All Subdivision Review Comments for Case # 16TS0217




For VDOT’s comments please contact Virginia Department of Transportation at (804) 674-2814 or send e-mail to Boris.Solomonov@VDOT.Virginia.gov

For Tentative Subdivision resubmittals:

1. Please note that submittal fees include the original submittal and two (2) additional reviews.

2. A letter of transmittal is required to accompany each submittal.

3. Please verify that Environmental Engineering, Fire, CDOT, VDOT, and Planning have reviewed the submittal before resubmitting. A resubmittal tendered, prior to receiving all the required departments’ review, will be counted as an additional submittal. Go to Case Selection Form or Go to Project List


 
CASE NO: 16TS0217 STATUS: PENDING APPROVAL
PROJECT NAME: HANCOCK VILLAGE TOWN - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: TENTATIVE SUBDIVISION
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ASSESSOR----: 01 04/18/16 05/09/16 ******** ********
ENVIR.ENGR.-: 01 04/18/16 05/09/16 AMENDED* 05/10/16 RPW 748-1028
FIRE DEPT.--: 01 04/18/16 05/09/16 COMPLETE 04/22/16 AWB 717-6167
HOUSE NUMBER: 01 04/18/16 05/09/16 ******** ********
MAPPING/GIS-: 01 04/18/16 05/09/16 ******** ********
PLANNING----: 01 04/18/16 05/09/16 COMPLETE 05/17/16 CH 717-6042
PARKS & REC.: 01 04/18/16 05/09/16 ******** ********
SCHOOL BOARD: 01 04/18/16 05/09/16 ******** ********
SOILS-------: 01 04/18/16 05/09/16 ******** ********
TRANSPORT.--: 01 04/18/16 05/09/16 COMPLETE 05/09/16 SES 751-4912
UTIL.PLAN.--: 01 04/18/16 05/09/16 AMENDED* 04/22/16 TVM 751-4435
UTILITIES---: 01 04/18/16 05/09/16 ******** ********
UTIL.R.O.W.-: 01 04/18/16 05/09/16 ******** ********
VDOT--------: 01 04/18/16 05/09/16 ******** ********
REVIEW DEPARTMENT: UTILITIES
REVIEWER / PHONE # : TERRY MAPLES 751-4435
PLAN NAME HANCOCK VILLAGE TOWNHOMES
PLAN NUMBER: 16TS0217
ORIGINAL PLAN DATE: 2/03/16
REVIEW DATE: 4/22/16
LATEST SUBMISSION DATE:4/15/16
SUBMITTAL NUMBER: 2
STATUS: APPROVED
TABLE REVIEW:
1. IT WILL BE THE RESPONSIBILITY OF THE SUB DIVIDER TO
MAKE CERTAIN, BY WHATEVER MEANS NECESSARY,
(I.E., ON-SITE WATER LINE LOOPING OR OFF-SITE
WATER LINE EXTENSIONS, ETC.) THAT THE DEMANDS
GENERATED BY THE PROPOSED PROJECT DO NOT
ADVERSELY AFFECT ANY PORTION OF THE PRESSURE
ZONE THE PROJECT IS LOCATED WITHIN AND THAT
THE ADDITION OF THIS PROJECT WILL NOT CAUSE ANY
AREA WITHIN THE PRESSURE ZONE TO FAIL TO COMPLY
WITH THE CHESTERFIELD COUNTY FIRE DEPARTMENT'S
REQUIRED FIRE FLOW OF 1000 GPM AT 20 PSI
RESIDUAL. (U)
2. THIS OFFICE MAY REQUIRE REDESIGN OR MODIFICATIONS
TO THE PROPOSED SEWER LAYOUT, AS SHOWN ON THE
APPROVED PRELIMINARY PLAN, ONCE THE FIELD WORK,
GRADING PLAN AND FINAL SEWER DESIGN HAS BEEN
COMPLETED BY THE ENGINEER AND SHOWN ON
INITIAL CONSTRUCTION PLAN SUBMITTAL FOR REVIEW
AND APPROVAL. (U)
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: HANCOCK VILLAGE
CASE NUMBER: 16TS0217
LATEST PLAN DATE: 02/03/2016
DEPT. REC'D. DATE: 03/09/2016
SUBMITTAL NUMBER: ONE
REVIEW DATE: 04/05/16
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
1. THE ADTS SHOWN WERE GENERATED USING THE TRIP RATE FOR
IN ADDITION TO THE TURN LANES THAT ARE SHOWN, AN EASTBOUND
LEFT TURN LANE SHOULD BE SHOWN ON THE TENTATIVE AT HANCOCK
CREST DRIVE.
. AS NOTED, PROFFERED CONDITION 9.J OF ZONING CASE
2. THE ALIGNMENT OF THE WESTBOUND THROUGH LANE BETWEEN BE
HANCOCK CREST DRIVE AND HANCOCK TOWNS DRIVE IS INCORRECTD
AND MUST BE RE-DRAWN.TIVE TO ENSURE THAT ADEQUATE STORAGE
ND TRANSITIONS CAN BE ACHIEVED BETWEEN THE PROPOSED
ACCESSES.
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: HANCOCK VILLAGE
CASE NUMBER: 16TS0217
LATEST PLAN DATE: 04/15/2016
DEPT. REC'D. DATE: 04/22/2016
SUBMITTAL NUMBER: TWO
REVIEW DATE: 05/09/16
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: NO
1. AS NOTED ON THE TENTATIVE, PROFFERED CONDITION 9.J OF
ZONING CASE 95SN0278 INDICATES THAT LEFT AND RIGHT TURN
LANES WILL BE PROVIDED AT EACH ACCESS TO ASHBROOK PARKWAY.
IN ADDITION TO THE TURN LANES THAT ARE SHOWN, AN EASTBOUND
LEFT TURN LANE SHOULD BE SHOWN ON THE TENTATIVE AT HANCOCK
CREST DRIVE.
2. THE ALIGNMENT OF THE WESTBOUND THROUGH LANE BETWEEN
HANCOCK CREST DRIVE AND HANCOCK TOWNS DRIVE IS INCORRECT
AND MUST BE RE-DRAWN.
