EXISTING 2" METER A
ONE EXISTING 5/8" METER. THE EXISTING METER IS AT THE
TERMINATION OF THE EXISTING 6" PORTION OF THE WATERLINE.
THERE IS NO 1.5" METER ON THE NORTH SIDE OF THE BUILDING
WHERE THE PLAN CALLS FOR THE CONVERSION OF THAT METER TO A
2". REVISE PLANS AND CLARIFY AS NECESSARY.
6. SUBMIT SEPARATE METER SIZING FORMS FOR ANY CHANGED MET
AND THE NEW MAINTENANCE BUILDING. FOR ANY CHANGED METER,
SHOW THE EXISTING AND PROPOSED FIXTURES AND DEMANDS
SEPARATELY.
7. MAKE THE SOUTHERN PROPOSED SANITARY SEWER PRIVATE. IN
GENERAL, THE RETAINING WALL IS TOO CLOSE FOR FUTURE
MAINTENANCE AND SLOPE STABILITY.
8. SHOW THE EXISTING "FUTURE" STUB TO THE SOUTHERN SEWER
MANHOLE TO BE ABANDONED ACCORDING TO THE UTILITIES
SPECIFICATIONS.
9. SHOW EXISTING UTILITIES SIZE, TYPE, PROJECT NUMBER.
10. PROVIDE MORE INFORMATION ON THE MAINTENANCE BUILDING.
FILL OUT A SITE UTILIZATION FORM FOR IT TO DETERMINE WHAT
PROPOSED TO BE STORED.
11. LABEL ANY EXISTING AND/OR PROPOSED MONITORING MANHOLE
12. PROVIDE APPROPRIATE VALVES TO ISOLATE THE DIRECTION O
FLOW FOR THE FIRE LOOP ON THE WEST SIDE OF THE BUILDING.
13. PROVIDE A BLOW UP OF THE WATERLINE CONNECTION TO THE
TERMINATION OF THE EXISTING 6" PORTION. LABEL ALL RESTRAIN
LENGTHS.
14. NO WATER OR SEWER PROFILES WERE FOUND WITH THIS
SUBMISSION. BE ADVISED THAT THEIR REVIEW MAY GENERATE
ADDITIONAL COMMENTS OR ALIGNMENT CHANGES.
15. SHOW ALL RESTRAINT LENGTHS ON THE WATER PROFILES, WHE
THEY'RE SUBMITTED.
16. THE OWNER MUST ENTER INTO A COUNTY CONTRACT PRIOR TO
THE START OF CONSTRUCTION. PLEASE SEND JACQUE HYDEN A COP
OF THE "ACCEPTED" BID PROPOSAL BETWEEN THE DEVELOPER AND T
CONTRACTOR SO WE MAY PREPARE THE COUNTY CONTRACT. THE BID
PROPOSAL MUST BE BASED ON THE APPROVED SITE PLAN.
ALL WORK MUST BE PERFORMED BY AN ACCEPTABLE UTILITIES
CONTRACTOR. IF THE SITE PLAN IS REVISED AFTER THE
UTILITY CONTRACT IS PREPARED, A REVISED BID PROPOSAL MAY
BE NECESSARY TO ACCURATELY REFLECT THE LATEST APPROVED
SITE PLAN, AND A NEW CONTRACT PREPARATION MAY BE
NECESSARY.
17. AFTER COMPLETE SITE PLAN APPROVAL, SUBMIT THREE (3)
SETS OF PLANS DIRECTLY TO THE UTILITY DEPARTMENT FOR OUR
USE.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : RYAN EVANS, P.E./748-1338
NAME OF PLAN : BRANDERMILL WOODS HEALTHCARE CENTER ADD
ADDRESS :
SUBMISSION DATE : 06/24/13
PLAN DATED : 06/18/13
REVIEW DATE : 07/09/13
SITE PLAN NO. : 13PR0177
COMMENTS : 2ND REVIEW-NOT APPROVED
TABLE REVIEW :
PLAT PROCESS :
1. SHOW WATERLINE STATIONING CORRESPONDING TO THE PROFILE
ON THE UTILITY PLANS.
2. MOVE THE GATE VALVE AT THE NORTHERN CONNECTION TO THE
NORTH SIDE OF THE FIRST FIRE HYDRANT TEE RATHER THAN AT TH
CONNECTION POINT.
3. THE GATE VALVE AT THE SOUTHERN CONNECTION CAN BE
ELIMINATED. THERE IS AN EXISTING GATE VALVE SOUTH OF THE
EXISTING FIRE HYDRANT TEE.
4. SHOW THE SANITARY SEWER EASEMENT TO BE ABANDONED ON TH
DEMOLITION PLAN.
5. SHOW THE STORM, SEWER AND WATER CROSSINGS ON THE
RESPECTIVE PROFILES. MAINTAIN THE MINIMUM SEPARATION
DISTANCE OF 1.5'.
6. SHOW A MONITORING MANHOLE AFTER THE OIL SEPARATOR AND
UPSTREAM OF ANY DOMESTIC SEWAGE CONNECTION FOR THE
MAINTENANCE BUILDING.
7. MOVE ANY PROPOSED BOLLARD A MINIMUM OF 5' AWAY FROM A
PROPOSED WATERLINE.
8. IT IS RECOMMENDED TO MOVE THE RETAINING WALL BACK FROM
THE PROPOSED PRIVATE SEWER LINE. SINCE THERE IS NO RETAINI
WALL DESIGN FOUND IN THE PLANS AND ASSUMING IT WILL BE
SEGMENTAL BLOCKS, THE WALL MAY BE UNDERMINED BY THE SEWER
MAINTENANCE IN THE FUTURE.
9. SHOW A 1" CORP STOP FOR A 1" WATER METER ON THE
MAINTENANCE BUILDING.
10. IT IS NOT ADVISABLE TO HAVE 90 DEGREE CLEAN OUTS IF N
ABSOLUTELY NECESSARY. A 90 DEGREE BEND ON A 4" SEWER LINE
MAY EASILY CLOG. REVISE IF DESIRED.
11. PLEASE SEND IN BY EMAIL OR HAND DELIVERY A HARD COPY
THE WATER METER SIZING FORMS. I NOTE THAT THEY ARE FOUND O
THE PLANS.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : RYAN EVANS, P.E./748-1338
NAME OF PLAN : BRANDERMILL WOODS HEALTHCARE CENTER
ADDITION
ADDRESS :
SUBMISSION DATE : 10/31/13
PLAN DATED : 06/18/13
REVIEW DATE : 11/14/13
SITE PLAN NO. : 13PR0177
COMMENTS : 3RD REVIEW-NOT APPROVED
TABLE REVIEW : YES
PLAT PROCESS :
1. PREVIOUS COMMENT NOT ADDRESSED: SHOW A 1" CORP STOP FO
A 1" WATER METER ON THE MAINTENANCE BUILDING.
2. REVISE THE WATERLINE EASEMENT TO EXCLUDE THE DOUBLE
CHECK VAULT. THE DCV IS PRIVATE.
3. SHOW AN RPZ BACKFLOW PREVENTER AFTER THE MAINTENANCE
METER.
4. LABEL THE TWO PROPOSED SEWER LATERALS INTO THE NORTHER
EXISTING MANHOLE AS PRIVATE.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: BRANDERMILL WOODS HC CENTER ADD
SITE PLAN NUMBER: 13PR0177
LATEST PLAN DATE: 01/31/13?
DEPT. REC'D. DATE: 02/04/13
SUBMITTAL NUMBER: ONE
REVIEW DATE: 02/15/13
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: NO
1. CONDITION 4 OF CASE 87SN0056 REQUIRES SUBMISSION AND
APPROVAL OF CONSTRUCTION PLANS FOR A 4-LANE DIVIDED
NORTH/SOUTH ROAD. THIS WAS DONE IN CONJUNCTION WITH SITE
PLAN CASE 87PR1018. CASE REQUIRES CONSTRUCTION OF 2 LANES
OF THE 4 LANE ROADWAY TO NORTH END OF THE RIGHT-OF-WAY.
SUBMIT A PHASING PLAN TO ADDRESS THE CONSTRUCTION OF THE 2
LANES TO THE NORTH. PLEASE CALL TO DISCUSS.
2. NOTE CONDITION 5 OF CASE 87SN0056 CONCERNING DEVELOPMEN
DENSITY ON THE NORTHERN AND SOUTHERN PORTIONS OF PARCEL.
3. NOTE BRANDERMILL PARKWAY FUNCTIONAL CLASSIFICATION ON
THE PLANS. ROAD IS CLASSIFIED AS A MAJOR ARTERIAL.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: BRANDERMILL WOODS HC CENTER ADD
SITE PLAN NUMBER: 13PR0177
LATEST PLAN DATE: 06/18/13
DEPT. REC'D. DATE: 06/21/13
SUBMITTAL NUMBER: TWO
REVIEW DATE: 07/08/13
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: YES - SIGHT DISTANCE ESMT
PRIOR TO FINAL SITE PLAN APPROVAL, PROVIDE A SIGHT DISTANC
EASEMENT ON THE PROPERTY FROM THE EXISTING ACCESS TO THE
NORTH BASED ON AN URBAN MINOR ARTERIAL (50 MPH DESIGN
SPEED) 4-LANE DIVIDED FACILITY. EASEMENT SHALL BE SHOWN O
THE PLAN. A TEMPLATE SIGHT DISTANCE EASEMENT WAS PROVIDED
DURING PREVIOUS CONVERSATIONS. THIS ROAD IS SHOWN AS AN
ULTIMATE 90' MAJOR ARTERIAL (4-LANE DIVIDED) ON THE
COUNTY'S THOROUGHFARE PLAN.
