Subdivision Review Comments
All Subdivision Review Comments for Case # 18CP0021




For VDOT’s comments please contact Virginia Department of Transportation at (804) 674-2814 or send e-mail to Boris.Solomonov@VDOT.Virginia.gov

For Tentative Subdivision resubmittals:

1. Please note that submittal fees include the original submittal and two (2) additional reviews.

2. A letter of transmittal is required to accompany each submittal.

3. Please verify that Environmental Engineering, Fire, CDOT, VDOT, and Planning have reviewed the submittal before resubmitting. A resubmittal tendered, prior to receiving all the required departments’ review, will be counted as an additional submittal. Go to Case Selection Form or Go to Project List


 
CASE NO: 18CP0021 STATUS: PENDING APPROVAL
PROJECT NAME: THE LANDINGS AT MEAD - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: CONSTRUCTION PLAN
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 00 09/18/17 10/16/17 COMPLETE 10/16/17 MCJ 751-2335
FIRE DEPT.--: 00 09/18/17 10/16/17 COMPLETE 10/16/17 JKL 748-1489
PLANNING----: 00 09/18/17 10/16/17 COMPLETE 10/12/17 BSM 717-6143
TRANSPORT.--: 00 09/18/17 10/16/17 COMPLETE 10/12/17 SES 751-4912
UTIL.PLAN.--: 00 09/18/17 10/16/17 ******** ********
UTILITIES---: 00 09/18/17 10/16/17 COMPLETE 10/03/17
UTIL.R.O.W.-: 00 09/18/17 10/16/17 ******** ********
VDOT--------: 00 09/18/17 10/16/17 ******** ********
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: MIKE LARSON/748-1338
PLAN NAME: THE LANDINGS AT MEADOWVILLE SEC 1
PLAN NUMBER: 18CP0021
ORIGINAL PLAN DATE: 8/25/17
REVIEW DATE: 10/2/17
LATEST SUBMISSION DATE: 9/18/17
SUBMITTAL NUMBER: 1
STATUS: FIRST REVIEW - NOT APPROVED
TABLE REVIEW: NO
1. SHOW THE COUNTY PROJECT NUMBER 15-0233 ON THE LOWER RIGHT
HAND CORNER OF EACH SHEET.
2. FOR DETAIL DES-2 ON SHEET C-3, THE ELEVATION WHERE
PRVS ARE REQUIRED IS 55. THIS CONDITION WILL LIKELY BE APPLI
CABLE FOR LOTS 45 AND 46, PLEASE PLACE THE LABEL "PRV" ON EA
CH OF THESE LOTS.
3. PROVIDE A NOTE FOR THE BUILDER FOR LOT 45 AND 46 TO CONSU
LT THE BUILDING CODE TO DETERMINE THE CORRECT SIZE OF THE PR
IVATE WATER SERVICE LINE FROM THE METER TO THE HOUSE. LONG
DISTANCE LINES WILL REQUIRE UPSIZE TO AT LEAST 1.5 OR 2 INCH
ES. A ¾" SERVICE LINE WILL STILL BE PROVIDED FROM THE MAIN
TO THE METER.
4. LABEL THE HYDRANT NUMBERS ON THE FLOW TEST AND PROVIDE A
COPY OF THE FLOW TEST LETTER AND CURVE.
5. WILL THERE BE ANY IRRIGATION METERS PROVIDED? IF
SO, PLEASE IDENTIFY THE LOCATION ON THE PLANS WITH A 10' X 1
*' EASEMENT FOR THE METER AND SUBMIT A METER SIZING FORM FOR
6. THE PROPERTY OWNER AND GPIN INFORMATION IS MISSING FOR TH
* ADJACENT MOUNT BLANCO LOTS AND THE RAO PROPERTY ON THE INS
7. IDENTIFY THE BENCH MARKS ON THE UTILITY PLAN SHEETS.
*
8. PROVIDE A NOTE THAT FOR LOTS WITH SIDEWALKS ALL WATER MET
ERS ARE TO BE SET 3 FT BEYOND THE SIDEWALK AND ALL SEWER LAT
ERALS ARE TO BE EXTENDED TO 3 FT BEYOND THE SIDEWALK.
9. IDENTIFY THAT ALL SEWER LATERALS FROM DUCTILE IRON SEWER
PIPES ARE TO BE DUCTILE IRON.
10. PROVIDE LABELS FOR WATER METER WITH ¾" SERVICE
(TYP) AND 6" LATERAL (TYP) ON EACH PLAN SHEET
11. NOTE THAT THE LOCATION OF THE WATER LINE IS 4 FT FROM FA
CE OF CURB (TYP) ON EACH PLAN SHEET.
12. PROVIDE DEFLECTION ANGLES FOR EACH MANHOLE.
13. PROVIDE NOTE THAT THE INVERT AT EACH EXISTING MANHOLE ON
*ROTUNDA LN AND WINBOLT DR HAS BEEN FIELD VERIFIED.
14. PROVIDE A NOTE THAT THE INVERT OF MANHOLE EX-3 THAT CURR
ENTLY UNDER CONSTRUCTION AS PART OF MEADOWVILLE LANDING SEC
5 IS TO BE FIELD VERIFIED PRIOR TO THE START OF CONSTRUCTION
.
15. NOTE THAT MANHOLE EX-3 IS TO BE CORE DRILLED WITH A KOR-
N-SEAL BOOT INSTALLED.
16. INSTEAD OF SHOWING THE FUTURE RIVERBOAT DR FOR THE SANIT
*RY SEWER EXTENSION INTO MEADOWVILLE LANDING, THE EXISTING D
17. COORDINATE WITH TOWNES SITE ENGINEERING (ZACK WILKINS) T
O SEE IF THE SANITARY SEWER EASEMENT CAN BE RECORDED AS PART
OF THE SUBDIVISION PLAT FOR MEADOWVILLE LANDING SECTION 6
18. CONSIDER PROVIDING LATERALS FOR THE FUTURE LOTS BETWEEN
*H EX-3 AND MH-6.
19. PROVIDE A SEWER LATERAL FOR LOT 45 AND 46 TO RECEIVE PUM
*ED FLOW.
20. WHAT IS THE PURPOSE OF THE 16' SANITARY SEWER EASEMENT B
ETWEEN LOT 45 AND 46?
21. A SECOND VALVE IS REQUIRED AT THE TEE AT ALMER CT
AND WINBOLD DR. THE VALVES SHOULD BE ON THE WEST AND SOUTH S
*DE OF THE TEE.
22. THE FIRE HYDRANT ON WINBOLT DR SHOULD BE RELOCATED TO AV
*ID A DEEP VALVE AND TEE.
23. IDENTIFY VALVES FOR SHUT OFF ON THE EXISTING 16" WATER M
*IN ON MEADOWVILLE RD.
24. PROVIDE 2-16" BUTTERFLY VALVES AND A 4" BLOW OFF AT THE
CONNECTION TO THE LINE ON MEADOWVILLE RD.
25. EXTEND A 20 FT SANITARY SEWER EASEMENT WITH 10 FT TEMPOR
ARY CONSTRUCTION EASEMENT ON EACH SIDE FROM MH 18 TO 11701 N
. ENON CHURCH RD.
26. IN ORDER TO MINIMIZE DISRUPTION TO THE ROAD AND
FUTURE LOT OWNERS, INCLUDE THE SANITARY SEWER RUN FROM MH 25
*BETWEEN LOT 30-31 UP TO AND INCLUDING THE MANHOLE TO THE NO
27. IN ORDER TO ACCOUNT FOR POTENTIAL FUTURE ROAD WIDENING,
THE 16" WATER LINE ALONG N. ENON CHURCH RD NEEDS TO BE INSTA
LLED ON THE NEW RIGHT-OF-WAY LINE WITH AN 8 FT PERMANENT EAS
EMENT. THE EASEMENT SHALL BE 16 FT WIDE THROUGH 11701 N. EN
ON CHURCH RD.
