Subdivision Review Comments
All Subdivision Review Comments for Case # 16CP0094




For VDOT’s comments please contact Virginia Department of Transportation at (804) 674-2814 or send e-mail to Boris.Solomonov@VDOT.Virginia.gov

For Tentative Subdivision resubmittals:

1. Please note that submittal fees include the original submittal and two (2) additional reviews.

2. A letter of transmittal is required to accompany each submittal.

3. Please verify that Environmental Engineering, Fire, CDOT, VDOT, and Planning have reviewed the submittal before resubmitting. A resubmittal tendered, prior to receiving all the required departments’ review, will be counted as an additional submittal. Go to Case Selection Form or Go to Project List


 
CASE NO: 16CP0094 STATUS: PENDING APPROVAL
PROJECT NAME: ST IVES SEC 3 - LAST INTERNET UPDATE: 11/20/17
SUBMITTAL TYPE: CONSTRUCTION PLAN
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 03 06/27/17 07/19/17 ******** 09/23/16 LAG 706-2116
FIRE DEPT.--: 03 06/27/17 07/19/17 AMENDED* 08/10/17 JKL 748-1489
PLANNING----: 03 06/27/17 07/19/17 COMPLETE 07/25/17 WST 768-7566
TRANSPORT.--: 03 06/27/17 07/19/17 COMPLETE 08/11/17 SES 751-4912
UTIL.PLAN.--: 03 06/27/17 07/19/17 ******** ********
UTILITIES---: 03 06/27/17 07/19/17 AMENDED* 07/25/17 WBV 748-1343
UTIL.R.O.W.-: 03 06/27/17 07/19/17 ******** ********
VDOT--------: 03 06/27/17 07/19/17 ******** ********
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: ST. IVES, SECTION 3
PLAN NUMBER: 16CP0094
ORIGINAL PLAN DATE: 3/24/16
REVIEW DATE: 4/20/16
LATEST SUBMISSION DATE: 4/11/16
SUBMITTAL NUMBER: 1
STATUS: REVISIONS REQUIRED
TABLE REVIEW: NO
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR THE
ABOVE REFERENCED PROJECT DATED MARCH 24, 2016, WE MAKE
THE FOLLOWING COMMENTS AND RECOMMENDATIONS:
1. A COPY OF VIRGINIA DEPARTMENT OF TRANSPORTATION'S
APPROVAL LETTER REGARDING PAVEMENT REPLACEMENT, METHOD
OF CROSSING, AND ALIGNMENT OF UTILITY WITH STATE RIGHT
OF WAY, AND A COPY OF ENVIRONMENTAL ENGINEERING'S
INITIAL REVIEW LETTER MUST BE SUBMITTED BEFORE REVISED
PLANS ARE SUBMITTED FOR RE-REVIEW.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION, A
COPY OF THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER
AND/OR ALL OTHER APPLICABLE LOCAL STATE AND FEDERAL
AGENCIES' APPROVAL LETTERS MUST BE RECEIVED BY THIS
DEPARTMENT. IN ADDITION, ALL EASEMENTS NOT INCLUDED
WITH THE SUBDIVISION PLAT MUST BE DEDICATED WITH A
SEPARATE PLAT AND AGREEMENT TO THE COUNTY PRIOR TO
RELEASING THE PROJECT TO THE CONSTRUCTION SECTION.
3. SHOW THE COUNTY PROJECT NUMBER 16-0088 ON THE LOWER
RIGHT HAND CORNER OF EACH SHEET.
4. REVISE THE SCALE OF THE PLAN VIEW SHEET TO 1" =
50'.
5. PROVIDE THE NAMES OF EACH STREET SHOWN IN THE PLAN
VIEW.
6. ST. IVES, SECTION 2, COUNTY PROJECT NUMBER 14-0251
HAS NOT BEEN BUILT AT THIS TIME. THEREFORE, REVISE AND
RESUBMIT THAT PROJECT TO AGREE WITH ALL IMPROVEMENTS
PROPOSED WITH SECTION 3 AND ELIMINATE ALL WATERLINE
ABANDONMENT CURRENTLY SHOWN. IN ADDITION, TAKE ALL
STEPS NECESSARY TO PROVIDE COMPLETE AGREEMENT BETWEEN
THESE TWO (2) SETS OF PLANS AND BE ADVISED THAT THE
PLANS FOR SECTION 3 WILL NOT BE RELEASED TO THE
CONSTRUCTION SECTION UNTIL SECTION 2 IS UNDER CONTRACT.
7. FIELD VERIFY THE TOP ELEVATION AND ALL INVERT
ELEVATIONS OF THE PROPOSED TIE IN MANHOLE, REFLECTING
THE FIELD DATA ON THE PLANS.
8. SHOW AND CALL OUT ALL PROPOSED RIP-RAP LOCATIONS IN
THE PLAN VIEW.
9. RELOCATE THE FIRE HYDRANT CURRENTLY SHOWN IN FRONT
OF LOT NUMBER 1 TO THE COMMON FRONT PROPERTY CORNER OF
LOT NUMBER 1 AND THE OPEN SPACE.
10. SHOW THE EXISTING 21" SEWER IN THE PROFILE VIEW OF
THE PROPOSED TIE IN MANHOLE AND MATCH THE EXISTING AND
PROPOSED PIPE CROWN ELEVATIONS.
11. SHOW THE STORM SEWER THAT IS PARALLEL TO THE RUN OF
SANITARY SEWER BETWEEN MANHOLE NUMBERS 2 AND 3 IN THE
PROFILE VIEW.
12. ALL WATERLINE LOCATED IN FILL IS TO BE SPECIFIED AS
DUCTILE IRON, CLASS 52 MINIMUM WITH RESTRAINED JOINTS
FOR THE ENTIRE DISTANCE SO LOCATED.
13. SPECIFY THE TYPE OF DROPSTACK (I.E. INTERNAL,
STANDARD) THAT IS PROPOSED AT MANHOLE NUMBER 3. PROVIDE
A COPY OF THE APPLICABLE DETAIL ON THE PLANS,
REFERENCING ITS LOCATION.
14. REVISE ITEM NUMBER 22 UNDER "STANDARD NOTES" TO
REFLECT AN ELEVATION OF 249'. NOTE THIS CONDITION ON
EACH APPLICABLE LOT IN THE PLAN VIEW.
15. PROVIDE AN ADDITIONAL 20 FT OF SEWER EASEMENT
PARALLEL AND NORTH OF THE EXISTING 15-INCH SEWER COUNTY
NUMBER 06-0309. THIS IS TO ACCOMMODATE FUTURE PROJECT
SEW-01-001-GRAV FROM THE WATER AND WASTEWATER FACILITIES
PLAN.
16. THE MINIMUM SIZE PIPE FOR PUBLIC WATERLINE WITH
FIRE HYDRANTS IS 8 INCHES.
17. RELOCATE THE LATERALS FOR LOTS 1 AND 17 SO THAT
THEY ARE NOT UNDER THE DRIVEWAY.
18. PROVIDE A CONSPICUOUS NOTE THAT ALL WATER METERS
ARE TO BE LOCATED 3 FT BEYOND THE SIDEWALK.
19. PROVIDE A CLAY DAM PER DETAIL SEW-09 ON EACH SIDE
OF ALL WETLAND CROSSINGS. SHOW THIS ON THE PLAN AND
PROFILE SHEETS.
20. THE COUNTY WILL NOT ACCEPT SEWER RUN FROM MH 3 TO
MH 7 AS A PUBLIC SEWER AS IT IS LIMITED TO A SINGLE LOT
AND IS A DEEP SECTION UNDER A WETLAND. THIS LINE CAN
EITHER BE A PRIVATE GRAVITY LINE WITH PRIVATE CLEAN OUTS
OR PROVIDE A SEWER PUMP ON THE LOT TO DISCHARGE TO A
SHALLOWER LATERAL INTO MH 3.
21. FOR THE CROSSING OF THE WATERLINE OVER THE STORM
SEWER AT APPROXIMATELY STA 19+75, CALL OUT THAT THE
CROSSING WITH ONLY 1.1 FT CLEARANCE SHALL HAVE STONE
BACKFILL BETWEEN THE PIPE AND THAT THE WATERLINE PIPE
SEGMENT SHALL BE CENTERED OVER THE STORM PIPE AT THAT
LOCATION.
22. THOROUGHLY EXAMINE ALL SHEETS TO CORRECT ALL
EXTRANEOUS MARKINGS, OVERLAPPING TEXT, ILLEGIBLE TEXT
AND DRAWING FEATURES, ETC. IN ORDER TO FACILITATE A
CLEAN DRAWING WITH ALL TEXT AND DRAWING FEATURES
COMPLETELY LEGIBLE AND ABUNDANTLY VISIBLE.
23. REVISE THE "MATERIALS LIST" AS NECESSARY. PLEASE
INCLUDE "MANHOLE INSERTS" ALONG WITH THE FRAME AND
COVER.
PLEASE MAKE ALL OF THE SUGGESTED CHANGES AND SUBMIT
ONE(1) SET OF REVISED PLANS.
THE OWNER MUST ENTER INTO A COUNTY CONTRACT PRIOR TO THE
START OF CONSTRUCTION. PLEASE SEND ME A COPY OF THE
"ACCEPTED" BID PROPOSAL BETWEEN THE DEVELOPER AND THE
CONTRACTOR SO WE MAY PREPARE THE COUNTY CONTRACT. THE
BID PROPOSAL MUST BE BASED ON THE LATEST REVISED
UTILITIES PLANS REFLECTING THE REVIEWER'S STAMP, AND ALL
WORK MUST BE PERFORMED BY AN ACCEPTABLE UTILITIES
CONTRACTOR. IF PLANS ARE REVISED AFTER CONTRACT
PREPARATION DUE TO A CHANGE BECAUSE OF VIRGINIA
DEPARTMENT OF TRANSPORTATION'S AND/OR ENVIRONMENTAL
ENGINEERING DEPARTMENT'S APPROVAL OF THE ROAD, DRAINAGE,
AND EROSION CONTROL DESIGN OR BECAUSE OF STATE AGENCIES'
REVIEW AND APPROVAL OF THE UTILITIES DESIGN, A REVISED
BID PROPOSAL MAY BE NECESSARY TO ACCURATELY REFLECT THE
LATEST UTILITIES DESIGN AND A NEW CONTRACT PREPARATION
MAY BE NECESSARY AND EXECUTED PRIOR TO THE START OF
CONSTRUCTION.
