All Subdivision Review Comments for Case # 17CP0109




For VDOT’s comments please contact Virginia Department of Transportation at (804) 674-2814 or send e-mail to Boris.Solomonov@VDOT.Virginia.gov

For Tentative Subdivision resubmittals:

1. Please note that submittal fees include the original submittal and two (2) additional reviews.

2. A letter of transmittal is required to accompany each submittal.

3. Please verify that Environmental Engineering, Fire, CDOT, VDOT, and Planning have reviewed the submittal before resubmitting. A resubmittal tendered, prior to receiving all the required departments’ review, will be counted as an additional submittal. Go to Case Selection Form or Go to Project List


 
CASE NO: 17CP0109 STATUS: PENDING APPROVAL
PROJECT NAME: MAG GREEN WOOLRIDGE - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: CONSTRUCTION PLAN
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 02 09/27/17 10/18/17 ******** ********
FIRE DEPT.--: 02 09/27/17 10/18/17 COMPLETE 09/29/17 AWB 717-6167
PLANNING----: 02 09/27/17 10/18/17 ******** ********
TRANSPORT.--: 02 09/27/17 10/18/17 COMPLETE 10/12/17 SES 751-4912
UTIL.PLAN.--: 02 09/27/17 10/18/17 ******** ********
UTILITIES---: 02 09/27/17 10/18/17 AMENDED* 10/11/17 WBP 751-4336
UTIL.R.O.W.-: 02 09/27/17 10/18/17 ******** ********
VDOT--------: 02 09/27/17 10/18/17 ******** ********
REVIEW DEPARTMENT: UTILITIES
REVIEWER / PHONE #: W.B. PAYNE III/751-4336
NAME OF PLAN: MAGNOLIA GREEN WOOLRIDGE ROAD EXTENSION PHASE
ADDRESS: WESTERN TERMINUS OF WOOLRIDGE ROAD
SUBMISSION DATE: 4/11/17
PLAN DATED: 3/24/17
REVIEW DATE: 4/17/17
SITE PLAN NUMBER: 17CP0109
COMMENTS: 1ST REVIEW - NOT APPROVED
TABLE REVIEW:
PLAT PROCESS:
1. ADD THE UTILITIES PROJECT NUMBER DESIGNATED FOR THIS
PROJECT (17-0076) TO ALL PLAN SHEETS.
2. THE WOOLRIDGE ROAD EXTENSION PHASE 3 PLAN (16-0067)
SHOWS A 4" BO AT THE END OF THE 12" WATERLINE IN BOTH
PLAN AND PROFILE HOWEVER SHEET C4.0 OF THIS PLAN SHOWS
REMOVAL OF THE EXISTING 2" BO; PLEASE CORRECT. NOTE THE
PROFILE ON SHEET C5.0 CORRECTLY SHOWS A 4" BO.
3. ADD A 1" ARV AT APPROXIMATELY STA 87+50. PROVIDE
AN APPROPRIATE 12" WATERLINE DEPTH FROM FINISHED GRADE TO
TOP OF PIPE AT STA 102+24 IN ORDER TO INSTALL A 1" TAP FOR
THE ARV. AS THE ARV LOCATION SHOULD BE OFFSET TO A POINT
OUTSIDE THE PAVEMENT (BEHIND THE SIDEWALK), THE COPPER
SERVICE LINE FROM THE 1" TAP SHOULD MAINTAIN A POSITIVE
SLOPE FROM THE CORPORATION STOP TO THE ARV DEVICE. LOCATE
THE ARV BOX 3' BEHIND THE SIDEWALK PER DETAIL WAT-1
WITH THE TOP OF THE BOX INSTALLED FLUSH WITH GRADE.
4. THE SPECIFICATIONS REQUIRE THAT MAINLINE VALVES BE
INSTALLED AT INTERVALS NOT TO EXCEED 1000'; PLEASE PROVIDE
ADDITIONAL 12" GV'S WHERE NECESSARY. UTILITIES PREFERS THAT
MAINLINE GV'S BE INSTALLED ADJACENT TO FH TEES WHERE
POSSIBLE FOR EASE OF LOCATION AND MAINTENANCE.
5. PLEASE INSTALL 8" CLASS 52 RESTRAINED JOINT DI PIPE WITHI
THE INTERSECTION OF INTERSECTION 3 SIMILAR TO THE BAY CREEK
ROAD/ASHTON OAKS TRAIL INTERSECTION.