************************************************************
REVIEW DEPARTMENT---------PLANNING
REVIEWER / PHONE #--------CHRIS HALE / (804) 717-6042
NAME OF PLAN--------------HANCOCK VILLAGE
PLAN NUMBER---------------16TS0217
ORIGINAL PLAN DATE--------02/03/16
LATEST PLAN DATE----------02/03/16
DEPT. REC'D. DATE---------02/08/16
ACCEPTED FOR REVIEW-------03/08/16
SUBMITTAL NUMBER----------ONE
REVIEW DATE---------------04/05/16
RECOMMENDATION------------REVISION REQUIRED
TABLE REVIEW--------------NO
01. PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT
10 FULL SETS TO THE PLANNING DEPARTMENT FOR YOUR NEXT
REVIEW. PROVIDE A COMPLETE RESPONSE TO COMMENTS FOR ALL
DEPARTMENTS TO THE PLANNING DEPARTMENT. BELOW EACH COMMENT
DESCRIBE HOW YOU HAVE ADDRESSED EACH REVIEW COMMENT.
INDICATE WHICH SHEETS SHOW THE REQUIRED CHANGES.
PROVIDE A TRANSMITTAL LETTER TO DESCRIBE ANY CHANGES TO THE
PLANS NOT CAUSED BY THE STAFF REVIEW COMMENTS.
02. PUT THE CHESTERFIELD COUNTY PRELIMINARY PLAT NUMBER
16TS0217 IN THE LOWER RIGHT CORNER OF EACH SHEET OF THE
PRELIMINARY PLAT. PUT THE CHESTERFIELD COUNTY SCHEMATIC
PLAN NUMBER 16PS0222 IN THE LOWER RIGHT CORNER OF EACH
SHEET OF THE SCHEMATIC PLAN.
03. CHANGE THE NAME OF THE TOWNHOUSE DEVELOPMENT TO
'HANCOCK VILLAGE TOWNHOMES'. UPDATE THE TITLE ON THE
PRELIMINARY PLAT.
04. THE SCHEMATIC PLAN 16PS0222 HAS BEEN SUBMITTED FOR
REVIEW. THE SCHEMATIC PLAN IS TO DEMONSTRATE AN APPROPRIATE
RELATIONSHIP AND TRANSITION BETWEEN THE TOWNHOMES AND THE
REAR OF THE SHOPPING CENTER. APPROVAL OF THE PRELIMINARY
PLAT IS CONTINGENT ON THE APPROVAL OF THE SCHEMATIC PLAN BY
THE PLANNING COMMISSION.
05. SHOW MORE CLEARLY ON THE PRELIMINARY PLAT AND SCHEMATIC
PLAN PROPERTY LINES BETWEEN ADJACENT PARCELS (WALMART AND
COLE MT CHFLD).
06. THE SCHEMATIC PLAN 16PS0222 DOES NOT SHOW AN ADEQUATE
BUFFER SEPARATING THE TOWNHOMES FROM THE REAR OF THE
SHOPPING CENTER. IT IS RECOMMENDED THAT THE ENTIRE LENGTH
OF THE EXISTING BERM AT THE REAR OF THE SHOPPING CENTER, AT
ITS CURRENT HEIGHT, REMAIN IN PLACE WITH THE USE OF
RETAINING WALLS. SOLID PRIVACY FENCING AND MULTIPLE ROW
EVERGREEN TREE PLANTINGS AT THE TOP OF THE BERM SHOULD ALSO
BE PROVIDED. THE CONCEPT PLAN PROVIDED BY THE PLANNING
DEPARTMENT SHOWS THAT THIS CAN BE ACHIEVED WITHOUT A
REDUCTION IN THE PROPOSED NUMBER OF LOTS.
07. IN THE CROSS SECTION SHOWN ON THE SCHEMATIC PLAN,
PROVIDE MORE DETAIL ON THE TOWNHOMES SUCH AS GARAGES ON THE
GROUND LEVEL, SECOND FLOOR DECKS, ETC.
08. IN THE CROSS SECTIONS SHOWN ON THE SCHEMATIC PLAN, SHOW
EVERGREEN TREES AT A HEIGHT OF 6 FEET TO ACCURATELY
REPRESENT SCREENING AT TIME OF PLANTING. ALSO SHOW A SIX
FOOT PRIVACY FENCE AT THE TOP OF BERM ON THE SECTIONS.
09. PROVIDE A PEDESTRIAN NETWORK AND PEDESTRIAN CONNECTIONS
BETWEEN THE TOWNHOME DEVELOPMENT AND THE SHOPPING CENTER.
PROVIDE WALKS ON BOTH SIDES OF ALL STREETS. PROVIDE WALKS
FROM THE WESTERN END OF HANCOCK TOWNS DRIVE CONNECTING TO
THE SHOPPING CENTER. A POTENTIAL ROUTE THROUGH THE WETLANDS
AND AROUND THE BMP HAS BEEN SUGGESTED BY THE PLANNING
DEPARTMENT AS ONE OPTION. TRAILS CAN ALSO COUNT TOWARD
PASSIVE RECREATION REQUIREMENTS.
10. R-TH STANDARDS REQUIRE 10% OF THE SUBDIVISION ACREAGE
AND NO LESS THE 1.5 ACRES BE PROVIDED FOR RECREATIONAL
FACILITIES WITHIN OPEN SPACE. THE PLAYGROUND, WALKS, AND
TRAILS CAN BE USED TO MEET THIS REQUIREMENT. INCLUDE THE
ACREAGE AND PERCENTAGE OF RECREATION AREA PROVIDED IN THE
GENERAL NOTES. 19.1-111.A
11. WITH WALKS AND PUBLIC ACCESS IN THE VICINITY OF THE
BMP, THE BMP SHOULD BE TREATED AS AN AMENITY. THIS CAN BE
ACHIEVED THROUGH PLANTINGS AND ORNAMENTAL FENCING.
12. CLUSTER BOX UNITS WILL NEED TO BE PROVIDED. INDICATE
THE PROPOSED LOCATION OF THE UNITS WITHIN A PROVIDED,
CENTRALLY LOCATED OPEN SPACE AREA THAT IS CONNECTED TO THE
PEDESTRIAN NETWORK.
13. PROVIDE TYPICAL ARCHITECTURAL ELEVATIONS WITH MATERIALS
AND COLORS INDICATED.