IF YOU HAVE ANY QUESTIONS, DO NOT HESITATE TO CONTACT ME
AT 748-1343.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: ST. IVES SECTION 3
PLAN NUMBER: 16CP0094
ORIGINAL PLAN DATE: 3/24/16
REVIEW DATE: 6/27/16
LATEST SUBMISSION DATE: 6/20/16
SUBMITTAL NUMBER: 2
STATUS: REVISIONS REQUIRED
TABLE REVIEW: NO
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR THE
ABOVE REFERENCED PROJECT DATED MARCH 24, 2016, WITH
THE LATEST REVISION DATED JUNE 14, 2016, WE MAKE THE
FOLLOWING COMMENTS AND RECOMMENDATIONS:
1. A COPY OF VIRGINIA DEPARTMENT OF TRANSPORTATION'S
APPROVAL LETTER REGARDING PAVEMENT REPLACEMENT, METHOD
OF CROSSING, AND ALIGNMENT OF UTILITY WITH STATE RIGHT
OF WAY, AND A COPY OF ENVIRONMENTAL ENGINEERING'S
INITIAL REVIEW LETTER MUST BE SUBMITTED BEFORE REVISED
PLANS ARE SUBMITTED FOR RE-REVIEW.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION, A
COPY OF THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER
AND/OR ALL OTHER APPLICABLE LOCAL STATE AND FEDERAL
AGENCIES' APPROVAL LETTERS MUST BE RECEIVED BY THIS
DEPARTMENT. IN ADDITION, ALL EASEMENTS NOT INCLUDED
WITH THE SUBDIVISION PLAT MUST BE DEDICATED WITH A
SEPARATE PLAT AND AGREEMENT TO THE COUNTY PRIOR TO
RELEASING THE PROJECT TO THE CONSTRUCTION SECTION.
3. THOROUGHLY EXAMINE THE MANHOLE COORDINATE TABLE FOR
ACCURACY AND COMPLETENESS, REVISING AS NECESSARY.
4. LABEL EASTBOURNE WAY IN THE PLAN VIEW.
5. CALL OUT THE EXISTING 20' SANITARY SEWER EASEMENT
PARALLEL TO AND NORTH OF EXISTING COUNTY PROJECT NUMBER
06-0390 INCLUDING THE APPLICABLE DEED BOOK AND PAGE
NUMBER.
6. RELOCATE THE WATER SERVICE FOR LOT NUMBER 1 TO THE
OTHER SIDE OF THE LOT BUT NOT IN THE SWALE.
7. ROTATE THE SEWER CONNECTION FOR LOT NUMBER 8 SUCH
THAT IT IS LOCATED BETWEEN THE DRIVEWAY AND DRAINAGE
EASEMENT.
8. RELOCATE MANHOLE NUMBER 3 AS DISCUSSED TO
FACILITATE SEWER SERVICE TO LOT NUMBER 9 BY THE
CONNECTION NOT CROSSING ANY PROPERTIES OTHER THAN THE
ONE IT SERVES.
9. PLEASE BE ADVISED THAT THE PLANS FOR THIS PROJECT
WILL NOT BE RELEASED TO THE CONSTRUCTION SECTION UNTIL
SUCH TIME "ST. IVES, SECTION 2", COUNTY PROJECT NUMBER
14-0251 IS UNDER CONTRACT. IN ADDITION, PLEASE TAKE ALL
STEPS NECESSARY TO PROVIDE COMPLETE AGREEMENT BETWEEN
THESE TWO (2) SETS OF PLANS.
10. THOROUGHLY EXAMINE ALL SHEETS TO CORRECT ALL
EXTRANEOUS MARKINGS, OVERLAPPING TEXT, ILLEGIBLE TEXT
AND DRAWING FEATURES, ETC. IN ORDER TO FACILITATE A
CLEAN DRAWING WITH ALL TEXT AND DRAWING FEATURES
COMPLETELY LEGIBLE AND ABUNDANTLY VISIBLE.
11. REVISE THE "MATERIALS LIST" AS NECESSARY.
PLEASE MAKE ALL OF THE SUGGESTED CHANGES AND SUBMIT
ONE(1) SET OF REVISED PLANS.
THE OWNER MUST ENTER INTO A COUNTY CONTRACT PRIOR TO THE
START OF CONSTRUCTION. PLEASE SEND ME A COPY OF THE
"ACCEPTED" BID PROPOSAL BETWEEN THE DEVELOPER AND THE
CONTRACTOR SO WE MAY PREPARE THE COUNTY CONTRACT. THE
BID PROPOSAL MUST BE BASED ON THE LATEST REVISED
UTILITIES PLANS REFLECTING THE REVIEWER'S STAMP, AND ALL
WORK MUST BE PERFORMED BY AN ACCEPTABLE UTILITIES
CONTRACTOR. IF PLANS ARE REVISED AFTER CONTRACT
PREPARATION DUE TO A CHANGE BECAUSE OF VIRGINIA
DEPARTMENT OF TRANSPORTATION'S AND/OR ENVIRONMENTAL
ENGINEERING DEPARTMENT'S APPROVAL OF THE ROAD, DRAINAGE,
AND EROSION CONTROL DESIGN OR BECAUSE OF STATE AGENCIES'
REVIEW AND APPROVAL OF THE UTILITIES DESIGN, A REVISED
BID PROPOSAL MAY BE NECESSARY TO ACCURATELY REFLECT THE
LATEST UTILITIES DESIGN AND A NEW CONTRACT PREPARATION
MAY BE NECESSARY AND EXECUTED PRIOR TO THE START OF
CONSTRUCTION.
IF YOU HAVE ANY QUESTIONS, DO NOT HESITATE TO CONTACT ME
AT 748-1343.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: ST. IVES SECTION 3
PLAN NUMBER: 16CP0094
ORIGINAL PLAN DATE: 3/24/16
REVIEW DATE: 9/22/16
LATEST SUBMISSION DATE: 9/14/16
SUBMITTAL NUMBER: 3
STATUS: REVISIONS REQUIRED
TABLE REVIEW: YES
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR THE
ABOVE REFERENCED PROJECT DATED MARCH 24, 2016, WITH
THE LATEST REVISION DATED SEPTEMBER 8, 2016, WE MAKE THE
FOLLOWING COMMENTS AND RECOMMENDATIONS:
1. A COPY OF VIRGINIA DEPARTMENT OF TRANSPORTATION'S
APPROVAL LETTER REGARDING PAVEMENT REPLACEMENT, METHOD
OF CROSSING, AND ALIGNMENT OF UTILITY WITH STATE RIGHT
OF WAY, AND A COPY OF ENVIRONMENTAL ENGINEERING'S
INITIAL REVIEW LETTER MUST BE SUBMITTED BEFORE REVISED
PLANS ARE SUBMITTED FOR RE-REVIEW.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION, A
COPY OF THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER
AND/OR ALL OTHER APPLICABLE LOCAL STATE AND FEDERAL
AGENCIES' APPROVAL LETTERS MUST BE RECEIVED BY THIS
DEPARTMENT. IN ADDITION, ALL EASEMENTS NOT INCLUDED
WITH THE SUBDIVISION PLAT MUST BE DEDICATED WITH A
SEPARATE PLAT AND AGREEMENT TO THE COUNTY PRIOR TO
RELEASING THE PROJECT TO THE CONSTRUCTION SECTION.
3. REVISE THE LABEL OF THE TABLE CURRENTLY SHOWN AS
"STRUCTURE TABLE" TO "COORDINATE TABLE" AND CORRECT THE
DRAFTING AND THE SPELLING OF "NORTHING AND EASTING".
4. PROVIDE A "NORTH ARROW" ON EACH OF SHEETS #2 AND #3.
5. LABEL EASTBORNE WAY ON SHEET #3.
6. THOROUGHLY EXAMINE ALL SHEETS TO CORRECT ALL
EXTRANEOUS MARKINGS, OVERLAPPING TEXT, ILLEGIBLE TEXT
AND DRAWING FEATURES, ETC. IN ORDER TO FACILITATE A
CLEAN DRAWING WITH ALL TEXT AND DRAWING FEATURES
COMPLETELY LEGIBLE AND ABUNDANTLY VISIBLE.
7. REVISE THE "MATERIALS LIST" AS NECESSARY.
PLEASE MAKE ALL OF THE SUGGESTED CHANGES AND SUBMIT
ONE(1) SET OF REVISED PLANS.
THE OWNER MUST ENTER INTO A COUNTY CONTRACT PRIOR TO THE
START OF CONSTRUCTION. PLEASE SEND ME A COPY OF THE
"ACCEPTED" BID PROPOSAL BETWEEN THE DEVELOPER AND THE
CONTRACTOR SO WE MAY PREPARE THE COUNTY CONTRACT. THE
BID PROPOSAL MUST BE BASED ON THE LATEST REVISED
UTILITIES PLANS REFLECTING THE REVIEWER'S STAMP, AND ALL
WORK MUST BE PERFORMED BY AN ACCEPTABLE UTILITIES
CONTRACTOR. IF PLANS ARE REVISED AFTER CONTRACT
PREPARATION DUE TO A CHANGE BECAUSE OF VIRGINIA
DEPARTMENT OF TRANSPORTATION'S AND/OR ENVIRONMENTAL
ENGINEERING DEPARTMENT'S APPROVAL OF THE ROAD, DRAINAGE,
AND EROSION CONTROL DESIGN OR BECAUSE OF STATE AGENCIES'
REVIEW AND APPROVAL OF THE UTILITIES DESIGN, A REVISED
BID PROPOSAL MAY BE NECESSARY TO ACCURATELY REFLECT THE
LATEST UTILITIES DESIGN AND A NEW CONTRACT PREPARATION
MAY BE NECESSARY AND EXECUTED PRIOR TO THE START OF
CONSTRUCTION.