6. REMOVE DETAIL WAT-16 FROM THE PLAN AND ADD WAT-4.
.
BE ADVISED THAT ALL PUBLIC WATER AND/OR SEWER LINES AND
APPURTENANCES TYPICALLY MUST EITHER BE IN RECORDED
EASEMENTS OR DEDICATED RIGHTS-OF-WAY PRIOR TO
ACCEPTANCE BY UTILITIES. A PLAT SHOWING THE SEGMENT OF
WATER EASEMENT FOR THE FH LOCATED AT STA 98+00 NEAR THE
INTERSECTION OF ASHTON OAKS TRAIL SHOULD BE SUBMITTED AS
SOON AS POSSIBLE AS THIS EASEMENT SHOULD BE DEDICATED
PRIOR TO UTILITIES RELEASING THIS PROJECT TO CONSTRUCTION.
PLEASE CONTACT KIM PULLEY AT 804-748-1376.
THE OWNER IS REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
PRIOR TO THE PREPARATION OF THE UTILITIES CONTRACT,
UTILITIES MUST BE IN RECEIPT OF THE "ACCEPTED" BID
PROPOSAL BETWEEN THE DEVELOPER AND THE COUNTY
APPROVED UTILITIES CONTRACTOR AS WELL AS THE PROJECT'S
INFORMATIONAL SHEET FOUND ON THE "DEVELOPER'S
CHECKLIST". PLEASE SEND THOSE TWO ITEMS TO THE
ATTENTION OF BILL PAYNE (PAYNEW@CHESTERFIELD.GOV
OR BY CALLING 804-751-4336). THE BID PROPOSAL MUST
BE BASED ON THE APPROVED SITE PLAN. BE ADVISED THAT
IF THE SITE PLAN IS REVISED AND REAPPROVED SUBSEQUENT
TO THE PREPARATION OR RECORDATION OF THE UTILITIES
CONTRACT, THE BID PROPOSAL SHALL BE REVISED ACCORDINGLY
AND A REVISED UTILITIES CONTRACT MAY BE NECESSARY.
AFTER FINAL SITE PLAN APPROVAL, FOUR SETS TOTAL OF THE
APPROVED PLANS MUST BE SENT DIRECTLY TO THE UTILITIES
DEPARTMENT FOR OUR USE DURING CONSTRUCTION INSPECTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEWER / PHONE #: W.B. PAYNE III/751-4336
NAME OF PLAN: MAGNOLIA GREEN WOOLRIDGE ROAD
EXTENSION PHASE 3B
ADDRESS: WESTERN TERMINUS OF WOOLRIDGE ROAD
SUBMISSION DATE: 6/15/17
PLAN DATED: 6/9/17
REVIEW DATE: 6/21/17
SITE PLAN NUMBER: 17CP0109
COMMENTS: 2ND REVIEW - NOT APPROVED
TABLE REVIEW: YES
PLAT PROCESS:
1.PLEASE REVISE THE QUANTITIES ON SHEET C1.0 TO REFLECT THRE
(3) 12" GV'S.
ONCE THIS REVISION HAS BEEN MADE, THE PLAN WILL BE ELIGIBLE
FOR UTILITIES APPROVAL AT A TABLE REVIEW. IT IS OUR
RECOMMENDATION THAT PDF'S OF ANY REVISED SHEETS BE
SUBMITTED TO UTILITIES BEFOREHAND TO ENSURE THE CHANGES ARE
ACCEPTABLE.
BE ADVISED THAT ALL PUBLIC WATER AND/OR SEWER LINES AND
APPURTENANCES TYPICALLY MUST EITHER BE IN RECORDED
EASEMENTS OR DEDICATED RIGHTS-OF-WAY PRIOR TO
ACCEPTANCE BY UTILITIES. PLEASE CONTACT KIM PULLEY AT
804-748-1376.
