Subdivision Review Comments
All Subdivision Review Comments for Case # 17CP0130




For VDOT’s comments please contact Virginia Department of Transportation at (804) 674-2814 or send e-mail to Boris.Solomonov@VDOT.Virginia.gov

For Tentative Subdivision resubmittals:

1. Please note that submittal fees include the original submittal and two (2) additional reviews.

2. A letter of transmittal is required to accompany each submittal.

3. Please verify that Environmental Engineering, Fire, CDOT, VDOT, and Planning have reviewed the submittal before resubmitting. A resubmittal tendered, prior to receiving all the required departments’ review, will be counted as an additional submittal. Go to Case Selection Form or Go to Project List


 
CASE NO: 17CP0130 STATUS: PENDING APPROVAL
PROJECT NAME: SILVERLEAF SEC H1 - LAST INTERNET UPDATE: 11/20/17
SUBMITTAL TYPE: CONSTRUCTION PLAN
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 00 06/12/17 07/03/17 ******** ********
FIRE DEPT.--: 00 06/12/17 07/03/17 COMPLETE 06/16/17 JKL 748-1489
PLANNING----: 00 06/12/17 07/03/17 ******** ********
TRANSPORT.--: 00 06/12/17 07/03/17 COMPLETE 06/30/17 SES 751-4912
UTIL.PLAN.--: 00 06/12/17 07/03/17 ******** ********
UTILITIES---: 00 06/12/17 07/03/17 COMPLETE 07/03/17 A B 768-7450
UTIL.R.O.W.-: 00 06/12/17 07/03/17 ******** ********
VDOT--------: 00 06/12/17 07/03/17 ******** ********
REVIEW DEPARTMENT: UTILITIES DEPARTMENT
REVIEWER/PHONE # : ANDREW BARNES / 804-768-7450
NAME OF PLAN : SILVERLEAF SEC. H1
ADDRESS : CONIFER ROAD, DALE
SUBMISSION DATE : 06/12/17
PLAN DATED : 05/24/17
REVIEW DATE : 06/30/17
SITE PLAN NO. : 17CP0130
COMMENTS : 1ST REVIEW-NOT APPROVED
TABLE REVIEW : NO
PLAT PROCESS :
1. PLEASE PUT UTILITIES CONTACT ANDREW BARNES, 804-768-
7450, BARNESAND@CHESTERFIELD.GOV ON THE COVER SHEET.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION, A
COPY OF THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER
AND/OR ALL OTHER APPLICABLE LOCAL STATE AND FEDERAL
AGENCIES' APPROVAL LETTERS MUST BE RECEIVED BY THIS
DEPARTMENT. IN ADDITION, ALL EASEMENTS NOT INCLUDED
WITH THE SUBDIVISION PLAT MUST BE DEDICATED WITH A
SEPARATE PLAT AND AGREEMENT TO THE COUNTY PRIOR TO
RELEASING THE PROJECT TO THE CONSTRUCTION SECTION.
3. PROVIDE A TABLE ON THE PLANS DETAILING WHETHER
EXISTING, PROPOSED, OR FUTURE SERVICE CONNECTIONS
(WATER/SEWER) ARE INTENDED FOR EACH LOT, AND THE
CORRESPONDING SECTION WHERE THE CONNECTION IS/WAS
PROPOSED.
4. LABEL EXISTING WATER AND SEWER LINES WITH SIZE,
MATERIAL, AND COUNTY PROJECT NUMBER IN BOTH PLAN AND
PROFILE.
5. LABEL PROPOSED AND FUTURE WATER AND SEWER LINES WITH
SIZE AND MATERIAL IN PLAN AND PROFILE VIEW.
6. A HYDRANT FLOW TEST AND THE RESULTING ANALYSIS IS
REQUIRED FOR THIS PROJECT. THE REQUEST SHOULD BE DIRECTED
TO TERRY MAPLES AT MAPLEST@CHESTERFIELD.GOV. PROVIDE
COPIES OF THE FLOW TEST RESULTS AND CALCULATIONS IN
THE PLANS.
7. EXTEND ALL WATERLINE AND SEWER STUBS FOR FUTURE
SECTIONS 1 FULL STICK (20') PAST THE PROPOSED EDGE OF
PAVEMENT. IF THE ROW IS NOT EXTENDED TO THE EDGE OF
PAVEMENT, PROVIDE AN EASEMENT FOR THE UTILITY EXTENSION.
8. IT APPEARS THAT BOTH VALVES AT THE INTERSECTION OF
CANNINGTON DRIVE AND SILVER MIST AVE WILL NEED TO BE
CLOSED TO FOR THE WL TIE-IN. IDENTIFY BOTH VALVES ON
THE PLAN.
9. LABEL FUTURE WATER AND SEWER LINES IN STERLING WOODS
LAND, LACROIX WAY, AND CANNINGTON DRIVE.
10. LABEL THE 8" PLUG AND 2" FLUSHING HYDRANT IN STERLING
WOODS LANE.