************************************************************
REVIEW DEPARTMENT---------PLANNING
REVIEWER / PHONE #--------CHRIS HALE / (804) 717-6042
NAME OF PLAN--------------HANCOCK VILLAGE TOWNHOMES
PLAN NUMBER---------------16TS0217
ORIGINAL PLAN DATE--------02/03/16
LATEST PLAN DATE----------04/15/16
DEPT. REC'D. DATE---------04/15/16
ACCEPTED FOR REVIEW-------04/18/16
SUBMITTAL NUMBER----------TWO
REVIEW DATE---------------05/17/16
RECOMMENDATION------------REVISION REQUIRED
TABLE REVIEW--------------NO
01. PUT A REVISION DATE ON THE RESUBMITTED PLANS. RESUBMIT
10 FULL SETS TO THE PLANNING DEPARTMENT FOR YOUR NEXT
REVIEW. PROVIDE A COMPLETE RESPONSE TO COMMENTS FOR ALL
DEPARTMENTS TO THE PLANNING DEPARTMENT. BELOW EACH COMMENT
DESCRIBE HOW YOU HAVE ADDRESSED EACH REVIEW COMMENT.
INDICATE WHICH SHEETS SHOW THE REQUIRED CHANGES.
PROVIDE A TRANSMITTAL LETTER TO DESCRIBE ANY CHANGES TO THE
PLANS NOT CAUSED BY THE STAFF REVIEW COMMENTS.
02. THE SCHEMATIC PLAN 16PS0222 HAS BEEN SUBMITTED FOR
REVIEW. THE SCHEMATIC PLAN IS TO DEMONSTRATE AN APPROPRIATE
RELATIONSHIP AND TRANSITION BETWEEN THE TOWNHOMES AND THE
SHOPPING CENTER. APPROVAL OF THE PRELIMINARY PLAT IS
CONTINGENT ON THE APPROVAL OF THE SCHEMATIC PLAN BY
THE PLANNING COMMISSION.
03. PROVIDE A PEDESTRIAN NETWORK AND PEDESTRIAN CONNECTIONS
BETWEEN THE TOWNHOME DEVELOPMENT AND THE SHOPPING CENTER.
PROVIDE WALKS FROM THE WESTERN END OF HANCOCK TOWNS DRIVE
CONNECTING TO THE SHOPPING PEDESTRIAN NETWORK IN THE
VICINITY OF THE PARKING LOT ON THE WEST SIDE OF PARCEL
722-670-0583. A POTENTIAL ROUTE THROUGH THE WETLANDS
AND AROUND THE BMP HAS BEEN SUGGESTED BY THE PLANNING
DEPARTMENT AS ONE OPTION. ELEVATED BOARDWALK TRAILS WOULD
NOT CREATE WETLAND IMPACTS (COORDINATE WITH EE). TRAILS CAN
COUNT TOWARD PASSIVE RECREATION REQUIREMENTS.
04. IF WALKS AND PUBLIC ACCESS ARE LOCATED IN AREAS
PROVIDING VIEWS OF THE BMP, THEN THE BMP SHOULD BE TREATED
AS AN AMENITY. THIS CAN BE ACHIEVED THROUGH PLANTINGS AND
ORNAMENTAL FENCING.
05. CLUSTER BOX UNITS WILL NEED TO BE PROVIDED. INDICATE
THE PROPOSED LOCATION OF THE UNITS ON THE PRELIMINARY PLAT
WITHIN A PROVIDED, CENTRALLY LOCATED OPEN SPACE AREA THAT
IS CONNECTED TO THE PEDESTRIAN NETWORK.
06. PER CONDITION 12 OF ZONING CASE 97SN0291:
THE LAST KNOWN PRESIDENT OF THE ASHBROOK COMMUNITY
ASSOCIATION SHALL BE MAILED NOTICES BY THE
OWNER / DEVELOPER OF ANY SITE PLAN SUBMISSION TO
CHESTERFIELD COUNTY PRIOR TO SITE PLAN APPROVAL (WILLIAM
MEGGINSON, PRESIDENT, MEGGMOBILE@GMAIL.COM, 241-8262). THE
OWNER DEVELOPER SHALL PROVIDE THE PLANNING DEPARTMENT
WITH EVIDENCE OF SUCH MAILING.
************************************************************
REVIEW DEPARTMENT : FIRE DEPARTMENT
REVIEWER / PHONE # : ANTHONY BATTEN / 717-6167
PLAN NAME : HANCOCK VILLAGE
PLAN NUMBER: 16TS0217
ORIGINAL PLAN DATE : 2/3/16
LATEST PLAN DATE : 2/3/16
REVIEW DATE : 3/14/16
DEPARTMENT RECEIVED DATE: 3/8/16
SUBMITTAL NUMBER : 1ST REVIEW
STATUS : APPROVED
TABLE REVIEW: YES
COMMENTS:
1. THE TENATIVE IS APPROVED AS SUBMITTED.
2. HYDRANT REQUIREMENTS AND LOCATIONS SHOWN ON THE
TENTATIVE PLAN MAY NOT BE ACCEPTABLE. HYDRANT(S)
REQUIRED AND THEIR LOCATION WILL BE EVALUATED AT
THE TIME OF CONSTRUCTION PLAN REVIEW.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT : FIRE DEPARTMENT
REVIEWER / PHONE # : ANTHONY BATTEN / 717-6167
PLAN NAME : HANCOCK VILLAGE
PLAN NUMBER: 16TS0217
ORIGINAL PLAN DATE : 2/3/16
LATEST PLAN DATE : 4/15/16
REVIEW DATE : 4/22/16
DEPARTMENT RECEIVED DATE: 4/22/16
SUBMITTAL NUMBER : 2ND REVIEW
STATUS : APPROVED
TABLE REVIEW: YES
COMMENTS:
1. THE TENATIVE IS APPROVED AS SUBMITTED.
2. HYDRANT REQUIREMENTS AND LOCATIONS SHOWN ON THE
TENTATIVE PLAN MAY NOT BE ACCEPTABLE. HYDRANT(S)
REQUIRED AND THEIR LOCATION WILL BE EVALUATED AT
THE TIME OF CONSTRUCTION PLAN REVIEW.
PLAN NAME: HANCOCK VILLAGE
REVIEW DEPARTMENT: ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE: REBECCAH P. WARD / 748-1977
PLAN NUMBER: 16TS0217
ORIGINAL PLAN DATE: 02/03/16
LATEST SUBMISSION DATE: 02/03/16
REVIEW DATE: 04/06/16
SUBMITTAL NUMBER: 1
STATUS: REVISION REQUESTED
TABLE REVIEW: NO
THE ENVIRONMENTAL ENGINEERING DEPARTMENT PRESENTS THE
FOLLOWING PRELIMINARY COMMENTS AND OBSERVATIONS PERTAINING
TO THE ABOVE REFERENCED PRELIMINARY PLAT DATED 02/06/16,
RECEIVED BY THE PLANNING DEPARTMENT FOR REVIEW ON 03/08/16
AND BY THE ENVIRONMENTAL ENGINEERING DEPARTMENT ON 03/08/16.
