Subdivision Review Comments
All Subdivision Review Comments for Case # 16CP0118




For VDOT’s comments please contact Virginia Department of Transportation at (804) 674-2814 or send e-mail to Boris.Solomonov@VDOT.Virginia.gov

For Tentative Subdivision resubmittals:

1. Please note that submittal fees include the original submittal and two (2) additional reviews.

2. A letter of transmittal is required to accompany each submittal.

3. Please verify that Environmental Engineering, Fire, CDOT, VDOT, and Planning have reviewed the submittal before resubmitting. A resubmittal tendered, prior to receiving all the required departments’ review, will be counted as an additional submittal. Go to Case Selection Form or Go to Project List


 
CASE NO: 16CP0118 STATUS: PENDING APPROVAL
PROJECT NAME: NEWMARKET - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: CONSTRUCTION PLAN
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 00 06/16/16 07/13/16 COMPLETE 07/13/16 MCJ 751-2335
FIRE DEPT.--: 00 06/16/16 07/13/16 COMPLETE 06/21/16 JKL 748-1489
PLANNING----: 00 06/16/16 07/13/16 COMPLETE 07/20/16 GWK 706-7691
TRANSPORT.--: 00 06/16/16 07/13/16 COMPLETE 07/13/16 SES 751-4912
UTIL.PLAN.--: 00 06/16/16 07/13/16 COMPLETE 07/07/16 TVM 751-4435
UTILITIES---: 00 06/16/16 07/13/16 ******** ********
UTIL.R.O.W.-: 00 06/16/16 07/13/16 ******** ********
VDOT--------: 00 06/16/16 07/13/16 ******** ********
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: NEWMARKET, SECTION 4
PLAN NUMBER: 16 CP0118
ORIGINAL PLAN DATE: 4/29/16
REVIEW DATE: 7/1/16
LATEST SUBMISSION DATE:
6/17/16 SUBMITTAL NUMBER: 1
STATUS: REVISIONS REQUIRED
TABLE REVIEW: NO
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR
THE ABOVE REFERENCED PROJECT DATED APRIL 29, 2016, WE
MAKE THE FOLLOWING COMMENTS AND RECOMMENDATIONS:
1. A COPY OF VIRGINIA DEPARTMENT OF
TRANSPORTATION'S APPROVAL LETTER REGARDING PAVEMENT
REPLACEMENT, METHOD OF CROSSING, AND ALIGNMENT OF
UTILITY WITH STATE RIGHT OF WAY, AND A COPY OF
ENVIRONMENTAL ENGINEERING'S INITIAL REVIEW LETTER
MUST BE SUBMITTED BEFORE REVISED PLANS ARE SUBMITTED
FOR RE-REVIEW.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION,
A COPY OF THE ENVIRONMENTAL ENGINEERING APPROVAL
LETTER AND/OR ALL OTHER APPLICABLE LOCAL STATE AND
FEDERAL AGENCIES' APPROVAL LETTERS MUST BE RECEIVED
BY THIS DEPARTMENT. IN ADDITION, ALL EASEMENTS NOT
INCLUDED WITH THE SUBDIVISION PLAT MUST BE DEDICATED
WITH A SEPARATE PLAT AND AGREEMENT TO THE COUNTY
PRIOR TO RELEASING THE PROJECT TO THE CONSTRUCTION
SECTION.
3. SHOW ALL EXISTING WATER AND SANITARY SEWERS
USING A "DARK, DASHED" LINE TYPE AND LABEL EACH WITH
THE APPLICABLE COUNTY PROJECT NUMBER THROUGHOUT EACH
OF THE PLAN AND PROFILE VIEWS.
4. PROVIDE A "MISS UTILITY" NOTE ON THE COVER
SHEET.
5. CLEARLY SHOW EACH VALVE THAT IS TO BE USED FOR
CUT OFF PURPOSES DURING EACH WATERLINE TIE IN,
LABELING EACH AS SUCH.
6. PROVIDE 10 L. F. MINIMUM HORIZONTAL SEPARATION
DISTANCES BETWEEN ALL FLUSHING HYDRANTS AND ALL WATER
SERVICES / METER BOXES AT ALL LOCATIONS.
7. REFERENCE THE TYPICAL LOCATION OF WATERLINE IN
CURB AND GUTTER STREETS AS 4.5 L. F. FROM THE BACK OF
CURB THROUGHOUT THE PLANS.
8. RELOCATE THE WATER SERVICE FOR LOT #15 SUCH
THAT IT IS NOT LOCATED BETWEEN THE REDUCER AND
VALVE.
9. SPECIFY EACH WATER SERVICE ? 60 L. F. AS 1"
DIAMETER AND NOTE THIS CONDITION ON EACH APPROPRIATE
LOT IN THE PLAN VIEWS.
10. THIS PROJECT PROPOSES TO TIE INTO A SEWER
"STUB" INSTALLED WITH COUNTY PROJECT #10-0037.
PROCEED AS
FOLLOWS:
A. VERIFY THE LENGTH, DIAMETER, SLOPE AND
MATERIAL OF THE SEWER "STUB" AND SHOW EACH OF
THESE IN THE PROFILE VIEW.
B. SHOW ALL OF THESE FOR THE PROPOSED
EXTENSION AS WELL AS ITS LENGTH.
C. SHOW THE TOTAL DISTANCE BETWEEN
MANHOLES WITH ALL PERTINENT DATA.
"HATCH" ALL LIMITS OF FILL IN THE PROFILE
VIEWS, LABELING EACH AS SUCH.
12. "HATCH" ALL DUCTILE IRON PIPE IN THE PROFILE
VIEWS LABELING IT AS SUCH.
13. PROVIDE COMPLETE PROFILE VIEWS OF ALL PROPOSED
WATER, SANITARY SEWER AND STORM SEWER SHOWN IN THE
SAME PROFILE VIEW. PROVIDE THE EXACT VERTICAL
SEPARATION DISTANCE AT ACHE STORM / SANITARY
CROSSING AND NOTE THAT 1.5 V. F. MINIMUM VERTICAL
SEPARATION IS REQUIRED AT EACH WATERLINE CROSSING
WITH THE STORM / SANITARY SEWERS IN THE PROFILE
VIEWS.
14. REGARDING EACH LOCATION OF VERTICALLY DEFLECTED
WATERLINE AS PER OUR TELEPHONE CONVERSATION.
15. SHOW AND LABEL EACH FIRE HYDRANT IN THE PROFILE
VIEWS.
16. SPECIFY MANHOLE INSERTS FOR EACH PROPOSED
MANHOLE.
17. THOROUGHLY EXAMINE ALL SHEETS TO CORRECT ALL
EXTRANEOUS MARKINGS, OVERLAPPING TEXT, ILLEGIBLE TEXT
AND DRAWING FEATURES, ETC. IN ORDER TO FACILITATE A
CLEAN DRAWING WITH ALL TEXT AND DRAWING FEATURES
COMPLETELY LEGIBLE AND ABUNDANTLY VISIBLE.
18. REVISE THE "MATERIALS LIST" AS NECESSARY.
PLEASE MAKE ALL OF THE SUGGESTED CHANGES PREVIOUSLY
MENTIONED, AND SUBMIT TWO (2) SETS OF REVISED PLANS.