==========================================================
==========================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMEN
REVIEWER/PHONE#: STEVEN J. ADAMS, P.E. (804)751-4461
EMAIL: ADAMSST@CHESTERFIELD.GOV
NAME OF PLAN: BRANDERMILL WOODS HC CENTER ADD
SITE PLAN NUMBER: 13PR0177
LATEST PLAN DATE: 10/30/13
DEPT. REC'D. DATE: 11/05/13
SUBMITTAL NUMBER: THREE
REVIEW DATE: 11/15/13
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: YES - SIGHT DISTANCE ESMT
PRIOR TO SITE PLAN APPROVAL, PROVIDE A SIGHT DISTANCE
EASEMENT ON THE PROPERTY FROM THE EXISTING ACCESS TO THE
NORTH BASED ON AN URBAN MINOR ARTERIAL (50 MPH DESIGN
SPEED) 4-LANE DIVIDED FACILITY. EASEMENT SHALL BE SHOWN O
THE PLAN. A TEMPLATE SIGHT DISTANCE EASEMENT WAS PROVIDED
DURING PREVIOUS CONVERSATIONS. THIS ROAD IS SHOWN AS AN
ULTIMATE 90' MAJOR ARTERIAL (4-LANE DIVIDED) ON THE
COUNTY'S THOROUGHFARE PLAN.
==========================================================
==========================================================
**********************************************************
REVIEW DEPARTMENT------PLANNING
REVIEWER / PHONE #-----ALAN COKER / 804 717-6042
NAME OF PLAN-----------BRANDERMILL WOODS HC ADDITION
SITE PLAN NUMBER-------13PR0177
ADDRESS----------------(EXISTING ADDRESS)
LATEST PLAN DATE-------JANUARY 22, 2013
DEPT. REC'D. DATE------JANUARY 23, 2013
SUBMITTAL NUMBER-------ONE
REVIEW DATE------------FEBRUARY 22 & 25, 2013
RECOMMENDATION---------NOT APPROVED
TABLE REVIEW-----------NO
PLAT PROCESSING--------
LANDSCAPE PLAN STATUS--MUST BE INCLUDED WITH 2ND SUBMISSIO
ARCHITECTURAL ELEVATIONS--NOT YET SUBMITTED
LIGHTING PLAN/CUTSHEETS---NOT YET SUBMITTED
IRRIGATION/HOSEBIB PLAN---NOT YET SUBMITTED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT
10 FULL SETS AND ONE COPY OF THE SITE PLAN SHEET TO THE
PLANNING DEPARTMENT FOR YOUR NEXT REVIEW. PROVIDE A COMPLE
RESPONSE TO COMMENTS FOR ALL DEPARTMENTS TO THE PLANNING
DEPARTMENT.
BELOW EACH COMMENT TO DESCRIBE HOW YOU HAVE ADDRESSED EACH
REVIEW COMMENT. BE SURE TO INDICATE WHICH SHEETS SHOW THE
REQUIRED CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE
ANY CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
(CL X.X REPRESENTS CHECKLIST ITEM NUMBER)
2. PUT THE CHESTERFIELD COUNTY SITE PLAN NUMBER (13PR0177)
IN THE LOWER RIGHT CORNER OF EACH SHEET. (CL B.1)
(THIS NUMBER IS IN ADDITION TO THE UTILITIES DEPT
PROJECT NUMBER)
3. PROVIDE THE OWNER NAME, GPIN AND CURRENT ZONING FOR EAC
ADJACENT PARCEL. (CL A.2). ADD THE ZONING TO THE INFORMATI
ALREADY PROVIDED AND PROVIDE THIS INFORMATION FOR
PROPERTY ACROSS ROADS.
4. ON THE SITE PLAN SHOW THE NUMBER OF STORIES FOR EACH
BUILDING OR BUILDING ADDITION (CL A.4)
5. ON THE SITE PLAN SHOW THE MAXIMUM HEIGHT FOR EACH
BUILDING OR BUILDING ADDITION. (CL A.14)
6. AT A MINIMUM, A CONCEPTUAL LANDSCAPE PLAN MUST BE
SUBMITTED PRIOR TO SITE PLAN APPROVAL THAT SHOWS THE
FOLLOWING: ALL SITE IMPROVEMENTS INCLUDING UTILITIES, STOR
SEWER, EASEMENTS AND RIGHTS OF WAY, FIRE HYDRANT AND VAUL
LOCATIONS, AND CONCEPTUAL SITE LIGHTING (IF SITE IS TO BE
LIT). THIS PLAN MUST BE DRAWN TO SCALE. THE PLAN MUST
INCLUDE DIMENSIONS OF PERIMETER YARDS AND BUFFERS AND
APPROPRIATE LANDSCAPE REQUIREMENTS FOR EACH YARD OR BUFFER
INTERIOR PARKING LOT AREAS, BMP AREAS AND ANY OTHER LAND-
SCAPE REQUIREMENTS. THE PLAN MUST SHOW THE GENERAL LAYOUT
OF EXISTING AND PROPOSED TREES AND SHRUBS, DESIGNATING THE
AS LARGE OR SMALL DECIDUOUS TREES, EVERGREEN TREES, EVER-
GREEN TREES AND SHRUBS AND GROUND COVERS.
THE CLIENT CAN SAVE ADDITIONAL REVIEW FEES IF A DETAILED
LANDSCAPE PLAN IS SUBMITTED IN LIEU OF A CONCEPTUAL PLAN.
IN ADDITION TO THE INFORMATION SHOWN ON THE CONCEPTUAL PLA
THE DETAILED LANDSCAPE PLAN SHALL SHOW THE FOLLOWING:
PLANT SIZES, SPECIFIC PLANT SPECIES, COUNTY REQUIRED NOTES
DETAILS AND ANY SPECIFIC REQUIREMENTS FOR THE SITE.
7. SHOW THE NAME, ADDRESS, PHONE AND FAX NUMBERS FOR THE
FIRM PREPARING THE LANDSCAPE PLAN.
8. PRIOR TO THE RELEASE OF THE BUILDING
PERMIT, 2 COPIES OF THE BUILDING ELEVATIONS MUST BE
SUBMITTED AND APPROVED. THESE ELEVATIONS MUST BE RECEIVED
SEPARATE OF THE CONSTRUCTION DOCUMENT ROLLS WHICH ARE
SUBMITTED TO THE BUILDING INSPECTIONS DEPARTMENT.
A) ELEVATIONS NEED TO IDENTIFY ALL BUILDING MATERIALS AND
COLORS AND SHOW ALL JUNCTION AND ACCESS BOXES, MECHANICAL
EQUIPMENT, AND UTILITY PAD FIXTURES THAT ARE ON OR
IMMEDIATELY ADJACENT TO THE BUILDING.
B) ALL JUNCTION AND ACCESS BOXES NEED TO BE SCREENED OR
PAINTED TO MATCH THE BUILDING. IF PAINTED, THIS NEEDS TO
BE STATED ON THE ELEVATION.
C) MECHANICAL EQUIPMENT, WHETHER ROOF-TOP OR GROUND LEVEL,
SHALL BE SHIELDED AND SCREENED FROM PUBLIC VIEW AND MUST B
DESIGNED TO BE PERCEIVED AS AN INTEGRAL PART OF THE
BUILDING. BUILDING ELEVATIONS NEED TO SHOW ANY ROOFTOP
UNITS. PARAPETS AND/OR SCREENS MUST BE EQUAL IN HEIGHT TO
ANY ROOFTOP UNITS, OR SIGHT LINE DRAWINGS MUST BE PROVIDED
TO DOCUMENT THAT LOWER PARAPET HEIGHT PROVIDES COMPLETE
SCREENING. IF AT THE TIME THE EQUIPMENT IS INSTALLED IT I
VISIBLE, THE METHOD OF SCREENING MUST BE ADJUSTED TO PROVI
THE REQUIRED SCREENING.
D) THE BUILDINGS WILL NEED TO BE ARCHITECTURALLY COMPATIBL
WITH THE EXISTING BUILDINGS.
9. TWO SEPARATE COPIES OF THE LIGHTING PLAN AND CUTSHEETS
MUST BE SUBMITTED DIRECTLY TO THE PLANNING DEPARTMENT. THE
LIGHTING PLAN AND ACCOMPANYING CUTSHEETS FOR ALL BUILDING-
MOUNTED AND FREE-STANDING LIGHTS MUST BE APPROVED PRIOR TO
THE RELEASE OF A BUILDING PERMIT. THE LIGHTING PLAN SHOUL
SHOW THE LOCATION OF ALL LIGHT FIXTURES. ALL LIGHT FIXTUR
MUST BE EITHER A SHOE BOX STYLE WITH A FLAT LENS OR HAVE
FULL EXTERNAL SHIELDS (LEVEL WITH THE BOTTOM OF THE LENS.
(SEC. 19.508.3)
10. TWO SEPARATE COPIES OF THE IRRIGATION AND/OR HOSEBIB
PLAN MUST BE SUBMITTED DIRECTLY TO THE PLANNING DEPARTMENT
THIS PLAN MUST BE APPROVED PRIOR TO RELEASE OF THE
BUILDING PERMIT.
A. ALL PLANTS ARE TO BE WITHIN 100 FEET OF A HOSEBIB IF
IRRIGATION IS NOT BEING USED.
B. ENSURE THAT WATER INFORMATION IS SUPPLIED ON UTILITY
DEPARTMENT METER SIZING FORMS.
C. SHOW ALL CONNECTIONS TO THE MAIN WATER LINE.
D. HOSEBIBS SHOULD BE SHOWN ON THE LANDSCAPE PLAN.
IRRIGATION HEADS AND COVERAGE AREAS NEED TO BE SHOWN ON
A SEPARATE IRRIGATION PLAN. (CL D.13)
11. REVISE THE BMP AS NEEDED SO THAT THE BMP WILL BE
VISUALLY ENHANCED PER SEC. 19-518(I). IF A FENCE IS
REQUIRED, PROVIDE AN ORNAMENTAL FENCE. PROVIDE DETAILS
ON THE PLANS FOR THE FENCE AND OTHER IMPROVEMENTS
TO BE PROVIDED. SEC. 19-518(I).