28. PROVIDE A FIRE HYDRANT AT SOME POINT TO PROTECT LOTS 53-
*0.
29. PROVIDE A 16" MAIN LINE BUTTERFLY VALVE AT THE 90 DEGREE
*BEND BETWEEN LOT 54 AND 55.
30. THE WATER SERVICE LINES FOR LOTS 49 AND 50 SHOULD
BE CALLED OUT AS 1" SERVICES.
*
31. THE PROPOSED WATER SERVICE LINE FOR LOT 53 IS NOT ACCEPT
*BLE. EXTEND A 6" PUBLIC MAIN TO LOT 53 AND RELOCATE THE WA
32. USE RESTRAINED VERTICAL BENDS TO GO UNDER STORM PIPES RA
*HER THAN DEFLECTION OF PVC PIPE.
33. PROVIDE COPIES OF JOINT RESTRAINT CALCULATIONS WITH THE
NEXT SUBMITTAL. MAKE SURE TO USE A TEST PRESSURE OF 150 PSI
AND 1.5 FACTOR OF SAFETY.
34. CAN THE WATER MAIN IN THE VICINITY OF STA 26+00 31+00 AL
MER CT BE BROUGHT UP ANY SHALLOWER? WE REALIZE THAT THERE A
RE SOME LATERAL CONFLICTS BUT THE PIPE
SHOULD BE SHOWN AS SHALLOW AS POSSIBLE.
*
35. THERE APPEARS TO BE A VERTICAL CONFLICT WITH THE PRIVATE
*PORTION OF THE LATERAL TO LOT 12 AND THE STORM SEWER, PLEAS
36. THERE APPEARS TO BE A FUTURE STORM SEWER SHOWN IN PROFIL
E ON ALMER LN BETWEEN MH 5-7. THE DEPTH OF THIS STORM SEWER
MAY RESULT IN VERTICAL CONFLICTS. PLEASE RESOLVE AND SHOW
THE INVERTS OF THE LATERAL IF APPLICABLE ON THE PLANS FOR TH
IS SECTION TO AVOID PROBLEMS IN SECTION 2.
37. FOR THE 16" WATERLINE, IT IS PREFERRED TO GO OVER THE TO
P OF THE SANITARY SEWER BETWEEN MH 16-19. IT APPEARS THAT I
F WE LOWER THE COVER TO 2.5 FT FOR A SHORT
DISTANCE, WE CAN OBTAIN ABOUT 1 FT VERTICAL CLEARANCE OVER T
*E PIPE, WHICH IS PREFERRED TO GOING UNDER A SANITARY SEWER.
38. MANHOLE TOPS THAT ARE IN MAINTAINED (MOWED) AREAS SHOULD
*BE SET FLUSH TO THE GRADE. THIS MAY APPLY TO MH 14 AND 16.
39. THE OWNER MUST ENTER INTO A COUNTY CONTRACT PRIOR TO THE
START OF CONSTRUCTION. PLEASE SEND ME A COPY OF THE "ACCEP
TED" BID PROPOSAL BETWEEN THE DEVELOPER AND THE CONTRACTOR S
O WE MAY PREPARE THE COUNTY CONTRACT. THE BID PROPOSAL MUST
BE BASED ON THE LATEST REVISED UTILITIES PLANS REFLECTING T
HE REVIEWER'S STAMP,
WORK MUST BE PERFORMED BY AN ACCEPTABLE UTILITIES CONTRACTOR
. IF PLANS ARE REVISED AFTER CONTRACT
PREPARATION DUE TO A CHANGE BECAUSE OF VIRGINIA DEPARTMENT O
F TRANSPORTATION'S AND/OR ENVIRONMENTAL ENGINEERING DEPARTME
NT'S APPROVAL OF THE ROAD, DRAINAGE, AND EROSION CONTROL DES
IGN OR BECAUSE OF STATE AGENCIES' REVIEW AND APPROVAL OF THE
UTILITIES DESIGN, A REVISED BID PROPOSAL MAY BE NECESSARY T
O ACCURATELY REFLECT THE LATEST UTILITIES DESIGN AND A NEW C
ONTRACT PREPARATION MAY BE NECESSARY AND EXECUTED PRIOR TO T
HE START OF CONSTRUCTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: THE LANDINGS AT MEADOWVILLE, SECTION 1
CASE NUMBER: 18CP0021
LATEST PLAN DATE: 08/25/2017
DEPT. REC'D. DATE: 09/20/2017
SUBMITTAL NUMBER: ONE
REVIEW DATE: 10/12/2017
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
.
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: BRAD MORRISON / 717-6143
PLAN NAME: THE LANDINGS AT MEADOWVILLE SEC. 1
PLAN NUMBER : 18CP0021
ORIGINAL PLAN DATE: 8/25/17
REVISION DATE:
LATEST SUBMISSION DATE: 9/18/17
REVIEW DATE: 10/11/17
SUBMITTAL NUMBER : 1
STATUS: REVISIONS REQUIRED
TABLE REVIEW: YES
.
1. THE VEGETATED/FORESTED BUFFER ADJACENT MOUNT BLANCO ON
THE JAMES PER ZONING CASE 17SN0501 MUST BE DEMONSTRATED
ON CONSTRUCTION PLAN & PRESERVED AND MARKED BY TREE
PROTECTION TAPE.
.
2. THE CORRECT FRONT BUILDING SETBACK FOR LOTS FRONTING ON
NORTH ENON CHURCH ROAD.
.
3. LABEL CROSSWALK CURB RAMPS.
.
4. CEMETERY ON LOT 46 MUST BE INCLUDED IN THE ACCESS
EASEMENT.
.
5. CEMETERY ON OPEN SPACE ADJACENT LOTS 77/78 MUST BE
INCLUDED IN ACCESS EASEMENT.
.
6. SHOW FRONT SETBACK ON LOTS WHERE LOT WIDTH IS NOT MET
AT ROAD FRONTAGE. INCLUDE LOT 21.
.
NOTES:
.
A) REFERENCES TO FUTURE DEVELOPMENT ARE NOT PERMITTED ON
FINAL CHECK AND RECORD PLAT.
B) STANDARD CONDITIONS PER 17-62 OF SUBDIVISION
ORDINANCE APPLY.
C) ANY BULK REQUIREMENTS (LOT AREA, LOT WIDTH,
SETBACKS, BUILDING ENVELOPES, ETC.) SHOWN ON
THE APPROVED CONSTRUCTION PLANS WILL BE SUBJECT
TO REVIEW FOR COMPLIANCE AT TIME OF FINAL CHECK.
REVIEW DEPARTMENT: FIRE DEPARTMENT
REVIEWER/PHONE#: KIM LESTER
EMAIL: LESTERK@CHESTERFIELD.GOV
NAME OF PLAN: MEADOWVILLE LANDING SECTION 1
PLAN NUMBER:18CP0021
LATEST PLAN DATE: 8/25/17
DEPT. REC'D. DATE: 9/25/17
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 10/16/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: YES
.
RELOCATE THE HYDRANT AT THE INTERSECTION OF
WINBOLT DRIVE AND ALMER COURT TO THE
PROPERTY LINE OF LOT 16 AND 17.
.
RELOCATE THE HYDRANT AT THE PROPERTY LINE OF
OF LOT 20 AND 21 TO THE PROPERTY LINE OF LOT
18 AND 19 ON ALMER COURT.
.