THE OWNER MUST ENTER INTO A COUNTY CONTRACT PRIOR TO
THE START OF CONSTRUCTION. PLEASE SEND ME A COPY OF
THE "ACCEPTED" BID PROPOSAL BETWEEN THE DEVELOPER AND
THE CONTRACTOR SO WE MAY PREPARE THE COUNTY CONTRACT.
THE BID PROPOSAL MUST BE BASED ON THE LATEST REVISED
UTILITIES PLANS REFLECTING THE REVIEWER'S STAMP, AND
ALL WORK MUST BE PERFORMED BY AN ACCEPTABLE UTILITIES
CONTRACTOR. IF PLANS ARE REVISED AFTER CONTRACT
PREPARATION DUE TO A CHANGE BECAUSE OF VIRGINIA
DEPARTMENT OF TRANSPORTATION'S AND/OR ENVIRONMENTAL
ENGINEERING DEPARTMENT'S APPROVAL OF THE ROAD,
DRAINAGE, AND EROSION CONTROL DESIGN OR BECAUSE OF
STATE AGENCIES' REVIEW AND APPROVAL OF THE UTILITIES
DESIGN, A REVISED BID PROPOSAL MAY BE NECESSARY TO
ACCURATELY REFLECT THE LATEST UTILITIES DESIGN AND A NEW
CONTRACT PREPARATION MAY BE NECESSARY AND EXECUTED PRIOR TO
THE START OF CONSTRUCTION.
IF YOU HAVE ANY QUESTIONS, DO NOT HESITATE TO CONTACT ME
AT 748-1343.
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: NEWMARKET, SECTION 4
CASE NUMBER: 16CP0118
LATEST PLAN DATE: 05/15/2016
DEPT. REC'D. DATE: 06/17/2016
SUBMITTAL NUMBER: ONE
REVIEW DATE: 07/13/2016
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: WHIT KIRTLEY / 706-7691
PLAN NAME: NEWMARKET SEC 4
PLAN NUMBER: 16CP0118
ORIGINAL PLAN DATE: 4/29/16
REVIEW DATE: 4/13/16
LATEST SUBMISSION DATE: 5/19/16
ACCEPTED DATE: 6/16/16
SUBMITTAL NUMBER: 1
STATUS: CORRECTIONS REQUIRED
TABLE REVIEW: NO
1. PROVIDE AUTOCAD FILE DEPICTING THE BOUNDARIES OF THIS
CONSTRUCTION PLAN.
2. THE LOTS SHOWN ON THE VICINITY MAP ARE CONFUSING AND
DO NOT MATCH THE PROPOSAL. REVISE TO ONLY SHOW THE
BOUNDARY OF THIS SECTION.
3. PROVIDE AREA THAT IS REMOVED FROM THE TOTAL SITE
AREA AS INDICATED IN 19.1-247 (A)(4)(A) P
4. OVERALL TREE CANOPY PLANS ARE APPROVED AT PART OF THE
PRELIMINARY PLAT PROCESS. PLEASE SUBMIT AN OVERALL PLAN
FOR APPROVAL SEPARATE FROM THIS CONSTRUCTION PLAN.
5. ON THE TREE CANOPY PLAN, INCLUDE THE FOLLOWING
NOTES: "LIMITS OF THE TREE CANOPY PRESERVATION AREAS
SHALL BE SHOWN ON THE SUBDIVISIONPLATS WHERE
APPLICABLE". "TREE CANOPY PRESERVATION AREAS TO
REMAIN UNDISTURBED. NO TREES IN THE TREE CANOPY
SHALL BE REMOVED WITHOUT COUNTY APPROVAL. SUCH
LANGUAGE SHALL BE INCLUDED WITHIN THE COVENANTS,
RESTRICTIONS, AND BYLAWS FOR THIS SUBDIVISION"
6. INDICATE THE PORTIONS OF THE OVERALL PLAN THAT WILL
BE RECORDED WITH THIS SECTION AND LABEL EACH
PORTION WITH THE ACREAGE.
7. INCLUDE TREE PROTECTION TAPE ON THE PHASE 1 AND 2
E&S PLANS. TREE PROTECTION TAPE SHALL BE PLACED ALONG
THE REQUIRED BUFFERS AND ANY TREE CANOPY AREAS.
8. PER 19.1-211, PROVIDE A LANDSCAPE PLAN FOR VISUAL
ENHANCEMENTOF THE BMPS PRIOR TO CONSTRUCTION
PLAN APPROVAL.
9. THERE IS AN ERRONEOUS SHEET INCLUDED BETWEEN
SHEETS C4.1 AND C4.2. THE SHEET IS FOR GREENWICH
WALK AT FOXCREEK. REMOVED THIS SHEET FROM THE PLAN
SET. THERE IS ALSO ANOTHER SHEET BETWEEN C6.1 AND
C6.2 AND BETWEEN C6.3 AND C7.0
10. THE BUILDING ENVELOP FOR LOT 24 EXTENDS PAST THE 8 FOOT
EASEMENT. REVISE SO THAT THE EASEMENT IS THE BUILDING
LINE BOUNDARY ON THAT SIDE.
11. THE BUILDING ENVELOP FOR LOT 14 APPEARS INCORRECT.
REVISE.
CONDITIONS
1. IN CONJUNCTION WITH THE SUBMITTAL OF THE FINAL CHECK
PLATS, THE SUBDIVIDER SHALL FLAG ALL BUFFERS FOR
INSPECTION BY THE PLANNING DEPARTMENT. IF INSUFFICIENT
VEGETATION REMAINS, THE SUBDIVIDER SHALL SUBMIT A
LANDSCAPE PLAN TO THE DIRECTOR OF PLANNING TO ENSURE
COMPLIANCE WITH THE CONDITION. IF CONDITIONS ON SITE
ARE NOT CONDUCIVE TO PLANT SURVIVAL, THE SUBDIVIDER
SHALL PROVIDE SURETY TO THE COUNTY IN THE AMOUNT
REQUIRED TO IMPLEMENT THE PLAN. AN ESTIMATE FROM A
LANDSCAPE CONTRACTOR SHALL SERVE AS THE BASIS FOR THE
SURETY AMOUNT.
NOTES
A. LOTS FRONTING ON THE BULBS OF CUL-DE-SACS SHALL BE
DESIGNED SUCH THAT BUILDING LINES ARE UNIFORM
AROUND THE BULB. (P)
B. A NOTE SHALL BE PLACED ON THE FINAL PLAT THAT
INDICATES THE BUFFERS ARE EXCLUSIVE OF
EASEMENTS, CUT AND FILL SLOPES AND SETBACKS. THE
BUFFERS ARE TO REMAIN UNDISTURBED AND NO ACCESS
IS PERMITTED THROUGH THEM TO ANY ADJACENT ROADS.