PLEASE SPECIFY THE TENTATIVE CASE NUMBER 16TS0217 ON SHEET
1.
THERE ARE TWO STREETS LABELED WITH THE STREET NAME OF
HANCOCK TOWNS DRIVE. PLEASE REVISE ONE OF THESE STREETS TO
LANE OR WAY, OR TO ANOTHER NAME APPROVED BY RICHMOND
REGIONAL PLANNING DISTRICT COMMISSION.
NOTE 2 INDICATES CBPA COMPLIANCE IS ACHIEVED THROUGH AN
ON-SITE WET POND. THE PRELIMINARY CBPA CALCULATIONS SHOW
ADDITIONAL BMPS ARE REQUIRED TO PROVIDE THE REQUIRED
PHOSPHORUS REMOVAL. PLEASE ADDRESS.
PLEASE LABEL THE PROPOSED PRELIMINARY POND ELEVATIONS.
THE EXISTING TOPOGRAPHY SHOWN ON THE PRELIMINARY PLAT IS NOT
CONSISTENT WITH THE EXISTING TOPOGRAPHY SHOWN ON THE
SCHEMATIC PLAN. PLEASE CLARIFY THE DISCREPANCY. THE
TOPOGRAPHY SHOWN ON THE SCHEMATIC PLAN SEEMS TO BE MORE
CONSISTENT WITH THE CURRENT FIELD CONDITIONS.
PLEASE SHOW THE PROPOSED SWM/BMP EASEMENT AND 50-FOOT
VEGETATIVE PERIMETER YARD, AS WELL AS THE LOCATION OF THE
BMP MAINTENANCE ACCESS DRIVE AND ACCESS EASEMENT.
PLEASE PROVIDE ON THE TENTATIVE PLAT THE SPECIFIC NAME OF
THE INDIVIDUAL WHO PERFORMED THE WETLANDS DELINEATION SO
THAT IT MAY BE CONFIRMED THAT HE OR SHE IS ON THE APPROVED
WETLANDS DELINEATOR LIST.
PLEASE CLARIFY ON THE PLAN SHEET WHAT WILL HAPPEN TO THE
EXISTING SEDIMENT BASIN ENCROACHING ONTO THE PROPERTY.
PRIOR TO APPROVAL OF THE HANCOCK VILLAGE TENTATIVE, THE
DEVELOPER WILL SUBMIT A LETTER OF ACKNOWLEDGEMENT OF THE
CONDITION REGARDING MASONRY EMBELLISHMENTS WITHIN THE VDOT
CLEAR ZONE. THIS ACKNOWLEDGEMENT IS THE RESPONSIBILITY OF
THE DEVELOPER AND NOT HIS REPRESENTATIVE AS HE IS ULTIMATELY
RESPONSIBLE FOR REMOVAL OF HEADWALLS IN ALL NEW SUBDIVISIONS
SHOULD IT BECOME NECESSARY. A DRAFT OF THAT LETTER IS
ENCLOSED.
CBPA/USCW:
1. PLEASE CLEARLY SHOW AND LABEL THE DRAINAGE AREA FOR THE
PROPOSED BMP.
2. PLEASE LABEL THE PRELIMINARY CBPA PLAN AS THE
"PRELIMINARY CBPA COMPLIANCE PLAN".
3. PLEASE PROVIDE A TYPICAL LOT FOOTPRINT FOR EACH TYPE OF
LOT.
4. PLEASE PROVIDE A TYPICAL ROAD SECTION FROM THE BACK TO
CURB TO BACK OF CURB.
5. THE IMPERVIOUS AREA FOR THE ALLEY DOES NOT APPEAR TO BE
INCLUDED IN THE SITE AREA IMPERVIOUS AREA BREAKDOWN. PLEASE
REVISE.
6. THE PROPOSED BMP IS NOT PROVIDING ALL OF THE REQUIRED
PHOSPHORUS REMOVAL. THIS SITE IS LOCATED WITHIN THE UPPER
SWIFT CREEK WATERSHED; THEREFORE, ALL WATER QUALITY REMOVAL
MUST BE PROVIDED USING ON-SITE BMPS. PLEASE ADDRESS.
7. ZONING CASES 95SN0278 AND 97SN0291, WHICH INCLUDE THIS
PROPERTY, INCLUDE A CONDITION THAT ALL IMPERVIOUS AREAS
SHALL DRAIN THROUGH A BMP. THE DRAINAGE AREA TO THE
PROPOSED BMP DOES NOT APPEAR TO INCLUDE ALL OF THE PROPOSED
IMPERVIOUS AREA SHOWN ON THE PLAN. PLEASE REVISE TO VERIFY
ALL PREFERRED CONDITIONS ARE ADDRESSED.
8. THERE ARE TWO STREETS LABELED WITH THE STREET NAME OF
HANCOCK TOWNS DRIVE. PLEASE REVISE ONE OF THESE STREETS TO
LANE OR WAY, OR TO ANOTHER NAME APPROVED BY RICHMOND
REGIONAL PLANNING DISTRICT COMMISSION.
9. PLEASE LABEL THE PROPOSED PRELIMINARY POND ELEVATIONS.
NOTES:
PLEASE PROVIDE A WRITTEN RESPONSE IN THE MARGIN OF A COPY OF
THESE COMMENTS WITH YOUR TENTATIVE PLAT REVISIONS.
PRIOR TO APPROVAL OF THE CONSTRUCTION PLAN, THE FINAL
ALIGNMENT OF THE SANITARY SEWER LINE AND EASEMENT ADJACENT
TO THE PROPOSED SWM/BMP MUST BE APPROVED BY BOTH THE
DEPARTMENT OF ENVIRONMENTAL ENGINEERING AND THE DEPARTMENT
OF PUBLIC UTILITIES.
TENTATIVE CONDITIONS COULD INCLUDE, BUT NOT BE LIMITED TO
THE FOLLOWING:
1. PER ZONING CASES 95SN0278 AND 97SN0291, ALL IMPERVIOUS
AREAS SHALL DRAIN THROUGH A BMP.
