Subdivision Review Comments
All Subdivision Review Comments for Case # 16CP0061




For VDOT’s comments please contact Virginia Department of Transportation at (804) 674-2814 or send e-mail to Boris.Solomonov@VDOT.Virginia.gov

For Tentative Subdivision resubmittals:

1. Please note that submittal fees include the original submittal and two (2) additional reviews.

2. A letter of transmittal is required to accompany each submittal.

3. Please verify that Environmental Engineering, Fire, CDOT, VDOT, and Planning have reviewed the submittal before resubmitting. A resubmittal tendered, prior to receiving all the required departments’ review, will be counted as an additional submittal. Go to Case Selection Form or Go to Project List


 
CASE NO: 16CP0061 STATUS: PENDING APPROVAL
PROJECT NAME: HARPERS MILL SOUTH P - LAST INTERNET UPDATE: 11/21/17
SUBMITTAL TYPE: CONSTRUCTION PLAN
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 04 03/02/17 03/03/17 COMPLETE 07/06/17 ASM 717-6711
FIRE DEPT.--: 04 03/02/17 03/03/17 COMPLETE 03/03/17 JKL 748-1489
PLANNING----: 04 03/02/17 03/03/17 ******** 09/20/16 GWK 706-7691
TRANSPORT.--: 04 03/02/17 03/03/17 COMPLETE 03/02/17 SES 751-4912
UTIL.PLAN.--: 04 03/02/17 03/03/17 ******** ********
UTILITIES---: 04 03/02/17 03/03/17 AMENDED* 03/02/17 M L 748-1338
UTIL.R.O.W.-: 04 03/02/17 03/03/17 ******** ********
VDOT--------: 04 03/02/17 03/03/17 ******** ********
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: HARPER'S MILL SOUTH PHASE, SECTION 2
PLAN NUMBER: 16CP0061
ORIGINAL PLAN DATE: 2/9/16
REVIEW DATE: 3/7/16
LATEST SUBMISSION DATE: 2/26/16
SUBMITTAL NUMBER: 1
STATUS: REVISIONS REQUIRED
TABLE REVIEW: NO
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR THE
ABOVE REFERENCED PROJECT DATED FEBRUARY 9, 2016,
WE MAKE THE FOLLOWING COMMENTS AND RECOMMENDATIONS:
1. A COPY OF VIRGINIA DEPARTMENT OF TRANSPORTATION'S
APPROVAL LETTER REGARDING PAVEMENT REPLACEMENT, METHOD
OF CROSSING, AND ALIGNMENT OF UTILITY WITH STATE RIGHT
OF WAY, AND A COPY OF ENVIRONMENTAL ENGINEERING'S
INITIAL REVIEW LETTER MUST BE SUBMITTED BEFORE REVISED
PLANS ARE SUBMITTED FOR RE-REVIEW.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION, A
COPY OF THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER
AND/OR ALL OTHER APPLICABLE LOCAL STATE AND FEDERAL
AGENCIES' APPROVAL LETTERS MUST BE RECEIVED BY THIS
DEPARTMENT. IN ADDITION, ALL EASEMENTS NOT INCLUDED
WITH THE SUBDIVISION PLAT MUST BE DEDICATED WITH A
SEPARATE PLAT AND AGREEMENT TO THE COUNTY PRIOR TO
RELEASING THE PROJECT TO THE CONSTRUCTION SECTION.
3. SHOW THE COUNTY PROJECT NUMBER 16-0032 ON THE LOWER
RIGHT HAND CORNER OF EACH SHEET.
4. PLEASE SIGN THE "LOT CERTIFICATION STATEMENT".
5. PROVIDE CALCULATIONS TO VERIFY THAT THE FIRE FLOW
AND DOMESTIC FLOWS CAN BE SUSTAINED WITH A RESIDUAL
PRESSURE OF 20 PSI.
6. PROVIDE, AS A PART OF THIS SET OF PLANS, A SANITARY
SEWER HYDRAULIC ANALYSIS, INCLUDING A DRAINAGE AREA MAP
AND CALCULATION TABLE (SEE CURRENT COUNTY
SPECIFICATIONS, DETAIL DRAWING NUMBER DES-1).
7. PROVIDE THE EXACT MINIMUM SEPARATION DISTANCE (1.5
VF MINIMUM REQUIRED) AT EACH SANITARY/STORM SEWER
CROSSING IN THE PROFILE VIEWS.