(P)
C. STANDARD CONDITIONS PER 17-62 OF THE SUBDIVISION
ORDINANCE. (P)
D. BUILDING ENVELOPES SHALL BE SHOWN ON ALL
BUILDING LOTS THAT ARE IMPACTED BY WETLANDS OR MINING
ACTIVITIES. DIMENSIONED FRONT BUILDING LINES SHALL BE
SHOWN ON ALL LOTS THAT DO NOT ACHIEVE THE REQUIRED LOT
WIDTH AT THE MINIMUM SETBACK DISTANCE. (P)
BUFFERS SHALL COMPLY WITH 19-523 (P)
F. ANY CHANGE IN WHETHER IT STEMS FROM
DEPARTMENT COMMENTS OR AN
ENGINEERING CHANGE REQUESTED BY
THE APPLICANT, MAY GENERATE
ADDITIONAL COMMENTS FROM THE
REVIEWING DEPARTMENTS, RESULTING IN
REQUIRED REVISIONS.
G. ANY BULK REQUIREMENTS (LOT AREA, LOT
WIDTH, SETBACKS, BUILDING ENVELOPES,
ETC.) SHOWN ON THE APPROVED
CONSTRUCTION PLANS WILL BE SUBJECT
TO REVIEW FOR COMPLIANCE AT TIME OF
FINAL CHECK.
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: NEWMARKET SECTION 4
PLAN NUMBER:16CP0118
LATEST REVISION DATE: 4/29/16
REVIEW DATE: 6/21/16
LATEST SUBMISSION DATE: 6/20/16
SUBMITTAL NUMBER: 1ST REVIEW
STATUS: APPROVED
TABLE REVIEW: YES
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
============================================================
============================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : MARIA C. JENKINS/ 751-2335
NAME OF PLAN : NEWMARKET - SECTION 4
SITE PLAN NO. : 16CP0118
LATEST PLAN DATE : 04/29/16
DEPT. REC'D DATE : 06/17/16
SUBMITTAL NUMBER : 1
REVIEW DATE : 07/13/16
RECOMMENDATION : REVISIONS REQUIRED
TABLE REVISION : NO
PLAT PROCESSING : NO
1. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND / OR ACQUIRE ALL APPLICABLE FEDERAL AND / OR
STATE PERMITS IN RELATIONSHIP TO ENVIRONMENTAL FEATURES
INCLUDING BUT NOT LIMITED TO WETLANDS, SURFACE WATERS
(E.G. VSMP PERMIT FOR CONSTRUCTION SITES, GROUND WATER
AND AIR QUALITY) FINAL APPROVAL OF THESE PLANS WILL NOT
RELIEVE YOU OF YOUR RESPONSIBILITY. WETLANDS
DOCUMENTATION MUST BE RECEIVED BY THIS DEPARTMENT PRIOR
TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
2. THIS OFFICE RECOGNIZES THAT THE 10-YEAR PRE/10-YEAR POST
REQUIREMENTS FOR FLOOD PROTECTION MAY BE ADDRESSED BY
DISCHARGING INTO THE 100-YEAR FLOODPLAIN.
== EROSION CONTROL ===
1. AN ITEMIZED EROSION CONTROL COST ESTIMATE MUST BE
SUBMITED FOR REVIEW AND/OR APPROVAL.
2. AS A PREREQUISITE TO THE ISSUANCE OF A LAND
DISTURBANCE PERMIT:
A) A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO
CAROLE CLIBORNE OF THE ENVIRONMENTAL ENGINEERING. THE
AUTOCAD FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD
VERSION 2009 OR EARLIER AND REFERENCED DIRECTLY TO THE
VIRGINIA STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN
THE NAD83 DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A
CD, DVD, OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH
THE SUBDIVISION NAME AND SECTION, SUBDIVISION PLAN
NUMBER, ENGINEERING FIRM AND CAD FILE PREPARER'S NAME
AND PHONE NUMBER. THE FILE MUST CONTAIN THE FOLLOWING,
EACH CLEARLY LABELED IN SEPARATE LAYERS:
I.EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
II. EDGES OF SIDEWALKS;
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
B) FLAGGING AROUND USACOE JURISDICTIONAL WETLANDS,
BUFFERS, AND SENSITIVE AREAS MUST BE VISIBLE.
C) THE LIMITS OF THE RPA MUST BE FLAGGED IN THE FIELD
(SURVEY LOCATED) WITH OPTIC ORANGE SAFETY FENCE
OR SAFETY FENCE PRIOR TO ISSUANCE OF A LAND
DISTURBANCE PERMIT.
D) DOCUMENTATION FROM THE USACOE/DEQ MUST BE RECEIVED
VERIFYING COMPLIANCE TO WETLAND PERMIT REGULATIONS.
E) A PROCESSED VSMP REGISTRATION AND FEE FORM MUST BE
RECEIVED.
F) A COPY OF VDOT LAND USE PERMIT MUST BE RECEIVED, IF
APPLICABLE.
G) AN EROSION CONTROL BOND MUST BE POSTED.
H) TWO ADDITIONAL SETS OF CONSTRUCTION PLANS TO BE
STAMPED "APPROVED FOR CONSTRUCTION" MUST BE RECEIVED.
I) AS APPLICABLE, A SWPPP BOOKLET (3 RING BINDER) MUST
BE PROVIDED.
3. WE OFFER, BUT NOT LIMITED TO, THE FOLLOWING COMMENTS:
A) PLEASE REVISE THE LINE TYPE PERTINENT TO THE SUPER
SILT FENCE TO BE -XX-XX- AS OPPOSED TO -]X[-]X[-. BE
SURE TO INCLUDE IN THE LEGEND FOR THE EC MEASURE THE
SUPER SILT FENCE.
B) THESE ARE IN REGARDS TO THE SB1 AND SB2:
B.1) PLEASE SHOW/LABEL THE EXISTING BAFFLES TO THE SB1
AND SB2. REFLECT THE CHANGES ON THE EC PHASE I/II.
B.2) REVISE THE DRAINAGE AREAS FOR THE SB1 AND SB2 TO BE
11.00 AC AND 11.30 AC RESPECTIVELY SINCE THEY WERE
DESIGNED AND APPROVED BASED ON ACREAGE PREVIOUSLY
MENTIONED WITH NEWMARKET SECTION 1. REFLECT THE CHANGES
ON THE EC PHASE I/II.
B.3) PLEASE LABEL THE SEDIMENT BASINS AS "EX. SB1 AND
EX. SB2" RESPECTIVELY. REFLECT THE CHANGES ON THE EC
PHASE I/II.
B.4) PLEASE REMOVE THE BOXLESS FILTERRA WITH THE
ASSOCIATED STORM SEWER FROM THE SB1/SB2 (I.E. SHEETS
C2.0, C2.1, ETC.) INSTEAD SHOW/LABEL THE TEMPORARY
OUTFALL PIPE TO SB2 AND THE TEMPORARY DITCH TO SB1. THE
BOXLESS FILTERRAS CAN BE SHOWN IN DARKER BOLDER LINES
FOR THE SB1/SB2 ON THE EC PHASE II.
B.5) PLEASE REVISE ITEM 9 UNDER PHASE I SEQUENCE OF
CONSTRUCTION (SHEETS C2.0 AND C2.1) TO STATE "PRIOR TO
COMMENCE THE EC PHASE I, THE SLOPES ALONG THE EMBANKMENT
OF THE SB1 AND SB2 MUST BE COMPLETELY STABILIZED WITH
GRASS VEGETATION AND SEDIMENTS MUST BE CLEANED OFF FROM
THE SB1/SB2 IF SEDIMENTS EXCEED THE ALLOW CLEANOUT
ELEVATION. THE COUNTY INSPECTOR MUST CHECK THE
CONDITIONS OF THE SPILLWAY/DEWATERING DEVICE FOR SB1/SB2
WHETHER OR NOT ADDITIONAL MEASURES MAY BE REQUIRED."