IF YOU HAVE ANY QUESTIONS, DO NOT HESITATE TO CONTACT ME
AT 748-1343.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: MIKE LARSON/748-1338
PLAN NAME: ST. IVES SECTION 3
PLAN NUMBER: 16CP0094
ORIGINAL PLAN DATE: 3/24/16
REVIEW DATE: 12/29/16
LATEST SUBMISSION DATE: 12/29/19/16
SUBMITTAL NUMBER: 4
STATUS: APPROVED
TABLE REVIEW: YES
ABOVE REFERENCED PROJECT DATED MARCH 24, 2016, WITH
THE LATEST REVISION DATED NOVEMBER 30, 2016, THIS PROJECT IS
REVIEW IS EFFECTIVE UNTIL DECEMBER 29, 2021
.
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: MIKE LARSON/748-1338
PLAN NAME: ST. IVES SECTION 3
PLAN NUMBER: 16CP0094
ORIGINAL PLAN DATE: 3/24/16
REVIEW DATE: 7/25/17
LATEST SUBMISSION DATE: 6/26/17
SUBMITTAL NUMBER: 5
STATUS: APPROVED WITH CONDITIONS
TABLE REVIEW: YES
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR THE
ABOVE REFERENCED PROJECT DATED MARCH 24, 2016, WITH
THE LATEST REVISION DATED JUNE 23, 2017, THIS PROJECT IS APP
ROVED WITH THE FOLLOWING CONDITION.
ON THE SUBDIVISION PLAT, A MFF (SAN) MUST BE CALCULATED AND
SHOWN FOR LOTS 11, 12, AND 13.
THIS REVIEW IS EFFECTIVE UNTIL JULY 25, 2022.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: ST. IVES, SEC 3
CASE NUMBER: 16CP0094
LATEST PLAN DATE: 03/24/2016
DEPT. REC'D. DATE: 04/12/2016
SUBMITTAL NUMBER: ONE
REVIEW DATE: 05/09/2016
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: ST. IVES, SEC 3
CASE NUMBER: 16CP0094
LATEST PLAN DATE: 06/14/2016
DEPT. REC'D. DATE: 06/21/2016
SUBMITTAL NUMBER: TWO
REVIEW DATE: 06/28/2016
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: ST. IVES, SEC 3
CASE NUMBER: 16CP0094
LATEST PLAN DATE: 09/08/2016
DEPT. REC'D. DATE: 09/15/2016
SUBMITTAL NUMBER: THREE
REVIEW DATE: 09/29/2016
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: ST. IVES, SEC 3
CASE NUMBER: 16CP0094
LATEST PLAN DATE: 11/30/2016
DEPT. REC'D. DATE: 12/29/2016
SUBMITTAL NUMBER: FOUR
REVIEW DATE: 12/30/2016
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: ST. IVES, SEC 3
CASE NUMBER: 16CP0094
LATEST PLAN DATE: 06/23/2017
DEPT. REC'D. DATE: 06/30/2017
SUBMITTAL NUMBER: FIVE
REVIEW DATE: 07/03/2017
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
.
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: ST. IVES, SEC 3
CASE NUMBER: 16CP0094
LATEST PLAN DATE: 07/25/2017
DEPT. REC'D. DATE: 08/10/2017
SUBMITTAL NUMBER: SIX
REVIEW DATE: 08/11/2017
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
.
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : STEVE TUGWELL / 768-7566
PLAN NAME : ST. IVES, SEC. 3
PLAN NUMBER : 16CP0094
ORIGINAL PLAN DATE : 3-24-16
REVIEW DATE : 4/22/16
LATEST SUBMISSION DATE : 4-11-16
SUBMITTAL NUMBER : 1
STATUS : CORRECTIONS REQUIRED
TABLE REVIEW: N
1. THIS PROJECT IS NOT WITHIN UPPER SWIFT CREEK,
THEREFORE TREE CANOPY ISN'T REQUIRED.
2. ON THE FINAL PLAT, ALL BUILDING ENVELOPES SHALL REFLECT
MEASUREMENTS FROM THE PROPERTY LINE TO THE BUILDING
ENVELOPE/BUILDING LINE. ENVELOPES SHOWN WITHIN THIS PLAN
HAVE NOT BEEN VERIFIED FOR CONFORMANCE WITH ORDINANCE
STANDARDS.
3. HOA DOCUMENTS AND MAINTENANCE RESPONSIBILITIES SHALL BE
ON THE FINAL PLAT.
4. PLEASE PROVIDE STANDARD CONDITIONS PER SEC. 17-62.
5. PROVIDE DETAIL SHOWING THE SIDEWALKS, AND A NOTE
STATING THAT THE HOA IS TO MAINTAIN THE SIDEWALKS, OR
RESPONSIBLE PARTY. THIS NOTE WILL CARRY OVER TO THE FINAL
PLAT.
6. NOTE ALL CONSTRUCTION-RELATED PROFFERS ON THE FINAL PLAT.
7. NOTE THE PROJECT CASE NUMBER (16CP0094) IN THE LOWER
RIGHT-HAND CORNER.
8. NOTE ZONING CASE NUMBER (16SN0504) ON THE TITLE SHEET
UNDER GENERAL NOTES.
9. IS SENIOR HOUSING PROPOSED? IF SO, THEN NOTE AND ID UNITS
ON THE FINAL PLAT.
10. SHOW TREE PROTECTION TAPE FOR THE 200' BUFFER ON E&S 1&2
11. THE 50' OPEN SPACE BUFFER SHOWN ON SHEET 2
SHOULD EXTEND NORTH FROM SEC. 1 INTO THE OPEN
SPACE OF SEC. 3.
NOTES:
1. LOTS FRONTING ON THE BULBS OF CUL-DE-SACS
SHALL BE DESIGNED SUCH THAT BUILDING LINES
ARE UNIFORM AROUND THE BULB. (P)
2. IN CONJUNCTION WITH THE SUBMITTAL OF THE FINAL
PLATS, THE SUBDIVIDER SHALL FLAG ALL BUFFERS
FOR INSPECTION BY THE PLANNING DEPARTMENT. IF
INSUFFICIENT VEGETATION REMAINS, THE SUBDIVIDER
SHALL SUBMIT A LANDSCAPE PLAN TO THE DIRECTOR
OF PLANNING TO ENSURE COMPLIANCE WITH THIS
CONDITION. IF CONDITIONS ON SITE ARE NOT
CONDUCIVE TO PLANT SURVIVAL, THE SUBDIVIDER SHALL
PROVIDE SURETY TO THE COUNTY IN THE AMOUNT
REQUIRED TO IMPLEMENT THE PLAN. AN ESTIMATE
FROM A LANDSCAPE CONTRACTOR SHALL SERVE AS
THE BASIS FOR THE SURETY AMOUNT. (P)
3. A NOTE SHALL BE PLACED ON THE FINAL PLAT THAT
INDICATES THE BUFFERS ARE EXCLUSIVE OF
EASEMENTS, CUT AND FILL SLOPES AND SETBACKS
. THE BUFFERS ARE TO REMAIN UNDISTURBED
AND NO ACCESS IS PERMITTED THROUGH THEM
TO ANY ADJACENT ROADS. (P)
4. PER SECTION 19-559, A HOMEOWNERS ASSOCIATION
WITH MANDATORY MEMBERSHIP WILL BE REQUIRED
. OWNERSHIP AND MAINTENANCE RESPONSIBILITIES
OF THE ASSOCIATION SHALL BE STATED ON ALL FINAL
PLATS. THE SUBDIVIDER SHALL SUBMIT DRAFT BYLAWS
AND COVENANTS OF THE ASSOCIATION WITH THE STATE
CORPORATION COMMISSION. THE APPROVED BYLAWS
AND COVENANTS SHALL BE RECORDED PRIOR TO OR
IN CONJUNCTION WITH THE RECORD PLAT. THE RECORDATION
INFORMATION SHALL BE SHOWN ON THE FINAL PLAT
AND EACH SUBSEQUENT FINAL PLAT. THE SUBDIVIDER
SHALL FUND THE FIRST YEAR OPERATIONAL EXPENSES
OF THE ASSOCIATION. (P
5. ANY ROAD AND LOT CONFIGURATIONS OUTSIDE THE
LIMITS OF CONSTRUCTION PLAN CASE 16CP0094 ARE NOT
INCLUDED IN THIS REVIEW. (P)
6. STANDARD CONDITIONS PER 17-62 OF THE
SUBDIVISION ORDINANCE. (P)
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE # : STEVE TUGWELL / 768-7566
PLAN NAME : ST. IVES, SEC. 3
PLAN NUMBER : 16CP0094
ORIGINAL PLAN DATE : 3/24/16
REVISION DATE:
LATEST SUBMISSION DATE : 6/14/16
REVIEW DATE: 7/8/16
SUBMITTAL NUMBER : 2
STATUS: REVISIONS REQUIRED
1. BUFFER ALONG NORTH OTTERDALE ROAD NEEDS
TO BE SHOWN ON THE E&S PLAN ON SHEET
6 ALONG WITH TREE PROTECTION TAPE.
2. THE MIN. LOT WIDTH HAS BEEN MET ON LOTS
11, 12, AND 13, SO THE BUILDING LINE
DOESN'T NEED TO BE SHOWN.
3. THE MIN. LOT WIDTH OF 70' HAS NOT
BEEN MET AT THE 20' SETBACK FOR
LOT #8, AND MOVING THE BUILDING LINE
BACK WOULD ENCROACH INTO THE 200' BUFFER.
4. PER ZONING CASE #05SN0329, "EACH LOT
SHALL HAVE AN AREA OF NOT LESS THAN
8,000 SQUARE FEET AND NOT MORE THAN
20,000 SQUARE FEET, AND A LOT
WIDTH OF NOT LESS THAN SEVENTY (70)
FEET WITH THE EXCEPTION OF ONE LOT
THAT SHALL HAVE AN AREA OF NOT LESS
THAN FIVE (5) ACRES". MOST LOTS ARE
SHOWN IN EXCESS OF THE 20,000 SQ. FT. MAX.