8. NOTE THAT 1.5 VF MINIMUM SEPARATION DISTANCE IS
REQUIRED AT EACH WATERLINE AND SANITARY SEWER CROSSING
IN THE PROFILE VIEWS.
9. LABEL EVERY STREET NAME THROUGHOUT THE PLAN VIEWS.
10. SHOW ALL EXISTING WATER AND SANITARY SEWER USING A
"DARK, DASHED" LINE AND LABELED WITH THE APPLICABLE
COUNTY PROJECT NUMBER.
11. SPECIFY EACH WATER SERVICE GREATER THAN OR EQUAL TO
60 LF AS 1" IN DIAMETER. NOTE THIS CONDITION ON EACH
LOT IN THE PLAN VIEWS.
12. CALL OUT THE VALVE TO BE USED FOR CUT OFF PURPOSES
DURING THE WATERLINE TIE IN, LABELING IT AS SUCH.
13. TO THE GREATEST EXTENT POSSIBLE, EXTEND THE SEWER
CONNECTIONS FROM THE MANHOLES.
14. DELETE THE VALVE AT STATION 16 + 40 ± EMBERTAN
ROAD.
15. THERE ARE SEVERAL LOCATIONS WHERE THE TRENCH DUG TO
INSTALL THE SANITARY SEWER WILL BE LOCATED UNDER AND/OR
IMMEDIATELY ADJACENT TO THE PROPOSED CURB AND GUTTER.
REVISE AS NECESSARY TO ELIMINATE THIS UNDESIRABLE
SITUATION, OR, IN THE EVENT THAT A REALIGNMENT OF THIS
NATURE IS NOT FEASIBLE, SPECIFY THAT THESE PORTIONS OF
THE SANITARY SEWER TRENCH ARE TO BE BACKFILLED TO THE
TOP WITH THOROUGHLY COMPACTED 21 A STONE. THIS
REQUIREMENT SHALL APPLY FOR A DISTANCE OF 5 LF PRIOR TO,
AS WELL AS AFTER SAID EXPOSURE. IN ADDITION, CLEARLY
NOTE THIS AS SUCH AT EACH APPLICABLE LOCATION IN THE
PROFILE VIEWS. THE LOCATIONS ARE AS FOLLOWS:
A. STATION 14 + 50 ±, EMBERTAN ROAD.
B. STATION 12 + 70 ±, EMBERTAN ROAD.
C. STATION 8 + 80 ±, EMBERTAN ROAD.
D. STATION 2 + 60 ±, EMBERTAN ROAD.
16. THERE ARE THREE (3) SANITARY SEWER CROSSINGS OF
OTTERDALE ROAD PROPOSED. HOW IS EACH PROPOSED TO BE
ACCOMPLISHED? OPEN CUT? BORE? PLEASE ADDRESS
THOROUGHLY, REVISING THE PLANS AS NECESSARY INCLUDING
ALL APPLICABLE NOTES, DETAILS, ETC.
17. DELETE THE 90° BEND AT THE INTERSECTION OF EMBERTAN
ROAD AND COURT AND CONTINUE THE ALIGNMENT OF THE
WATERLINE ALONG THE NORTH SIDE OF EMBERTAN ROAD.
18. PROVIDE "COMPLETE" PROFILE VIEWS (I.E. MANHOLE TO
MANHOLE, WITHOUT MATCH LINES) FOR EACH PROPOSED RUN OF
SANITARY SEWER.
19. TAKE ALL STEPS NECESSARY TO PROVIDE 1.5 VF
SEPARATION AT EACH SEWER CONNECTION CROSSING OF
WATERLINES AND STORM SEWERS.
20. THERE APPEARS TO BE AN ERROR IN THE SANITARY SEWER
SLOPE CALCULATION BETWEEN MANHOLE NUMBERS 26 AND 27.
PLEASE EXAMINE THOROUGHLY, REVISING AS NECESSARY.
21. "HATCH" ALL LIMITS OF FILL AND DUCTILE IRON PIPE IN
THE PROFILE VIEWS, LABELING EACH AS SUCH.
22. PROVIDE PERMANENT SANITARY SEWER EASEMENTS (EACH
SPECIFICALLY LABELED AS SUCH) SUFFICIENT TO ENCUMBER ALL
SANITARY SEWER LOCATED BEYOND THE LIMITS OF THE RIGHT-
OF-WAY PROPOSED TO BE DEDICATED IN CONJUNCTION WITH THIS
PROJECT.