THE OWNER IS REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
AFTER FINAL SITE PLAN APPROVAL, FOUR SETS TOTAL OF THE
APPROVED PLANS MUST BE SENT DIRECTLY TO THE UTILITIES
DEPARTMENT FOR OUR USE DURING CONSTRUCTION INSPECTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEWER / PHONE #: W.B. PAYNE III/751-4336
NAME OF PLAN: MAGNOLIA GREEN WOOLRIDGE ROAD
EXTENSION PHASE 3B
ADDRESS: WESTERN TERMINUS OF WOOLRIDGE ROAD
SUBMISSION DATE: 9/29/17
PLAN DATED: 9/25/17
REVIEW DATE: 10/10/17
SITE PLAN NUMBER: 17CP0109
COMMENTS: 3RD REVIEW - APPROVED
THE PLAN, DATED SEPTEMBER 25, 2017, IS NOW APPROVABLE BY UTI
LITIES.
BE ADVISED THAT ALL PUBLIC WATER AND/OR SEWER LINES AND
APPURTENANCES TYPICALLY MUST EITHER BE IN RECORDED
EASEMENTS OR DEDICATED RIGHTS-OF-WAY PRIOR TO
ACCEPTANCE BY UTILITIES. PLEASE CONTACT KIM PULLEY AT
804-748-1376 OR JOE DUTY AT 804-717-6583.
THE OWNER IS REQUIRED TO ENTER INTO A COUNTY
UTILITIES CONTRACT PRIOR TO THE START OF CONSTRUCTION.
THREE (3) ADDITIONAL SETS OF THE APPROVED PLAN MUST BE
SUBMITTED TO THE UTILITIES DEPARTMENT FOR OUR USE PRIOR
TO UTILITIES GRANTING A RELEASE TO CONSTRUCTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: MAGNOLIA GREEN WOOLRIDGE EXT. PH. 3B
CASE NUMBER: 17CP0109
LATEST PLAN DATE: 03/24/2017
DEPT. REC'D. DATE: 04/11/2017
SUBMITTAL NUMBER: ONE
REVIEW DATE: 05/02/2017
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
.
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: MAGNOLIA GREEN WOOLRIDGE EXT. PH. 3B
CASE NUMBER: 17CP0109
LATEST PLAN DATE: 06/09/2017
DEPT. REC'D. DATE: 06/13/2017
SUBMITTAL NUMBER: TWO
REVIEW DATE: 06/28/2017
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
.
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: MAGNOLIA GREEN WOOLRIDGE EXT. PH. 3B
CASE NUMBER: 17CP0109
LATEST PLAN DATE: 09/25/2017
DEPT. REC'D. DATE: 09/28/2017
SUBMITTAL NUMBER: THREE
REVIEW DATE: 10/12/2017
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
.
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: MAGNOLIA GREEN PARKWAY EXT PHASE 3B
PLAN NUMBER: 17CP0109
LATEST PLAN DATE: 3/24/17
DEPT. REC'D. DATE: 4/10/17
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 4/11/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
COMMENTS:
1. THE PLAN IS APPROVED AS SUBMITTED.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: MAGNOLIA GREEN PARKWAY EXT PHASE 3B
PLAN NUMBER: 17CP0109
LATEST PLAN DATE: 6/9/17
DEPT. REC'D. DATE: 6/14/17
SUBMITTAL NUMBER: 2ND REVIEW
REVIEW DATE: 6/15/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
COMMENTS:
1. THE PLAN IS APPROVED AS SUBMITTED.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: FIRE
REVIEWER/PHONE#: ANTHONY BATTEN / 717-6167
EMAIL: BATTENA@CHESTERFIELD.GOV
NAME OF PLAN: MAGNOLIA GREEN PARKWAY EXT PHASE 3B
PLAN NUMBER: 17CP0109
LATEST PLAN DATE: 9/25/17/17
DEPT. REC'D. DATE: 9/28/17
SUBMITTAL NUMBER: 3RD REVIEW
REVIEW DATE: 9/29/17
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
COMMENTS:
1. THE PLAN IS APPROVED AS SUBMITTED.
.
============================================================
.
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : LYNDA GILBERTSON, P.E. / 706-2116
NAME OF PLAN : MAGNOLIA GREEN- WOOLRIDGE RD EXT. PHASE 3B
SITE PLAN NO. : 17CP 0109
ORININAL PLAN DATE : MARCH 24, 2017
DEPT. REC'D DATE : APRIL 10, 2017
SUBMITTAL NUMBER : ONE
REVIEW DATE : APRIL 28, 2017
RECOMMENDATION : REVISION REQUESTED
TABLE REVISION : NO
.