11. 8" X 6" TEES FOR FIRE HYDRANTS SHOULD BE UNIQUELY
IDENTIFIED AS "HYDRANT TEES" IN PLAN VIEW AND IN THE
MATERIAL QUANTITY LIST.
12. PROVIDE A TIE-IN NOTE FOR THE PROPOSED WL SHOWN IN THE
STERLING WOODS LANE PROFILE (C4.4).
13. ADD AND LABEL 1 VERTICAL FOOT OF STONE ABOVE SANITARY
SEWER 2-1 FROM APPROXIMATE STAS. 11+75 -12+50, WHERE DEPTH
OF BURY EXCEEDS 14'.
14. PROVIDE RESTRAINED VERTICAL BENDS AT 24+00 OF
CANNINGTON DRIVE. PROVIDE JOINT RESTRAINT
CALCULATIONS WITH THE NEXT SUBMISSION IN ADDITION TO
INDICATING THE OVERALL LENGTH OF RESTRAINT ON THE PLANS
15. PROVIDE A NOTE ON THE PROFILES THAT LATERALS TIED TO
MANHOLES AT THE INVERT SHOULD ARE TO HAVE CROWNS MATCHED TO
THE MAIN LINE.
16. PROVIDE A 24' EASEMENT FROM MH 2-1 DUE TO THE DEPTH.
17. AS A RESULT OF ANY CHANGES TO THE PROPOSED UTILITIES
RESULTING FROM THESE COMMENTS, PLEASE UPDATE THE MATERIAL
QUANTITIES ON THE COVER SHEET ACCORDINGLY.
18. THE OWNER SHALL BE REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
PRIOR TO THE PREPARATION OF THE UTILITIES CONTRACT,
UTILITIES MUST BE IN RECEIPT OF THE "ACCEPTED" BID PROPOSAL
BETWEEN THE DEVELOPER AND THE COUNTY APPROVED UTILITIES
CONTRACTOR AS WELL AS THE PROJECT'S INFORMATIONAL SHEET
FOUND ON THE "DEVELOPER'S CHECKLIST". PLEASE SEND THOSE TWO
ITEMS TO THE ATTENTION OF ANDREW BARNES
(BARNESAND@CHESTERFIELD.GOV). THE BID PROPOSAL MUST BE
BASED ON THE APPROVED SITE PLAN. BE ADVISED THAT IF THE
SITE PLAN IS REVISED AND REAPPROVED SUBSEQUENT TO THE
PREPARATION OR RECORDATION OF THE UTILITIES CONTRACT, THE
BID PROPOSAL SHALL BE REVISED ACCORDINGLY AND A REVISED
UTILITIES CONTRACT MAY BE NECESSARY.
19. AFTER FINAL SITE PLAN APPROVAL, SUBMIT THREE SETS OF
THE APPROVED PLANS DIRECTLY TO THE UTILITIES DEPARTMENT FOR
OUR USE DURING CONSTRUCTION INSPECTION. THIS IS IN
ADDITION TO THE ONE APPROVED SET FROM PLANNING (4 TOTAL
SETS). ONE ADDITIONAL ROLLED SET WILL BE REQUESTED AFTER
THE PROJECT IS RELEASED TO CONSTRUCTION TO BE USED FOR AS-
BUILTS.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: SILVERLEAF, SECTION H1
CASE NUMBER: 17CP0130
LATEST PLAN DATE: 05/24/2017
DEPT. REC'D. DATE: 06/13/2017
SUBMITTAL NUMBER: ONE
REVIEW DATE: 06/30/2017
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
.
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : WHIT KIRTLEY / 706-7691
PLAN NAME : SILVER LEAF SECTION H
PLAN NUMBER : 16CP0114
ORIGINAL PLAN DATE : 7/17/17
REVIEW DATE : 7/19/16
LATEST SUBMISSION DATE : 5/25/17
ACCEPTED DATE: 6/12/17
SUBMITTAL NUMBER : 7
STATUS : MINOR COMMENTS
TABLE REVIEW : Y
.
NOTES:
.
2. HAVE THE SIDEWALKS BEEN INSTALLAD ALONG SILVERMIST AVE, A
CANNINGTON DR AT LOTS 23-24 WITH PREVIOUS SECTIONS? BE ADVI
SIDWALKS ADJACENT TO THE LOTS IN SECTION H1 SHALL BE INSTALL
TO CO APPROVAL
.
3. PROVIDE AN AUTOCAD FILE WITH THE NEW BOUNDARIES OF SECTIO
. H1.
4. ADD CASE NUMBER 17CP0109
SHEET
REVIEW DEPARTMENT: FIRE DEPARTMENT
REVIEWER/PHONE#: KIM LESTER / (804) 748-1489
EMAIL: LESTERK@CHESTERFIELD.GOV
NAME OF PLAN: SILVERLEAF SEC. H1
PLAN NUMBER: 17CP0130
LATEST PLAN DATE: 5/24/17
DEPT. REC'D. DATE: 6/14/17
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 6/16/17
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
COMMENTS:
.
THE WATER FLOW TEST RESULTS AND GRAPH SHALL BE SHOWN
ON THE SUBMITTED PLAN. SHOW THE NODE MAP AND RESULTS
TABLE FOR THE PROPOSED OR EXISTING HYDRANTS ON SITE
SHOWING THE MAXIMUM FIRE FLOW CAN BE ACHIEVED.
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++