23. ALL WATERLINE PROPOSED TO BE LOCATED IN FILL
SECTIONS SHALL BE DUCTILE IRON, CLASS 52 MINIMUM WITH
RESTRAINED JOINTS FOR THE ENTIRE DISTANCE SO LOCATED.
REVISE AS NECESSARY TO SATISFY THIS SPECIFICATION,
CLEARLY NOTING AS SUCH AT EACH APPLICABLE LOCATION IN
THE PROFILE VIEWS.
24. ALL SANITARY SEWER WITH GREATER THAN OR EQUAL TO 20
VF OF COVER ARE TO BE SPECIFIED AS DUCTILE IRON AND THE
ADDITIONAL STONE REQUIREMENT IS NO LONGER REQUIRED.
25. PLEASE BE ADVISED THAT THE PLANS FOR THIS PROJECT
WILL NOT BE RELEASED TO THE CONSTRUCTION SECTION UNTIL
SUCH TIME "HARPER'S MILL SOUTH PHASE C, SECTION 1"
(COUNTY PROJECT NUMBER 15-0207) IS UNDER CONTRACT. IN
ADDITION TAKE ALL STEPS NECESSARY TO PROVIDE COMPLETE
AGREEMENT BETWEEN THESE SETS OF PLANS.
26. ARE ANY IRRIGATION METERS PROPOSED WITH THIS
PROJECT? PLEASE ADDRESS THOROUGHLY, REVISING THE PLANS
AS NECESSARY, AND PROVIDE A SIGNED COMPLETED WATER METER
SIZING FORM FOR EACH PROPOSED IRRIGATION METER.
27. PLEASE BE ADVISED THAT PER A CONDITION OF ZONING,
WHICH REQUIRES THAT THE DEVELOPER CONTRIBUTE TOWARDS THE
COST OF EXPANDING THE DRY CREEK WASTEWATER PUMP STATION,
PAYMENT TO THE COUNTY IN THE AMOUNT OF $ 4,214.00 MUST
BE MADE PRIOR TO ISSUANCE OF THE FIRST BUILDING PERMIT
FOR THIS SITE. PAYMENTS ARE TO BE SENT TO THE ATTENTION
OF MICHAEL A. LARSON, P. E., PRINCIPAL ENGINEER,
DEVELOPMENT SECTION, CHESTERFIELD COUNTY UTILITIES
DEPARTMENT. CHECKS ARE TO BE MADE PAYABLE TO
"TREASURER, CHESTERFIELD COUNTY".
28. PROVIDE A "BLOW-UP" DETAIL DEPICTING THE SPATIAL
RELATIONSHIP OF THE FIRE HYDRANT, VALVE, SIDEWALK AND
CURB AND GUTTER WITH ALL APPLICABLE SEPARATION
DISTANCES NOTED.
29. PROVIDE PERMANENT EASEMENTS (EACH SPECIFICALLY
LABELED AS TO ITS INTENDED USE) FOR ALL SANITARY
SEWER/WATER FACILITIES LOCATED BEYOND THE LIMITS OF THE
RIGHT-OF-WAY PROPOSED TO BE DEDICATED IN CONJUNCTION
WITH THIS PROJECT.
30. THOROUGHLY EXAMINE ALL SHEETS TO CORRECT ALL
EXTRANEOUS MARKINGS, OVERLAPPING TEXT, ILLEGIBLE TEXT
AND DRAWING FEATURES, ETC. IN ORDER TO FACILITATE A
CLEAN DRAWING WITH ALL TEXT AND DRAWING FEATURES
COMPLETELY LEGIBLE AND ABUNDANTLY VISIBLE.
31. REVISE THE "MATERIALS LIST" AS NECESSARY.
PLEASE MAKE ALL OF THE SUGGESTED CHANGES AND SUBMIT
ONE(1) SET OF REVISED PLANS.