B.6) PLEASE SHOW/LABEL THE EXISTING SUPER SILT FENCE
B.7) PLEASE REMOVE THE FENCE LOCATED TO SURROUND THE
SB1/SB2 FROM THE EC PHASE I PLANS.
B.8) PLEASE SHOW THE RIPRAP ARMORING THE EMERGENCY
SPILLWAY FOR THE SB1 AND EXTEND THE RIPRAP TO NEAR THE
LIMITS OF THE WETANDS AS SHOWN IN THE NEWMARKET SECTION
1.
B.9) PLEASE REVISE LINE OF THE EXISTING CONTOURS
PERTINENT TO THE SB1/SB2 TO SHOW THAT IT CONTINUES
UNIFORMLY WITHIN THE BASIN AREA AS OPPOSED TO SHOWING
BREAKS WITHIN THE LINE. REVISE ACCORDINGLY.
B.10) PLEASE CLEARLY SHOW/LABEL THE EXISTING GRAVEL
ACCESS ROAD TO ACCESS TO SB2 FROM AMETHYST DRIVE TO SB2
AND FROM AVADA DRIVE TO SB1. REFLECT THE CHANGES ON THE
EC PHASE I/PHASE II.
B.11) PLEASE REVISE ITEM 9 (SHEETS C2.2, C2.3, ETC.) TO
STATE, "UPON APPROVAL BY THE ENVIRONMENTAL INSPECTOR AND
THE LAST SECTION DRAINING TO THESE SB1/SB2 HAVE BEEN
CONSTRUCTED AND COMPLETELY STABILIZED, THE SEDIMENT
BASINS SHALL BE CONVERTED TO PERMANENT DETENTION DRY
POND WITH BOXLESS FILTERRAS. THE WET STORAGE FROM THE
SB1/SB2 MUST BE DEWATERED FOLLOWING THE APPROVED METHODS
IN THE VESCH 1992 EDITION. ALL SILT MUST BE CLEANED FROM
THE SB1/SB2 AND COMPLETELY STABILIZED PRIOR TO THE
CONVERSION TO PERMANENT SWM/BMP DETENTION POND."
"SEE NEWMARKET SECTION 1 FOR THE SEQUENCE FOR CONVERTING
THE SEDIMENT BASINS TO SWM/BMP'S. IN ADDITION, REFER TO
SHEETS ___ FOR ADDITIONAL CHANGES IN THE GRADING ALONG
THE CUL-DE-SACS AND SOME CHANGES IN THE STORM SEWERS
ASSOCIATED TO THE OUTFALL PIPES (I.E. THE TOP ELEVATION
OF DI-6'S/INVERTS/ DIAMETER/MATERIAL/ETC.)."
C) PLEASE REMOVE THE LINE PERTINENT TO BUILDING
ENVELOPES FROM THE EC PHASE I/II TO CLEARLY DEPICT THE
EXISTING CONTOURS AND OTHER EC MEASURES FROM THE EC
PLANS.
D) SIMILARLY, PLEASE REMOVE THE LINE PERTINENT TO THE
50' VEGETATIVE PERIMETER SETBACK TO ALLOW THE EC
MEASURES TO STANDOUT FROM OTHER FEATURES.
E) PLEASE REVISE THE EC PHASE II PLANS TO SHOW THE STORM
SEWER IN DARKER BOLDER LINES.
F) PLEASE PROVIDE SUPER SILT FENCE TO SURROUND THE
FUTURE FILL GRADING PERTINENT TO THE CUL-DE-SAC ON AVADA
TERRACE IN THE PROXIMITY OF STATION 10+00. REFLECT THE
CHANGES ON THE EC PHASE I/PHASE II.
G) PLEASE PROVIDE SILT FENCE TO SURROUND THE DIVERSION
DIKE SPECIFIED IN THE PROXIMITY OF STATIONS 10+50 TO
12+00.
H) PLEASE PROVIDE TWO SMALL EXCAVATED PITS WITH GRAVEL
OUTLET STRUCTURE AT THE TOE OF FILL IN THE PROXIMITY OF
STATION 10+50/10+90 ON AVADA LOOP. IN ADDITION, ADJUST
THE SUPER SILT FENCE TO INCLUDE THESE SMALL EXCAVATED
PITS. REFLECT THE CHANGES ON THE EC PHASE I/PHASE II.
IN ADDITION, INCLUDE THE ENCLOSED DETAIL OF SMALL
EXCAVATED PIT WITH GRAVEL ON THE EC PLANS.
I) PLEASE BE SURE TO PROVIDE TEMPORARY SLOPE DRAINS OVER
FILL SLOPES EXCEEDING 5' IN HEIGHT (I.E. IN THE
PROXIMITY OF STATION 10+90 ON AVADA LOOP, ETC.). BE SURE
THIS SLOPE DRAIN DISCHARGES INTO THE SMALL EXCAVATED PIT
REQUESTED IN THE PREVIOUS COMMENT.
IN ADDITION, PROVIDE DIMENSIONS OF THIS SLOPE DRAIN AND
DETAIL OF THE EC PLANS.
J) PLEASE REMOVE ITEM 4 UNDER PHASE I SEQUENCE OF
CONSTRUCTION (SHEETS C2.0 AND C2.1) SINCE THE PIPE
BARREL/RISER IS ALREADY INSTALLED IN THE SB1/SB2.
K) PLEASE BE SURE TO REFERENCE DETENTION BASIN 1/BASIN 2
WITH BOXLESS FILTERRA AS OPPOSED RETENTION BASIN 1/BASIN
2 IN ALL APPLICABLE AREAS (I.E. IN THE STORMWATER
MANAGEMENT UNDER THE EROSION CONTROL NARRATIVE (SHEET
C2.5), ETC.). REVISE ACCORDINGLY.
C2.5), ETC.). REVISE ACCORDINGLY.
L) PLEASE REMOVE THE STIPPLE PATTERN WITHIN THE PROPOSED
ROADS FROM THE EC PHASE I.
M) PLEASE BE SURE TO PROVIDE CHECK DAMS ALONG THE
SWALES/DITCHES REQUESTED IN THIS REVIEW.
N) IT APPEARS DURING THE EC PHASE I PLANS LOTS 9/10 OF
NEWMARKET SECTION 1 AND LOTS 22/23 OF NEWMARKET SECTION
4 WOULD NOT DRAIN TO THE SB1 AS INDICATED ON EC PHASE I.
IN THIS CASE, PLEASE PROVIDE A SEDIMENT TRAP IN THE
PROXIMITY OF STATION 15+00 ON THE LEFT SIDE OF AVADA
LOOP. ADJUST THE DIVERSION DIKE TO DRAIN TO THIS TRAP.
PROVIDE DIMENSIONS OF THIS DEVICE AND DRAINAGE AREAS
INTERCEPTED BY THIS TRAP.