ADD A HYDRANT AT THE PROPERTY LINE OF LOT 23
AND 24 ON ALMER COURT.
.
ADD A HYDRANT AT THE PROPERTY LINE OF LOT 56
AND 57 ON NORTH ENON CHURCH ROAD.
.
ADJUST THE NEW LOCATIONS OF THE HYDRANTS ON THE WATER
TEST RESULTS.
.
REVISED THE WATER FLOW TEST TO SHOW THE NEW LOCATIONS
OF THE HYDRANTS AND THE TWO ADDITIONAL HYDRANTS.
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
============================================================
============================================================
.
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : MARIA JENKINS/751-2335
NAME OF PLAN : THE LANDING AT MEADOWVILLE SECTION 1
SITE PLAN NO. : 18CP0021
LATEST PLAN DATE : 08/25/17
DEPT. REC'D DATE : 09/18/17
SUBMITTAL NUMBER : 1
REVIEW DATE : 10/16/16
RECOMMENDATION : REVISIONS REQUIRED
TABLE REVISION : NO
PLAT PROCESSING : NO
.
1. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND/OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR STATE
PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURES INCLUDING
BUT NOT LIMITED TO WETLANDS, SURFACE WATERS (E.G. VSMP
PERMIT FOR CONSTRUCTION SITES, GROUND WATER AND AIR
QUALITY) FINAL APPROVAL OF THESE PLANS WILL NOT RELIEVE YOU
OF YOUR RESPONSIBILITY. WETLANDS DOCUMENTATION MUST BE
RECEIVED BY THIS DEPARTMENT PRIOR TO ISSUANCE OF THE LAND
DISTURBANCE PERMIT.
.
2. THIS OFFICE RECOGNIZES THAT THE 10-YEAR PRE/10-YEAR POST
REQUIREMENTS FOR FLOOD PROTECTION MAY BE ADDRESSED BY
DISCHARGING INTO THE 100-YEAR FLOODPLAIN.
.
=== EROSION CONTROL ===
.
1. AN ITEMIZED EROSION CONTROL COST ESTIMATE MUST BE
SUBMITED FOR REVIEW AND/OR APPROVAL.
.
2. AS A PREREQUISITE TO THE ISSUANCE OF A LAND
DISTURBANCE PERMIT:
.
A) A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO
CAROLE CLIBORNE OF THE ENVIRONMENTAL ENGINEERING. THE
AUTOCAD FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD
VERSION 2009 OR EARLIER AND REFERENCED DIRECTLY TO THE
VIRGINIA STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN
THE NAD83 DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A
CD, DVD, OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH
THE SUBDIVISION NAME AND SECTION, SUBDIVISION PLAN
NUMBER, ENGINEERING FIRM AND CAD FILE PREPARER'S NAME
AND PHONE NUMBER. THE FILE MUST CONTAIN THE FOLLOWING,
EACH CLEARLY LABELED IN SEPARATE LAYERS:
.
I. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
.
II. EDGES OF SIDEWALKS;
.
III. ALL STORM SEWER AND INLETS;
.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
.
B) FLAGGING AROUND USACOE JURISDICTIONAL WETLANDS,
BUFFERS, AND SENSITIVE AREAS MUST BE VISIBLE.
.
C) DOCUMENTATION FROM THE USACOE/DEQ MUST BE RECEIVED
VERIFYING COMPLIANCE TO WETLAND PERMIT REGULATIONS.
.
D) A COPY OF VDOT LAND USE PERMIT MUST BE RECEIVED.
.
E) AN EROSION CONTROL BOND MUST BE POSTED.
.
F) TWO ADDITIONAL SETS OF CONSTRUCTION PLANS TO BE
STAMPED "APPROVED FOR CONSTRUCTION" MUST BE RECEIVED AND
A 11" X 17" SET FOR THE SWPPP BOOKLET."
.
G) AS APPLICABLE, A SWPPP (3 RING BINDER) MUST BE
PROVIDED.
.
3. THESE ARE IN REGARDS TO THE MS-19:
.
A) PLEASE INCLUDE A SEPARATE SHEET DRAWN TO SCALE TO DEPICT
THE LIMITS OF DRAINAGE AREAS OF 4,325.12 ACRES AND THE
LIMITS OF THE PROJECT AREA AT THE CONCRETE CHANNEL/LEVEL
SPREADER. A NOTE IN BOLD PRINT SHOULD BE PROVIDED ON THIS
SHEET STATING, "THE MS-19 STR.124 AT THIS LOCATION HAS BEEN
ADDRESSED BY 1% RULE (PROJECT DRAINAGE AREAS= ____ AND TOTAL
DRAINAGE AREAS=4,325.12 ACRES). BE SURE TO SHOW/LABEL THE
EXISTING CONTOURS WITH ELEVATIONS, ETC.
.
B) PER COMMENT #28.F UNDER ROAD AND DRAINAGE, PLEASE PERFORM
MS-19 ANALYSIS ALONG THE EXISTING SWALE(S) AT TWO DIFFERENT
LOCATIONS ONE NEAR LOTS 7/67 AND THE SECOND POINT OF
ANALYSIS NEAR LOTS 4/61.
.
SUBMIT 2/10-YEAR HYDROLOGIC/HYDRAULIC DITCH CALCULATIONS
WITH SCALED X-SECTIONS, SHOW/LABEL THE MS-19 SECTIONS-
LOCATIONS, AND THE MS-19 TABLE TO INCLUDE THESE LOCATIONS.
.
IN ADDITION, PLEASE PERFORM MS-19 ANALYSIS AT THE EXISTING
24" RPC USING THE 10-YEAR STORM SEWER/HGL CALCULATIONS TO
VERIFY IT IS ADEQUATE. SHOW/LABEL THE MS-19 SECTION-LOCATION
ON THE PLANS AND UPDATE THE MS-19 TABLE TO INCLUDE THIS
LOCATION.
.
C) PLEASE PERFORM MS-19 ANALYSIS AT THE EXISTING 24" RCP
PIPE LOCATED TO INTERCEPT THE FLOW FROM THE ROADSIDE DITCH
ON ENON CHURCH ROAD. INCLUDE 10-YEAR STORM ANALYSIS,
SHOW/LABEL THE MS-19 SECTION-LOCATION ON THE PLANS AND
UPDATE THE MS-19 TABLE TO INCLUDE THIS LOCATION.
.
BE SURE TO INCLUDE THE INCREMENTAL DRAINAGE AREAS PERTINENT
TO THE LEFT ROADSIDE DITCH ON ENON CHURCH ROAD. SINCE THERE
APPEAR TO BE A CULVERT IN THE PROXIMITY OF STATION 10+50.
.
4. WE OFFER, BUT NOT LIMITED TO, THE FOLLOWING COMMENTS:
.
A) PLEASE REVISE THE TEMPORARY SEDIMENT TRAP DETAIL (SHEET
C-19) TO SPECIFY 1:1 OR FLATTER TO THE SIDE SLOPE
OF THE EXCAVATED WET VOLUME.
.
B) PLEASE BE SURE TO PROVIDE TURBIDITY CURTAIN AT THE
OUTFALL PIPES EXISTING STR'S 59/69/24" RCP PIPES LOCATED AT
THE EXISTING POND E. INCLUDE A DETAIL OF THE TURBIDITY
CURTAIN ON THE PLANS AND REFLECT THE CHANGES ON THE EC PHASE
I/II PLANS.
.
C) PLEASE PROVIDE SUPER SILT FENCE ALONG THE DOWNSTREAM SIDE
PRIOR TO THE INSTALLATION OF THE SANITARY SEWER MH-16 THRU
19, ETC. REFLECT THE CHANGES ON THE EC PHASE II PLANS.