THE OWNER MUST ENTER INTO A COUNTY CONTRACT PRIOR TO THE
START OF CONSTRUCTION. PLEASE SEND ME A COPY OF THE
"ACCEPTED" BID PROPOSAL BETWEEN THE DEVELOPER AND THE
CONTRACTOR SO WE MAY PREPARE THE COUNTY CONTRACT. THE
BID PROPOSAL MUST BE BASED ON THE LATEST REVISED
UTILITIES PLANS REFLECTING THE REVIEWER'S STAMP, AND ALL
WORK MUST BE PERFORMED BY AN ACCEPTABLE UTILITIES
CONTRACTOR. IF PLANS ARE REVISED AFTER CONTRACT
PREPARATION DUE TO A CHANGE BECAUSE OF VIRGINIA
DEPARTMENT OF TRANSPORTATION'S AND/OR ENVIRONMENTAL
ENGINEERING DEPARTMENT'S APPROVAL OF THE ROAD, DRAINAGE,
AND EROSION CONTROL DESIGN OR BECAUSE OF STATE AGENCIES'
REVIEW AND APPROVAL OF THE UTILITIES DESIGN, A REVISED
BID PROPOSAL MAY BE NECESSARY TO ACCURATELY REFLECT THE
LATEST UTILITIES DESIGN AND A NEW CONTRACT PREPARATION
MAY BE NECESSARY AND EXECUTED PRIOR TO THE START OF
CONSTRUCTION.
IF YOU HAVE ANY QUESTIONS, DO NOT HESITATE TO CONTACT ME
AT 748-1343.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: HARPER'S MILL SOUTH, SECTION 2
PLAN NUMBER: 16CP0061
ORIGINAL PLAN DATE: 2/9/16
REVIEW DATE: 6/15/16
LATEST SUBMISSION DATE: 6/2/16
SUBMITTAL NUMBER: 2
STATUS: REVISIONS REQUIRED
TABLE REVIEW: NO
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR THE
ABOVE REFERENCED PROJECT DATED FEBRUARY 9, 2016, WITH
THE LATEST REVISION DATED MAY 26, 2016, WE MAKE THE
FOLLOWING COMMENTS AND RECOMMENDATIONS:
1. A COPY OF VIRGINIA DEPARTMENT OF TRANSPORTATION'S
APPROVAL LETTER REGARDING PAVEMENT REPLACEMENT, METHOD
OF CROSSING, AND ALIGNMENT OF UTILITY WITH STATE RIGHT
OF WAY, AND A COPY OF ENVIRONMENTAL ENGINEERING'S
INITIAL REVIEW LETTER MUST BE SUBMITTED BEFORE REVISED
PLANS ARE SUBMITTED FOR RE-REVIEW.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION, A
COPY OF THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER
AND/OR ALL OTHER APPLICABLE LOCAL STATE AND FEDERAL
AGENCIES' APPROVAL LETTERS MUST BE RECEIVED BY THIS
DEPARTMENT. IN ADDITION, ALL EASEMENTS NOT INCLUDED
WITH THE SUBDIVISION PLAT MUST BE DEDICATED WITH A
SEPARATE PLAT AND AGREEMENT TO THE COUNTY PRIOR TO
RELEASING THE PROJECT TO THE CONSTRUCTION SECTION.
3. PROVIDE, AS A PART OF THIS PLAN SET, A SANITARY
SEWER HYDRAULIC ANALYSIS, INCLUDING A DRAINAGE AREA MAP
AND CALCULATION TABLE (SEE CURRENT COUNTY
SPECIFICATIONS, DETAIL DRAWING NUMBER DES-1).
4. CONSPICUOUSLY DISPLAY THE FOLLOWING NOTE IN THE
PLAN VIEWS: "FOR EACH LOT 'FRONTING' ON A SIDEWALK, THE
'FRONT' SIDE OF THE METER BOX IS TO BE LOCATED 3 LF FROM
THE 'HOUSE' SIDE OF THE SIDEWALK".
5. LABEL OTTERDALE ROAD, GRAHAM'S FERRY LANE, AS WELL
AS WIDTHBY COURT AND ROAD ON SHEET 3.0.
6. CLEARLY SHOW THE EXISTING WATERLINE IN OTTERDALE
ROAD WITH ITS COUNTY PROJECT NUMBER (I.E. 09-0094)
USING A DARK, DASHED LINE TYPE. CLEARLY SHOW ALL
EXISTING FITTINGS, VALVES, ETC. IN THE INTERSECTION OF
OTTERDALE ROAD AND KENBROOK DRIVE LABELING ALL VALVES TO
BE USED FOR CUT OFF PURPOSES DURING THE WATERLINE TIE IN
AS SUCH.