5. THE EXTENSION OF ST. IVES DRIVE APPEARS
TO INTERFERE WITH THE FOCAL POINT LOCATED
NORTH OF LOT 16, SEC. 2. AN AMENDMENT TO
THE FOCAL POINT MAY BE NECESSARY.
6. LABEL THE 20' EASEMENT THAT IS SHOWN ON
SHEET 2.
NOTES:
1. PLACE CONSTRUCTION-RELATED PROFFERS AS A
NOTE ON THE FINAL PLAT.
2.PER SECTION 19-559, A HOMEOWNERS
ASSOCIATION WITH MANDATORY MEMBERSHIP
WILL BE REQUIRED.OWNERSHIP AND MAINTENANCE
RESPONSIBILITIES OF THE ASSOCIATION SHALL
BE STATED ON ALL FINAL PLATS.
THE SUBDIVIDER SHALL SUBMIT DRAFT BYLAWS
AND COVENANTS OF THE ASSOCIATION WITH THE
STATE CORPORATION COMMISSION. THE APPROVED
BYLAWS AND COVENANTS SHALL BE RECORDED PRIOR
TO OR IN CONJUNCTION WITH THE RECORD PLAT.
THE RECORDATION INFORMATION SHALL BE SHOWN
ON THE FINAL PLAT AND EACH SUBSEQUENT FINAL
PLAT.THE SUBDIVIDER SHALL FUND THE FIRST YEAR
OPERATIONAL EXPENSES OF THE ASSOCIATION.
3.ANY ROAD AND LOT CONFIGURATIONS OUTSIDE THE
LIMITS OF CONSTRUCTION PLAN CASE 16CP0110 ARE
NOT INCLUDED IN THIS REVIEW.
END OF 2ND PLAN PLANNING REVIEW.
******************************************************
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE # : STEVE TUGWELL / 768-7566
PLAN NAME : ST. IVES, SEC. 3
PLAN NUMBER : 16CP0094
ORIGINAL PLAN DATE : 3/24/16
REVISION DATE: 9/8/16
LATEST SUBMISSION DATE : 9/12/16
REVIEW DATE: 9/28/16
SUBMITTAL NUMBER : 3
STATUS: TABLE REVIEW YES
1. PROVIDE AN AUTO CAD FILE DEPICTING THE
BOUNDARIES OF THIS CONSTRUCTION PLAN. THIS
MAY BE EMAILED TO TUGWELLS@CHESTERFIELD.GOV
NOTES:
1. PLACE CONSTRUCTION-RELATED PROFFERS AS A
NOTE ON THE FINAL PLAT.
. PER SECTION 19.1-303, A HOMEOWNERS ASSOCIATION
WITH MANDATORY MEMBERSHIP WILL BE REQUIRED
OWNERSHIP AND MAINTENANCE RESPONSIBILITIES
OF THE ASSOCIATION SHALL BE STATED ON ALL FINAL
PLATS. THE SUBDIVIDER SHALL SUBMIT DRAFT BYLAWS
AND COVENANTS OF THE ASSOCIATION WITH THE STATE
CORPORATION COMMISSION. THE APPROVED BYLAWS
AND COVENANTS SHALL BE RECORDED PRIOR TO OR
IN CONJUNCTION WITH THE RECORD PLAT. THE
RECORDATION INFORMATION SHALL BE SHOWN ON THE
FINAL PLAT AND EACH SUBSEQUENT FINAL PLAT. THE
SUBDIVIDER SHALL FUND THE FIRST YEAR OPERATIONAL
EXPENSES OF THE ASSOCIATION.
3.ANY ROAD AND LOT CONFIGURATIONS OUTSIDE THE
LIMITS OF CONSTRUCTION PLAN CASE 16CP0094 ARE
NOT INCLUDED IN THIS REVIEW.
4. STANDARD COMMENT: ANY BUILDING ENVELOPE SHOWN
ON THE APPROVED CONSTRUCTION PLANS WILL BE
SUBJECT TO REVIEW FOR COMPLIANCE AT TIME OF
FINAL CHECK.
5. STANDARD COMMENT: BUFFER IS EXCLUSIVE OF
EASEMENTS AND SETBACKS. BUFFER MUST REMAIN
IN A NATURAL STATE. BUFFER WILL BE FIELD
VERIFIED AT TIME OF FINAL CHECK. ANY
CLEARING OR REMOVAL OF VEGETATION FROM BUFFER
WILL RESULT IN LANDSCAPE PLAN SUBMITTAL AND
BONDS AT FINAL CHECK.
**********************************************************
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE # : STEVE TUGWELL / 768-7566
PLAN NAME : ST. IVES, SEC. 3
PLAN NUMBER : 16CP0094
ORIGINAL PLAN DATE : 4/24/16
REVISION DATE: 6/23/17
LATEST SUBMISSION DATE : 6/26/17
REVIEW DATE: 7/24/17
SUBMITTAL NUMBER : 5
STATUS: TABLE REVIEW: NO
1. PROVIDE AN AUTO CAD FILE DEPICTING THE
BOUNDARIES OF THIS CONSTRUCTION PLAN.
ONLY IF BOUNDARIES HAVE CHANGED) THIS
MAY BE EMAILED TO TUGWELLS@CHESTERFIELD.GOV
2. ACCESS TO THE OPEN SPACE HAS NOT BEEN
PROVIDED WITH THIS SUBMITTAL. THE OPEN
SPACE SHOULD BE CLEARLY DELINEATED AND
AN EASEMENT SHOULD BE PROVIDED TO THE OPEN
SPACE.
3. A RETAINING WALL IN EXCESS OF 7-FEET IN HEIGHT
IS SHOWN THAT SPANS THROUGH LOTS 10-12.
PLEASE CERTIFY THAT THE FENCE WON'T PUNCH
THROUGH GEOFABRIC, AND PROVIDE AN EASEMENT
FOR THE RETAINING WALL THAT SPECIFIES
THE HOA WILL BE RESPONSIBLE FOR ITS MAINTENANCE.
4. PLEASE CORRECT THE LOT AREA FOR LOTS 1-8.
NOTES:
1. PLACE CONSTRUCTION-RELATED PROFFERS AS A
NOTE ON THE FINAL PLAT.
2. PER SECTION 19.1-303, A HOMEOWNERS ASSOCIATION
WITH MANDATORY MEMBERSHIP WILL BE REQUIRED
OWNERSHIP AND MAINTENANCE RESPONSIBILITIES
OF THE ASSOCIATION SHALL BE STATED ON ALL FINAL
PLATS. THE SUBDIVIDER SHALL SUBMIT DRAFT BYLAWS
AND COVENANTS OF THE ASSOCIATION WITH THE STATE
CORPORATION COMMISSION. THE APPROVED BYLAWS
AND COVENANTS SHALL BE RECORDED PRIOR TO OR
IN CONJUNCTION WITH THE RECORD PLAT. THE
RECORDATION INFORMATION SHALL BE SHOWN ON THE
FINAL PLAT AND EACH SUBSEQUENT FINAL PLAT. THE
SUBDIVIDER SHALL FUND THE FIRST YEAR OPERATIONAL
EXPENSES OF THE ASSOCIATION.
3.ANY ROAD AND LOT CONFIGURATIONS OUTSIDE THE
LIMITS OF CONSTRUCTION PLAN CASE 16CP0094 ARE
NOT INCLUDED IN THIS REVIEW.
4. STANDARD COMMENT: ANY BUILDING ENVELOPE SHOWN
ON THE APPROVED CONSTRUCTION PLANS WILL BE
SUBJECT TO REVIEW FOR COMPLIANCE AT TIME OF
FINAL CHECK.
5. STANDARD COMMENT: BUFFER IS EXCLUSIVE OF
EASEMENTS AND SETBACKS. BUFFER MUST REMAIN
IN A NATURAL STATE. BUFFER WILL BE FIELD
VERIFIED AT TIME OF FINAL CHECK. ANY
CLEARING OR REMOVAL OF VEGETATION FROM BUFFER
WILL RESULT IN LANDSCAPE PLAN SUBMITTAL AND
BONDS AT FINAL CHECK.
**********END OF 5TH REVIEW*****************
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: ST. IVES SECTION 3
PLAN NUMBER: 16CP0094
LATEST REVISION DATE: 3/24/16
REVIEW DATE: 4/27/16
LATEST SUBMISSION DATE: 4/12/16
SUBMITTAL NUMBER: 1ST REVIEW
STATUS: APPROVED
TABLE REVIEW: YES
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: ST. IVES SECTION 3
PLAN NUMBER: 16CP0094
LATEST REVISION DATE: 6/14/16
REVIEW DATE: 6/21/16
LATEST SUBMISSION DATE: 6/20/16
SUBMITTAL NUMBER: 2ND REVIEW
STATUS: APPROVED
TABLE REVIEW: YES
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: HALLSLEY SECTION 19
PLAN NUMBER:15CP0062
LATEST REVISION DATE: 6/13/16
REVIEW DATE: 6/21/16
LATEST SUBMISSION DATE: 6/20/16
SUBMITTAL NUMBER: 3RD REVIEW
STATUS: APPROVED
TABLE REVIEW: YES
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: ST. IVES SECTION 3
PLAN NUMBER: 16CP0094
LATEST REVISION DATE: 11/30/16
REVIEW DATE: 12/30/16
LATEST SUBMISSION DATE: 12/29/16
SUBMITTAL NUMBER: 4TH REVIEW
STATUS: APPROVED
TABLE REVIEW: YES
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: ST. IVES SECTION 3
PLAN NUMBER: 16CP0094
LATEST REVISION DATE: 6/23/17
REVIEW DATE: 7/8/17
LATEST SUBMISSION DATE: 6/30/17
SUBMITTAL NUMBER: 5TH REVIEW
STATUS: APPROVED
TABLE REVIEW: YES
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: ST. IVES SECTION 3
PLAN NUMBER: 16CP0094
LATEST REVISION DATE: 7/25/17
REVIEW DATE: 8/10/17
LATEST SUBMISSION DATE: 6/30/17
SUBMITTAL NUMBER: 6TH REVIEW
STATUS: APPROVED
TABLE REVIEW: YES
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
=========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : LYNDA GILBERTSON, P.E. / 706-2116
NAME OF PLAN : ST. IVES - SECTION 3
SITE PLAN NO. : 16CP0094
ORIGINAL PLAN DATE : MARCH 24, 2016
DEPT. REC'D DATE : APRIL 11, 2016
SUBMITTAL NUMBER : ONE
REVIEW DATE : MAY 9, 2016
RECOMMENDATION : REVISION REQUESTED
TABLE REVISION : NO
AS A REMINDER THE RESPONSIBILITY FOR ACHIEVING AND
MAINTAINING SATISFACTORY LOT DRAINAGE WILL BE THAT OF
THE DEVELOPER UP THROUGH A PERIOD OF ONE YEAR AFTER
STATE ACCEPTANCE OF THE SUBDIVISION ROADS.