IN ADDITION, INCLUDE A DETAIL FOR SEDIMENT TRAP ON EC
PLANS.
FURTHERMORE, REVISE THE LIMITS OF DRAINAGE AREAS/THE
ACREAGE THAT DRAINS TO THE SB1 ON THE EC PHASE I TO BE
LESS THAN 10.90 ACRES.
O) PLEASE SHOW/LABEL THE PROPOSED SWALE/DITCH IN DARKER
BOLDER LINES SHOWN ON LOT 24 TO BMP1 REQUESTED IN THIS
REVIEW AND REMOVE THE DIVERSION DIKE SHOWN ON EC PHASE
II. REFLECT THE CHANGES ON THE EC PHASE I/PHASE II. BE
SURE TO PROVIDE CHECK DAMS ALONG THIS SWALE/DITCH ON THE
EC PHASE I/PHASE II.
P) PLEASE PROVIDE SUPER SILT FENCE TO SURROUND THE FILL
GRADING REQUESTED ON LOTS 27/28 (REFER COMMENT ITEM 14
UNDER ROAD AND DRAINAGE) WITH SMALL EXCAVATED PIT/OUTLET
GRAVEL STRUCTURE TO BE LOCATED AT THE LOW OF THE SUPER
SILT FENCE IN THE VICINITY OF 270.00 CONTOUR-ELEVATION.
REFLECT THE CHANGES ON THE EC PHASE II.
Q) PLEASE PROVIDE SUPER SILT FENCE/SMALL EXCAVATED PIT
TO ADDRESS THE GRADING SPECIFIED IN THE PROXIMITY OF LOT
25. REFLECT THE CHANGES ON THE EC PHASE II PLANS.
R) PLEASE REVISE THE LIMITS OF CLEARINGS IN THE EC PHASE
I TO INCLUDE THE CONSTRUCTION ENTRANCE ON AVADA
DRIVE/CARINDALE DRIVE AND HALF OF THE ROAD RIGHT-OF-WAY
TO ACCESS THE STOCKPILE.
S) PLEASE BE SURE TO PROVIDE INLET PROTECTION FOR ALL
INLETS OF THE STORM SEWER (I.E. STRUCTURES 2, 14, R29,
E18, ETC.). REFLECT THE CHANGES ON THE EC PHASE 2 PLANS.
T) PLEASE PROVIDE TENTATIVE CONDITION #22 IN THE EC
PHASE I/PHASE II PLANS, WHICH STATES, "THE ENVIRONMENTAL
ENGINEERING DEPARTMENT MAY IMPOSE A MORE RIGOROUS
EROSION AND SEDIMENT CONTROL PROGRAM THAN THAT WHICH IS
PROVIDED BY MINIMUM STANDARDS FOUND IN THE VIRGINIA
EROSION AND SEDIMENT CONTROL HANDBOOK FOR THE PROTECTION
OF THE SWIFT CREEK RESERVOIR AND EXISTING DOWNSTREAM
PONDS."
U) ANY TIMBERING THAT IS TO OCCUR AS THE FIRST PHASE OF
INFRASTRUCTURE CONSTRUCTION WILL BE INCORPORATED INTO
THE PROJECT'S EROSION-AND-SEDIMENT CONTROL PLAN
NARRATIVE AND WILL NOT COMMENCE UNTIL THE ISSUANCE OF A
LAND DISTURBANCE PERMIT FOR SUBDIVISION CONSTRUCTION AND
PROPER INSTALLATION OF EROSION CONTROL MEASURES.
==== CBPA =====
1. PLEASE REVISE THE CBPA NOTE (SHEET C1.0) TO ADDRESS THE
PRO-RATA PAYMENT TO MEET 0.22 LBS/YEAR USCW DEFAULT AND
BMP'S MEET THE 0.45 LBS/YEAR STATE DEFAULT. BE SURE TO
MENTION BMP#1/BMP#2 ARE DETENTION DRY PONDS IN THE CBPA
NOTE.
2. PLEASE REVISE THE BMP EFFICIENCY IN THE WORKSHEET A
CALCULATIONS TO BE 65% AS OPPOSED TO 74% AND SUBMIT REVISED
CALCULATIONS FOR FURTHER REVIEW AND APPROVAL.
3. PLEASE PROVIDE THE CBPA/MS-4 TABLE IN THE CBPA
COMPLIANCE SHEET. FILL IN THE TABLE ACCORDINGLY.
4. THESE ARE IN REGARDS TO THE CBPA COMPLIANCE SHEET:
A) REVISE THIS SHEET TO SHOW ONLY THE APPROVED SECTIONS
OF NEWMARKET (I.E. SECTIONS 1, 2, 4 AND 6).
B) REVISE SECTION 4 TO CLEARLY SHOW THE LOT LINES WITH
LOT NUMBERING.
C) PLEASE REMOVE SECTIONS 3, 5, 7 AND 8 FROM THE CBPA
COMPLIANCE CALCULATIONS TABLE LOCATED IN THE UPPER LEFT
CORNER.
D) PLEASE REVISE THE CBPA LPRE FOR THE OVERALL PROJECT
TO BE 96.44 LB/YR AS OPPOSED TO 96.40 LB/YR.
E) PLEASE REVISE LPOST TO BE 126.44 LB/YR. IN LIEU OF
126.60 LB/YR.
F) PLEASE CORRECT THE CBPA REMOVAL REQUIRED TO BE 30.10
LB/YR AS OPPOSED TO 30.20 LB/YR.
==== SWM/BMP =======
1. THESE ARE IN REGARDS TO THE BMP1 AND BMP2:
A) PLEASE PROVIDE A BLOW OUT OF BMP1/BMP2 DRAWN TO SCALE
TO 1"=20' TO CLEARLY DEPICT THE EXISTING FEATURES, SUCH
AS: THE EXISTING GRAVEL ACCESS ROAD, THE TEMPORARY
DRAINAGE IMPROVEMENTS, THE EXISTING 1' CONTOURED
GRADING, ETC. THAT WOULD BE REMOVED FOR THE PLACEMENT OF
THE PROPOSED ROAD/CUL-DE-SAC'S WITH THE ASSOCIATED
PROPOSED GRADING, AND LAYOUT OF THE NEW STORM SEWERS,
ETC. CLEARLY ANNOTATE THE FEATURES TO BE REMOVED ON THIS
VIEW.
IN ADDITION, INCLUDE IN DARKER BOLDER LINES TO SHOW THE
FENCE AS PROPOSED TO BE LOCATED TO SURROUND THE
SWM/BMP#1/#2, THE BOXLESS FILTERRAS, SHOW THE EXISTING
GRADING IN LIGHTER-GHOSTED LINES AND THE PROPOSED 1'
CONTOURS IN DARKER LINES, DEPICT THE EMERGENCY SPILLWAY,
GATED ACCESS, ETC. SHOW/LABEL THE APPROVED 10/100-YEAR
WSE FOR BMP#1/#2.