2. THE BMP'S INITIAL, PREDOMINANT WATER-QUALITY FUNCTION
SHALL BE SEDIMENT CONTROL; THE IMPLEMENTATION OF WHICH SHALL
BE COORDINATED WITH THE FIRST PORTION OF THE PROJECT THAT
DRAINS IN ITS DIRECTION.
3. THE PEDESTRIAN-ACCESS FACILITIES DESIGN AS SHOWN ON THE
TENTATIVE SHALL BE INCLUDED IN THE ROAD AND DRAINAGE PLANS
THAT MUST BE APPROVED BY BOTH VDOT AND THE ENVIRONMENTAL
ENGINEERING DEPARTMENT. ROAD RIGHT-OF-WAY SHALL BE WIDE
ENOUGH TO ENCOMPASS THE PEDESTRIAN-ACCESS FACILITIES IF THE
SIDEWALKS MEET STATE CRITERIA.
4. GRADING ON INDIVIDUAL LOTS WILL BE PROVIDED SO THAT EACH
PROPERTY WILL HAVE A SURFACE DRAINAGE CONFIGURATION
FUNCTIONING INDEPENDENTLY FROM ITS ADJACENT PROPERTIES.
5. A DAM-FAILURE ANALYSIS SHALL, AT A MINIMUM, BE PERFORMED
BASED ON AN OVER-TOPPING BREACH OF THE DAM EMBANKMENT DURING
A 100 YEAR STORM EVENT. CRITERIA PER THE VIRGINIA DAM
SAFETY ACT WILL TAKE PRECEDENCE. EXISTING OR PROPOSED HOMES
SHALL BE OUTSIDE OF THE DAM FAILURE INUNDATION LIMITS.
6. THE DESIGN AND CONSTRUCTION OF THE SWM/BMPS THAT WILL BE
COUNTY MAINTAINED FACILITIES SHALL BE SUBJECT TO DOCUMENTED
GEOTECHNICAL APPROVAL. THE SERVICES THAT MUST BE PROVIDED
BY THE GEOTECHNICAL ENGINEER SHALL INCLUDE FULL-TIME
GEOTECHNICAL INSPECTION PAID FOR BY THE DEVELOPER. THAT
FULL-TIME INSPECTION SHALL INCLUDE BUT NOT BE LIMITED TO THE
FOLLOWING:
A. PARTICIPATION/INPUT INTO THE DESIGN PROCESS AS NECESSARY
TO FACILITATE THE APPROVAL PROCESS OF THE INDEPENDENT
GEOTECHNICAL CONSULTANT. OBSERVATION, TESTING AND
DOCUMENTATION OF:
I. SUITABLE SUB-GRADES TO RECEIVE COMPACTED STRUCTURAL FILL
FOR EARTH DAM CONSTRUCTION.
II. THE CUT-OFF TRENCH, SPILLWAY PIPE, DRAINAGE BLANKET,
RISER STRUCTURE, AND CONCRETE CHUTE SPILLWAY SUB-GRADES AS
APPLICABLE TO EVALUATE WHETHER SUITABLE SOIL IS PRESENT AT
BEARING GRADE TO VERIFY PROPER INSTALLATION.
III. REINFORCING STEEL, IF REQUIRED, TO EVALUATE ITS
CONFORMANCE WITH THE PROJECT PLANS AND SPECIFICATIONS.
7. THE FACILITY CERTIFICATION PROCESS SHALL BE PERFORMED BY
AN ENGINEERING/SURVEYING PROFESSIONAL APPROVED BY THE COUNTY
AT THE OWNER'S EXPENSE.
8. THE NAME OF THE GEOTECHNICAL PROFESSIONAL WHO WILL
PROVIDE THE GEOTECHNICAL APPROVAL ON THE DAM WILL BE
FURNISHED PRIOR TO THE ISSUANCE OF THE LAND DISTURBANCE
PERMIT.
9. THE 100-YEAR FLOODPLAIN SURROUNDING THE WETLANDS WILL BE
SHOWN AS FIELD LOCATED ON THE CONSTRUCTION PLANS AND SHALL
BE RE-FIELD VERIFIED PRIOR TO THE ISSUANCE OF A BUILDING
PERMIT. AN NBP SHALL BE STIPULATED FOR THE AFFECTED LOTS.
10. THE FLOODPLAIN AS SHOWN ON THE APPROVED CONSTRUCTION
PLANS AND THE RECORDED SUBDIVISION PLAT SHALL BE THE RESULT
OF HYDROLOGIC AND HYDRAULIC ENGINEERING METHODS AND
ASSUMPTIONS WHICH ARE APPROVED BY THE ENVIRONMENTAL
ENGINEERING DEPARTMENT.
11. AS DIRECTED BY ENVIRONMENTAL ENGINEERING, ENGINEERED
FILLING, GRADING, AND DRAINAGE IMPROVEMENTS SHALL BE
INCLUDED IN THE CONSTRUCTION PLANS FOR THOSE LOTS IMPACTED
BY THE CONCENTRATION OF STORMWATER RUNOFF. THE AFFECTED LOTS
SHALL BE ANNOTATED WITH AN NBP.
12. PRIOR TO CONSTRUCTION PLAN APPROVAL, DOCUMENTATION MUST
BE PROVIDED TO ENVIRONMENTAL ENGINEERING THAT CERTAIN
PROPERTY OWNERS HAVE BEEN NOTIFIED OF THE PROPOSED
CONSTRUCTION ACTIVITY.
13. SPECIAL UPPER SWIFT CREEK WATERSHED END TREATMENT AS
DIRECTED BY THE ENVIRONMENTAL ENGINEERING DEPARTMENT WILL BE
PLACED IN THE VICINITY OF THE TERMINUS OF MANMADE STORM
DRAINAGE OUTFALLS. THE DI-7 END TREATMENTS SHALL BE EXCLUDED
FROM WITHIN THE LIMITS OF LOTS.
14. UNLESS OTHERWISE APPROVED, THE SPILLWAY STRUCTURE FOR
WET PONDS SHALL BE A CONCRETE WEIR.
15. ENVIRONMENTAL ENGINEERING MAY IMPOSE MORE RIGOROUS
EROSION AND SEDIMENT CONTROL MEASURES THAN THAT WHICH IS
PROVIDED BY THE MINIMUM STANDARDS FOUND IN THE VIRGINIA
EROSION AND SEDIMENT CONTROL HANDBOOK.