RESPONSIBILITY FOR COMPLIANCE TO CHESTERFIELD COUNTY
STANDARDS AND POLICIES AND STATE AND FEDERAL REGULATIONS
WILL BE PLACED ON THE PROFESSIONAL ENGINEER WHO SIGNS
AND SEALS THE CONSTRUCTION PLANS APPROVAL.
AS A REMINDER $100.00 BMP MAINTENANCE FEE PER LOT
MUST BE PAID PRIOR TO SUBDIVISION PLAT RECORDATION
THIS OFFICE RECOGNIZES THAT 10-YEAR PRE/POST
REQUIREMENTS FOR FLOOD PROTECTION CAN BE ADDRESSED BY
DISCHARGING INTO AN ESTABLISHED 100-YEAR FLOODPLAIN.
THOUGH THIS PROJECT IN NOT SUBJECT TO THE PRELIMINARY
(TENTATIVE) PROCESS SINCE IT FALLS UNDER THE 50-LOT
THRESHOLD, PLEASE BE ADVISED THAT ALL STANDARD
CONDITIONS PER SECTION 17-62 OF THE COUNTY ORDINANCE
STILL APPLY.
======== CBPA/VRRM ============
1. PROVIDE AN EXHIBIT PRIOR TO LAND DISTURBANCE ISSUANCE TO
BE INCLUDED IN THE HOA COVENANTS FOR COMPLYING WITH THE
VRRM GUIDELINES REGARDING THE FORESTED/OPEN SPACE
AREAS (FOS), REFER TO THE CHESTERFIELD COUNTY APPROVED
DECLARATION OF RESTRICTED COVENANTS SENT VIA E-MAIL ON
APRIL 29TH AT 9:49 AM.
2. PLEASE INCLUDE IN CBPA NOTE ON THE COVER SHEET THE
NUTRIENT CREDIT BANK AND ITS 8 DIGIT CODE THE 0.98 LBS
ARE PURCHASED FROM. VERIFY THE LOAD REMOVAL REQUIRED
THE COVER SHEET 0.98 LBS ON THE COVER AND THE MS-4 TABLE
ON SHEET 10 AND THE LAND COVER SUMMARY HAS 0.05 LBS.
3. A RECEIPT FOR THE NUTRIENT CREDIT PURCHASE MUST BE
RECEIVED PRIOR TO PLAN APPROVAL.
4. ST. IVES SECTION 2 MET COMPLIANCE WITH TECHNICAL
CRITERIA PART IIC, SECTION THREE WILL MEET COMPLIANCE
WITH TECHNICAL CRITERIA PART IIB. A PORTION OF ST. IVES
DRIVE BETWEEN STATION 16+65.18 AND APPROXIMATE STATION
19+80 IN SECTION 2 FALLS UNDER PART IIB. CONSIDER
DIRECTING STRUCTURES 2/4 TO STRUCTURE 12. AS PROPOSED,
STRUCTURES 2 AND 19 MUST SATISFY COMPLIANCE BY ENERGY
BALANCE PART IIB. ENVIRONMENTAL ENGINEERING WOULD
ACCEPT THE PROPOSED EXTENSION OF STORM SEWER STRUCTURE
17 UNDER IIC AS PROPOSED WITH REDUCED IMPERVIOUS AREA.
FURTHER DISCUSSION MAY BE HELPFUL.
5. IT APPEARS LOTS 10-17 MAY QUANTITY REQUIREMENTS UNDER
SECTION 870-66 ITEM D INCREASED VOLUMES OF SHEET FLOW.
HOW HAS LOTS 8/9 ADDRESSED 870-66 WITH THE NATURAL
CONVEYANCE SYSTEM CROSSING THE LOTS?
6. PROVIDE THE VRRM SITE DATA SPREADSHEET ON SHEET 10, A
MODIFIED VERSION IS NOT ACCEPTABLE.
7. VERIFY THE AREA LISTED ON THE SOILS MAP ON SHEET 10.
THE FORESTED AREA TOTALS 16.42 AC, TURF 5.44 AC AND THE
IMPERVIOUS 2.96 AC FOR A TOTAL OF 24.82 AC NOT 24.47 AC.
8. DELETE THE SITE DISCHARGE TABLE ON SHEET 10, AS THIS
WILL NOT APPLY TO SECTION 3.
9. INCLUDE THE STORMWATER COMPLIANCE AND STORMWATER TABLES
(SEE ENVIRONMENTAL ENGINEERING WEBSITE) ON THE CBPA
COMPLIANCE SHEET 10.
10. SHOW THE TYPICAL IMPERVIOUS AREA ON EACH LOT, I.E.
HOMESITE, DRIVEWAYS, SIDEWALKS, ETC. ON SHEET 10.
======== EROSION CONTROL ============
1. PLEASE SUBMIT AN ITEMIZED COST ESTIMATE FOR REVIEW OF
THE EROSION AND SEDIMENT CONTROL BOND AMOUNT.
2. AS A PREREQUISITE TO ISSUANCE OF A LAND DISTURBANCE
PERMIT:
A. PLANNING DEPARTMENT APPROVAL MUST BE RECEIVED.
B. WETLANDS TREE PROTECTION FLAGGING MUST BE INSTALLED.
C. A PROCESSED VSMP REGISTRATION AND FEE FORM MUST BE
RECEIVED.
D. AN EROSION AND SEDIMENT CONTROL BOND FOR AN APPROVED
AMOUNT MUST BE POSTED.
E. A COPY OF THE VDOT LAND USE PERMIT MUST BE RECEIVED,
IF APPLICABLE.
F. TWO ADDITIONAL SETS OF PLANS TO BE STAMPED "APPROVED
FOR CONSTRUCTION" MUST RECEIVED.
G. SIGNED CONFIRMATION OF WRITTEN NOTIFICATION (U.S.
POSTAL CERTIFIED MAIL RETURN RECEIPT REQUESTED) FROM
THE FOLLOWING PROPERTY OWNERS MUST BE RECEIVED
ACKNOWLEDGING THE IMPENDING CONSTRUCTION ACTIVITY
ADJACENT TO THEIR PROPERTY (INCLUDE AN 8½" X 11" PLAN
OF THE PROPOSED CONSTRUCTION ACTIVITY IN THE VICINITY
OF THEIR PROPERTY). IF THE SECTION 2, 16/17/18 LOTS ARE
OCCUPIED PRIOR TO SECTION 3 LAND DISTURBANCE ISSUANCE.
H. A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD FILE
MUST BE SAVED AS A .DWG OR .DXF IN AUTO CAD VERSION
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINIA
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD,
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE
SUBDIVISION NAME AND SECTION, SUBDIVISION PLAN NUMBER,
THE ENGINEERING FIRM AND THE CAD FILE PREPARER'S NAME
AND PHONE NUMBER. THE FILE MUST CONTAIN THE FOLLOWING,
EACH CLEARLY LABELED IN SEPARATE LAYERS:
1. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
2. EDGES OF SIDEWALKS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
3. INCLUDE A DETAILED CONSTRUCTION SEQUENCE IN THE PHASE 1
CONSTRUCTION NARRATIVE FOR THE INSTALLATION OF STRUCTURE
1 ON SHEET 6 TO INCLUDE BUT NOT LIMITED TO THE
FOLLOWING:
A. ALL PIPE SECTIONS FOR STRUCTURE 1 WILL BE ON SITE PRIOR
TO CLEARING AND GRADING.
B. INSTALLATION WILL BE SCHEDULED WHEN PRECIPITATION IS
NOT FORECASTED FOR THE DURATION OF INSTALLATION AND
BACKFILLING.
C. DIVERT ALL FLOW WHILE THE NORTHERN MOST SECTION IS
INSTALLED FIRST.
D. THE FLOW WILL THEN BE DIVERTED THROUGH THE NORTHERN
SECTION AND THE REMAINING SECTION IS INSTALLED AND
BACKFILLED.
E. INSTALL FILL DIVERSION AT THE END OF EACH DAY
DISCHARGING INTO SEDIMENT TRAP.
F. INSTALL THE ENDWALLS.
G. SEED AND STABILIZE THE SLOPES IMMEDIATELY AFTER
FINISHED GRADE IS ESTABLISHED.
4. SHOW AND LABEL FOUR BEST FIT DIMENSION SEDIMENT TRAPS ON
SHEET 6 IN EACH CORNER OF STRUCTURE 1 THAT THE FILL
DIVERSION AND SLOPE DRAINS DISCHARGE INTO.
5. REVISE THE TEMPORARY CREEK CROSSING (TCC) TO THE
TEMPORARY VEHICULAR STREAM CROSSING ((SC) STD 3.24) IN
THE PLAN VIEW. INCLUDE IN THE LEGEND ON SHEET 6.
6. REVISE THE GRAVEL OUTLET STRUCTURE LABEL FOR THE
SEDIMENT TRAPS FROM SO TO GRAVEL OUTLET STRUCTURE ON
SHEETS 6 AND 7. THE LABEL SO IS FOR SODDING (SPEC 3.33)
AND MAYBE CONFUSING.
7. GHOST LABEL THE LOT NUMBERS AND STREET NAMES ON SHEETS 6
AND 7, SO THE EROSION CONTROL MEASURES STANDOUT.
8. INCLUDE THE INLET PROTECTION (SPEC 3.07) IN THE LEGEND
ON SHEET 6.
9. DELETE ONE OF THE TWO SAFETY FENCE (SPEC 3.01) LABELS
FROM THE LEGEND ON SHEETS 6 AND 7.