B) PLEASE REVISE THE LABELING OF EX. POND SWM/BMP#1 AND
EX. SWM/BMP#2 (SHEETS C3.0 AND C3.1) TO BE LABELED AS
"SWM/BMP#1 AND SWM/BMP#2 APPROVED WITH NEWMARKET SECTION
1". IN ADDITION, PROVIDE A NOTE TO BMP#1/#2 STATING,
"BMP'S #1#2 ARE CURRENTLY WORKING AS SEDIMENT BASINS,
THE CONVERSION TO PERMANENT SWM/BMP'S WOULD OCCUR WITH
THIS SECTION. PLEASE REFER TO NEWMARKET SECTION 1 FOR
THE CONVERSION TO A PERMANENT SWM/BMP #1/#2 AND THE
INSTALLATION OF THE BOXLESS FILTERRAS AND LANDSCAPE
PLANS WITHIN THE FILTERRA AND AROUND THE SWM/BMP. THE
12" PVC OUTFALL THAT ARE CONNECTED TO DI-6'S WOULD BE
REPLACED WITH 24"/30" RCP'S AS SHOWN ON THESE PLANS."
C) REVISE THE LABELING OF "EX. BMP SETBACK" TO BE "50'
VEGETATIVE PERIMETER YARD SETBACK". THE LABELING AND
LINE PERTINENT TO THE SETBACK SHOULD BE SHOWN IN DARKER
BOLDER LINES. REFLECT THE CHANGES ON ALL APPLICABLE
SHEETS.
IN ADDITION, PLEASE BE SURE THE 50' VEGETATIVE PERIMETER
SETBACK IS MEASURED OFF THE 100-YEAR WSE OR THE TOE OF
DAM SECTION WHICHEVER IS MOST RESTRICTIVE. CONSEQUENTLY,
REVISE THE 50' SETBACK ON LOTS 24/25 TO BE TAKEN FROM
THE TOE OF THE DAM SECTION AS OPPOSED THE 100-YEAR WSE.
REFLECT THE CHANGES ON ALL APPLICABLE SHEETS.
D) PLEASE SHOW/LABEL THE EXISTING VARIABLE DRAINAGE AND
ACCESS EASEMENT IN ITS ENTIRETY, THE 20' DRAINAGE AND
TEMPORARY ACCESS EASEMENT, THE TEMPORARY 20' BMP ACCESS
ROAD, THE TEMPORARY 16' DRAINAGE EASEMENT, ETC. WITH
DEED BOOK AND PAGE NUMBER. REFLECT THE CHANGES ON ALL
APPLICABLE VIEWS.
E) PLEASE REVISE THE OUTFALL STR. 14 TO ENSURE THE
INVERT-OUT TO BE 277.64 AS OPPOSED TO 275.45. THE STORM
SEWER SYSTEM UPSTREAM OF STR. 14 SHOULD BE RAISED TO
ENSURE DAYLIGHT. REVISE THE PLAN, PROFILES AND
COMPUTATION SHEETS TO REFLECT THE CHANGES. A FURTHER
DISCUSSION MAY BE HELPFUL.
F) PLEASE BE SURE TO SPECIFY DI-6 WITH MINIMUM 2'
CONCRETE GUTTER AS OPPOSED TO DI-7 AT STR. 2. INCLUDE
THE SLOT OPENING ORIENTATION TO THE EAST. REFLECT THE
CHANGES ON ALL APPLICABLE SHEETS.
G) PLEASE REVISE THE STM STR. 13-BMP1 AND STM STR. E37-
BMP 2 (SHEET C4.2) TO INCLUDE THE 12" PVC AND CLEAN OUT
STRUCTURE WITH PERTINENT INFORMATION. IN ADDITION,
SHOW/LABEL THE OUTLET PROTECTION WITH DIMENSIONS (I.E.
WIDTH, LENGTH AND 24" THICK LAYER OF RIPRAP OVER FILTER
FABRIC) DOWNSTREAM OF THE OUTFALL PIPES STRUCTURES 2/14.
REFLECT THE CHANGES ON THE PLANS AND PROFILES.
==== ROAD AND DRAINAGE =====
1. THIS OFFICE WAS NOT ABLE TO PERFORM A FIELD INSPECTION.
ADDITIONAL COMMENTS MAY ARISE AFTER PERFORMING A SITE
INSPECTION IF INDICATED BY THE EXISTING CONDITIONS.
2. PER TENTATIVE CONDITION #12, PRIOR TO CONSTRUCTION PLAN
APPROVAL, THE ENVIRONMENTAL ENGINEERING DEPARTMENT MUST
HAVE RECEIVED SIGNED WRITTEN NOTIFICATION FROM THE ADJACENT
PROPERTY OWNERS, N/F GRAHAM J. & L. AT 20241 SWAMP FOX
ROAD, N/F HARDEE D. & J. AT 2011 SWAMP FOX ROAD, YOUNG T. &
R. AT 2021 SWAMP FOX ROAD AND KNAB W. & P. AT 2031 SWAMP
FOX ROAD, WHICH SHOULD BE SENT U.S. POSTAL CERTIFIED MAIL,
RETURN RECEIPT REQUESTED. INCLUDE AN 8½ X 11 COPY OF THE
PROPOSED CONSTRUCTION ACTIVITY ADJACENT TO THEIR PROPERTY.
IN ADDITION, PRIOR TO APPROVAL OF THESE PLANS, IF ANY LOTS
FROM NEWMARKET SECTION 1 THAT ARE ADJACENT TO THE PROPOSED
CONSTRUCTION ACTIVITY WERE SOLD DURING THE REVIEW PROCESS
FOR THIS SECTION, THESE NEW PROPERTY OWNER(S) SHOULD BE
NOTIFIED AS WELL AS PER TENTATIVE CONDITION #12.
3. PLEASE SPECIFY THE AMOUNT OF DISTURBED ACRES IN THE SITE
DATA (SHEET C1.0).
4. THERE ARE SEVERAL SHEETS OF GREENWICH WALK PHASE 1
WITHIN THE NEWMARKET SECTION 4 CONSTRUCTION PLANS. BE SURE
TO REMOVE THESE SHEETS OF GREENWICH WALK FOR THE NEXT PLAN
SUBMITTAL. REVISE ACCORDINGLY.
5. PLEASE CORRECT THE LABELING OF "16' DRAINAGE EASEMENT"
THAT IS ENCLOSING STRUCTURES 8/9/11 TO BE 16' DRAINAGE
EASEMENT FOR VDOT MAINTENANCE". REFLECT THE CHANGES ON ALL
APPLICABLE SHEETS.
6. PLEASE PROVIDE A DI-6B WITH MINIMUM 2' CONCRETE GUTTER
AS OPPOSED TO MH AT STR. E18. REVISE THE PLANS, PROFILES
AND COMPUTATION SHEETS TO REFLECT THE CHANGES.
7. PLEASE REVISE THE LABELING OF "LIMITS OF WETLANDS TO BE
DISTURBED" IN THE LEGEND (SHEETS C3.0, C3.1, ETC.) TO BE
LABELED AS "LIMITS OF WETLANDS TO BE IMPACTED."
8. PLEASE SPECIFY A SWALE OF 5:1 SIDE SLOPE AND 5' OFF THE
PROPERTY LINE ON LOT 16 ADJACENT TO LOTS 6/7 OF NEWMARKET
SECTION 1. START THIS SWALE AT GRADE INCREASING IN DEPTH
AND CONTINUE THIS SWALE IN A RADIUS TURN TO RUN ALONG THE
PROPERTY LINE PERTINENT TO LOTS 24-16/15.