16. ALL ROADS AND DRAINAGE DESIGN INFORMATION AND
CONSTRUCTION SPECIFICATIONS REQUIRED IN THE CONSTRUCTION
PLANS FOR ROADS SHALL ALSO APPLY TO THE ALLEYS.
17. THE ALLEYS SHALL FUNCTION AS STORM WATER CONVEYANCE
SYSTEMS SUCH THAT THE LOW SIDE OF THE ALLEY WILL CORRESPOND
TO AN INCREMENTAL DRAINAGE AREA RIDGE LINE. THE ALLEY
TYPICAL SECTION CAN BE AN INVERTED CROWN WITH A 1-INCH PER
FOOT CROSS SLOPE SUCH THAT THERE WILL BE A MINIMUM 6-INCHES
OF ELEVATION DIFFERENCE BETWEEN THE EDGE OF PAVEMENT AND
CENTERLINE IF THE ALLEY WIDTH WERE TO BE 12-FEET OR CURB AND
GUTTER MAY BE USED.
18. THE 100-YEAR STORM SHALL NOT EXCEED THE CONTAINMENT
DEPTH OF THE ALLEYS. UNLESS OTHERWISE APPROVED, THE ENTIRE
ALLEY SHALL BE IN A CUT SECTION.
19. STORM WATER IN THE ALLEYS SHALL BE PICKED UP BY GRATED
INLETS INTO WHICH THE INVERTED CROWNS WOULD FLOW AND BE
DISCHARGED VIA STORM SEWER OR OTHER METHOD APPROVED BY THE
ENVIRONMENTAL ENGINEERING DEPARTMENT.
20. ROOF GUTTERS AND DOWNSPOUTS SHALL BE INSTALLED ON THE
DWELLINGS. ALL ROOF DRAINAGE LEADERS WILL BE TIED DIRECTLY
INTO MINIMUM 12" ONSITE STORM SEWERS OR OTHER STABLE
CONVEYANCE SYSTEMS DEEMED APPROPRIATE BY THE ENVIRONMENTAL
ENGINEERING DEPARTMENT.
(PLEASE PLACE ON DEVELOPER LETTERHEAD)
(DATE)
KIRKLAND A. TURNER, DIRECTOR
CHESTERFIELD COUNTY PLANNING DEPARTMENT
P. O. BOX 40
CHESTERFIELD, VIRGINIA 23832
RE: ENTRANCE EMBELLISHMENTS (____________ TENTATIVE)
DEAR MR. TURNER:
AS DEVELOPER OF THE PROPOSED __________________ SUBDIVISION,
I AM AWARE THAT THE FOLLOWING NOTE IS NOW REQUIRED NOT ONLY
ON TENTATIVES BUT ALSO ON RECORD PLATS.
"NO STRUCTURE EMBELLISHMENTS WILL BE ALLOWED ON VDOT
RIGHT-OF-WAY WITHOUT THE COMMITMENT OF, OR THE ISSUANCE OF,
A VDOT LAND USE PERMIT. WITHIN THE 10' CLEAR ZONE (MEASURED
FROM THE EDGE OF THE ROADWAY'S PAVEMENT OUT
10'), NO STRUCTURE EMBELLISHMENT WILL BE PERMITTED THAT IS
CLOSER THAN 3' FROM THE EDGE OF PAVEMENT OF THE PUBLIC
STREET OR HIGHER THAN 6" ABOVE THE SURFACE OF THE DRIVE."
I WILL DO ALL POSSIBLE TO PROVIDE THE CORRECT INFORMATION
FOR BUILDERS OR CITIZENS CONSTRUCTING ENTRANCE
EMBELLISHMENTS.
I AM ALSO AWARE THAT, PRIOR TO STATE ACCEPTANCE OF THE
ROADS, I AM RESPONSIBLE FOR REMOVING EMBELLISHMENTS THAT DO
NOT MEET STATE STANDARDS.
SINCERELY,
DEVELOPER NAME (PRINTED)
DEVELOPER SIGNATURE
(DATE)
****************************************
PLAN NAME: HANCOCK VILLAGE
REVIEW DEPARTMENT: ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE: REBECCAH P. WARD / 748-1977
PLAN NUMBER: 16TS0217
ORIGINAL PLAN DATE: 02/03/16
LATEST SUBMISSION DATE: 04/15/16
REVIEW DATE: 05/10/16
SUBMITTAL NUMBER: 2
STATUS: REVISION REQUESTED
TABLE REVIEW: NO
THE ENVIRONMENTAL ENGINEERING DEPARTMENT PRESENTS THE
FOLLOWING PRELIMINARY COMMENTS AND OBSERVATIONS PERTAINING
TO THE ABOVE REFERENCED PRELIMINARY PLAT DATED LAST REVISED
04/15/16, RECEIVED BY THE PLANNING DEPARTMENT FOR REVIEW ON
04/18/16 AND BY THE ENVIRONMENTAL ENGINEERING DEPARTMENT ON
04/21/16.
THE BUILDING SETBACK LINE IS LABELED AS BSL ON SHEET 1 OF 2;
HOWEVER, IT IS LISTED AS BS IN THE CALLOUT LEGEND ON SHEET 2
OF 2. PLEASE REVISE.
THERE APPEAR TO BE TWO SETS OF CONTOURS SHOWN ON THE REVISED
PRELIMINARY PLAT. PLEASE REVISE.
NOTE 4 UNDER GENERAL NOTES INDICATES THE CONTOURS SHOWN WERE
CREATED FROM COUNTY GIS. THE CONTOURS ARE NOT CONSISTENT
WITH COUNTY GIS AND APPEAR TO BE TAKEN FROM A FIELD SURVEY.
PLEASE CLARIFY AND REVISE THE NOTE ACCORDINGLY.
CBPA/USCW:
1. THERE ARE CURRENTLY FOUR DIFFERENT DRAINAGE AREAS SHOWN
ON THE PRELIMINARY CBPA COMPLIANCE PLAN; HOWEVER ONLY ONE IS
LABELED AS THE BMP DRAINAGE AREA. PLEASE CLEARLY LABEL BOTH
THE ONSITE AND OFFSITE DRAINAGE AREAS TO THE POND WITH THE
AREA PROVIDED FOR EACH DRAINAGE AREA. IN ADDITION, PLEASE
CLARIFY THE TWO ADDITIONAL DRAINAGE AREAS SHOWN ON THE PLAN
AND PROVIDE INFORMATION ON WHERE THESE AREAS DRAIN.