10. MOVE STEP 3 OF THE PHASE 1 CONSTRUCTION NARRATIVE TO THE
LAST STEP OF THE NARRATIVE.
11. COMBINE STEPS 5 AND 6 OF THE PHASE 1 CONSTRUCTION
NARRATIVE ON SHEET 6, THESE ARE SIMILAR STEPS.
12. DELETE THE FOURTH AND SEVENTH NOTES UNDER THE PHASE 1
CONSTRUCTION NARRATIVE ON SHEET 6, THE PROJECT IS NOT IN
THE UPPER SWIFT CREEK WATERSHED.
13. DELETE THE SUPER SILT FENCE FROM THE FLOW PATH OF THE
INTERMITTENT STREAM AT EACH END OF STRUCTURE 1 ON SHEETS
6 AND 7.
14. A TEMPORARY SLOPE DRAIN (STD. & SPEC. #3.15) MUST BE
PROVIDED TO CONVEY RUNOFF FROM THE TOP OF THE
FINISHED SLOPE TO THE BOTTOM AND THEN INTO A BEST FIT
SEDIMENT TRAPPING FACILITY WHERE FILL SECTIONS ARE
GREATER THAN 5-FEET (SHEET 7).
15. DELETE THE SUPER SILT FENCE FROM THE FLOW PATH OF THE
INTERMITTENT STREAM AT EACH END OF STRUCTURE 19 ON SHEET
7.
16. INCLUDE TEMPORARY SLOPE DRAIN (STD & SPEC. 3.15) IN THE
LEGEND ON SHEET 7.
17. DELETE THE FIRST NOTE UNDER THE PHASE II CONSTRUCTION
NARRATIVE ON SHEET 7, THE PROJECT IS NOT IN THE UPPER
SWIFT CREEK WATERSHED.
18. INCLUDE IN STEP 7 OF THE PHASE II CONSTRUCTION NARRATIVE
THAT THE UTILITY INSTALLATION AND THE UTILITY STREAM
CROSSINGS WILL BE DONE DURING A PRIOR WHEN NO
PRECIPITATION IS FORECASTED AND WILL BE BROUGHT TO FINAL
GRADE, SEEDED AND STABILIZED IMMEDIATELY.
19. INCLUDE A STEP 5 IN THE PHASE II CONSTRUCTION NARRATIVE
ON SHEET 7.
20. INCLUDE THE UTILITY STREAM CROSSING AND TEMPORARY SLOPE
DRAIN IN SECTION 7 AND 11 OF THE EROSION CONTROL
NARRATIVE ON SHEET 8.
21. REDUCE THE FONT OF THE RPA RESTORATION PLAN TO ROTATE
THE TREE PRESERVATION & PROTECTION TYPICAL AND INSERT A
TEMPORARY SLOPE DRAIN TYPICAL DETAIL ON SHEET 9.
========= ROAD AND DRAINAGE ==============
1. THE TYPE II, 24-HOUR RAINFALL DEPTHS FOR THIS AREA SHOULD
BE AS FOLLOWS, PLEASE REVISE;
1-YEAR - 2.77"
2-YEAR - 3.36"
10-YEAR - 5.09"
100-YEAR - 8.42"
2. INCLUDE A FIRM FLOOD MAP REFERENCE NOTE ON THE COVER
SHEET TO THE FEMA PANEL 51041C0015D & THE DATE DECEMBER
18, 2012.
3. SUBMIT THE 100-YEAR FLOODPLAIN CALCULATIONS ALONG
MICHAUX CREEK TO THE PROJECT LIMITS, SHOW AND LABEL THE
CROSS SECTION WITH 100-YEAR WSE ON SHEET 11. AS A
REMINDER COUNTY APPROVED ELEVATIONS BECOME FEMA.
4. SHOW AND LABEL THE MORE RESTRICTED FEMA FLOODPLAIN
LIMITS; BASED ON FIELD CROSS SECTIONS AND TOPOGRAPHY OR
FROM THE FEMA PANEL 51041C0015D ON SHEET 11.
5. VERIFY THE TOTAL AREA AND THE CA TOTAL TO STRUCTURE 22,
THE LD-269 STRUCTURE CALCULATION WORKSHEET, WITH THE
HYDROLOGY WORKSHEET CROSS SECTION 3 TOTAL AREA AND CA.
CROSS-SECTION 3 IS JUST UPSTREAM AND THE VALUES ARE
DIFFERENT IN THE TWO FORMS. CA VALUES 3.03 AND 19.48
RESPECTIVELY AND THE CW OF 0.11.
F. VERIFY THE 4.15 DISTURBED AREA IN THE GENERAL NOTES ON
THE COVER SHEET, THE EROSION CONTROL NARRATIVE ON SHEET
8 HAS 4.12 ACRES.
7. THE TREE CANOPY PLAN (SHEET 2) IS NOT REQUIRED; THE
LOCATION IS OUTSIDE OF THE UPPER SWIFT CREEK WATERSHED.
8. SHOW AND LABEL AT LEAST ONE BENCHMARK REFERENCED TO
MEAN SEA LEVEL WITHIN THE LIMIT OF CONSTRUCTION.
9. AS A REMINDER, THE $1,000.00 ENVIRONMENTAL ENGINEERING
PROGRAM ADMINISTRATION FEE FOR THE RE-APPROVAL OF ST.
IVES SECTION 2 FOR THE REMOVAL OF THE CUL DE SAC AND
REALIGNMENT FROM STATION 17+00 TO 18+00 OF ST. IVES
DRIVE IS A PREREQUISITE TO PLAN APPROVAL OF ST. IVES
SECTION 3.
10. INCLUDE A NOTE ON SHEET 3 THAT LOTS 10 - 15 REQUIRE AN
ELEVATION CERTIFICATE FOR THE FEMA 100-YEAR FLOODPLAIN
SIGNED AND SEALED BY A REGISTERED PROFESSIONAL ENGINEER
OR ARCHITECT PRIOR TO ISSUANCE OF THE C.O.
11. PLEASE PROVIDE A "MINIMUM FINISHED FLOOR ELEVATION
(MFF(FLPL)) ONE FOOT ABOVE THE FEMA FLOOD PLAIN
ELEVATION" IN THE ENVIRONMENTAL NOTES ON SHEET 3.
12. REVISE THE SECOND ROW NOTE IN THE LOWER RIGHT CORNER OF
SHEET TO READ 3' IN LIEU 2'.
13. SHOW AND LABEL THE LIMITS OF THE 100-YEAR BACKWATER
ELEVATION CREATED BY STRUCTURE 22 ON SHEETS 3, 5 AND 11,
NOT OVERTOPPING THE DRIVEWAY.
14. RELOCATE THE RPA SIGNS TO THE NORTH REAR CORNER OF LOT
10, BETWEEN LOTS 11/12 AND THE REAR OF LOT 13 ON SHEET
3.
15. CORRECT THE STRUCTURE TYPE OF STRUCTURES 8 AND 20 TO
VDOT MH-1 AND REVISE STRUCTURE 16 TO A DI-6B WITH THE
SLOT LOCATION (NSEW) IN THE DRAINAGE DESCRIPTION ON
SHEET 3.
16. VERIFY THE 100-YEAR FLOODPLAIN DOTTED LINE AND THE DAM
FAILURE LIMITS CROSSING ST IVES DRIVE AT STRUCTURE 1 ON
SHEET 3, LIMITS SHOULD NOT CROSS THE ROAD SECTION.
17. VERIFY THE 100-YEAR BACKWATER (222.96) CREATED BY
STRUCTURE 1 TOP THE ROAD SAG (222.87) OF ST IVES DRIVE
ON SHEETS 3 AND 5, THIS IS NOT ACCEPTABLE. SINGLE POINT
ACCESS ROADS SHALL NOT BE TOPPED BY A 100-YEAR STORM
EVENT, PLEASE ADDRESS.
18. PROVIDE CURB AND GUTTER FLOW ARROWS ON SHEET 3.
19. LABEL THE FEMA FLOODPLAIN LIMITS IN THE STR 19-10
PROFILE VIEW ON SHEET 5.
20. LABEL THE FEMA FLOODPLAIN LIMITS AND THE 100-YEAR
BACKWATER WATER SURFACE ELEVATION IN THE STR 22 PROFILE
VIEW ON SHEET 5.
21. DELETE THE SOLID LINE FROM STATION 25+00 TO THE DASHED
EXISTING GRADE IN THE SWALE LOT 1 PROFILE VIEW ON
SHEET 5.
22. MAKE THE FOLLOWING CORRECTIONS TO STR 2 - 5 PROFILE VIEW
ON SHEET 5;
A. LABEL THE OUTLET PROTECTION AT THE END OF STRUCTURE
2.
B. VERIFY THE FILL SECTION BEYOND THE END OF STRUCTURE
2, LENGTHEN THE PIPE SECTION AS NEEDED.
23. CLARIFY THE GRADING AT APPROXIMATELY STATION 48+00 OF
SWALE LOT 8 PROFILE VIEW ON SHEET 5, IT APPEARS TO BE
BLOCKING THE FLOW OF THE SWALE.
24. MAKE THE FOLLOWING CORRECTIONS TO STR 17 - E23 PROFILE
VIEW ON SHEET 5.
A. SHOW AND LABEL THE PROPOSED GRADING OVER E22 TO E23.
B. DELETE THE EMBOLDEN SOLID PROPOSED LINE FROM STATION
00+25 TO 00+75.
C. LABEL THE RPA AND FLOODPLAIN LIMITS.
D. LABEL THE OUTLET PROTECTION AT THE END OF STRUCTURE
17.
25. SHOW STRUCTURES 15/16 RELOCATED BETWEEN LOTS 7/8 TO
PICK UP THE FLOW FROM THE 0.74 AC BUFFER DRAINAGE AREA.
A. SHOW AN LABEL A 5:1 GRASS SWALE SECTION AT THE REAR
OF LOT 6 CHANGING TO A 3:1 GRASS DITCH SECTION AT THE
REAR OF LOT 7 DRAINAGE AREA CROSSING THE HOMESITE.