RESPONSIBILITY FOR COMPLIANCE TO CHESTERFIELD COUNTY
STANDARDS AND POLICIES AND STATE AND FEDERAL REGULATIONS
WILL BE PLACED ON THE PROFESSIONAL ENGINEER WHO SIGNS
AND SEALS THE CONSTRUCTION PLANS APPROVED.
.
THIS OFFICE RECOGNIZES THAT 10-YEAR PRE/POST
REQUIREMENTS FOR FLOOD PROTECTION CAN BE ADDRESSED BY
DISCHARGING INTO AN ESTABLISHED 100-YEAR FLOODPLAIN.
.
======== CBPA ============
.
01. INCLUDE THE 2014-2019 VSMP CONSTRUCTION PERMIT NUMBER
FOR THIS PROJECT ON THE COVER SHEET.
.
02. VERIFY THE DRAINAGE AREA IN THE WORKSHEET A ON SHEET
C3.2 AS 7.38 AC AND ON SHEET C10.2 IS 7.37 AC.
.
================== BMP/ SWM ==================
.
01. VERIFY THE SIZE OF 2 HP PUMP ON SHEET C10.0 THAT IS
RECOMMENDED TO DRAIN THE APPROXIMATE 7-FOOT OF WATER
FROM THE BMP FOR MAINTENANCE, THE PUMP MUST BE SIZED
TO DRAIN WITHIN 24 HOURS. INCLUDE THE HORSEPOWER AND
HOSE DIAMETER (INCHES) OF THE RECOMMENDED PUMP
.
02. PROVIDE JUSTIFICATION FOR USING A RUNOFF COEFFICIENT
C FACTOR OF 0.25 IN THE HYD. NO. 1 REPORT ON SHEET
C10.1 IN AN UNDEVELOPED FORESTED DRAINAGE AREA.
.
03. REVISE THE TWO END CURTAIN WALLS FROM 24-INCHES TO
36-INCHES IN THE DETAIL IN THE UPPER LEFT CORNER OF
SHEET C10.0.
.
04. CONSIDER REVISING THE 2:1 SIDE SLOPES TO 1:1 IN THE
FOREBAY DETAIL ON SHEET C10.0.
.
05. REVISE THE TWO RPA SIGN LOCATIONS ON SHEETS C10.0
AND C10.3 TO THE RPA LIMITS, CURRENTLY SHOWN ON THE
VARIABLE WIDTH SWM/BMP EASEMENT DASHED LINE.
.
06. SHOW AND LABEL THE SECTION VIEW AND SIDE VIEW CROSS
SECTIONS FOR THE EMERGENCY SPILLWAY IN THE PLAN VIEW
ON SHEET C10.0.
.
07. DIMENSION THE 8-FOOT TOP OF DAM FROM THE EMERGENCY
SPILLWAY TO THE SOUTHEAST CORNER IN THE PLAN VIEW ON
SHEET C10.0.
.
08. LABEL THE BMP NWSE (223.0) IN THE PLAN VIEW ON SHEET
C10.0.
.
09. SHOW AND LABEL TWO PLANTED AQUATIC BENCH SIGNS IN THE
PLAN VIEW ON SHEET C10.0.
.
10. LABEL CROSS SECTION A-A JUST BELOW THE EMERGENCY
SPILLWAY AS MS-19 AND 100-YEAR ON SHEET C10.0.
.
11. INCLUDE A LOCATION NOTE (SHEET C8.2) OF THE
CROSS-SECTIONS A-A AND B-B BY THE SECTIONS IN THE BMP
PLAN VIEW ON SHEET C10.0.
.
12. SHOW, LABEL AND PROVIDE A CROSS-SECTION VIEW ACROSS
TO THE RIP RAP/CG-2 BELOW THE EMERGENCY SPILLWAY ON
SHEET C10.0.
.
13. LABEL THE SLOPE AT 0% FOR THE RIP RAP OUTFALL
PROTECTION LABEL IN THE PLAN VIEW DETAIL ON THE LEFT
SIDE OF SHEET C10.0.
.
14. SHOW CONTAINMENT IN THE EMERGENCY SPILLWAY BY LABELING
THE NWSE/10/100 WATER SURFACE ELEVATIONS AND THE
TOP OF DAM IN THE SECTION VIEW ON SHEET C10.0
.
15. MAKE THE FOLLOWING CORRECTIONS TO THE SAFETY AND AQUATIC
BENCH PLAN ON THE LEFT SIDE OF SHEET C10.3;
.