12. LABEL ON THE SITE PLANS THE 'ULTIMATE RIGHT OF WAY LIN
ALONG BOTH ROADS. IF THIS IS DIFFERENT FROM THE EXISTING
RIGHT OF WAY ALSO LABEL THE EXISTING RIGHT OF WAY LINES.
SETBACKS FROM THE ROADS ARE FROM THE 'ULTIMATE RIGHT OF
WAY LINES'. (SEC. 19-264 & 19-505)
13. CONDITION 7(B) OF CASE 87S056 LIMITS USES THAT CAN
OCCUR WITHIN THE 25 AND 50 FT BUFFER ALONG THE WESTERN
PROPERTY LINE.
DEPENDING UPON WHAT IS DEVELOPED ON THE PROPERTY TO THE
WEST, THIS COMMENT MAY BE REVISED, HOWEVER, CONDITION
7(B) DOES NOT ALLOW THE FIRE LANE AND BMP TO BE LOCATED
WITHIN THE BUFFER. REVISE.
14. THE CONCEPTUAL LANDSCAPE PLANS FOR THE SETBACKS
AND BUFFERS WILL NEED TO BE APPROVED BY THE PLANNING
COMMISSION PER CONDITION 7(D).
15. AS A POINT OF INFORMATION, PRIOR TO RELEASE OF A
FULL OR TEMPORARY CERTIFICATE OF OCCUPANCY, A FULLY
EXECUTED AND ACCEPTED LANDSCAPE MAINTENANCE AGREEMENT IS
REQUIRED. (AT YOUR OPTION, A LANDSCAPE MAINTENANCE BOND
IS ALSO ACCEPTABLE).
16. CONDITION 16 REQUIRES THAT AT LEAST 50% OF THE GROSS
SITE BE OPEN SPACE. PROVIDE CALCULATIONS ON THE SITE
PLAN. READ CONDITION 16.
**********************************************************
REVIEW DEPARTMENT------PLANNING
REVIEWER / PHONE #-----ALAN COKER / 804 717-6042
NAME OF PLAN-----------BRANDERMILL WOODS HC ADDITION
SITE PLAN NUMBER-------13PR0177
ADDRESS----------------(EXISTING ADDRESS)
LATEST PLAN DATE-------JUNE 18, 2013
DEPT. REC'D. DATE------JUNE 20, 2013
SUBMITTAL NUMBER-------TWO
REVIEW DATE------------JULY 30, 2013& SEPTEMBER 19 2013
RECOMMENDATION---------NOT APPROVED
TABLE REVIEW-----------NO
PLAT PROCESSING--------
LANDSCAPE PLAN STATUS--INCLUDED IN SET
ARCHITECTURAL ELEVATIONS--NOT YET SUBMITTED
LIGHTING PLAN/CUTSHEETS---INCLUDED IN SET
IRRIGATION/HOSEBIB PLAN---NOT YET SUBMITTED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT
10 FULL SETS AND ONE COPY OF THE SITE PLAN SHEET TO THE
PLANNING DEPARTMENT FOR YOUR NEXT REVIEW. PROVIDE A COMPLE
RESPONSE TO COMMENTS FOR ALL DEPARTMENTS TO THE PLANNING
DEPARTMENT.
BELOW EACH COMMENT TO DESCRIBE HOW YOU HAVE ADDRESSED EACH
REVIEW COMMENT. BE SURE TO INDICATE WHICH SHEETS SHOW THE
REQUIRED CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE
ANY CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
2. PER PREVOUS COMMENT 2, ADD THE SITE PLAN NUMBER
(13PR0177) IN THE LOWER RIGHT CORNER OF EACH SHEET.
ADD THE SITE PLAN NUMBER TO SHEET WM1.0.
3. REGARDING PREVIOUS COMMENTS 4 & 5 CONCERNING ADDING THE
HEIGHT AND NUMBER OF STORIES FOR EACH BUILDING, BE SURE
TO INCLUDE ALL HEALTHCARE CENTER ADDITIONS PLUS THE
MAINTENANCE BUILDING. REVISE THE GENERAL NOTES SO THAT
THIS INFORMATION IS PROVIDED FOR ALL THE ADDITIONS AND
BUILDINGS.
4. CONDITION 14 OF CASE 87SN0056 REQUIRES THAT AT LEAST
50% OF THE AREA BE MAINTAINED AS "OPEN SPACE".
CALCULATIONS HAVE BEEN PROVIDED ON THE COVER SHEET THAT
SHOWS THAT IMPERVIOUS AREA IS 31.19%. HOWEVER, THIS
AREA SEEMS TO INCLUDE AREA OUTSIDE OF ZONING CASE 87SN0056
YOU MAY KEEP THE CALCULATIONS ALREADY SHOWN, HOWEVER, ADD
CALCULATIONS TO SHOWS THE OPEN AREA ON THIS SITE THAT ARE
WITHIN CASE 87SN0056. BASED ON THE INFORMATION PROVIDED,
THIS SHOULD RESULT IN APPROXIMATELY 60.28% OPEN SPACE
WITHIN THE ZONING CASE AND SUBJECT TO CONDITION 14.
5. PER PREVIOUS COMMENT 8, PRIOR TO RELEASE OF BUILDING
PERMIT, 2 COPIES OF ARCHITECTURAL ELEVATIONS MUST BE
SUBMITTED AND APPROVED. SEE PREVIOUS COMMENT FOR ADDITIONA
INFORMATION.
RECENTLY, PDF ELEVATIONS HAVE BEEN PROVIDED, HOWEVER,
REVIEW OF THE INFORMATION IS NOT COMPLETE.
6. PER PREVIOUS COMMENT 10, TWO COPIES OF THE IRRIGATION/
HOSE BIB PLAN MUST BE SUBMITTED DIRECTLY TO THE PLANNING
DEPARTMENT. SEE PREVIOUS COMMENT FOR ADDITIONAL
INFORMATION.
7. PER PREVIOUS COMMENT 13, THE BMP CANNOT BE LOCATED
WITHIN THE BUFFER. PART OF THE DAM SECTION OF THE BMP
IS STILL LOCATED WITHIN THE BUFFER. ALSO, THE EXISTING
TREES HAVE BEEN REMOVED FROM THE BUFFER. REVISE THE BMP
SO THAT IT IS NOT LOCATED IN THE BUFFER.
8. WHILE PLANTS HAVE BEEN PROVIDE WITHIN THE BMP, THE
PLANTS AND TREES FOR THE VISUAL AMENITY, NEED TO BE ON
THE PERIMETER OF THE BMP WHERE THEY WILL REDUCE THE
VISUAL IMPACT OF THE BMP. IN THIS CASE THE PLANTS NEED TO
BE LOCATED ALONG THE NORTHERN EDGE, ESPECIALLY WHERE TREES
DO NOT EXIST OR ARE SPACED WITH VISIBILITY OF THE BMP AND
ALONG THE EASTERN SIDE FACING BRANDERMILL PARKWAY
(TO BE EXTENDED). (PREVIOUS COMMENT 11)
9. PER PREVIOUS COMMENT 14, THE CONCEPTUAL LANDSCAPE PLANS
FOR THE SETBACKS AND THE BUFFERS NEED TO BE APPROVED BY
THE PLANNING COMMISSION PRIOR TO ROUGH CLEARING.
(PREVIOUS COMMENT 14)
10. THERE ARE AT LEAST TWO RED MAPLE TREES THAT ARE TOO
CLOSE TO A POLE MOUNTED LIGHTING FIXTURE. THESE SHOULD BE
MOVED AWAY FROM THE LIGHT SO THAT AS THE TREES MATURE, THE
DO NOT BLOCK LIGHT FROM THE FIXTURE.
11. CLARIFY THE LOCATION OF THE AQUATIC BENCH LOCATION
ON SHEET C4.3 OR OTHER LOCATION IN THE PLANS.
COORDINATE THE AQUATIC BENCH DETAIL ON L2.1 WITH THE
FACILITY DESIGN AND LANDSCAPE PLAN FOR CLARITY.
ENGINEERING.
**********************************************************
REVIEW DEPARTMENT------PLANNING
REVIEWER / PHONE #-----ALAN COKER / 804 717-6042
NAME OF PLAN-----------BRANDERMILL WOODS-HEALTHCARE CTR/AD
SITE PLAN NUMBER-------13PR0177
ADDRESS----------------2100 BRANDERMILL PKWY
LATEST PLAN DATE-------OCTOBER 30, 2013
DEPT. REC'D. DATE------OCTOBER 31, 2013
SUBMITTAL NUMBER-------THREE
REVIEW DATE------------NOVEMBER 25, 2013
RECOMMENDATION---------SUBSTANTIAL APPROVAL
TABLE REVIEW-----------YES
PLAT PROCESSING--------
LANDSCAPE PLAN STATUS--SUBMITTED
ARCHITECTURAL ELEVATIONS--PARTIAL SUBMITTED
LIGHTING PLAN/CUTSHEETS---SUBMITTED
IRRIGATION/HOSEBIB PLAN---NOT YET SUBMITTED
1. PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT
10 FULL SETS AND ONE COPY OF THE SITE PLAN SHEET TO THE
PLANNING DEPARTMENT FOR YOUR NEXT REVIEW. PROVIDE A COMPLE
RESPONSE TO COMMENTS FOR ALL DEPARTMENTS TO THE PLANNING
DEPARTMENT.