D) PLEASE PROVIDE SUPER SILT FENCE TO BE LOCATED ALONG THE
NORTHERN AND SOUTHERN SIDE PRIOR TO THE REMOVAL OF THE
EXISTING PAVED ROAD AND THE INSTALLATION OF THE STORM SEWER
STR'S 39 THRU 43, ETC. REFLECT THE CHANGES ON THE EC PHASE I
AND PHASE II.
.
IN ADDITION, SHOW SOME TYPE OF PATTERN TO INDICATE THE
REMOVAL OF THE EXISTING PAVED DRIVEWAY IN THE VICINITY OF
LOTS 14/15/4950/51/54/55/ETC. REFLECT THE CHANGES THE EC
PHASE I.
.
FURTHERMORE, PROVIDE A NOTE IN THE SEQUENCE CONSTRUCTION
NARRATIVE FOR THE REMOVAL OF THE EXISTING DOUBLE 15" RCP AND
SINGLE 15" RCP PIPE LOCATED ALONG THIS EXISTING PAVED DRIVE.
ADDITIONALLY, PROVIDE A LABELING "TO BE REMOVED" ON THE PLAN
VIEW.
.
BE SURE TO PROVIDE RIPRAP AFTER THE REMOVAL OF THE EXISTING
SINGLE 15" RCP AND GRADING TO ENSURE PERMANENT
STABILIZATION. REFLECT THE CHANGES ON THE PHASE I/PHASE II.
.
E) SUPER SILT FENCE SHOULD BE PROVIDED ALONG THE DOWNSTREAM
SIDE OF THE INSTALLATION OF THE STORM SEWER STR'S 43 THRU
46. REFLECT THE CHANGE ON THE EC PHASE I/II PLANS.
.
F) PLEASE PROVIDE SILT FENCE TO BE LOCATED ALONG THE
DOWNSTREAM SIDE ON THE SANITARY SEWER STRUCTURES MH-21, ETC.
REFLECT THE CHANGES ON THE EC PHASE II PLANS.
.
G) PLEASE PROVIDE INLET PROTECTION AT THE EXISTING STR'S
70/72 LOCATED IN THE PROXIMITY OF LOTS 49/52/53. IN
ADDITION, LABEL THESE STR'S ACCORDINGLY ON THE PLAN VIEWS.
REFLECT THE CHANGES ON THE EC PHASE I/PHASE II PLANS.
.
H) PLEASE PROVIDE A DIVERSION DIKE IN THE PROXIMITY OF
STATION 11+60 ON ENON CHURCH ROAD TO DIRECT DRAINAGE TO ST-
1. REFLECT THE CHANGES ON THE EC PHASE I/PHASE II PLANS.
.
I) PLEASE PROVIDE A SMALL SEDIMENT TRAP TO INTERCEPT
SEDIMENT FROM THE ROAD CONSTRUCTION IN THE PROXIMITY OF
STATION 10+50 ON THE RIGHT SIDE OF WINBOLT DRIVE.
.
INCLUDE DRAINAGE AREAS INTERCEPTED BY THIS TRAP AND
DIMENSIONS OF THIS TRAP ON THE PLANS. REFLECT THE CHANGES ON
THE EC PHASE I/PHASE II PLANS.
.
IN ADDITION, A RIGHT-OF-WAY DIVERSION SHOULD BE SPECIFIED IN
THE PROXIMITY OF STATION 10+50 TO DIRECT SEDIMENT FROM THE
ROAD CONSTRUCTION ON WINBOLT DRIVE.
.
J) A SEDIMENT TRAP SHOULD BE PROVIDED IN THE PROXIMITY OF
STATION 13+00 ON THE RIGHT SIDE OF ALMER LANE. INCLUDE
DRAINAGE AREAS AND DIMENSIONS OF THIS TRAP. REFLECT THE
CHANGES ON THE EC PHASE I/PHASE II.
.
IN ADDITION, PROVIDE DIVERSION DIKE IN THE PROXIMITY OF
STATION 10+00 TO APPROXIMATE STATION 12+50 ON THE RIGHT SIDE
OF ALMER LANE OR UNTIL IT REACHES THE SEDIMENT TRAP REQUEST
IN THE PREVIOUS PARAGRAPH.
.
K) PLEASE REMOVE ITEM #3 UNDER NOTES SHOWN ON SHEETS C-10
THRU C-17. REVISE ACCORDINGLY.
.
L) PLEASE PROVIDE TENTATIVE CONDITION #9 ON THE EC PLANS,
WHICH STATES, "ENVIRONMENTAL ENGINEERING MAY IMPOSE MORE
RIGOROUS EROSION AND SEDIMENT CONTROL MEASURES THAN THAT
WHICH IS PROVIDED BY THE MINIMUM STANDARDS FOUND IN THE
VIRGINIA EROSION AND SEDIMENT CONTROL HANDBOOK."
.
4. IF TIMBERING IS REQUIRED ON THE PROJECT, IT SHOULD BE
INCORPORATED INTO THE EROSION CONTROL PLAN / NARRATIVE AND
SHOULD NOT BEGIN UNTIL AFTER THE ISSUANCE OF A LAND
DISTURBANCE PERMIT AND THE INSTALLATION OF THE APPROVED
EROSION CONTROL DEVICES.
.
======= CBPA =======
.
1. THESE ARE IN REGARDS TO THE PLAN VIEW CBPA PLAN (SHEET
C-35):
.
A) PLEASE CLEARLY SHOW/LABEL THE LIMITS OF DRAINAGE AREAS
WITH ACREAGE FOR EACH POND.
.
BASED ON THIS PROPOSED SECTION, THE OFFSITE DRAINAGE AREAS
TO POND E HAVE BEEN CHANGED TO APPROXIMATELY 7.49 ACRES.
REVISE ACCORDINGLY AND REVISE THE NOTES ON THE PLAN VIEW TO
CLEARLY LABEL THE ACREAGE/OFFSITE AREAS DRAINING TO POND E
AND TO THE JAMES.
.
B) CLEARLY SHOW/LABEL THE EXISTING/PROPOSED CONTOURS WITH
ELEVATIONS. BE SURE THE ELEVATIONS ARE LEGIBLE.
.
2. THESE ARE IN REGARDS TO WORKSHEET A CALCULATIONS:
.
A) PLEASE REVISE STEP 2 TO PROVIDE A LABELING FOR THE 66.97
ACRES AS "MEADOWVILLE SECTIONS 1 AND 2".
.
B) BASED ON AN IN-HOUSE CHECK THE AVERAGE RESIDENTIAL LOTS
LAND USE APPEARS TO BE 0.64 ACRES AND THEREFORE BASED ON
TABLE 2 THE % IMPERVIOUS TO BE 19%. CONSEQUENTLY, THE LPOST
APPEARS TO BE 34.82 LBS/YR AND THE REMOVAL REQUIREMENTS TO
BE 4.68 LBS/YR. PLEASE SEE THE ENCLOSED COPY FOR
CLARIFICATION AND REVISE ACCORDINGLY.
.
C) PLEASE REVISE THE DRAINAGE AREAS FOR THE OFFSITE-POND E
IN STEP 4, WHICH APPEARS TO BE AROUND 7.49 ACRES WITH
%IMPERVIOUS OF 20% USING THE AVERAGE RESIDENTIAL LOTS LAND
USE AND TABLE 2.
.
THEREFORE, REVISE THE POLLUTANT REMOVAL FOR THE TOTAL
DRAINAGE AREAS AND THE LOAD REMOVE FOR BMP DESIGN 7.
.