2. THE BMP DRAINAGE AREA IS NOT CONSISTENT WITH THE
TOPOGRAPHY SHOWN. IT IS UNCLEAR IF THE EXISTING DITCH TO
THE EXISTING SEDIMENT BASIN WILL BE DIVERTED TO THE PROPOSED
BMP FACILITY, OR IF OFFSITE IMPROVEMENTS ARE PROPOSED TO
PREVENT TRAPPING DRAINAGE BETWEEN THIS DEVELOPMENT AND THE
SHOPPING CENTER. AT THIS TIME, IT APPEARS THAT THE EXISTING
DITCH WOULD DRAIN TO THE PROPOSED BMP; THEREFORE, THE
DRAINAGE AREA AND CALCULATIONS SHOULD BE ADJUSTED
ACCORDINGLY. IF OFFSITE IMPROVEMENTS ARE PROPOSED,
ADDITIONAL PROFFERS MAY BE REQUIRED.
3. THE IMPERVIOUS AREA FOR THE ALLEY STILL DOES NOT APPEAR
TO BE INCLUDED IN THE SITE AREA IMPERVIOUS AREA BREAKDOWN.
IT IS INCLUDED IN THE BMP ONSITE CALCULATIONS; HOWEVER, IT
IS NOT SHOWN ON THE SITE AREA INFORMATION. PLEASE REVISE.
4. THE AREAS LISTED IN THE LOTS UNDER THE SITE AREA
INFORMATION IS 5.14 ACRES; HOWEVER, UNDER THE ONSITE TO BMP1
INFORMATION IT IS LISTED AS 5.54 ACRES. PLEASE CLARIFY.
5. THE CONTRIBUTING DRAINAGE AREA USED IN THE CALCULATIONS
TO DETERMINE THE REQUIRED VOLUME OF THE PERMANENT POOL DOES
NOT INCLUDE THE OFFSITE DRAINAGE AREA. PLEASE REVISE.
6. A BMP DESIGN 7 WET POND REQUIRES THE VOLUME OF THE
PERMANENT POOL EQUAL TO 10 TIMES THE VOLUME OF RUNOFF
GENERATED BY THE MEAN STORM OVER THE CONTRIBUTING DRAINAGE
AREA. PLEASE VERIFY THIS VOLUME CAN BE PROVIDED BY THE
PROPOSED BMP.
7. PLEASE VERIFY ADEQUATE SPACE IS PROVIDED WITHIN THE
PROPOSE BMP LAYOUT THE REQUIRED AQUATIC BENCH.
8. THERE APPEAR TO BE TWO SETS OF CONTOURS SHOWN ON THE
PRELIMINARY CBPA COMPLIANCE PLAN. PLEASE REVISE.
NOTES:
PRIOR TO APPROVAL OF THE CONSTRUCTION PLAN, THE FINAL
ALIGNMENT OF THE SANITARY SEWER LINE AND EASEMENT ADJACENT
TO THE PROPOSED SWM/BMP MUST BE APPROVED BY BOTH THE
DEPARTMENT OF ENVIRONMENTAL ENGINEERING AND THE DEPARTMENT
OF PUBLIC UTILITIES.
TENTATIVE CONDITIONS COULD INCLUDE, BUT NOT BE LIMITED TO
THE FOLLOWING:
1. PER ZONING CASES 95SN0278 AND 97SN0291, ALL IMPERVIOUS
AREAS SHALL DRAIN THROUGH A BMP.
2. THE BMP'S INITIAL, PREDOMINANT WATER-QUALITY FUNCTION
SHALL BE SEDIMENT CONTROL; THE IMPLEMENTATION OF WHICH SHALL
BE COORDINATED WITH THE FIRST PORTION OF THE PROJECT THAT
DRAINS IN ITS DIRECTION.
3. THE PEDESTRIAN-ACCESS FACILITIES DESIGN AS SHOWN ON THE
TENTATIVE SHALL BE INCLUDED IN THE ROAD AND DRAINAGE PLANS
THAT MUST BE APPROVED BY BOTH VDOT AND THE ENVIRONMENTAL
ENGINEERING DEPARTMENT. ROAD RIGHT-OF-WAY SHALL BE WIDE
ENOUGH TO ENCOMPASS THE PEDESTRIAN-ACCESS FACILITIES IF THE
SIDEWALKS MEET STATE CRITERIA.
4. GRADING ON INDIVIDUAL LOTS WILL BE PROVIDED SO THAT EACH
PROPERTY WILL HAVE A SURFACE DRAINAGE CONFIGURATION
FUNCTIONING INDEPENDENTLY FROM ITS ADJACENT PROPERTIES.
5. A DAM-FAILURE ANALYSIS SHALL, AT A MINIMUM, BE PERFORMED
BASED ON AN OVER-TOPPING BREACH OF THE DAM EMBANKMENT DURING
A 100 YEAR STORM EVENT. CRITERIA PER THE VIRGINIA DAM
SAFETY ACT WILL TAKE PRECEDENCE. EXISTING OR PROPOSED HOMES
SHALL BE OUTSIDE OF THE DAM FAILURE INUNDATION LIMITS.
6. THE DESIGN AND CONSTRUCTION OF THE SWM/BMPS THAT WILL BE
COUNTY MAINTAINED FACILITIES SHALL BE SUBJECT TO DOCUMENTED
GEOTECHNICAL APPROVAL. THE SERVICES THAT MUST BE PROVIDED
BY THE GEOTECHNICAL ENGINEER SHALL INCLUDE FULL-TIME
GEOTECHNICAL INSPECTION PAID FOR BY THE DEVELOPER. THAT
FULL-TIME INSPECTION SHALL INCLUDE BUT NOT BE LIMITED TO THE
FOLLOWING:
A. PARTICIPATION/INPUT INTO THE DESIGN PROCESS AS NECESSARY
TO FACILITATE THE APPROVAL PROCESS OF THE INDEPENDENT
GEOTECHNICAL CONSULTANT. OBSERVATION, TESTING AND
DOCUMENTATION OF:
I. SUITABLE SUB-GRADES TO RECEIVE COMPACTED STRUCTURAL FILL
FOR EARTH DAM CONSTRUCTION.