BELOW EACH COMMENT TO DESCRIBE HOW YOU HAVE ADDRESSED EACH
REVIEW COMMENT. BE SURE TO INDICATE WHICH SHEETS SHOW THE
REQUIRED CHANGES. PROVIDE A TRANSMITTAL LETTER TO DESCRIBE
ANY CHANGES TO THE PLANS NOT CAUSED BY THE STAFF REVIEW
COMMENTS.
A REVIEW FEE OF $250.00 IS REQUIRED FOR EACH ADDITIONAL
SITE PLAN REVIEW SUBMITTAL.
2. REVISE THE CHAIN LINK FENCE AROUND THE BMP TO BE AN
ORNAMENTAL STYLE FENCE PER SEC.19-518(I). THE PREVIOUS
PLAN SET REFERENCED THIS FENCE TO BE AN ORNAMENTAL
STYLE FENCE.
3. PREVIOUS NOTE 8 INDICATED THAT ADDITIONAL LANDSCAPING
IS REQUIRED ALONG THE NORTHERN PROPERTY LINE. PERIMETER
LANDSCAPE 'A' APPLIES, HOWEVER, LANDSCAPING RELATED TO THE
BMP AS A VISUAL AMENITY IS ALSO REQUIRED. THE REQUIREMENT
GENERALLY RELATES TO THE APPEARANCE FROM OFF-SITE.
THE REPLY INDICATES THAT AN INSPECTION WILL BE HELD. IN
THIS CASE, PROVIDE A CLEAR NOTE ON THE LANDSCAPE PLANS
INDICATING THAT AN INSPECTION WILL BE HELD WITH THE
REPRESENTATIVE OF THE PLANS REVIEW TEAM OF THE PLANNING
DEPARTMENT TO DETERMINE ANY ADDITIONAL LANDSCAPING THAT
IS REQUIRED TO MEET THE ZONING ORDINANCE REQUIREMENTS.
THE OWNER/DEVELOPER IS TO REQUEST THIS INSPECTION AFTER
ROUGH GRADING IS COMPLETE.
(AS A SUGGESTION, INCLUDE AN ESTIMATED COST FOR THIS WORK
AS PART OF THE BUDGET).
ALSO PROVIDE THE SAME NOTE FOR THE EXTENSION OF BRANDERMIL
PARKWAY WHERE THE SIGHT DISTANCE EASEMENT &THE MAINTENANCE
BUILDING WILL BE LOCATED. PERIMETER LANDSCAPE 'C' IS
REQUIRED IN THIS AREA, BUT NEEDS TO BE SET OUT OF THE
SIGHT DISTANCE EASEMENT.
4. PER PREVIOUS COMMENT, TWO COPIES OF THE IRRIGATION/HOSE
BIB PLAN NEEDS TO BE SUBMITTED AND APPROVED PRIOR TO
RELEASE OF THE BUILDING PERMIT. SEE PREVIOUS COMMENTS
FOR ADDITIONAL INFORMATION.
==========================================================
==========================================================
REVIEW DEPARTMENT: IST / GIS
REVIEWER : NANCY PARKER 751-4319
NAME OF PLAN : BRANDERMILL WOODS HEALTHCARE CENTER ADD
PLAN NO. : 13PR0177
ADDRESS :
LATEST PLAN DATE : 1/22/13
RECEIVED DATE : 1/23/13
SUBMITTAL NUMBER : 1
REVIEW DATE : 2/6/13
RECOMMENDATION : NOT APPROVED
PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS CONCERNING
THE COMMENTS BELOW.
1. COORDINATE POINTS BASED ON THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, NORTH AMERICAN DATUM
1983 ARE NOT PRESENT. TWO POINTS MUST BE SHOWN ON THE
SITE BOUNDARY.
==========================================================
==========================================================
REVIEW DEPARTMENT: IST / GIS
REVIEWER : NANCY PARKER 751-4319
NAME OF PLAN : BRANDERMILL WOODS HEALTHCARE CENTER ADD
PLAN NO. : 13PR0177
ADDRESS :
LATEST PLAN DATE : 6/18/13
RECEIVED DATE : 6/20/13
SUBMITTAL NUMBER : 2
REVIEW DATE : 7/9/13
RECOMMENDATION : APPROVED
==========================================================
==========================================================
REVIEW DEPARTMENT: IST / GIS
REVIEWER : NANCY PARKER 751-4319
NAME OF PLAN : BRANDERMILL WOODS HEALTHCARE CENTER ADD
PLAN NO. : 13PR0177
ADDRESS :
LATEST PLAN DATE : 10/30/13
RECEIVED DATE : 10/31/13
SUBMITTAL NUMBER : 3
REVIEW DATE : 11/19/13
RECOMMENDATION : APPROVED
==========================================================
==========================================================
DEPARTMENT REVIEW: IST / HOUSE NUMBERING SECTION
REVIEWER: NANCY PARKER
PHONE NUMBER: 751-4319
CASE NUMBER: 13PR0177
NAME OF PLAN:BRANDERMILL WOODS HEALTHCARE CENTER ADD
ADDRESS: 2100 BRANDERMILL PKWY
DATE OF REVIEW:2/6/13 REVIEW # 1
STATUS: HOUSE NUMBERING APPROVED
==========================================================
==========================================================
DEPARTMENT REVIEW: IST / HOUSE NUMBERING SECTION
REVIEWER: NANCY PARKER
PHONE NUMBER: 751-4319
CASE NUMBER: 13PR0177
NAME OF PLAN:BRANDERMILL WOODS HEALTHCARE CENTER ADD
ADDRESS: 2100 BRANDERMILL PKWY
DATE OF REVIEW:7/9/13 REVIEW # 2
STATUS: HOUSE NUMBERING APPROVED
==========================================================
==========================================================
DEPARTMENT REVIEW: IST / HOUSE NUMBERING SECTION
REVIEWER: NANCY PARKER
PHONE NUMBER: 751-4319
CASE NUMBER: 13PR0177
NAME OF PLAN:BRANDERMILL WOODS HEALTHCARE CENTER ADD
ADDRESS: 2100 BRANDERMILL PKWY
DATE OF REVIEW:11/19/13 REVIEW # 3
STATUS: HOUSE NUMBERING APPROVED
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: GREG SMITH / 706-2012
EMAIL: SMITHGD@CHESTERFIELD.GOV
NAME OF PLAN: BRANDERMILL WOODS HEALTCARE CNTR ADD.
SITE PLAN NUMBER: 13PR0177
ADDRESS: 2100 BRANDERMILL PKWY
LATEST PLAN DATE: 1/21/13
DEPT. REC'D. DATE: 1/31/13
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 1/12/13
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
PLAT PROCESSING: NO
COMMENTS:
1. THE FIRE FLOW ESTIMATE FORM SHALL SHOW THE REQUIRED
FIRE FLOW OF THE ENTIRE BUILDING, EXISTING AND PROPOSED.
2.PROVIDE A FIRE FLOW ESTIMATE FORM FOR THE MAINTENANCE
BUILDING.
3. REVISE THE FIRE FLOW ESTIMATE FORM FOR THE HEALTH
CARE CENTER TO SHOW A 75% REDUCTION IN FLOW DUE TO
SPRINKLERS (CURRENTLY SHOWING A 25% REDUCTION)
4. PROVIDE COMPUTER GENERATED WATER FLOW TEST DATA,
PROVIDED BY THE CHESTERFIELD COUNTY UTILITIES
DEPARTMENT, VERIFYING THE REQUIRED WATER FLOW FOR FIRE
PROTECTION IS AVAILABLE AT THE SITE. THE WATERFLOW TEST
RESULTS AND GRAPH SHALL BE SHOWN ON THE SUBMITTED PLAN.
THE MINIMUM REQUIRED FIRE FLOW FOR ALL BUILDINGS, WITH
THE EXCEPTION OF ONE AND TWO-FAMILY DWELLINGS, IS 1500
GPM (SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED) IN
ACCORDANCE WITH THE INTERNATIONAL FIRE CODE (2009) -
SECTION B105.2 AND TABLE B105.1.
5. SHOW THE NODE MAP AND RESULTS TABLE FOR THE PROPOSED
OR EXISTING HYDRANTS ON SITE SHOWING THE MAXIMUM FIRE
FLOW CAN BE ACHIEVED. WHEN MULTIPLE FIRE HYDRANTS ARE
USED THE COMBINED FLOW MUST BE SIMULTANEOUS.
6. WHERE A FIRE HYDRANT IS LOCATED ON A FIRE APPARATUS
ACCESS ROAD, THE MINIMUM ROAD WIDTH SHALL BE 26 FEET. SEE
THE INTERNATIONAL FIRE CODE SECTION D103.1 AND
FIGURE D103.1 "MINIMUM CLEARANCE AROUND A FIRE HYDRANT"
7. PROVIDE THE GATE DETAIL FOR THE GATE SECURING THE FIRE
APPARATUS ACCESS ROAD. THE DETAILS SHALL COMPLY WITH
THE 2009 INTERNATIONAL FIRE CODE, APPENDIX D,
SECTION D103.5
8. THE GATE SECURING THE FIRE APPARATUS ACCESS ROAD
SHALL BE SECURED WITH A KNOX PAD LOCK. PROVIDE A NOTE
WITH THE GATE DETAIL TO THAT EFFECT WITH THE GATE DETAIL.
9. WILL THE WATER SUPPLY FOR THE FIRE PROTECTION SYSTEM
BE PROVIDED THROUGH THE EXISTING BUILDING?
10. IF THE ANSWER TO THE ABOVE QUESTION IS YES, PROVIDE
A DETAILED SEQUENCE OF OPERATIONS SHOWING HOW THE
TIE IN TO THE SPRINKLER SYSTEM WILL OCCUR, MINIMIZING
THE LENGTH OF TIME THE BUILDING WILL BE WITHOUT FIRE
PROTECTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: GREG SMITH / 706-2012
EMAIL: SMITHGD@CHESTERFIELD.GOV
NAME OF PLAN: BRANDERMILL WOODS HEALTCARE CNTR ADD.