3. PLEASE REVISE THE LOAD REMOVE, TOTAL DRAINAGE AREAS FOR
BMP AND THE TOTAL LOAD REMOVE IN THE CBPA/MS-4 TABLE TO
REFLECT THE REVISED DATA.
.
4. PLEASE EITHER LABEL THE RPA SYMBOL AS "RPA SIGN (TYP)
SHOWN ON LOT 45(SHEET C-24) OR PROVIDE A LEGEND. REVISE
ACCORDINGLY.
.
5. PLEASE REPLACE THE RPA RESTORATION PLAN TABLE (SHEET C-
4) WITH THE ENCLOSED RPA ESTABLISHMENT PLAN LAST REVISED
12/04/14.
.
======= ROAD AND DRAINAGE =======
.
1. DUE TO THE ABSENCE OF CENTERLINE STAKING AND HEAVY
VEGETATION, OUR CONCERNS ARE BASED ON THE INFORMATION SHOWN
IN THE CONSTRUCTION PLANS. THE RESPONSIBILITY FOR
IDENTIFYING CRITICAL AREAS IS PLACED ON THE PROFESSIONAL
ENGINEER WHO SEALS THE CONSTRUCTION PLANS APPROVED. WE
RESERVE THE RIGHT TO INSPECT CONVEYANCE SYSTEMS PRIOR TO
PLAT RECORDATION AND/OR STATE ACCEPTANCE TO DETERMINE IF
ADDITIONAL IMPROVEMENTS ARE REQUIRED.
.
2. PLEASE BE SURE TO LABEL THE ADJACENT PROPERTY OWNERS'
NAME WITH PERTINENT GPIN NUMBERS ON THE PLANS (I.E. LOTS 5
THRU 16 OF MOUNT BLANCO SECTION 2 AND LOTS 59 THRU 62/67
THRU 70 OF MOUNT BLANCO SECTION 3). REVISE ACCORDINGLY.
.
3. THE ADJACENT PROPERTY OWNERS SHOULD BE NOTIFIED OF THE
IMPEDING CONSTRUCTION ACTIVITY NEAR THEIR PROPERTIES. THE
NOTIFICATION SHOULD BE VIA U.S. POSTAL CERTIFIED MAIL,
SIGNED RETURN RECEIVED REQUEST. THIS CONCERN MUST BE
ADDRESSED PRIOR TO PLAN APPROVAL PER TENTATIVE CONDITION
#8. INCLUDE AN 8½ X 11 COPY OF THE PROPOSED CONSTRUCTION
ACTIVITY ADJACENT TO THEIR PROPERTIES.
.
- VAUGHAN, M. AT 12036 ROTUNDA LANE,
- BACON, C. AT 12037 ROTUNDA LANE,
- SCALORA, M. AT 12206 DECLARATION AVENUE,
- STEELE, M. AT 12043 WINBOLT DRIVE,
- MEREUS, R. AT 12115 WINBOLT COURT,
- HATCHER, C. AT 12109 WINBOLT COURT,
- SPRATLEY, A. AT 12103 WINBOLT COURT,
- HUBBARD, J. AT 12102 WINBOLT COURT,
- WINBUSH, D. AT 1613 ONORA LANE,
- KENNEY, A. AT 1619 ONORA LANE,
- NVR INC. AT 1625 ONORA LANE,
- AJALA, O. AT 1631 ONORA LANE,
- MADISON, M. AT 12142 ALMER LANE,
- PERSON, N. AT 11701 ENON CHURCH ROAD,
- ETC.
.
4. PLEASE PROVIDE THE TENTATIVE APPROVAL DATE ON THE COVER
SHEET (SHEET C-1) OF 09/26/17.
.
5. PLEASE PROVIDE THE LATITUDE AND LONGITUDE IN DECIMAL
DEGREE OF THE APPROXIMATE LOCATION OF THIS PROJECT ON THE
COVER SHEET (SHEET C-1).
.
6. PLEASE PROVIDE THE STATE ROUTE NUMBER FOR ALL EXISTING
ROADS (I.E. WINBOLT DRIVE, ONORA LANE, ALMER LANE, ETC.)
THAT HAVE BEEN ACCEPTED INTO THE STATE SYSTEM.
.
7. PROVIDE A NOTE ON THE COVER SHEET (C-1) STATING, "THIS
PROPERTY IS LOCATED WITHIN FEMA ZONE X ON PANEL 352 DATED
12/18/12."
.
8. BASED ON A FIELD INSPECTION, PLEASE FIELD LOCATE THE
EXISTING FENCE ON 1619 ONORA LANE WITH PERTINENT INFORMATION
OF THIS FENCE (I.E. HIGH, MATERIAL, ETC.). IF THE FENCE IS
WITHIN THE 16' DRAINAGE EASEMENT, IT SHOULD BE RELOCATED TO
BE OUTSIDE OF THIS EASEMENT. PROVIDE NOTES AND MEASURES TO
ADDRESS THIS CONCERN ON THE PLANS.
.
IN ADDITION, PLEASE FIELD LOCATE THE TWO ROWS OF EXISTING
EVERGREEN TREES PLANTED ALONG THE REAR OF LOTS 1 THRU 9.
REFLECT THE CHANGES ON ALL APPLICABLE SHEETS.
.
ADDITIONALLY, PLEASE FIELD LOCATE THE EXISTING SWALE(S) THAT
CROSS MULTIPLE LOTS. THEY ARE ENCUMBERING BETWEEN LOTS 59 -
69 OF MOUNT BLANCO SECTION 3 AND LOTS 1 - 9 OF THE LANDING
AT MEADOWVILLE SECTION 1. BE SURE TO CLEARLY SHOW THE
EXISTING CONTOURS WITH ELEVATIONS.
.
9. THERE APPEARS TO BE A DISCREPANCY ON THE CONTOURED
GRADING SHOWN ON LOT 46 WHEN COMPARING WITH THE SIDE
INSPECTION. ON THE FIELD INDICATED THAT THERE IS A FLAT FILL
AREA PRIOR TO REACHING THE LIMITS OF THE 100-YEAR FEMA
FLOODPLAIN AND THEN IT STARTS TO SLOPE DOWN BELOW THE LIMITS
OF THE 100-YEAR FLOODPLAIN. ON THE PLANS SHOWN THAT THERE IS
AN AREA WITH STEEP SLOPE PRIOR TO REACHING THE 100-YEAR FEMA
FLOODPLAIN. PLEASE CLARIFY OR REVISE ACCORDINGLY.
.
IN ADDITION, NO-RISE CERTIFICATE MUST BE SUBMITTED TO THIS
OFFICE FOR APPROVAL AND DOCUMENTATION. SINCE THE FILL
GRADING APPEAR TO ENCROACH INTO THE 100-YEAR FEMA
FLOODPLAIN.
.
10. PLEASE INDICATE WITH ARROWS THE DIRECTION OF FLOW ALONG
THE NATURAL DRAINAGEWAY/WETLANDS, JAMES RIVER, ETC. REFLECT
THE CHANGES ON ALL APPLICABLE SHEETS.
.
11. PLEASE SPECIFY CG-9 DRIVEWAY ENTRANCE TO ALL PROPOSED
LOTS AND BE SURE TO SHOW THE APPROXIMATE LOCATION ON THE
PLAN VIEWS. IN ADDITION, INCLUDE CG-9 DRIVEWAY ENTRANCE
DETAIL ON THE PLANS.
.
12. CG-9 DRIVEWAY ENTRANCE SHOULD BE SPECIFIED TO ACCESS THE
EXISTING DRIVEWAY LOCATED ON LOTS 45/46. PLEASE ADDRESS
.