A. CORRECT THE NWSE FROM 242.00 TO 223.00 AND THE
BOTTOM FROM 237.00 TO 216.0.
B. DELETE THE PLANTED SHALLOW MARSH SIGN AND REPLACE
WITH A TYPICAL SIGN DETAIL FOR THE PLANTED AQUATIC
BENCH SIGN.
C. CORRECT THE WIDTH OF THE AQUATIC BENCH FROM 6-FEET
TO 10-FEET AND THE SLOPE FROM 6:1 TO 10:1.
.
======== EROSION CONTROL ============
.
01. PLEASE REVISE THE EROSION AND SEDIMENT CONTROL
ITEMIZED COST ESTIMATE FOR THE FINE
GRADING/SEEDING/MULCHING TO $2,000.00 FOR THE 11.72 AC.
.
02. AS A PREREQUISITE TO ISSUANCE OF A LAND DISTURBANCE
PERMIT:
.
A. PLANNING DEPARTMENT APPROVAL MUST BE RECEIVED.
B. A COPY OF THE COE WETLANDS PERMIT
C. A COPY OF THE VSMP COVERAGE LETTER FOR THIS PROJECT
MUST BE RECEIVED.
D. THE EXISTING SWPPP BOOK FOR THE EXISTING CONSTRUCTION
GENERAL PERMIT MUST BE SUBMITTED FOR A COMPLETENESS
REVIEW.
E. AN EROSION AND SEDIMENT CONTROL BOND FOR AN APPROVED
AMOUNT MUST BE POSTED.
F. A COPY OF THE VDOT LAND USE PERMIT MUST BE RECEIVED,
IF APPLICABLE.
G. TWO ADDITIONAL SETS OF PLANS TO BE STAMPED "APPROVED
FOR CONSTRUCTION" MUST RECEIVED.
H. THE TEMPORARY RISER AND PIPE BARREL ASSOCIATED WITH
THE SEDIMENT BASIN MUST BE ON-SITE.
I. A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD FILE
MUST BE SAVED AS A .DWG OR .DXF IN AUTO CAD VERSION
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINIA
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD,
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE
SUBDIVISION NAME AND SECTION, SUBDIVISION PLAN NUMBER,
THE ENGINEERING FIRM AND THE CAD FILE PREPARER'S NAME
AND PHONE NUMBER. THE FILE MUST CONTAIN THE FOLLOWING,
EACH CLEARLY LABELED IN SEPARATE LAYERS:
.
1. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
2. EDGES OF SIDEWALKS.
.
ENVIRONMENTAL ENGINEERING MUST APPROVE THE FILE
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
.
03. AS A REMINDER ANY SOIL MATERIAL THAT IS BROUGHT IN OR
REMOVED FROM THE PROJECT LIMITS MUST BE TO A PERMITTED
LAND DISTURBING SITE, THE ENVIRONMENTAL ENGINEERING
INSPECTOR MUST BE INFORMED OF THIS LOCATION.
.
04. PERFORM AN MS-19 ANALYSIS AT THE OUTFALLS FOR CULVERTS
C-1, C-2, AND C-3. INCLUDE 10-YEAR CALCULATIONS FOR
CULVERT AND SHOW / LABEL CROSS-SECTION LOCATIONS
(SHEET C4.0 THRU C4.3) AND INCLUDE IN THE MS-19 TABLE
ON SHEET C3.2.
.
05. SHOW AND LABEL A SOIL STOCKPILE AREA LOCATION IN THE
PLANS. SILT FENCE MUST BE SHOWN AROUND THE PERIMETER.
.
06. INCLUDE A GUTTER BUDDY OR APPROVED SIMILAR PRODUCT
TYPICAL DETAIL ON SHEET C3.1, THAT THE CONTACTOR MIGHT
CHOOSE THE USE AS INLET PROTECTION.
.
07. VERIFY AND CORRECT DRAINAGE AREA TO SEDIMENT TRAPS 3 AND
7 IN THE TABLE ON SHEET C3.2 TO MATCH THE DRAINAGE AREAS
LABELED IN THE PLAN VIEWS ON SHEET C3.5 AND C3.3.
.
08. LABEL THE GRAVEL OUTLET STRUCTURES FOR EACH SEDIMENT
TRAP IN EROSION CONTROL PHASE 1 AND 2 PLAN SHEETS (C3.3
THRU C3.6.
.