B. SHOW A DI-6 STRUCTURE BETWEEN LOTS 7/8 TO PICK UP THE
FLOW AND PIPE IT TO THE INTERMITTENT STREAM.
C. SHOW AND LABEL A 100-YEAR OVERFLOW SWALE ABOVE THE
STORM SEWER.
D. THE REAR LOT DITCH SECTIONS AND STORM SEWER
STRUCTURES MUST BE ENCLOSED IN A 16' DRAINAGE
EASEMENT AND PROVIDE AN ACCESS EASEMENT TO THE STORM
SEWER.
E. PROVIDE A TYPICAL SECTION DETAIL AND CALCULATIONS.
F. FURTHER DISCUSSION WOULD BE HELPFUL.
26. REVISE THE DRAINAGE IMPROVEMENTS BETWEEN LOTS 5 AND 6 TO
DELETE STRUCTURE 15/16 AND SHOW A TYPICAL 5:1 GRASS
SWALE SECTION ON SHEETS 3, 7 AND 11. PROVIDE A TYPICAL
SECTION DETAIL.
27. SHOW THE SIDE YARD SWALE ON LOT 1 ON SHEET 11.
28. CONSIDER DELETING THE SWM-1 TYPICAL DETAIL IN THE CENTER
BOTTOM OF SHEET 16.
29. CORRECT THE GUTTER PAN FROM 8'-0' TO 2'-0" IN THE DI-6A,
6B TYPICAL ON SHEET 16.
30. INCLUDE THE SIDEWALK IN THE SAINT IVES DRIVE DETAIL ON
SHEET 16.
31. ROTATE THE PAVEMENT JOINT DETAIL ON SHEET 17.
32. IF NECESSARY PROVIDE AN ENLARGED DIMENSIONED DETAIL FOR
THE HEADWALL/WINGWALL FOR STRUCTURES 1 AND 2 ON SHEET
17. IF STRUCTURE 2 IS RELOCATED DELETE EW-1.1A.
33. PLEASE PROVIDE A WRITTEN RESPONSE TO THESE COMMENTS
WITH YOUR NEXT PLAN SUBMITTAL. DESIGN, DETAIL, AND
CALCULATIONS REQUIRED BY THE ABOVE COMMENTS WILL BE
SUBJECT TO FURTHER REVIEW.
---- END OF ENV. ENG. COMMENTS ----
============================================================
========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : LYNDA GILBERTSON, P.E. / 706-2116
NAME OF PLAN : ST. IVES - SECTION 3
SITE PLAN NO. : 16CP0094
ORIGINAL PLAN DATE : MARCH 24, 2016
DEPT. REC'D DATE : JUNE 20, 2016
SUBMITTAL NUMBER : TWO
REVIEW DATE : JULY 8, 2016
RECOMMENDATION : REVISION REQUESTED
TABLE REVISION : NO
AS A REMINDER THE RESPONSIBILITY FOR ACHIEVING AND
MAINTAINING SATISFACTORY LOT DRAINAGE WILL BE THAT OF
THE DEVELOPER UP THROUGH A PERIOD OF ONE YEAR AFTER
STATE ACCEPTANCE OF THE SUBDIVISION ROADS.
RESPONSIBILITY FOR COMPLIANCE TO CHESTERFIELD COUNTY
STANDARDS AND POLICIES AND STATE AND FEDERAL REGULATIONS
WILL BE PLACED ON THE PROFESSIONAL ENGINEER WHO SIGNS
AND SEALS THE CONSTRUCTION PLANS APPROVAL.
AS A REMINDER $100.00 BMP MAINTENANCE FEE PER LOT
MUST BE PAID PRIOR TO SUBDIVISION PLAT RECORDATION
THIS OFFICE RECOGNIZES THAT 10-YEAR PRE/POST
REQUIREMENTS FOR FLOOD PROTECTION CAN BE ADDRESSED BY
DISCHARGING INTO AN ESTABLISHED 100-YEAR FLOODPLAIN.
THOUGH THIS PROJECT IN NOT SUBJECT TO THE PRELIMINARY
(TENTATIVE) PROCESS SINCE IT FALLS UNDER THE 50-LOT
THRESHOLD, PLEASE BE ADVISED THAT ALL STANDARD
CONDITIONS PER SECTION 17-62 OF THE COUNTY ORDINANCE
STILL APPLY.
======== CBPA/VRRM ============
1. PROVIDE AN EXHIBIT PRIOR TO CONSTRUCTION PLAN APPROVAL
TO BE INCLUDED IN THE HOA COVENANTS FOR COMPLYING WITH
THE VRRM GUIDELINES REGARDING THE FORESTED/OPEN SPACE
AREAS (FOS).
2. PLEASE INCLUDE IN CBPA NOTE ON THE COVER SHEET THE
NUTRIENT CREDIT BANK AND ITS 8 DIGIT CODE THE 7.88 LBS
ARE PURCHASED FROM. VERIFY THE LOAD REMOVAL REQUIRED
THE COVER SHEET 7.88 LBS ON THE COVER AND THE LAND COVER
SUMMARY ON SHEET 10 HAS -1.89 LBS.
3. AS PREVIOUSLY REQUESTED, PROVIDE THE VRRM SITE DATA
SPREADSHEET SIMILAR TO WYNWOOD SEC. 18A, HALLSLEY SEC.
23.
4. A RECEIPT FOR THE NUTRIENT CREDIT PURCHASE MUST BE
RECEIVED PRIOR TO PLAN APPROVAL.
5. PLEASE PROVIDE THE MS-19 ANALYSIS AND CROSS SECTION
LOCATION BELOW THE OUTFALL FOR STRUCTURES 1 AND 17 THAT
MEETS THE TECHNICAL CRITERIA PART IIC FOR ST IVES,
SECTION 2. PLEASE INCLUDE AN MS-19 TABLE FOR THIS
OUTFALL LOCATION.
6. LOTS 10-17 MEETS QUANTITY REQUIREMENTS UNDER SECTION
870-66 ITEM D FOR THE INCREASED VOLUMES OF SHEET FLOW.
PLEASE INCLUDE IN THE STORMWATER COMPLIANCE TABLE AND
INCLUDE A NOTE ON SHEET 10.
7. AS PREVIOUSLY REQUESTED, HOW HAS LOTS 8/9 ADDRESSED
870-66 WITH THE NATURAL CONVEYANCE SYSTEM CROSSING THE
LOTS? A PORTION OF LOT 8 DRAINS TO THE ROW AND SOME
SHEET FLOWS TO THE DRAINAGEWAY.
8. SHOW AND LABEL THE ANALYSIS POINTS BELOW THE EACH OF THE
OUTFALLS ON SHEET 10.
9. SHOW THE LIMITS OF THE DRAINAGE AREAS ON LOTS 8 AND 9
FOR TWO DIFFERENT DRAINAGEWAYS CROSSING LOT 9.
10. DELETE THE "DISTURBED" DRAINAGE AREA IN THE THREE 1%
RULE TABLES TO DRAINAGE AREA ON SHEET 10. THE
DRAINAGE AREA IS THE CONTRIBUTING ]AREA, NOT JUST THE
DISTURBED AREA. REFER TO THE NOTE ON HALLSLEY SECTION
23 CONSTRUCTION PLANS. VERIFY THE AREA NUMBERS ARE
CORRECT TO THE LOCATIONS.
11. REMOVE THE REFERENCE TO MS-19 ANALYSIS FROM THE 1%
TABLES, THESE LOCATIONS FALL UNDER TECHNICAL CRITERIA
IIB.
12. VERIFY THE AREA LISTED ON THE SOILS MAP, FORESTED AREA
TOTALS 17.83 AC, TURF 4.39 AC ON SHEET 10. THESE DO NOT
MATCH THE LAND COVER SUMMARY TABLE.
13. SHOW AND LABEL THE STORM SEWER AND DITCHES ON SHEET 10.
14. COMPLETE THE STORMWATER COMPLIANCE TABLE AND STORMWATER
OUTFALL TABLE, MOST SPACES HAVE N/A IN IT. INCLUDE A
LOCATION OF THE OUTFALL, I.E STRUCTURE 2 OR LOTS 10-17,
ETC. FURTHER DISCUSSION MAYBE USEFUL.
15. AS PREVIOUSLY REQUESTED, SHOW THE TYPICAL IMPERVIOUS
AREA ON EACH LOT, I.E. HOMESITE, DRIVEWAYS, SIDEWALKS,
ETC. ON SHEET 10. INCLUDE THE IMPERVIOUS IN THE
CALCULATIONS.
16. INCREASE THE SIX DRAINAGE AREA LABELS ON SHEET 12 THAT
ARE JUST OFFSITE OF THE SECTION, FOR ROUTE 288 ROW AND
THE BUFFER AREA. THE FONT IS TOO SMALL TO READ AND
THESE LABELS DO NOT SHOW UP ON SHEET 11.
======== EROSION CONTROL ============
1. PLEASE SUBMIT AN ITEMIZED COST ESTIMATE FOR REVIEW OF
THE EROSION AND SEDIMENT CONTROL BOND AMOUNT.
2. AS A PREREQUISITE TO ISSUANCE OF A LAND DISTURBANCE
PERMIT:
A. PLANNING DEPARTMENT APPROVAL MUST BE RECEIVED.
B. WETLANDS TREE PROTECTION FLAGGING MUST BE INSTALLED.
C. A PROCESSED VSMP REGISTRATION AND FEE FORM MUST BE
RECEIVED.
D. AN EROSION AND SEDIMENT CONTROL BOND FOR AN APPROVED
AMOUNT MUST BE POSTED.
E. A COPY OF THE VDOT LAND USE PERMIT MUST BE RECEIVED,
IF APPLICABLE.
F. TWO ADDITIONAL SETS OF PLANS TO BE STAMPED "APPROVED
FOR CONSTRUCTION" MUST RECEIVED.