IN ADDITION, PLEASE CLARIFY IF THERE IS AN EXISTING
INGRESS/EGRESS EASEMENT ENCLOSING THE EXISTING DRIVEWAY
LOCATED ON LOTS 45/46. PROVIDE THE APPLICABLE NOTES TO
ADDRESS THIS CONCERN ON THE PLAN AND REFLECT THE CHANGES ON
ALL APPLICABLE SHEETS.
.
13. A NOTE IN BOLD PRINT SHOULD BE PROVIDED ON THE PLANS TO
RESTORE A PORTION OF THE EXISTING GRAVEL DRIVEWAY AFTER THE
INSTALLATION OF THE STORM SEWER STR'S 32/111/110/115/117
THRU 121/ETC., STATING, RESTORE A PORTION OF THE GRAVEL
DRIVEWAY ONCE THE STORM SEWER STR'S ARE INSTALLED."
.
IN ADDITION, A LICENSED AGREEMENT IS REQUIRED FOR THE
PORTION OF THE GRAVEL DRIVEWAY LOCATED WITHIN THE 16'
DRAINAGE EASEMENT. THIS LICENSED AGREEMENT SHOULD CONCUR
WITH THE SUBDIVISION PLAT RECORDATION. PLEASE PROVIDE A NOTE
ON THE PLANS TO ADDRESS THIS CONCERN.
.
14. PLEASE IDENTIFY THE EXISTING EASEMENT LOCATED ON LOT 46
(SHEET C-24) AND PROVIDE APPLICABLE NOTES FOR THE VACATION
OF THIS EASEMENT.
.
15. PLEASE PROVIDE A NOTE IN BOLD PRINT FOR ALL PROPOSED
DITCHES IN COUNTY EASEMENT STATING, "IF UNABLE TO ACHIEVE
SUITABLE STAND OF GRASS VEGETATION, EE MAY REQUIRE THE DITCH
TO BE PAVED (I.E. PG-2A, ETC.)". REFLECT THIS NOTE ON ALL
APPLICABLE SHEETS.
.
16. THESE ARE IN REGARDS TO THE PROPOSED CONCRETE DITCH
LOCATED DOWNSTREAM OF STR. 125:
.
A) PLEASE PROVIDE DITCH TRANSITION FROM THE OUTFALL STR. 125
TO THE TRAPEZOIDAL CONCRETE DITCH. INCLUDE ENLARGED DETAIL
DRAWN TO SCALE WITH APPLICABLE NOTES AND DIMENSIONS ON THE
PLANS.
.
B) PLEASE REVISE LEVEL SPREADER PLAN VIEW DETAIL (SHEET C-
28) TO DEPICT THE TRAPEZOIDAL CONCRETE DITCH AS OPPOSED TO
THE 48" RCP/HEADWALL. REVISE ACCORDINGLY.
.
C) PLEASE SUBMIT 10/100-YEAR YEAR DITCH CALCULATIONS FOR
FURTHER REVIEW AND/OR APPROVAL.
.
D) BASED ON THE 27 - 123 STORM PROFILE, THE PROPOSED
CONCRETE DITCH DOES NOT APPEAR TO HAVE 1.50' CONTAINMENT.
PLEASE ADDRESS.
.
IF A BERM IS REQUIRED ALONG THIS PROPOSED DITCH TO ENSURE
CONTAINMENT, PLEASE REFLECT THE PROPOSED FILL GRADING ON THE
PLAN VIEWS.
.
IN ADDITION, OFFSET RIGHT/LEFT EXISTING GROUND/TOP OF DITCH
OFF THE CENTERLINE OF THIS DITCH SHOULD BE SHOWN ON PROFILE
VIEW TO VERIFY CONTAINMENT. A FURTHER DISCUSSION IS
RECOMMENDED.
.
E) PLEASE RELOCATE THE CONCRETE DITCH DETAIL (SHEET C-5) TO
BE SHOWN WITH THE PROFILE OF THIS DITCH ON SHEET C-32.
.
F) PLEASE REVISE 27-123 STORM PROFILE (SHEET C-32) TO DEPICT
THE LIMITS OF THE RPA, 100-YEAR FEMA FLOODPLAIN, ETC.
.
G) REVISE THE OUTFALL DITCH DETAIL (SHEET C-5) TO REFERENCE
PG-5. REVISE ACCORDINGLY.
.
H) PLEASE REVISE THE LABELING OF "SEE OUTFALL DITCH DETAIL"
SHOWN ON PLAN VIEW (SHEET C-24) TO REFERENCE SHEET C-32.
.
I) PLEASE PROVIDE THE EW-2 DETAIL ON THE PLANS.
.
17. IT APPEARS THE STORM SEWER STR'S 101/103 WITH PERTINENT
INFORMATION ARE CURRENTLY MISSING FROM THE STORM SUMMARY
TABLE (SHEET C-21). PLEASE ADDRESS.
.
18. A PROFILE OF THE STORM SEWER STRUCTURES 101/103 WITH
PERTINENT INFORMATION SHOULD BE PROVIDED ON THE PLANS.
.
ADDITIONALLY, PROVIDE A NOTE ON THE PLANS AND PROFILE HOW
THE DROP INLETS STR'S 101/103 WOULD BE INSTALLED INTO THE
INTO THE EXISTING PIPE 30" RCP.
.
FURTHERMORE, SUBMIT 10/100-YEAR STORM SEWER/HGL CALCULATIONS
FOR FURTHER REVIEW AND/OR APPROVAL.
.
19. THESE ARE IN REGARDS TO THE 100-YEAR FLOODPLAIN:
.
A) PERFORM 100-YEAR FLOODPLAIN ANALYSIS WITHIN THE
WETLANDS/DRAINAGEWAY TO VERIFY IF THEY ARE CONTAINED OR
OUTSIDE THE WETLAND AREA. THE ANALYSIS OF THE 100-YEAR
FLOODPLAIN SHOULD BE IN THE PROXIMITY OF LOTS 22/57, 15/49,
16, 20/21, 23/59, ETC. INCLUDE SUPPORT HYDROLOGIC/HYDRAULIC
CALCULATIONS WITH SCALED X-SECTIONS, SHOW/LABEL THE 100-YEAR
FLOODPLAIN SECTIONS-LOCATIONS ON THE PLANS, ETC. BE SURE TO
USE THE ULTIMATE DEVELOPED FOR THE OFFSITE AREAS.
.
IF THE 100-YEAR FLOODPLAIN LIMITS ARE OUTSIDE THE WETLAND
AREA, MFF'S TO BE ABOVE 1' THE 100-YEAR FLOODPLAIN SHOULD BE
SPECIFIED ON THE AFFECTED LOTS.
.
20. PLEASE CALCULATE THE 100-YEAR BACKWATER TO THE EXISTING
24" PIPE LOCATED ON LOT 11 OF MOUNT BLANCO SECTION 2.
INCLUDE SUPPORT CALCULATIONS, AND SHOW/LABEL THE 100-YEAR
BACKWATER LIMITS/ELEVATION IF THEY ARE OUTSIDE THE WETLAND
LIMITS.
.
IN ADDITION, AS APPLICABLE SPECIFY MFF TO BE 1' ABOVE THE
100-YEAR BACKWATER ELEVATION ON LOTS 15 AND 49.
.
21. PLEASE PROVIDE A LEGEND FOR THE WETLANDS THAT ARE GOING
TO REMAIN UNDISTURBED AND FOR THE WETLANDS THAT ARE GOING TO
BE IMPACTED. REFLECT THE CHANGES ON ALL APPLICABLE SHEETS.
.