09. INCLUDE AN EROSION CONTROL MEASURES LEGEND ON SHEETS
C3.3 THRU C3.6.
.
10. CLARIFY THE TEMPORARY DIVERSION DIKE FROM STATION 94+00
AROUND SEDIMENT TRAP #2 ON SHEET C3.3, LABEL AS A CLEAN
WATER DIVERSION IF APPLICABLE.
.
11. DELETE THE LABELS FOR THE 50' R/W FOR ASHTON OAKS TRAIL
AND BAY CREEK ROAD AND WAY ON SHEET C3.3. THE RIGHT OF
WAY IS NOT SHOWN BETWEEN STATIONS 97+00 AND 98+00.
.
12. SHOW AND LABEL INLET PROTECTION ON EXISTING STRUCTURES
7-13, 7-15, 7-17, 7-29, 7-31, AND 7-33 ON SHEETS C3.3
AND C3.5.
.
13. INCLUDE ON SHEETS C3.3 AND C3.4 A SEQUENCE OF
CONSTRUCTION FOR THE INSTALLATION OF CULVERTS C1, C2 AND
C3 TO INCLUDE BUT NOT LIMITED TO;
.
A. INSTALLATION WILL TAKE PLACE WHEN NO MEASURABLE
PRECIPITATION IS EXPECTED DURING THE INITIAL
INSTALLATION.
B. CULVERT SECTIONS WILL BE ON SITE OR IN AN APPROVED
STAGING LOCATION PRIOR TO EXCAVATION.
C. INSTALLATIONS OF TEMPORARY FILL DIVERSIONS DIRECTING
RUNOFF TO THE SEDIMENT TRAPS. THE RIGHT OF WAY AND
FILL DIVERSIONS WILL BE MAINTAINED EVERY EVENING
UNTIL THE ROAD HAS REACHED FINAL GRADE.
D. SEED AND STABILIZE THE SLOPE ONCE THE FINAL GRADE HAD
BEEN REACHED.
.
14. SHOW, LABEL, AND DIMENSION TEMPORARY SLOPE DRAINS (TSD)
DOWN THE SLOPES GREATER THAN 5-FEET HIGH AT 2:1 ON THE
NORTH SIDE OF STATION 88+50 AND BOTH SIDES AT STATIONS
95+00 AND 96+00. THE SLOPE DRAINS SHOULD DRAIN INTO THE
SEDIMENT TRAPS ON SHEETS C3.5 AND C. LABEL WITH THE
DIAMETER, MATERIAL, LENGTH.
.
15. SHOW THE STORM SEWER STRUCTURES ON THE EROSION CONTROL
PHASE II PLAN SHEETS (C3.5 AND C3.6). THE INLET
PROTECTION IS SHOWN AND LABELED.
.
=============== ROAD AND DRAINAGE ============
.
01. DUE TO THE HEAVY VEGETATION AND LACK OF CENTERLINE
STAKING, THIS OFFICE RESERVES THE RIGHT TO INSPECT
EXISTING CONVEYANCE SYSTEMS PRIOR TO LOT RECORDATION
TO DETERMINE IF ADDITIONAL IMPROVEMENTS ARE NECESSARY.
.
02. STORM SEWER DESIGN CALCULATIONS AND HGL ANALYSIS TABLES
WERE SPOT CHECKED AND APPEAR TO BE CORRECT.
.
03. PROVIDE THE ULTIMATE 100-YEAR STORMWATER CALCULATIONS
BELOW CULVERTS C1, C2 AND C3 THAT SHOW THE 100-YEAR
TYING TO THE FEMA LIMITS. TO PROVIDE 10-YEAR FLOOD
PROTECTION FOR THE FUTURE DEVELOPMENTS. SHOW AND LABEL
THE CROSS SECTIONS WITH ELEVATIONS ON THE PLAN VIEW
SHEETS C6.0 THRU C6.2.
.
04. PROVIDE THE STANDARD ENDWALL (EW-2, 2A) DETAIL FOR
48"/42" PIPE FOR THE C-1 AND C-3 STRUCTURES, ONLY THE
12" TO 36" ENDWALL (EW-1, 1A) DETAIL IS ON SHEET C2.2.
.
05. INCLUDE THE DRAINAGE DESCRIPTIONS FOR THE STORM SEWER
STRUCTURES THAT ARE SHOWN ON SHEETS C4.0 THRU C4.2.