II. THE CUT-OFF TRENCH, SPILLWAY PIPE, DRAINAGE BLANKET,
RISER STRUCTURE, AND CONCRETE CHUTE SPILLWAY SUB-GRADES AS
APPLICABLE TO EVALUATE WHETHER SUITABLE SOIL IS PRESENT AT
BEARING GRADE TO VERIFY PROPER INSTALLATION.
III. REINFORCING STEEL, IF REQUIRED, TO EVALUATE ITS
CONFORMANCE WITH THE PROJECT PLANS AND SPECIFICATIONS.
7. THE FACILITY CERTIFICATION PROCESS SHALL BE PERFORMED BY
AN ENGINEERING/SURVEYING PROFESSIONAL APPROVED BY THE COUNTY
AT THE OWNER'S EXPENSE.
8. THE NAME OF THE GEOTECHNICAL PROFESSIONAL WHO WILL
PROVIDE THE GEOTECHNICAL APPROVAL ON THE DAM WILL BE
FURNISHED PRIOR TO THE ISSUANCE OF THE LAND DISTURBANCE
PERMIT.
9. THE 100-YEAR FLOODPLAIN SURROUNDING THE WETLANDS WILL BE
SHOWN AS FIELD LOCATED ON THE CONSTRUCTION PLANS AND SHALL
BE RE-FIELD VERIFIED PRIOR TO THE ISSUANCE OF A BUILDING
PERMIT. AN NBP SHALL BE STIPULATED FOR THE AFFECTED LOTS.
10. THE FLOODPLAIN AS SHOWN ON THE APPROVED CONSTRUCTION
PLANS AND THE RECORDED SUBDIVISION PLAT SHALL BE THE RESULT
OF HYDROLOGIC AND HYDRAULIC ENGINEERING METHODS AND
ASSUMPTIONS WHICH ARE APPROVED BY THE ENVIRONMENTAL
ENGINEERING DEPARTMENT.
11. AS DIRECTED BY ENVIRONMENTAL ENGINEERING, ENGINEERED
FILLING, GRADING, AND DRAINAGE IMPROVEMENTS SHALL BE
INCLUDED IN THE CONSTRUCTION PLANS FOR THOSE LOTS IMPACTED
BY THE CONCENTRATION OF STORMWATER RUNOFF. THE AFFECTED LOTS
SHALL BE ANNOTATED WITH AN NBP.
12. PRIOR TO CONSTRUCTION PLAN APPROVAL, DOCUMENTATION MUST
BE PROVIDED TO ENVIRONMENTAL ENGINEERING THAT CERTAIN
PROPERTY OWNERS HAVE BEEN NOTIFIED OF THE PROPOSED
CONSTRUCTION ACTIVITY.
13. SPECIAL UPPER SWIFT CREEK WATERSHED END TREATMENT AS
DIRECTED BY THE ENVIRONMENTAL ENGINEERING DEPARTMENT WILL BE
PLACED IN THE VICINITY OF THE TERMINUS OF MANMADE STORM
DRAINAGE OUTFALLS. THE DI-7 END TREATMENTS SHALL BE EXCLUDED
FROM WITHIN THE LIMITS OF LOTS.
14. UNLESS OTHERWISE APPROVED, THE SPILLWAY STRUCTURE FOR
WET PONDS SHALL BE A CONCRETE WEIR.
15. ENVIRONMENTAL ENGINEERING MAY IMPOSE MORE RIGOROUS
EROSION AND SEDIMENT CONTROL MEASURES THAN THAT WHICH IS
PROVIDED BY THE MINIMUM STANDARDS FOUND IN THE VIRGINIA
EROSION AND SEDIMENT CONTROL HANDBOOK.
16. ALL ROADS AND DRAINAGE DESIGN INFORMATION AND
CONSTRUCTION SPECIFICATIONS REQUIRED IN THE CONSTRUCTION
PLANS FOR ROADS SHALL ALSO APPLY TO THE ALLEYS.
17. THE ALLEYS SHALL FUNCTION AS STORM WATER CONVEYANCE
SYSTEMS SUCH THAT THE LOW SIDE OF THE ALLEY WILL CORRESPOND
TO AN INCREMENTAL DRAINAGE AREA RIDGE LINE. THE ALLEY
TYPICAL SECTION CAN BE AN INVERTED CROWN WITH A 1-INCH PER
FOOT CROSS SLOPE SUCH THAT THERE WILL BE A MINIMUM 6-INCHES
OF ELEVATION DIFFERENCE BETWEEN THE EDGE OF PAVEMENT AND
CENTERLINE IF THE ALLEY WIDTH WERE TO BE 12-FEET OR CURB AND
GUTTER MAY BE USED.
18. THE 100-YEAR STORM SHALL NOT EXCEED THE CONTAINMENT
DEPTH OF THE ALLEYS. UNLESS OTHERWISE APPROVED, THE ENTIRE
ALLEY SHALL BE IN A CUT SECTION.
19. STORM WATER IN THE ALLEYS SHALL BE PICKED UP BY GRATED
INLETS INTO WHICH THE INVERTED CROWNS WOULD FLOW AND BE
DISCHARGED VIA STORM SEWER OR OTHER METHOD APPROVED BY THE
ENVIRONMENTAL ENGINEERING DEPARTMENT.
20. ROOF GUTTERS AND DOWNSPOUTS SHALL BE INSTALLED ON THE
DWELLINGS. ALL ROOF DRAINAGE LEADERS WILL BE TIED DIRECTLY
INTO MINIMUM 12" ONSITE STORM SEWERS OR OTHER STABLE
CONVEYANCE SYSTEMS DEEMED APPROPRIATE BY THE ENVIRONMENTAL
ENGINEERING DEPARTMENT.
21. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT FOR THE
HANCOCK VILLAGE TOWNHOMES, A LETTER OF PERMISSION FROM COLE
MT CHFLD (HANCOCK) VA LLC MUST BE OBTAINED TO USE THE
EXISTING SEDIMENT BASIN DURING CONSTRUCTION.
22. ACCUMULATED SEDIMENT IN THE EXISTING DOWNSTREAM BMP ON
THE COLE MT CHFLD (HANCOCK) VA LLC PROPERTY, WHICH IS
RECEIVING RUNOFF FROM PROPOSED SIDEWALKS IN THE OPEN SPACE
ADJACENT TO THE WETLANDS, MUST BE REMOVED PRIOR TO STATE
ACCEPTANCE OF THE PROPOSED ROADS WITHIN THE HANCOCK VILLAGE
TOWNHOMES DEVELOPMENT.
****************************************