G. SIGNED CONFIRMATION OF WRITTEN NOTIFICATION (U.S.
POSTAL CERTIFIED MAIL RETURN RECEIPT REQUESTED) FROM
THE FOLLOWING PROPERTY OWNERS MUST BE RECEIVED
ACKNOWLEDGING THE IMPENDING CONSTRUCTION ACTIVITY
ADJACENT TO THEIR PROPERTY (INCLUDE AN 8½" X 11" PLAN
OF THE PROPOSED CONSTRUCTION ACTIVITY IN THE VICINITY
OF THEIR PROPERTY). IF THE SECTION 2, 16/17/18 LOTS ARE
OCCUPIED PRIOR TO SECTION 3 LAND DISTURBANCE ISSUANCE.
H. A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD FILE
MUST BE SAVED AS A .DWG OR .DXF IN AUTO CAD VERSION
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINIA
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD,
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE
SUBDIVISION NAME AND SECTION, SUBDIVISION PLAN NUMBER,
THE ENGINEERING FIRM AND THE CAD FILE PREPARER'S NAME
AND PHONE NUMBER. THE FILE MUST CONTAIN THE FOLLOWING,
EACH CLEARLY LABELED IN SEPARATE LAYERS:
1. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
2. EDGES OF SIDEWALKS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
3. RELOCATE THE DIMENSIONS FOR THE FOUR BEST FIT SEDIMENT
TRAPS ON SHEET 9 TO THE SEDIMENT TRAP TABLE ON SHEET 7.
4. AS PREVIOUSLY MENTIONED, REVISE THE TEMPORARY VEHICLE
CROSSING (TVC) TO THE TEMPORARY VEHICULAR STREAM
CROSSING ((SC) STD 3.24) IN THE PLAN VIEW. INCLUDE IN
THE LEGEND ON SHEET 6.
5. SHOW THE SUPER SILT FENCE UP TO THE WINGWALLS FOR
STRUCTURE 1 ON THE BOTH SIDES OF ST IVES DRIVE AT THE
TOE OF THE FILL SLOPES ON SHEETS 6 AND 7.
========= ROAD AND DRAINAGE ==============
1. AS PREVIOUSLY REQUESTED, VERIFY THE TOTAL AREA AND THE
CA TOTAL TO STRUCTURE 22, THE LD-269 STRUCTURE
CALCULATION WORKSHEET, WITH THE HYDROLOGY WORKSHEET
CROSS SECTION 3 TOTAL AREA AND CA. CROSS-SECTION 3 IS
JUST UPSTREAM AND THE VALUES ARE DIFFERENT IN THE TWO
FORMS SUBMITTED WITH THE FIRST SUBMITTAL PACKAGE CA
VALUES 3.03 AND 19.48 RESPECTIVELY AND THE CW OF 0.11.
2. EXTEND THE FEMA FLOODPLAIN UP TO THE OUTFALL FOR
STRUCTURE 2 ON SHEETS 3, 5, 10 AND 11.
3. SHOW AND LABEL THE WETLAND IMPACTS FOR THE DRIVEWAY FOR
LOT 9 ON SHEET 3, THE IMPACT CROSS HATCHING IS ONLY ON
LOT 8.
4. PROVIDE THE STATIONING ON ALL THE SWALE/DITCHES AND
DRAINAGE EASEMENTS ON SHEET 3 IN THE SAME DIRECTION AS
THE PROFILE VIEW ON SHEET 5 & 6.
5. IT IS NOT ACCEPTABLE TO DISCHARGE A DITCH SECTION OVER
CURB AND GUTTER. SHOW AND LABEL A DI-3 WITH REAR SLOT TO
PICK OF THE DITCH FLOW BETWEEN LOTS 7 &8 AND PIPE TO
STRUCTURE 10 (SHEET3).
ANOTHER OPTION IS TO EXTEND THE DITCH SECTION ACROSS THE
REAR OF LOT 8 TO STRUCTURE 22. FURTHER DISCUSSION MAYBE
HELPFUL.
6. PROVIDE A PROFILE VIEW FOR STRUCTURES 16 TO 7 ON SHEET
5.
7. PLEASE PROVIDE A WRITTEN RESPONSE TO THESE COMMENTS
WITH YOUR NEXT PLAN SUBMITTAL. DESIGN, DETAIL, AND
CALCULATIONS REQUIRED BY THE ABOVE COMMENTS WILL BE
SUBJECT TO FURTHER REVIEW.
---- END OF ENV. ENG. COMMENTS ----
============================================================
=========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : LYNDA GILBERTSON, P.E. / 706-2116
NAME OF PLAN : ST. IVES - SECTION 3
SITE PLAN NO. : 16CP0094
ORIGINAL PLAN DATE : MARCH 24, 2016
DEPT. REC'D DATE : SEPTEMBER 14, 2016
SUBMITTAL NUMBER : THREE
REVIEW DATE : SEPTEMBER 23, 2016
RECOMMENDATION : REVISION REQUESTED
TABLE REVISION : YES
AS A REMINDER THE RESPONSIBILITY FOR ACHIEVING AND
MAINTAINING SATISFACTORY LOT DRAINAGE WILL BE THAT OF
THE DEVELOPER UP THROUGH A PERIOD OF ONE YEAR AFTER
STATE ACCEPTANCE OF THE SUBDIVISION ROADS.
RESPONSIBILITY FOR COMPLIANCE TO CHESTERFIELD COUNTY
STANDARDS AND POLICIES AND STATE AND FEDERAL REGULATIONS
WILL BE PLACED ON THE PROFESSIONAL ENGINEER WHO SIGNS
AND SEALS THE CONSTRUCTION PLANS APPROVAL.
AS A REMINDER $100.00 BMP MAINTENANCE FEE PER LOT
MUST BE PAID PRIOR TO SUBDIVISION PLAT RECORDATION
THIS OFFICE RECOGNIZES THAT 10-YEAR PRE/POST
REQUIREMENTS FOR FLOOD PROTECTION CAN BE ADDRESSED BY
DISCHARGING INTO AN ESTABLISHED 100-YEAR FLOODPLAIN.
THOUGH THIS PROJECT IN NOT SUBJECT TO THE PRELIMINARY
(TENTATIVE) PROCESS SINCE IT FALLS UNDER THE 50-LOT
THRESHOLD, PLEASE BE ADVISED THAT ALL STANDARD
CONDITIONS PER SECTION 17-62 OF THE COUNTY ORDINANCE
STILL APPLY.
======== CBPA/VRRM ============
1. INCLUDE THE MS-19 TABLE (SHEET 8) AND STORMWATER TABLE
(SHEET 10) LOCATIONS IN THE INDEX ON THE COVER SHEET.
2. VERIFY THE AREAS LISTED ON THE SOILS MAP, ON SHEET 10.
ENSURE THEY MATCH THE LAND COVER SUMMARY TABLE.
1. LOTS 1 / 2, TOTAL IS 1.71 ACRES AND FOREST IS 1.74
ACRES.
2. LOT 17, TOTAL IS 5.68 ACRES AND THE THREE AREAS
TOTAL 5.67 ACRES.
3. LOTS 5 / 6, TOTAL IS 13.99 ACRES AND THE THREE AREAS
TOTAL 19.98 ACRES.
4. DEPENDING ON WHICH VALUES ARE USED THE SITE AREA
WOULD BE 24.48 AC, AND TP LOAD REDUCTION REQUIRED
WOULD BE -1.87 LB/YR.
======== EROSION CONTROL ============
1. PLEASE SUBMIT AN ITEMIZED COST ESTIMATE FOR REVIEW OF
THE EROSION AND SEDIMENT CONTROL BOND AMOUNT.
2. AS A PREREQUISITE TO ISSUANCE OF A LAND DISTURBANCE
PERMIT:
A. PLANNING DEPARTMENT APPROVAL MUST BE RECEIVED.
B. WETLANDS TREE PROTECTION FLAGGING MUST BE INSTALLED.
C. A PROCESSED VSMP REGISTRATION AND FEE FORM MUST BE
RECEIVED.
D. AN EROSION AND SEDIMENT CONTROL BOND FOR AN APPROVED
AMOUNT MUST BE POSTED.
E. A COPY OF THE VDOT LAND USE PERMIT MUST BE RECEIVED,
IF APPLICABLE.
F. TWO ADDITIONAL SETS OF PLANS TO BE STAMPED "APPROVED
FOR CONSTRUCTION" MUST RECEIVED.
G. SIGNED CONFIRMATION OF WRITTEN NOTIFICATION (U.S.
POSTAL CERTIFIED MAIL RETURN RECEIPT REQUESTED) FROM
THE FOLLOWING PROPERTY OWNERS MUST BE RECEIVED
ACKNOWLEDGING THE IMPENDING CONSTRUCTION ACTIVITY
ADJACENT TO THEIR PROPERTY (INCLUDE AN 8½" X 11" PLAN
OF THE PROPOSED CONSTRUCTION ACTIVITY IN THE VICINITY
OF THEIR PROPERTY). IF THE SECTION 2, 16/17/18 LOTS ARE
OCCUPIED PRIOR TO SECTION 3 LAND DISTURBANCE ISSUANCE.
H. A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD FILE
MUST BE SAVED AS A .DWG OR .DXF IN AUTO CAD VERSION
2009 OR EARLIER AND REFERENCED DIRECTLY TO THE VIRGINIA
STATE PLANE COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83
DATUM. THE AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD,
OR VIA EMAIL AND MUST BE CLEARLY LABELED WITH THE
SUBDIVISION NAME AND SECTION, SUBDIVISION PLAN NUMBER,
THE ENGINEERING FIRM AND THE CAD FILE PREPARER'S NAME
AND PHONE NUMBER. THE FILE MUST CONTAIN THE FOLLOWING,
EACH CLEARLY LABELED IN SEPARATE LAYERS:
1. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
2. EDGES OF SIDEWALKS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
========= ROAD AND DRAINAGE ==============
1. REVISE THE STRUCTURE 24 FROM MANHOLE (MH1) TO A DI-3
TYPE B WITH A REAR SLOT IN THE DRAINAGE DESCRIPTION ON
SHEET 3.
2. PLEASE PROVIDE A WRITTEN RESPONSE TO THESE COMMENTS
WITH YOUR NEXT PLAN SUBMITTAL. DESIGN, DETAIL, AND
CALCULATIONS REQUIRED BY THE ABOVE COMMENTS WILL BE
SUBJECT TO FURTHER REVIEW.
---- END OF ENV. ENG. COMMENTS ----
============================================================