SITE PLAN NUMBER: 13PR0177
ADDRESS: 2100 BRANDERMILL PKWY
LATEST PLAN DATE: 6/18/13
DEPT. REC'D. DATE: 6/21/13
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 7/2/13
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. AS PREVIOUSLY REQUESTED, PROVIDE A FIRE FLOW ESTIMATE
FORM FOR THE MAINTENANCE BUILDING. ENSURE FLOW CAN
MEET REQUIRED DEMAND.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: GREG SMITH / 706-2012
EMAIL: SMITHGD@CHESTERFIELD.GOV
NAME OF PLAN: BRANDERMILL WOODS HEALTCARE CNTR ADD.
SITE PLAN NUMBER: 13PR0177
ADDRESS: 2100 BRANDERMILL PKWY
LATEST PLAN DATE: 10/31/13
DEPT. REC'D. DATE: 11/5/13
SUBMITTAL NUMBER: 3RD REVIEW
REVIEW DATE: 11/14/13
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
PLAT PROCESSING: YES
COMMENTS:
1. THE REVISED PLAN IS APPROVED AS SUBMITTED.
==========================================================
==========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : SCOTT DUNN, P.E. / 748-1030
NAME OF PLAN : BRANDERMILL WOODS RETIREMENT ADDITION
ADDRESS : 2100 BRANDERMILL PARKWAY
SITE PLAN NO. : 13PR0177
LATEST PLAN DATE : 01/22/13
DEPT. REC'D DATE : 01/31/13
SUBMITTAL NUMBER : ONE
REVIEW DATE : 02/14/13
RECOMMENDATION : NOT APPROVED
TABLE REVISION : NO
PLAT PROCESSING : NO
01. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND / OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURE
INCLUDING BUT NOT LIMITED TO WETLANDS, SURFACE WATERS
(E.G. VSMP PERMIT FOR CONSTRUCTION SITES, GROUND WATER
AND AIR QUALITY) FINAL APPROVAL OF THESE PLANS WILL NO
RELIEVE YOU OF YOUR RESPONSIBILITY. WETLANDS
DOCUMENTATION MUST BE RECEIVED BY THIS DEPARTMENT PRIO
TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
(CL-XX #) REPRESENTS A SUBMITTAL CHECKLIST COMMENT -
SECTION AND COMMENT NUMBER
02. IT HAS RECENTLY COME TO OUR ATTENTION THAT THE STATE
STORMWATER POLLUTION PREVENTION PLAN (SWPPP)
REQUIREMENTS CONCERNING THE 10-YEAR STORM PEAK
ATTENUATION AND WATER QUALITY COMPLIANCE WHICH VARIES
FROM BAY ACT COMPLIANCE MAY BECOME AN ISSUE DURING THE
STATE SITE INSPECTION PROCESS. COUNTY CONSTRUCTION PL
APPROVAL DOES NOT RELIEVE THE OWNER/DEVELOPER OF
RESPONSIBILITY FOR COMPLIANCE WITH STATE REGULATIONS -
E.G. 4VAC50-60-80 FLOODING, 4VAC50-60-60 WATER QUALITY
ETC. TECHNICAL ASSISTANCE FROM DCR IS AVAILABLE AND
RECOMMENDED.
03. REVISE THE MAGISTERIAL DISTRICT TO CLOVER HILL ON THE
COVER SHEET.
04. PROVIDE A STATEMENT ADJACENT TO EE'S ZONING CONDITIONS
ON SHEET C1.1 ON HOW EACH CONDITION HAS BEEN ADDRESSED
05. CURB AND GUTTER IS REQUIRED AROUND ALL PAVED DRIVES.
06. ALL EXISTING AND PROPOSED STORM SEWERS, CULVERTS, DROP
INLETS AND APPURTENANCES MUST BE ASSIGNED A STRUCTURE
NUMBER AND LISTED IN TABULAR FORM ON THE PLAN SHEET ON
WHICH THEY ARE LOCATED. (CL-G&D 14) MOVE THE STORM PI
TABLES FROM SHEET C4.2 TO SHEET C4.1.
07. INCLUDE THE FILTERRA'S IN THE STORM PIPE TABLE.
08. THE MINIMUM DIAMETER FOR STORM SEWER PIPE IS 15".
ADDRESS FOR STRUCTURE 12.
09. STEPS STD. ST-1 MUST BE SPECIFIED IN THE TABULAR
DRAINAGE DESCRIPTION OF ANY STRUCTURE OVER 4 FEET IN
HEIGHT. (CL-G&D 20)
10. BOOT CONNECTORS MUST BE SPECIFIED IN THE TABULAR
DRAINAGE DESCRIPTION FOR ALL PLASTIC PIPES THAT TIE IN
A CONCRETE STRUCTURE. (CL-G&D 21)
11. A SEPARATE PLAN SHEET MUST BE ADDED WHICH ONLY SHOWS A
PROPOSED EASEMENTS AND RIGHT OF WAY TO BE DEDICATED.
METES AND BOUNDS MUST BE PROVIDED. (CL-G&D 30)
12. REMOVE THE REFERENCE TO THE RPA IN THE PHAE I EROSION
CONTROL NARRATIVE ON SHEET C2.2 AS NO RPA IS PRESENT O
THIS SITE.
13. STEP 7 OF THE PHASE I EROSION CONTROL NARRATIVE
REFERENCES INSTALLATION OF SEDIMENT TRAPS. HOWEVER, T
PLAN VIEW DOES NOT SHOW ANY SEDIMENT TRAPS. CLARIFY.
14. CONCENTRATED FLOW IS NOT PERMITTED DOWN THE SLOPES OF
THE SWM/BMP. ADDRESS FOR THE EXISTING LOW TO THE NORT
OF THE SWM/BMP.
15. STEPS MUST BE INCLUDED IN THE SEQUENCE OF CONSTRUCTION
EVENTS FOR AND BUILDING CONSTRUCTION. (CL-EC 6)
16. THE CONSTRUCTION ENTRANCE MUST BE GRAPHICALLY SHOWN ON
THE PLANS AND CONSTRUCTED AS WIDE AS THE PROPOSED
PERMANENT ENTRANCE. (CL-EC 9)
17. A MINIMUM 10' BREAK MUST BE PROVIDED IN THE LOW AREA O
THE SILT FENCE . THE BREAK MUST BE BACKFILLED WITH
STONE TO WITHIN 1' OF THE TOP OF THE SILT FENCE TO
SERVE AS AN OVERFLOW. A DETAIL MUST BE SHOWN. (CL-EC 1
18. DRAINAGE IMPROVEMENTS MUST BE MADE DOWN TO AN ADEQUATE
CHANNEL PER MS-19. ADDRESS FOR STRUCTURES 8 AND 12.
19. ADEQUACY SITUATION G ALSO APPLIES TO ANY MS-19 ANALYSI
POINT DOWNTREAM OF AN SWM. A VARIANCE REQUEST IS
REQUIRED.
20. ANY SOIL STOCKPILE AREA MUST BE LOCATED ON THE PLANS.
SILT FENCE MUST BE PROVIDED AROUND THE PERIMETER.
(CL-EC 39)
21. CLARIFY WHERE THE TARGET/ALLOWABLE FLOWS ARE ENTERED I
THE SWM/BMP ROUTING CALCULATIONS.
22. THE FOLLOWING MUST BE ADDRESSED ON THE CBPA DATA MAP O
SHEET C5.2 (CL-CBPA 3):
A. OUTLINE AND LABEL THE PROJECT AREA (A PORTION OF THE
DRIVE TO THE PROPOSED MAINTENANCE BUILDING IS ON ANOTH
PARCEL);
B. SPECIFY THE EXISTING IMPERVIOUS AREA;
C. SHOW, LABEL AND QUANTIFY THE EXISTING FORESTED/OPEN
SPACE AREAS;
D. SHOW, LABEL AND QUANTIFY THE EXISTING MANAGED TURF
AREAS;
E. SPECIFY THE POST DEVELOPED IMPERVIOUS AREA;
F. SHOW, LABEL AND QUANTIFY THE PROPOSED FORESTED/OPEN
SPACE AREAS;
G. SHOW, LABEL AND QUANTIFY THE PROPOSED MANAGED TURF
AREAS;
H. SHOW AND LABEL THE DRAINAGE AREA TO EACH BMP;
I. SPECIFY THE IMPERVIOUS AREA WITHIN EACH BMP DRAINAGE
AREA;
J. THE BMP SIZE, LOCATION, AND GRADING PLAN (1" = 20').
(CL-CBPA 3B)
K. DETAILS AND SPECIFICATIONS FOR MANUFACTURED BMP'S.
(CL-CBPA 3D)
23. THE RUNOFF REDUCTION WORKSHEET WILL BE REVIEWED WITH T
NEXT PLAN SUBMITTAL ONCE THE PREVIOUS COMMENT AS BEEN
ADEQUATELY ADDRESSED.
24. VEHICULAR SAFETY MEASURES ARE REQUIRED ALONG PARKING
SPACES AND DRIVE AISLES ADJACENT TO RETENTION AND
DETENTION FACILITIES. (CL-CBPA 10)
25. PROVIDE A DISCUSSION ON THE PROPOSED ELEVATION
DIFFERENCE BETWEEN THE FOREBAY AND THE MAIN POND.
26. THE ENTIRE BASIN MUST BE ENCLOSED WITHIN AN SWM / BMP
EASEMENT WHICH EXTENDS 8 FT. BEYOND THE 100-YEAR WSE.