22. PLEASE REVISE THE LABELING OF THE EASEMENT THAT IS
ENCLOSING STR'S 27 THRU 29 TO BE "VARIABLE WIDTH DRAINAGE
EASEMENT FOR VDOT MAINTENANCE." REFLECT THE CHANGES ON ALL
APPLICABLE SHEETS.
.
23. SIMILARLY, REVISE THE LABELING OF THE EASEMENT THAT IS
ENCLOSING STR'S 9 THRU 11, 53 THRU 55, ETC. TO BE "16'
DRAINAGE EASEMENT FOR VDOT MAINTENANCE." REFLECT THE CHANGES
ON ALL APPLICABLE SHEETS.
.
24. PLEASE BE SURE TO INCLUDE STR'S 49/50 IN THE STORM
SUMMARY TABLE (SHEET C-21). IN ADDITION, BE SURE TO SPECIFY
DI-6 WITH MINIMUM 2' CONCRETE GUTTER AT STR. 49 AND PROVIDE
THE SLOT OPENING LOCATION IN THE STORM SUMMARY TABLE.
.
ADDITIONALLY, ENCLOSE THESE STR'S 49/50 IN A 16' DRAINAGE
EASEMENT.
.
25. THESE ARE IN REGARDS TO STR. 39:
.
A) PLEASE SPECIFY HEADWALL AT STR. 39 FOR PIPES 30" OR
LARGER. REFLECT THE CHANGES ON ALL APPLICABLE SHEETS.
.
B) EC-1 RIPRAP SHOULD BE SPECIFIED AT THE BEGINNING OF THE
STORM SEWER STR. 39. INCLUDE DIMENSIONS OF THE RIPRAP (I.E.
WIDTH, LENGTH WITH 24" THICK LAYER OF RIPRAP OVER FILTER
FABRIC). REFLECT THE CHANGES ON THE PLANS AND PROFILES.
.
C) PLEASE SUBMIT 100-YEAR BACKWATER CALCULATIONS AT STR. 39
FOR FURTHER REVIEW AND DOCUMENTATION. IF THE 100-YEAR
BACKWATER LIMITS ARE OUTSIDE THE WETLANDS, THEN THE LIMITS
OF THE 100-YEAR BACKWATER/ELEVATIONS MUST BE SHOWN ON THE
PLANS AND MMF SHOULD BE SPECIFIED ON THE AFFECTED LOTS.
.
26. PLEASE BE SURE TO SPECIFY DI-6 WITH MINIMUM 2' CONCRETE
GUTTER AS OPPOSED TO DI-7 TYPE III FOR ALL STR'S IN COUNTY
EASEMENT(S) (I.E. STR'S 1/3/5/37/65/ETC.). IN ADDITION,
SPECIFY THE SLOT OPENING LOCATION (I.E. N, E, W, S) AND
PROVIDE A DETAIL OF THE DI-6 WITH MINIMUM 2' CONCRETE GUTTER
ON THE PLANS.
.
27. PLEASE PROVIDE SOME TYPE OF PATTERN FOR THE REMOVAL THE
EXISTING DRIVEWAY LOCATED IN THE PROXIMITY OF LOTS
15/16/49/50/54/55/ETC. AND BE SURE TO DENOTE IT IN THE
LEGEND. REFLECT THE CHANGES ON THE EC PHASE I, ROAD PLANS
AND GRADING PLANS.
.
28. THESE ARE IN REGARDS TO THE GRADING PLANS (SHEET C-25
THRU C-28):
.
A) PLEASE ANNOTATE THE EXISTING PIPES THAT ARE GOING TO BE
REMOVED ON THIS SHEET TO BE CONSISTENT THROUGHOUT THE PLAN
SET.
.
B) PLEASE SHOW THE PROPOSED GRADING TO ENSURE DAYLIGHT AT
THE PROPOSED STR. 39. REFLECT THE CHANGES ON THE PLANS AND
PROFILES.
.
C) IT APPEARS THE 1% GRADIENT FROM THE LOWEST AND/OR MOST
REMOTE POINT WITHIN THE LOT TO AN ADEQUATE RECEIVING OUTFALL
HAS NOT BEEN ACHIEVED ON NUMEROUS LOTS (I.E. LOTS 1 THRU 16,
18 THRU 44, 49 THRU 60, ETC.). REFER TO TENTATIVE CONDITIONS
#2, #7A, 7.B, ETC. ONLY LOTS 17, 45, AND 46 APPEAR TO
ADDRESS TENTATIVE CONDITION #7.
.
IN ADDITION, THE SURFACE GRADING ON ALL PROPOSED LOTS MUST
FUNCTION INDEPENDENTLY THAT IS ACHIEVED BY PROVIDING GRASS
SWALES BETWEEN LOTS. REFER TO TENTATIVE CONDITION #7.C. A
FURTHER DISCUSSION IS RECOMMENDED.
.
GRASS SWALES WOULD REQUIRE SERVING AS SURFACE RELIEF DUE TO
THE FLAT TOPOGRAPHY POORLY DRAIN (I.E. BETWEEN LOTS 4/5,
5/6, 6/7, 10/11, 11/12, 18/19, 21/22, 22/23, 24/25, 25/26,
26/27, 27/28, 28/29, 29/30, 30/31, 31/32, 34/35, 35/36,
36/37, 37/38, 38/39, 39/40, 41/42, 42/43, 43/44, 49/50,
51/52, 53/54, 54/55, 55/56, 56/57, 57/58, 58/59/ 59/60,
ETC.).
.
ON OTHER SITUATION GRASS SWALES WOULD REQUIRE ADDRESSING THE
CROSS LOT DRAINAGE (I.E. BETWEEN LOTS 3/4, ETC.).
.
D) THE LOTS THAT HAVE WETLANDS SHOULD HAVE MINIMUM 1' OF
FILL WITH 1% GRADIENT AND 3:1 TYING BACK TO THE EXISTING
GROUND AT THE LIMITS OF THE WETLANDS (I.E. LOTS 16, 19 THRU
24, 49 THRU 60, ETC.). PLEASE SEE THE ENCLOSED DETAILS. A
FURTHER DISCUSSION IS RECOMMENDED.
.
F) IT APPEARS THE OVERALL TOPOGRAPHY ON MOUNT BLANCO SECTION
3 WAS PROPOSED TO BE MASS GRADED. THESE AREAS IN THE
PROXIMITY OF LOTS 1 THRU 12 MUST BE FIELD SURVEY TO VERIFY
THE DRAINAGE PATTERNS AND/OR BREAKS.
.
IF THERE IS NOT A DITCH WITHIN THE EXISTING 16' DRAINAGE
EASEMENT LOCATED ON THE REAR OF LOTS 1 THRU 12, THEN A
PROPOSED DITCH SHOULD BE PROVIDED TO ADDRESS SURFACE
DRAINAGE GOING INTO THE EXISTING LOTS OF MOUNT BLANCO
SECTION 3.
.
G) PLEASE PROVIDE LOT FILLING AND GRADING ON LOTS 47/48 TO
ELIMINATE THE LOW AREA NEAR THE 81 CONTOUR-ELEVATION. IN
ADDITION, BE SURE THESE LOTS ARE GRADED TO CREATE POSITIVE
DRAINAGE.
.
IN ADDITION, ANNOTATE LOTS 47/48 WITH "NBP". REFLECT THE
CHANGES ON ALL APPLICABLE SHEETS.
.
H) THE PROPOSED LIMITS OF DISTURBANCE SHOWN ON SHEET C-14 DO
NOT PROVIDE A REASONABLE REAR YARD AREA NOR INSURE ADEQUATE
LOT DRAINAGE DUE TO THE EXTREMELY FLAT TOPOGRAPHY (I.E. LOTS
18 THRU 20, 49 THRU 52, 53 THRU 59, ETC.). A FURTHER
DISCUSSION IS RECOMMENDED.