THIS SWALE SHOULD BECOME A DITCH OF 3:1 SIDE SLOPE WHEN IT
CROSSES LOT 15 AND CONTINUE THIS DITCH UNTIL IT REACHES THE
DI-6 STR. 14. ENCLOSE PART OF THIS DITCH IMPROVEMENT IN A
16' DRAINAGE EASEMENT. THE 16' DRAINAGE EASEMENT SHOULD BE
ILLUSTRATED ALONG THE PROPERTY LINE PERTINENT TO LOTS 24-
16/15 UNTIL IT REACHES THE EXISTING SWM/BMP EASEMENT.
REFLECT THE CHANGES ON THE EC PLANS, ROAD PLANS, DRAINAGE
MAP PLANS, PROFILE, ETC.
IN ADDITION, PROVIDE 10/100-YEAR DITCH CALCULATIONS,
TYPICAL DITCH DESIGN OF 3:1 SIDE SLOPE, DESIGN DEPTH,
LINING, ETC. IN ADDITION, INCLUDE A PROFILE OF THIS DITCH
WITH PERTINENT INFORMATION ON THE PLANS.
ADDITIONALLY, PLEASE BE SURE TO PROVIDE CONTAINMENT OF THE
SWALE SPECIFIED ON LOT 15 AT THE END OF THIS SWALE (SHEET
C4.4). REVISE PROFILE ACCORDINGLY.
9. PLEASE PROVIDE A SWALE ON LOT 17 TO CUT UPSTREAM RUNOFF.
START THIS SWALE AT GRADE ON THE REAR OF THIS LOT, 5' OFF
FROM THE 25' BUILDING SETBACK AND CONTINUE THIS SWALE IN A
RADIUS TURN AND 5' OFF THE PROPERTY LINE PERTINENT TO LOTS
17/20 UNTIL IT REACHES THE RIGHT-OF-WAY. ANNOTATE LOT 17
WITH NBP. REFLECT THE CHANGES ON ALL APPLICABLE SHEETS.
10. PLEASE PROVIDE A SWALE OF 5:1 SIDE SLOPE ON THE REAR OF
LOTS 18 AND 19. START THE SWALE AT GRADE AND 5' OFF REAR
PROPERTY LINE NEAR/ADJACENT TO 17 ON LOT 18 PROGRESSIVELY
INCREASING IN DEPTH UNTIL IT REACHES STR. E18, WHICH A DI-6
HAS BEEN REQUESTED.
FOR LOT 19 START THE SWALE AT GRADE FROM THE WESTERN SIDE
NEAR THE PROPERTY LINE PERTINENT TO LOT 19/20 AND CONTINUE
THIS SWALE UNTIL IT REACHES STR. E18. REFLECT THE CHANGES
ON ALL APPLICABLE SHEETS.
11. PLEASE REVISE THE OVERALL DRAINAGE DESIGN PERTINENT TO
THE STORM SEWER STRUCTURES 21/22P/22/24P. PLEASE CONSIDER
THE FOLLOWING:
A) PLEASE ELIMINATE THE SWALE SPECIFIED BETWEEN LOTS 3/4
AND ELIMINATE STRUCTURES 22/24P AND INSTEAD SPECIFY A
SWALE OF 5:1 SIDE SLOPE AT THE BEGINNING ON THE REAR OF
LOT 5 TO CONTINUE THIS SWALE TO BECOME A DITCH OF 3:1
SIDE SLOPE WHEN CROSSES LOTS 4 THRU 2. ANNOTATE LOT 5
WITH NBP.
B) EXTEND STRUCTURES 21/22P TO THE REAR PROPERTY LINE TO
INTERCEPT THIS DITCH REQUESTED ON THE PREVIOUS COMMENT.
STR. 21 SHOULD BE LOCATED AT THE PROPERTY LINE BETWEEN
LOTS 1/2, AS A RESULT, THE STORM SEWER PIPE STR. 22P
WOULD BE PLACED FEW INCHES OFF CENTER IN RELATION TO
STR. 18.
C) PROVIDE 10/100-YEAR DITCH CALCULATIONS, PROFILE,
TYPICAL DITCH, LINING, %SLOPE, ETC. ON THE PLANS AND
PROFILES.
D) SUBMIT REVISED 10/100-YEAR STORM SEWER/HGL
CALCULATIONS FOR FURTHER REVIEW AND APPROVAL.
E) PROVIDE A SWALE ON THE REAR PROPERTY LINE AND 5'OFF
THE PROPERTY LINE ON LOT 1 NEAR THE 295.00 CONTOUR-
ELEVATION AND CONTINUE THIS SWALE UNTIL IT REACHES STR.
21.
F) ENCLOSE THESE DRAINAGE IMPROVEMENTS IN A 16' DRAINAGE
EASEMENT. THE 16' EASEMENT SHOULD BE ILLUSTRATED FROM
LOTS 4 THRU 2 AND ENCLOSING STRUCTURES 21/22P. REFLECT
THE CHANGES ON ALL APPLICABLE SHEETS.
G) THE SWALE SPECIFIED ON LOT 3 SHOULD BE EXTENDED AND
PRIOR TO DISCHARGING INTO THE RIGHT-OF-WAY FLATTEN THE
SIDE SLOPES TO ENCOURAGE SHEET FLOW OVER THE CURB/STR.
19. REFLECT THE CHANGES ON ALL APPLICABLE SHEETS.
12. PLEASE EXTEND THE DRAINAGE IMPROVEMENTS FOR THE SWALE
SPECIFIED ON THE REAR OF LOT 11 AND CONTINUE THIS SWALE TO
BECOME A DITCH OF 3:1 SIDE SLOPE TO CROSS LOTS 12/14 UNTIL
IT REACHES BMP#1. THE DITCH CONTAINMENT SHOULD CONTINUE
UNTIL IT REACHES THE BOTTOM OF THE BMP WITH OUTLET
PROTECTION. BE SURE TO SPECIFY DIMENSIONS OF THIS OUTLET
PROTECTION (I.E. WIDTH, LENGTH, WITH 24" THICK LAYER OF
RIPRAP OVER FILTER FABRIC) ON THE PLANS AND PROFILES.
IN ADDITION, REVISE THE TYPICAL DITCH AT LOT 11 TO BE
LABELED AS GRASS SWALE WITH 5:1 SIDE SLOPE. REFLECT THE
CHANGES ON SHEETS C3.0, C4.4, ETC.
INCLUDE PROFILE OF THIS DITCH, TYPICAL DITCH DESIGN, %SLOPE,
DEPTH, LINING, 10/100-YEAR DITCH CALCULATIONS, ETC. REFLECT
THE CHANGES ON ALL APPLICABLE SHEETS.
ADDITIONALLY, INCLUDE THESE DRAINAGE IMPROVEMENTS IN A 16'
DRAINAGE EASEMENT. THE 16' DRAINAGE EASEMENT SHOULD BE
ILLUSTRATED FROM LOT 14 UNTIL IT REACHES THE EXISTING
SWM/BMP EASEMENT.