INCLUDE A NOTE THAT THE PIPE STRUCTURES MUST BE RCP
CLASS III MATERIAL.
.
06. INCLUDE IN THE 5-FOOT SIDEWALK LABEL OR AS A SEPARATE
NOTE THAT THE TYPICAL SIDEWALK DETAIL IS ON SHEET C2.1.
.
07. LABEL THE VARIABLE WIDTH SWM/BMP EASEMENT FOR STRUCTURES
2-4 AND ACCESS ROAD AS EITHER PERMANENT OR TEMPORARY ON
SHEETS C4.0 C4.1 AND C10.3. IF STRUCTURE 2-4 TO 2-2
WILL REMAIN WITH THE FUTURE SUBDIVISION THEY WILL NEED
TO BE IN A DRAINAGE EASEMENT.
.
08. LABEL THE 12-FOOT GRAVEL SWM/BMP ACCESS ROAD AS
TEMPORARY ON SHEETS C4.0 AND C4.1.
.
09. CORRECT THE TITLE OF THE ROAD PROFILES ON SHEETS C5.0
THRU C5.2 TO WOOLRIDGE ROAD PH3B.
.
10. CORRECT THE CULVERT BACKWATER LABEL TO C3 IN THE
PROFILE VIEW ON SHEET C8.1, CURRENTLY LABEL AS C2.
.
11. INCLUDE IN THE PIPE STRUCTURE LABELS IN THE STORM
PROFILE VIEWS ON SHEET C8.0 THRU C8.2 THAT THE PIPE
MUST BE RCP CLASS III.
.
XX. VERIFY THE TOPS OF STRUCTURES 2-33 AND 2-35, THE STORM
2-35 TO 2-33 PROFILE VIEW ON SHEET C8.0 IS 255.50/256.55
AND SHEET 11.0 IS 254.46/257.27 RESPECTIVELY.
.
XX. ENSURE THE SHEET ARE PRINTED AND STAPLED IN THE CORRECT
ORDER C8.0 IS AFTER C8.1 IN THE SUBMITTED SETS.
.
XX. VERIFY THE BMP 7 LABEL AT INTERSECTION 1 AND WOOLRIDGE
ROAD. THERE IS NO BMP 7 ASSOCIATED WITH THE MAGNOLIA GREEN -
WOOLRIDGE ROAD EXT PHASE 3 CONSTRUCTION PLANS.
.
XX. CORRECT THE THREE CULVERT CALCULATION SPREAD SHEET ON
SHEET C11.1, THE DIAMETER OF C1 IS 4 IN LIEU OF 3.5,
C2 IS 2 IN LIEU OF 1.75 AND C3 IS 3.5 IN LIEU 3.
.
============= UPPER SWIFT CREEK ==============
.
01. ADDITIONAL EROSION CONTROL MEASURES OTHER THAN THE
MINIMUM STANDARDS CONTAINED IN THE VIRGINIA EROSION AND
SEDIMENT CONTROL HANDBOOK WI.3LL BE REQUIRED IF IT IS
DETERMINED THAT SUCH MEASURES ARE NECESSARY FOR
PROTECTION OF SENSITIVE ENVIRONMENTAL FEATURES AND/OR
WATER RESOURCE.
.
02. THE EROSION CONTROL MUST SPECIFY OPTIC ORANGE SUPER
SILT FENCE (STD. & SPEC. 3.05 OF THE VESCH) ALONG THE
RPA WITHIN 50-FEET OF THE LIMITS OF CLEARING, FILLING
AND GRADING.
.
A. SHOW AND LABEL THE SUPER SILT FENCE ON THE NORTH
AND EAST SIDE OF SEDIMENT BASIN 2 AS OPTIC ORANGE
SUPER SILT FENCE.
B. SHOW AND LABEL RPA FLAGGING WITHIN 50-FEET OF THE
CLEARING AND GRADING FOR SEDIMENT BASIN 2, TO ENSURE
THEY REMAIN UNDISTURBED.
.
03. PLEASE PROVIDE A WRITTEN RESPONSE TO THESE COMMENTS
WITH YOUR NEXT PLAN SUBMITTAL. DESIGN, DETAIL, AND
CALCULATIONS REQUIRED BY THE ABOVE COMMENTS WILL BE
SUBJECT TO FURTHER REVIEW.
.
---- END OF ENV. ENG. COMMENTS ----