OR DOWNSTREAM TOE OF DAM, WHICHEVER APPLIES.(CL-CBPA 1
SWM/BMP EASEMENTS ARE ALSO REQUIRED FOR THE FILTERRA'S
27. A MINIMUM 20' WIDE ACCESS EASEMENT MUST BE PROVIDED FR
THE SWM/BMP EASEMENT TO A PUBLIC RIGHT-0F-WAY FOR FUTU
MAINTENANCE. (CL-CBPA 15)
28. METES AND BOUNDS MUST BE PROVIDED ON THE PLAN SHEET FO
SWM/BMP EASEMENTS AND ACCESS EASEMENTS. (CL-CBPA 16)
29. A MINIMUM 12 FOOT WIDE RAMP MUST BE PROVIDED FROM THE
ACCESS GATE TO THE BOTTOM OF THE SWM/BMP FACILITY. TH
SLOPE CANNOT EXCEED 6:1. (CL-CBPA 17)
30. ALL SWM/BMP FACILITIES WHICH ARE MORE THAN 4 FEET IN
DEPTH OR MORE THAN ONE ACRE FEET IN SURFACE AREA MUST
PROVIDE BOTH A SAFETY BENCH AND AN AQUATIC BENCH, OR B
ENCLOSED WITHIN A 6-FOOT HIGH PERIMETER FENCE. A
VEGETATIVE BARRIER MAY BE SUBSTITUTED FOR THE FENCE,
HOWEVER A PERFORMANCE BOND MUST BE PROVIDED FOR THE CO
AND INSTALLATION OF THE PLANT MATERIALS. A GATE MUST
ALSO BE PROVIDED WHICH ALIGNS WITH THE 20 FOOT ACCESS
EASEMENT. (CL-CBPA 19)
31. THE 2, 10, AND 100 YEAR WATER SURFACE ELEVATIONS MUST
SHOWN FOR ALL SWM/BMP FACILITIES ON THE PLAN AND PROFI
VIEWS. (CL-CBPA 24)
32. ALL BARREL AND RISER ASSEMBLIES MUST BE "O-RING"
CONCRETE PIPE, NO SMALLER THAN 15 INCHES IN DIAMETER.
(CL-CBPA 29)
33. PROVIDE A TRASH RACK FOR THE PROPOSED 2" ORIFICE. A
DETAIL IS REQUIRED.
34. A DETAIL MUST BE PROVIDED ON THE PLAN SHOWING THE
METHOD OF SECURING THE PLASTIC TRASH RACK / ANTI VORTE
DEVICE TO THE CONCRETE RISER PIPE. (CL-CBPA 31)
35. A GATE VALVE (MINIMUM 12" DIAMETER) MUST BE PROVIDED
TO FACILITATE DRAINING THE BMP FOR MAINTENANCE.
(CL-CBPA 33)
36. THE LENGTH TO WIDTH RATIO IN BMP BASINS (WATER QUALITY
SHALL BE A MINIMUM OF THREE TO ONE (3:1). CALCULATION
ARE REQUIRED PER THE METHODOLOGY OUTLINED IN SECTION
3.14 OF THE VESCH. (CL-CBPA 34)
37. PROVIDE A BMP SIZING CALCULATION SHEET.
38. THE SIDE SLOPES IN SWM/BMP FACILITIES SHALL BE NO
STEEPER THAN THREE TO ONE (3:1). LABEL IN THE PROFILE
VIEW. (CL-CBPA 37)
39. ADDRESS THE CONSTRUCTION OF THE SWM/BMP IN THE EROSION
CONTROL NARRATIVE.
40. A BMP MAINTENANCE FEE IN THE AMOUNT OF $1,500 PER
IMPERVIOUS ACRE IS REQUIRED FOR COMMERCIAL DEVELOPMENT
PAYMENT MUST BE RECEIVED PRIOR TO ISSUANCE OF A LAND
DISTURBANCE PERMIT. (CL-USC 1)
41. DUE TO THE SITE BEING WITHIN THE UPPER SWIFT CREEK
WATERSHED, ALL SILT FENCE MUST BE SUPER SILT FENCE.
REVISE THE PLANS ACCORDINGLY.
42. AN ALTERNATIVE MEANS OF DEFINING PAVEMENT EDGES AS
DETERMINED BY THE DIRECTOR OF ENVIRONMENTAL ENGINEERIN
MAY BE SUBSTITUTED FOR CURB AND GUTTER WHEN LOW IMPACT
DEVELOPMENT PRACTICES ARE USED. (CL-USC 8)
43. THE DESIGN AND CONSTRUCTION OF THE SWM/BMP WHICH WILL
A COUNTY MAINTAINED FACILITY WILL BE SUBJECT TO
INDEPENDENTLY DOCUMENTED GEOTECHNICAL APPROVAL. THE
SERVICES WHICH MUST BE PROVIDED BY THE INDEPENDENT
GEOTECHNICAL ENGINEERING FIRM SHALL INCLUDE FULL TIME
GEOTECHNICAL INSPECTION PAID FOR BY THE DEVELOPER. TH
FULL TIME INSPECTION SHALL INCLUDE BUT NOT BE LIMITED
THE FOLLOWING:
A. PARTICIPATION/INPUT INTO THE DESIGN PROCESS AS NECESSA
TO FACILITATE THE APPROVAL PROCESS OF THE INDEPENDENT
GEOTECHNICAL CONSULTANT.
OBSERVATION, TESTING AND DOCUMENTATION OF:
B. SUITABLE SUBGRADES TO RECEIVE COMPACTED STRUCTURAL FIL
FOR EARTH DAM CONSTRUCTION.
C. THE CUT OFF TRENCH, SPILLWAY PIPE, DRAINAGE BLANKET,
RISER STRUCTURE AND CONCRETE CHUTE SPILLWAY SUBGRADES
APPLICABLE TO EVALUATE WHETHER SUITABLE SOIL IS PRESEN
AT BEARING GRADE TO VERIFY PROPER INSTALLATION.
D. FILL PLACEMENT AND FIELD DENSITY TESTING TO EVALUATE/
VERIFY PROPER COMPACTION.
44. THE FACILITY CERTIFICATION PROCESS SHALL BE PERFORMED
BY AN ENGINEERING/SURVEYING PROFESSIONAL CHOSEN BY THE
COUNTY AT THE OWNERS EXPENSE.
45. THE NAME OF THE GEOTECHNICAL PROFESSIONAL WHO WILL
PROVIDE THE GEOTECHNICAL APPROVAL OF THE SWM/BMP WILL
FURNISHED ON THE LAND DISTURBANCE PERMIT.
46. ALL ONSITE DRAINAGE EASEMENTS INCLUDING STORMWATER /
B.M.P. DRAINAGE EASEMENTS MUST BE RECORDED PRIOR TO
ISSUANCE OF A BUILDING PERMIT FOR THIS PROJECT.
47. THE STORMWATER / B.M.P. FACILITY MUST BE CERTIFIED BY
A PROFESSIONAL ENGINEER PRIOR TO ISSUANCE OF ANY
OCCUPANCY CERTIFICATES.
48. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A COPY
OF THE AUTOCAD .DWG OR .DXF MUST BE SUBMITTED TO
CAROLE CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE
AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD, OR VIA
EMAIL. THE FILE MUST CONTAIN THE FOLLOWING, EACH
CLEARLY IN SEPARATE LAYERS:
A. PROPOSED BUILDING FOOTPRINT;
B. ALL IMPERVIOUS AREAS (PARKING LOTS, DRIVEWAYS, ROADS,
ETC);
C. THE STORM SEWER SYSTEM AND ALL CULVERTS;
D. ALL JURISDICTIONAL WETLAND AREAS AND/OR WATERS OF THE
U.S./STATE;
E. STREAMS AND OTHER WATER BODIES;
F. LOCATIONS OF FIELD VERIFIED RESOURCE PROTECTION AREA
DESIGNATIONS TO INCLUDE WATER BODIES WITH PERENNIAL
FLOW, TIDAL SHORES, TIDAL WETLANDS, NON-TIDAL WETLANDS
WHICH ARE CONNECTED AND CONTIGUOUS TO TIDAL WETLANDS O
PERENNIAL FLOW;
G. LOCATIONS OF PERENNIAL FLOW ORIGINS AND THEIR ASSOCIAT
GPS COORDINATES (NAD83 STATE PLANE VA SOUTH FEET);
H. LOCATION(S) OF BREAK POINT(S) IN SURFACE FLOW AND/OR
NON-CONTIGUOUS WETLANDS AND THEIR ASSOCIATED GPS
COORDINATES; AND
I. FLOOD PLAINS.
ALL AUTOCAD FILES MUST BE SAVED AS A .DWG OR .DXF IN
AUTOCAD VERSION 2009 OR EARLIER AND REFERENCED DIRECTL
TO THE VIRGINIA STATE PLANE COORDINATE SYSTEM, SOUTH
ZONE IN THE NAD83 DATUM. THE CD, DVD, OR EMAIL MUST B
LABELED WITH THE SITE PLAN NAME, SITE PLAN NUMBER,
ENGINEERING FIRM AND CONTACT NAME AND PHONE NUMBER.
49. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND SUBSTANTIAL OR FULL SITE PLAN APPROVAL IS REQUIRED
PRIOR TO ITS ISSUANCE. A LAND DISTURBANCE PERMIT IS
A PREREQUISITE TO A BUILDING PERMIT.
50. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND THE FOLLOWING ARE REQUIRED PRIOR TO ITS ISSUANCE:
A. SUBSTANTIAL OR FULL SITE PLAN APPROVAL
B. A VDOT LAND USE PERMIT
C. A LETTER MUST BE RECEIVED FROM A QUALIFIED WETLANDS
EXPERT STATING:
1.THERE ARE NO WETLANDS IMPACTED ON THIS PROJECT, OR
2.ALL APPLICABLE FEDERAL AND STATE WETLAND PERMITS HAVE
BEEN ACQUIRED (COPIES OF THE PERMITS MUST BE SUBMITTED
D. COPIES OF THE VIRGINIA STORMWATER MANAGEMENT PERMIT
(VSMP) REGISTRATION STATEMENT AND PERMIT FEE FORM (AS
DEVELOPED BY THE DEPARTMENT OF CONSERVATION AND
RECREATION) MUST BE SUBMITTED
E. POSTING OF AN EROSION AND SEDIMENT CONTROL SURETY
(AMOUNT TO BE APPROVED BY EE)
F. SWM/BMP CONSTRUCTION ESTIMATE
G. PAYMENT OF THE UPPER SWIFT CREEK MAINTENANCE FEE
==========================================================
==========================================================
==========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : SCOTT DUNN, P.E. / 748-1030
NAME OF PLAN : BRANDERMILL WOODS RETIREMENT ADDITION
ADDRESS : 2100 BRANDERMILL PARKWAY
SITE PLAN NO. : 13PR0177
LATEST PLAN DATE : 06/18/13
DEPT. REC'D DATE : 06/21/13
SUBMITTAL NUMBER : TWO
REVIEW DATE : 07/09/13
RECOMMENDATION : NOT APPROVED
TABLE REVISION : NO
PLAT PROCESSING : NO
01. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND / OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURE
INCLUDING BUT NOT LIMITED TO WETLANDS, SURFACE WATERS
(E.G. VSMP PERMIT FOR CONSTRUCTION SITES, GROUND WATER
AND AIR QUALITY) FINAL APPROVAL OF THESE PLANS WILL NO
RELIEVE YOU OF YOUR RESPONSIBILITY. WETLANDS
DOCUMENTATION MUST BE RECEIVED BY THIS DEPARTMENT PRIO
TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
(CL-XX #) REPRESENTS A SUBMITTAL CHECKLIST COMMENT -
SECTION AND COMMENT NUMBER
02. STEPS STD. ST-1 MUST BE SPECIFIED IN THE TABULAR
DRAINAGE DESCRIPTION OF ANY STRUCTURE OVER 4 FEET IN
HEIGHT. (CL-G&D 20)
03. CLARIFY WHERE THE TARGET/ALLOWABLE FLOWS ARE ENTERED I
THE SWM/BMP ROUTING CALCULATIONS FOR THE INFLOW
HYDROGRAPHS.
04. ADDRESS THE FOLLOWING IN REFERENCE TO THE MS-19 ANALYS
FOR SECTION A-A:
A. IT APPEARS FROM A FIELD VISIT THAT THE CROSS SECTION
PROVIDED IS NOT AN ACCURATE REPRESENTATION OF THE
EXISTING CHANNEL. PROVIDE SURVEYED CROSS-SECTIONS.
B. SPECIFY THE CHANNEL LINING TO DETERMINE IF THE TWO YEA
VELOCITY IS EROSIVE OR NON-EROSIVE. SEE THE TABLES IN
CHAPTER 5 OF THE VESCH.
C. PROVIDE CALCULATIONS PER THE VESCH TO DETERMINE THE
ROUGHNESS COEFFICIENT USED IN THE CROSS SECTION
ANALYSIS.
D. IT APPEARS CONTAINMENT IS NOT MAINTAINED WITHIN THE
CHANNEL OFF-SITE. ADDRESS ACCORDINGLY.
E. CORRECT THE TEN YEAR DEPTH ON SHEET C5.1.
05. THE CBPA CALCULATIONS MAY BE CALCULATED FOR A NO NET
POLLUTANT INCREASE FOR COUNTY COMPLIANCE AS THE SITE
IMPROVEMENTS ARE NOT CONSIDERED REDEVELOPMENT. A TEN
PERCENT REDUCTION WILL STILL BE REQUIRED UNDER SITUATI
THREE OF THE STATE STORM WATER CALCULATION SHEETS.
06. VEHICULAR SAFETY MEASURES ARE REQUIRED ALONG PARKING
SPACES AND DRIVE AISLES ADJACENT TO RETENTION AND
DETENTION FACILITIES. (CL-CBPA 10)
07. THE ENTIRE BASIN MUST BE ENCLOSED WITHIN AN SWM / BMP
EASEMENT WHICH EXTENDS 8 FT. BEYOND THE 100-YEAR WSE.
OR DOWNSTREAM TOE OF DAM, WHICHEVER APPLIES.(CL-CBPA 1
08. OFF-SET THE PROPOSED 6' SWM/BMP FENCE TO THE OUTSIDE O
THE TOP OF DAM TO PROVIDE ACCESS FOR MAINTENANCE.
09. PROVIDE A TRASH RACK FOR THE PROPOSED 12" ORIFICE. A
DETAIL IS REQUIRED.
10. A BMP MAINTENANCE FEE IN THE AMOUNT OF $1,500 PER
IMPERVIOUS ACRE IS REQUIRED FOR COMMERCIAL DEVELOPMENT
PAYMENT MUST BE RECEIVED PRIOR TO ISSUANCE OF A LAND
DISTURBANCE PERMIT. (CL-USC 1)
11. THE DESIGN AND CONSTRUCTION OF THE SWM/BMP WHICH WILL
A COUNTY MAINTAINED FACILITY WILL BE SUBJECT TO
INDEPENDENTLY DOCUMENTED GEOTECHNICAL APPROVAL. THE
SERVICES WHICH MUST BE PROVIDED BY THE INDEPENDENT
GEOTECHNICAL ENGINEERING FIRM SHALL INCLUDE FULL TIME
GEOTECHNICAL INSPECTION PAID FOR BY THE DEVELOPER. TH
FULL TIME INSPECTION SHALL INCLUDE BUT NOT BE LIMITED
THE FOLLOWING:
A. PARTICIPATION/INPUT INTO THE DESIGN PROCESS AS NECESSA
TO FACILITATE THE APPROVAL PROCESS OF THE INDEPENDENT
GEOTECHNICAL CONSULTANT.
OBSERVATION, TESTING AND DOCUMENTATION OF:
B. SUITABLE SUBGRADES TO RECEIVE COMPACTED STRUCTURAL FIL
FOR EARTH DAM CONSTRUCTION.
C. THE CUT OFF TRENCH, SPILLWAY PIPE, DRAINAGE BLANKET,
RISER STRUCTURE AND CONCRETE CHUTE SPILLWAY SUBGRADES
APPLICABLE TO EVALUATE WHETHER SUITABLE SOIL IS PRESEN
AT BEARING GRADE TO VERIFY PROPER INSTALLATION.
D. FILL PLACEMENT AND FIELD DENSITY TESTING TO EVALUATE/
VERIFY PROPER COMPACTION.
12. THE FACILITY CERTIFICATION PROCESS SHALL BE PERFORMED
BY AN ENGINEERING/SURVEYING PROFESSIONAL CHOSEN BY THE
COUNTY AT THE OWNERS EXPENSE.
13. THE NAME OF THE GEOTECHNICAL PROFESSIONAL WHO WILL
PROVIDE THE GEOTECHNICAL APPROVAL OF THE SWM/BMP WILL
FURNISHED ON THE LAND DISTURBANCE PERMIT.
14. ALL ONSITE DRAINAGE EASEMENTS INCLUDING STORMWATER /
B.M.P. DRAINAGE EASEMENTS MUST BE RECORDED PRIOR TO
ISSUANCE OF A BUILDING PERMIT FOR THIS PROJECT.
15. THE STORMWATER / B.M.P. FACILITY MUST BE CERTIFIED BY
A PROFESSIONAL ENGINEER PRIOR TO ISSUANCE OF ANY
OCCUPANCY CERTIFICATES.
16. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A COPY
OF THE AUTOCAD .DWG OR .DXF MUST BE SUBMITTED TO
CAROLE CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE
AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD, OR VIA
EMAIL. THE FILE MUST CONTAIN THE FOLLOWING, EACH
CLEARLY IN SEPARATE LAYERS:
A. PROPOSED BUILDING FOOTPRINT;
B. ALL IMPERVIOUS AREAS (PARKING LOTS, DRIVEWAYS, ROADS,
ETC);
C. THE STORM SEWER SYSTEM AND ALL CULVERTS;
D. ALL JURISDICTIONAL WETLAND AREAS AND/OR WATERS OF THE
U.S./STATE;
E. STREAMS AND OTHER WATER BODIES;
F. LOCATIONS OF FIELD VERIFIED RESOURCE PROTECTION AREA
DESIGNATIONS TO INCLUDE WATER BODIES WITH PERENNIAL
FLOW, TIDAL SHORES, TIDAL WETLANDS, NON-TIDAL WETLANDS
WHICH ARE CONNECTED AND CONTIGUOUS TO TIDAL WETLANDS O
PERENNIAL FLOW;
G. LOCATIONS OF PERENNIAL FLOW ORIGINS AND THEIR ASSOCIAT
GPS COORDINATES (NAD83 STATE PLANE VA SOUTH FEET);
H. LOCATION(S) OF BREAK POINT(S) IN SURFACE FLOW AND/OR
NON-CONTIGUOUS WETLANDS AND THEIR ASSOCIATED GPS
COORDINATES; AND
I. FLOOD PLAINS.
ALL AUTOCAD FILES MUST BE SAVED AS A .DWG OR .DXF IN
AUTOCAD VERSION 2009 OR EARLIER AND REFERENCED DIRECTL
TO THE VIRGINIA STATE PLANE COORDINATE SYSTEM, SOUTH
ZONE IN THE NAD83 DATUM. THE CD, DVD, OR EMAIL MUST B
LABELED WITH THE SITE PLAN NAME, SITE PLAN NUMBER,
ENGINEERING FIRM AND CONTACT NAME AND PHONE NUMBER.
17. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND SUBSTANTIAL OR FULL SITE PLAN APPROVAL IS REQUIRED
PRIOR TO ITS ISSUANCE. A LAND DISTURBANCE PERMIT IS
A PREREQUISITE TO A BUILDING PERMIT.
18. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND THE FOLLOWING ARE REQUIRED PRIOR TO ITS ISSUANCE:
A. SUBSTANTIAL OR FULL SITE PLAN APPROVAL
B. A VDOT LAND USE PERMIT
C. A LETTER MUST BE RECEIVED FROM A QUALIFIED WETLANDS
EXPERT STATING:
1.THERE ARE NO WETLANDS IMPACTED ON THIS PROJECT, OR
2.ALL APPLICABLE FEDERAL AND STATE WETLAND PERMITS HAVE
BEEN ACQUIRED (COPIES OF THE PERMITS MUST BE SUBMITTED
D. COPIES OF THE VIRGINIA STORMWATER MANAGEMENT PERMIT
(VSMP) REGISTRATION STATEMENT AND PERMIT FEE FORM (AS
DEVELOPED BY THE DEPARTMENT OF CONSERVATION AND
RECREATION) MUST BE SUBMITTED
E. POSTING OF AN EROSION AND SEDIMENT CONTROL SURETY
(AMOUNT TO BE APPROVED BY EE)
F. SWM/BMP CONSTRUCTION ESTIMATE
G. PAYMENT OF THE UPPER SWIFT CREEK MAINTENANCE FEE
==========================================================
==========================================================
==========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : SCOTT DUNN, P.E. / 748-1030
NAME OF PLAN : BRANDERMILL WOODS RETIREMENT ADDITION
ADDRESS : 2100 BRANDERMILL PARKWAY
SITE PLAN NO. : 13PR0177
LATEST PLAN DATE : 10/30/13
DEPT. REC'D DATE : 11/01/13
SUBMITTAL NUMBER : THREE
REVIEW DATE : 11/19/13
RECOMMENDATION : NOT APPROVED
TABLE REVISION : NO
PLAT PROCESSING : NO
01. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND / OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURE
INCLUDING BUT NOT LIMITED TO WETLANDS, SURFACE WATERS
(E.G. VSMP PERMIT FOR CONSTRUCTION SITES, GROUND WATER
AND AIR QUALITY) FINAL APPROVAL OF THESE PLANS WILL NO
RELIEVE YOU OF YOUR RESPONSIBILITY. WETLANDS
DOCUMENTATION MUST BE RECEIVED BY THIS DEPARTMENT PRIO
TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
02. AS DISCUSSED, PROVIDE THE MS-19L CRITERIA FOR THE BASI
ADJACENT TO THE MS-19 COMPLIANCE TABLE. THE BASIN
ROUTING CALCULATIONS MUST BE REVISED ACCORDINGLY.
03. VEHICULAR SAFETY MEASURES ARE REQUIRED ALONG PARKING
SPACES AND DRIVE AISLES ADJACENT TO RETENTION AND
DETENTION FACILITIES. (CL-CBPA 10) BUMPER BLOCKS ARE
NOT AN ACCEPTABLE SAFETY MEASURE.
04. CLARIFY THE AQUATIC BENCH THAT IS NOW PROPSED FOR THE
BMP. IT APPEARS PART OF THE BENCH IS ABOVE THE PROPOS
NORMAL WATER SURFACE ELEVATION.
05. PROVIDE THE BMP SIZING CALCULATIONS.
06. A BMP MAINTENANCE FEE IN THE AMOUNT OF $1,500 PER
IMPERVIOUS ACRE IS REQUIRED FOR COMMERCIAL DEVELOPMENT
PAYMENT MUST BE RECEIVED PRIOR TO ISSUANCE OF A LAND
DISTURBANCE PERMIT. (CL-USC 1)
07. THE DESIGN AND CONSTRUCTION OF THE SWM/BMP WHICH WILL
A COUNTY MAINTAINED FACILITY WILL BE SUBJECT TO
INDEPENDENTLY DOCUMENTED GEOTECHNICAL APPROVAL. THE
SERVICES WHICH MUST BE PROVIDED BY THE INDEPENDENT
GEOTECHNICAL ENGINEERING FIRM SHALL INCLUDE FULL TIME
GEOTECHNICAL INSPECTION PAID FOR BY THE DEVELOPER. TH
FULL TIME INSPECTION SHALL INCLUDE BUT NOT BE LIMITED
THE FOLLOWING:
A. PARTICIPATION/INPUT INTO THE DESIGN PROCESS AS NECESSA
TO FACILITATE THE APPROVAL PROCESS OF THE INDEPENDENT
GEOTECHNICAL CONSULTANT.
OBSERVATION, TESTING AND DOCUMENTATION OF:
B. SUITABLE SUBGRADES TO RECEIVE COMPACTED STRUCTURAL FIL
FOR EARTH DAM CONSTRUCTION.
C. THE CUT OFF TRENCH, SPILLWAY PIPE, DRAINAGE BLANKET,
RISER STRUCTURE AND CONCRETE CHUTE SPILLWAY SUBGRADES
APPLICABLE TO EVALUATE WHETHER SUITABLE SOIL IS PRESEN
AT BEARING GRADE TO VERIFY PROPER INSTALLATION.
D. FILL PLACEMENT AND FIELD DENSITY TESTING TO EVALUATE/
VERIFY PROPER COMPACTION.
08. THE FACILITY CERTIFICATION PROCESS SHALL BE PERFORMED
BY AN ENGINEERING/SURVEYING PROFESSIONAL CHOSEN BY THE
COUNTY AT THE OWNERS EXPENSE.
09. THE NAME OF THE GEOTECHNICAL PROFESSIONAL WHO WILL
PROVIDE THE GEOTECHNICAL APPROVAL OF THE SWM/BMP WILL
FURNISHED ON THE LAND DISTURBANCE PERMIT.
10. ALL ONSITE DRAINAGE EASEMENTS INCLUDING STORMWATER /
B.M.P. DRAINAGE EASEMENTS MUST BE RECORDED PRIOR TO
ISSUANCE OF A BUILDING PERMIT FOR THIS PROJECT.
11. THE STORMWATER / B.M.P. FACILITY MUST BE CERTIFIED BY
A PROFESSIONAL ENGINEER PRIOR TO ISSUANCE OF ANY
OCCUPANCY CERTIFICATES.
12. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A COPY
OF THE AUTOCAD .DWG OR .DXF MUST BE SUBMITTED TO
CAROLE CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE
AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD, OR VIA
EMAIL. THE FILE MUST CONTAIN THE FOLLOWING, EACH
CLEARLY IN SEPARATE LAYERS:
A. PROPOSED BUILDING FOOTPRINT;
B. ALL IMPERVIOUS AREAS (PARKING LOTS, DRIVEWAYS, ROADS,
ETC);
C. THE STORM SEWER SYSTEM AND ALL CULVERTS;
D. ALL JURISDICTIONAL WETLAND AREAS AND/OR WATERS OF THE
U.S./STATE;
E. STREAMS AND OTHER WATER BODIES;
F. LOCATIONS OF FIELD VERIFIED RESOURCE PROTECTION AREA
DESIGNATIONS TO INCLUDE WATER BODIES WITH PERENNIAL
FLOW, TIDAL SHORES, TIDAL WETLANDS, NON-TIDAL WETLANDS
WHICH ARE CONNECTED AND CONTIGUOUS TO TIDAL WETLANDS O
PERENNIAL FLOW;
G. LOCATIONS OF PERENNIAL FLOW ORIGINS AND THEIR ASSOCIAT
GPS COORDINATES (NAD83 STATE PLANE VA SOUTH FEET);
H. LOCATION(S) OF BREAK POINT(S) IN SURFACE FLOW AND/OR
NON-CONTIGUOUS WETLANDS AND THEIR ASSOCIATED GPS
COORDINATES; AND
I. FLOOD PLAINS.
ALL AUTOCAD FILES MUST BE SAVED AS A .DWG OR .DXF IN
AUTOCAD VERSION 2009 OR EARLIER AND REFERENCED DIRECTL
TO THE VIRGINIA STATE PLANE COORDINATE SYSTEM, SOUTH
ZONE IN THE NAD83 DATUM. THE CD, DVD, OR EMAIL MUST B
LABELED WITH THE SITE PLAN NAME, SITE PLAN NUMBER,
ENGINEERING FIRM AND CONTACT NAME AND PHONE NUMBER.
13. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND SUBSTANTIAL OR FULL SITE PLAN APPROVAL IS REQUIRED
PRIOR TO ITS ISSUANCE. A LAND DISTURBANCE PERMIT IS
A PREREQUISITE TO A BUILDING PERMIT.
14. A LAND DISTURBANCE PERMIT IS REQUIRED FOR THIS PROJECT
AND THE FOLLOWING ARE REQUIRED PRIOR TO ITS ISSUANCE:
A. SUBSTANTIAL OR FULL SITE PLAN APPROVAL
B. A VDOT LAND USE PERMIT
C. A LETTER MUST BE RECEIVED FROM A QUALIFIED WETLANDS
EXPERT STATING:
1.THERE ARE NO WETLANDS IMPACTED ON THIS PROJECT, OR
2.ALL APPLICABLE FEDERAL AND STATE WETLAND PERMITS HAVE
BEEN ACQUIRED (COPIES OF THE PERMITS MUST BE SUBMITTED
D. COPIES OF THE VIRGINIA STORMWATER MANAGEMENT PERMIT
(VSMP) REGISTRATION STATEMENT AND PERMIT FEE FORM (AS
DEVELOPED BY THE DEPARTMENT OF CONSERVATION AND
RECREATION) MUST BE SUBMITTED
E. POSTING OF AN EROSION AND SEDIMENT CONTROL SURETY
(AMOUNT TO BE APPROVED BY EE)
F. SWM/BMP CONSTRUCTION ESTIMATE
G. PAYMENT OF THE UPPER SWIFT CREEK MAINTENANCE FEE
==========================================================

Modify comments view for case # 13PR0177