.
29. PLEASE LABEL WITH STRUCTURE NUMBERS THE EXISTING STORM
SEWER LOCATED ON THE REAR OF LOTS 4/7 (I.E. EX 13, EX 15).
IN ADDITION, INCLUDE THE PERTINENT INFORMATION OF THIS STORM
SEWER ON THE PLANS (I.E. INVERTS, DIAMETER, ETC.).
.
30. PLEASE SPECIFY MFF'S TO BE 1' ABOVE THE 100-YEAR
FLOODPLAIN, ROAD SAG OR 100-YEAR BACKWATER, ETC. WHICHEVER
IS MOST RESTRICTIVE AT LOTS 53, 55, ETC. REFLECT THE CHANGES
ON ALL APPLICABLE SHEETS.
.
31. BASED ON THE ROTUNDA LANE ROAD PROFILE (SHEET C-30), IT
APPEARS THE ROAD WOULD BE SLIGHTLY ELEVATED. PLEASE PROVIDE
A GRASS SWALE ALONG THE PROPERTY LINE BETWEEN LOTS 50/51
STARTING NEAR THE LIMITS OF THE RIGHT-OF-WAY AND CONTINUE
THIS GRASS SWALE TO THE REAR PROPERTY LINE OF LOT 50 IN A
RADIUS TURN. DO NOT END THIS GRASS SWALE UNTIL IT REACHES
STR. 49.
.
PLEASE BE SURE TO SHOW SPOT ELEVATIONS OR PROPOSED GRADING
ALONG THE FLOW LINE OF THIS SWALE.
.
32. PLEASE BE SURE TO ANNOTATE WITH "NBP" TO THE LOTS WHERE
PROPOSED GRADING OR GRASS SWALES OR REMOVAL OF THE EXISTING
ROAD HAVE BEEN SPECIFIED (I.E. LOTS 1 THRU 10, 15, 16, 18
THRU 32, 35 THRU 38, 49 THRU 54, 56 THRU 60, ETC.).
.
33. THESE ARE IN REGARDS TO THE DRAINAGE AREAS PLAN SHEET
(SHEETS C-6 THRU C-9):
.
A) PLEASE SHOW THE ULTIMATE DRAINAGE AREAS/FUTURE STORM
SEWER WITH THE INCREMENTAL DRAINAGE AREAS/ETC. THAT WOULD
DRAIN OR BE CONNECTED TO THE STORM SEWER PROPOSED WITH THIS
SECTION TO VERIFY THAT IT IS DESIGNED FOR THE ULTIMATE
DEVELOPED. BE SURE TO LABEL THE STORM SEWER PROPOSED ON
SECTION 2 AS FUTURE.
.
B) A PARTIAL INSTALLATION OF THE STORM SEWER PIPE STR. 92
SHOULD BE INSTALLED WITH THIS SECTION WITH A TEMPORARY BLOCK
FOR THE FUTURE EXTENSION OF THIS PIPE. INCLUDE THE PERTINENT
INFORMATION OF THIS PIPE (I.E. LENGTH, INVERTS, TEMPORARY
CAP/MATERIALS, ETC.) ON THE PLAN VIEWS AND PROFILES.
.
IN ADDITION, PLEASE ENCLOSE THIS PIPE STR. 92 IN A VARIABLE
WITH DRAINAGE EASEMENT FOR VDOT MAINTENANCE AND EXTEND THIS
EASEMENT UNTIL IT REACHES THE REAR PROPERTY LINE ON LOT 44.
.
34. PLEASE SPECIFY THE FEMA ELEVATION ALONG THE LIMITS OF
THE 100-YEAR FEMA FLOODPLAIN, WHICH APPEARS TO BE
"ELEVATION= 17.00". REFLECT THE CHANGES ON ALL APPLICABLE
SHEETS.
.
IN ADDITION, BE SURE THAT THE LIMITS OF THE 100-YEAR FEMA
FLOODPLAIN ARE DELINEATED ALONG THE 17.00 CONTOUR-ELEVATION.
REFLECT THE CHANGES ON ALL APPLICABLE SHEETS.
.
ADDITIONALLY, PLEASE SPECIFY MINIMUM FINISH FLOOR (MFF) TO
BE 1' ABOVE THE 100-YEAR FEMA FLOODPLAIN ON LOTS 45 AND 46.
IN THIS CASE IT APPEARS TO BE MFF(FP)=18.00.
.
FURTHERMORE, ANNOTATE WITH ASTERISK LOTS 45/46 AND PROVIDE A
NOTE IN BOLD PRINT STATING, "LOTS 45, 46, ETC. ARE REQUIRED
FEMA ELEVATION CERTIFICATE PRIOR TO THE ISSUANCE OF
CERTIFICATE OF OCCUPANCY (CO)."
.
35. PLEASE PROVIDE DRAINAGE IMPROVEMENTS IN THE REAR OF LOTS
25 THRU 44 TO INTERCEPT SURFACE DRAINAGE FROM THE FUTURE
LOTS PERTINENT TO THE LANDING AT MEADOWVILLE SECTION 2 BY
PROVIDING A DITCH ON THE REAR OF THESE LOTS WITH A SERIES OF
DI-6'S/STORM SEWER TO CONVEY THIS RUNOFF TO THE STORM SEWER
PROPOSED ON THIS SECTION 1. A FURTHER DISCUSSION IS
RECOMMENDED.
.
BE SURE TO ENCLOSE THESE DRAINAGE IMPROVEMENTS IN A 16'
DRAINAGE EASEMENT. REFLECT THE CHANGES ON THE PLANS,
PROFILES, AND COMPUTATION SHEETS.
.
36. PLEASE PROVIDE A DI-6 WITH MINIMUM 2' CONCRETE GUTTER AS
OPPOSED TO MH AT STR. 45 TO SERVE SURFACE RELIEF FOR LOT 18.
BE SURE TO SPECIFY THE SLOT OPENING ORIENTATION AT THIS
STRUCTURE IN THE DRAINAGE SUMMARY SCHEDULE. REFLECT THE
CHANGES ON THE PLANS, PROFILES, AND COMPUTATION SHEETS.
.
37. PLEASE REVISE THE PLAN VIEWS AND PROFILES FOR THE
PROPOSED CONCRETE ROADSIDE DITCH LOCATED ON ENON CHURCH TO
BE PG-2A. IN ADDITION, INCLUDE A DETAIL OF THE PG-2A ON THE
PLANS.
.
38. THESE ARE IN REGARDS TO THE PROFILES:
.
A) PLEASE REVISE ROTUNDA LANE PROFILE (SHEET C-30) TO DEPICT
STR'S 101/103 AND THE EXISTING 30" RCP. REVISE ACCORDINGLY.
.
B) PLEASE REVISE THE ALMER LANE PROFILE (SHEET C-30) TO SHOW
THE PROPOSED GRADE AT THE END OF CONSTRUCTION TYING BACK TO
THE EXISTING GRADE IN THE PROXIMITY OF STATION 13+00.
.
IN ADDITION, IT APPEARS THE RUNOFF FROM THE ROAD WOULD
TEMPORARILY POND AT THE END OF THE ROAD CONSTRUCTION. A
TEMPORARY DITCH AND/OR RELOCATING STR'S 29/31 SHOULD BE
CONSIDERED. A FURTHER DISCUSSION IS RECOMMENDED.
.
39. AS A PREREQUISITE TO SUBDIVISION PLAT RECORDATION:
.
A) THE $100/LOT BMP MAINTENANCE FEE MUST BE RECEIVED.
.
==================== END OF EE COMMENTS ====================
.