FURTHERMORE, A CULVERT RCP 12 L.F. SHOULD BE PROVIDED WITHIN
THE DITCH LINE TO ALLOW VEHICLES TO CROSS OVER WITHIN THE
BMP MAINTENANCE CORRIDOR. A FURTHER DISCUSSION IS
RECOMMENDED. INCLUDE 10/100-YEAR CULVERT CALCULATIONS FOR
FURTHER REVIEW AND APPROVAL. REFLECT THE CHANGES ON THE
PLANS AND PROFILES.
13. PLEASE PROVIDE A SWALE OF 5:1 SIDE SLOPE ON THE REAR OF
LOT 22 AND 5' OFF THE REAR PROPERTY LINE TO START AT GRADE
AND CONTINUE IN A RADIUS TURN/5' OFF THE PROPERTY LINE
PERTINENT TO LOTS 22/23 AND PRIOR TO REACHING THE RIGHT-OF-
WAY THE SIDE SLOPE OF THIS SWALE SHOULD FLATTEN TO ENCOURAGE
SHEET FLOW OVER THE CURB. REFLECT THE CHANGES ON ALL
APPLICABLE SHEETS.
14. PLEASE PROVIDE LOT FILLING AND GRADING ON LOTS 27 AND 28
TO ELIMINATE THE NATURAL LOW. ANNOTATE THESE LOTS WITH NBP.
REFLECT THE CHANGES ON ALL APPLICABLE SHEETS.
15. PLEASE REVISE THE SWALE LOT 24-25 PROFILE (SHEET C4.4)
TO SHOW THE DITCH/STR. 14 REQUESTED IN COMMENT 7 UNDER
ROAD AND DRAINAGE. BE SURE TO SHOW CONTAINMENT OF 0.8'
WITHIN THE SWALE.
16. PLEASE SHOW/LABEL 5' TYP. DIMENSION FROM THE PROPERTY
LINE TO THE CENTERLINE OF THE PROPOSED SWALES. REFLECT THE
CHANGES ON ALL APPLICABLE SHEETS.
17. PLEASE BE SURE IN THE FUTURE WHEN PROVIDING DITCH
CALCULATIONS TO USE FOR MANNING ROUGHNESS COEFFICIENT OF
0.05 AS OPPOSED TO 0.04.
18. PLEASE BE SURE THE MS-19 SHEETS SUBMITTED SEPARATELY ARE
INCORPORATED IN THE CONSTRUCTION PLANS IN THE NEXT PLAN
SUBMITTAL.
19. PLEASE CLARIFY THE DARK LINE THAT IS SHOWING IN THE
PROXIMITY OF STATION 15+00 ON AVADA TERRACE.
20. PLEASE REVISE CARINDALE DRIVE PROFILE (SHEET C4.1) AT
THE END OF THE CUL-DE-SAC TO SHOW PROPOSED GRADE TYING BACK
TO EXISTING GRADE.
21. THESE ARE IN REGARDS TO ONSITE DRAINAGE AREAS (SHEET
C5.0, C5.1, ETC.):
A) PLEASE SHOW THE PROPOSED CONTOURS FROM THE LOTS AND
FROM THE ROAD ON SHEETS C5.0, C5.1, ETC. TO VERIFY
DRAINAGE BREAKS/PATTERNS. BE SURE THE PROPOSED CONTOURS
ARE SHOWING IN DARKER LINES AND ARE CLEARLY LABELED WITH
ELEVATIONS.
IN ADDITION, SHOW/LABEL THE PROPOSED CONTOURS FROM THE
OFFSITE NEWMARKET SECTION 1 ON SHEETS C5.0, C5.1, ETC.
TO VERIFY DRAINAGE BREAKS/INCREMENTAL DRAINAGE
ACRES/ETC.
B) IT APPEARS THE 1' EXISTING CONTOURS STOP WITHIN THE
LOT AREA INSTEAD OF SHOWING TO CONTINUE WITHIN THE
LIMITS OF DRAINAGE AREAS. REVISE ACCORDINGLY.
22. THESE ARE IN REGARDS TO THE 100-YEAR HGL CALCULATIONS:
A) PLEASE BE SURE TO USE THE MOST RESTRICTIVE WHEN
SELECTING THE WSE AT STRUCTURES 2, 14, WHICH APPEARS TO
BE THE 100-YEAR WSE PERTINENT TO THE BMP#2/BMP#1 OF
276.76/278.78 RESPECTIVELY AS OPPOSED TO 272.60/277.00.
IN ADDITION, AN IN-HOUSE WAS PERFORMED USING THE 100-
YEAR WSE OF THE BMP'S AND IT APPEARS THE 100-YEAR IS
ESCAPING ON SEVERAL STRUCTURES (I.E. 2, 3, 8, 14, 15,
17, 18, ETC.). PLEASE EITHER ANALYZE THE INLETS WHERE
THE RUNOFF IS ESCAPING. WOULD IT STAY WITHIN THE RIGHT-
OF-WAY OR WOULD IT ENCROACH THE LOTS BY PROVIDING
SURCHARGE ANALYSIS/X-SECTIONS AT THE ROAD SAG, ETC. A
FURTHER DISCUSSION MAY BE HELPFUL.
OR ADJUST THE STORM SEWER TO ENSURE CONTAINMENT. SUBMIT
REVISED 10/100-YEAR STORM SEWER/HGL CALCULATIONS FOR
FURTHER REVIEW AND APPROVAL.
23. AS A PREREQUISITE TO SUBDIVISION PLAT RECORDATION:
A) THE $100/LOT BMP MAINTENANCE FEE MUST BE RECEIVED.
B) PER TENTATIVE CONDITION #18, WHICH STATES, "PRIOR TO
RECORDATION, A COPY OF THE COVENANTS AND ARTICLES OF
INCORPORATION OF THE HOMEOWNERS' ASSOCIATION SHALL BE
PROVIDED TO THE ENVIRONMENTAL ENGINEERING DEPARTMENT FOR
APPROVAL. IN ADDITION, TO LANGUAGE PERTAINING TO THE
RPA, THE ENVIRONMENTAL ENGINEERING DEPARTMENT WILL
DETERMINE WHETHER THE SUBDIVISION HAS BEEN
PROVIDED WITH THE INFORMATION TO DEVELOP AND IMPLEMENT A
FERTILIZATION/LAWN CARE PROGRAM TO MINIMIZE PHOSPHOROUS
RUNOFF FORM WILKES BEND. THE REQUIREMENTS OF THE PROGRAM
SHALL BECOME A PART OF THE COVENANTS FOR THE PROJECT
AFFECTING ALL PROPERTIES WITHIN THE DEVELOPMENT.
C) PER TENTATIVE CONDITION #23, WHICH STATES, "PRIOR TO
RECORDATION, THE ENVIRONMENTAL ENGINEERING DEPARTMENT
MUST HAVE RECEIVED NOTIFICATION FROM VDOT THAT
IMPROVEMENTS TO THE STATE ROAD(S) INTO WHICH THIS
PROJECT INTERSECTS AND WHICH, HAVE BEEN AUTHORIZED BY AN
ISSUED LAND USE PERMIT, HAVE BEEN SATISFACTORILY
COMPLETED."
==========================================================