7. CLEARLY DELINEATE THE EXACT LIMITS OF WATER AND
SANITARY SEWER THAT IS PROPOSED TO BE INSTALLED WITH
THIS PROJECT. (IF ANY POSSIBLE FUTURE LINES ARE SHOWN
CLEARLY DELINEATE THEIR LIMITS, SHOW USING A "DARK,
DASHED" LINE TYPE AND LABEL AS SUCH.
8. CALL OUT EACH VALVE (INCLUDING THE SIZES)
THROUGHOUT THE PLAN VIEWS.
9. CLEARLY SHOW EACH MANHOLE NUMBER THROUGHOUT THE
PLAN AND PROFILE VIEWS.
10. THE SEWER FOR THIS PROJECT IS SHOWN AS TYING INTO A
MANHOLE NUMBER 1 WHICH IS CURRENTLY PROPOSED WITH COUNTY
PROJECT NUMBER 15-0207. REVISE AS NECESSARY TO INDICATE
AS SUCH AT ALL APPLICABLE LOCATIONS. SHOW THE REVISED
NOTE AND COUNTY PROJECT NUMBER IN THE PROFILE VIEW, SHOW
THIS MANHOLE USING A "DARK, DASHED" LINE TYPE AND TAKE
ALL STEPS NECESSARY TO PROVIDE COMPLETE AGREEMENT
BETWEEN THIS SET OF PLANS AND THE PLANS FOR COUNTY
PROJECT NUMBER 15-0207.
11. LABEL OTTERDALE ROAD ON SHEET C5.4.
12. PROVIDE A 2" FLUSHING HYDRANT AT THE WATERLINE
TERMINUS POINT AT STATION 16+55±, BLOOMING ROAD.
13. PROVIDE DIRECTION OF FLOW ARROWS FOR EACH RUN OF
SANITARY SEWER THROUGHOUT THE PLAN VIEWS.
14. EXTEND THE SEWER CONNECTION FOR LOT NUMBER 31
BEYOND THE STORM SEWER.
15. THERE APPEARS TO BE VERTICAL CONFLICTS BETWEEN EACH
OF THE SEWER SERVICES FOR LOT NUMBERS 30 AND 31 WHERE
EACH IS CROSSING THE STORM SEWER. REVISE AS NECESSARY
TO PROVIDE 1.5 VF CLEARANCE AT ALL LOCATIONS.
16. EACH WATER SERVICE GREATER THAN OR EQUAL TO 60 LF
IS TO BE SPECIFIED AS 1" DIAMETER. NOTE THIS CONDITION
ON EACH APPLICABLE LOT IN THE PLAN VIEWS.
17. SPECIFY 1 VF OF EXTRA STONE ABOVE THE PIPE AT EACH
LOCATION IN THE PROFILE VIEWS WITH GREATER THAN OR EQUAL
TO 14 VF OF COVER OVER A PVC SEWER LINE.
18. PROVIDE A VERTICAL BENCHMARK ON EACH PLAN VIEW
SHEET.
19. ARE ANY IRRIGATION METERS PROPOSED WITH THIS
PROJECT? PLEASE ADDRESS THOROUGHLY, REVISING THE PLANS
AS NECESSARY, AND PROVIDE A SIGNED, COMPLETED WATER
METER SIZING FORM FOR EACH PROPOSED IRRIGATION METER.
20. PLEASE BE ADVISED THAT THE PLANS FOR THIS PROJECT
WILL NOT BE RELEASED TO THE CONSTRUCTION SECTION UNTIL
SUCH TIME "HARPER'S MILL SOUTH PHASE C, SECTION 1"
(COUNTY PROJECT NUMBER 15-0207) IS UNDER CONTRACT. IN
ADDITION, TAKE ALL STEPS NECESSARY TO PROVIDE COMPLETE
AGREEMENT BETWEEN THESE SETS OF PLANS.
21. SPECIFY MANHOLE INSERTS TO BE INSTALLED IN EACH
MANHOLE AND REVISE THE SEWER PORTION OF THE MATERIALS
LIST TO REFLECT AS SUCH.
22. THOROUGHLY EXAMINE ALL SHEETS TO CORRECT ALL
EXTRANEOUS MARKINGS, OVERLAPPING TEXT, ILLEGIBLE TEXT
AND DRAWING FEATURES, ETC. IN ORDER TO FACILITATE A
CLEAN DRAWING WITH ALL TEXT AND DRAWING FEATURES
COMPLETELY LEGIBLE AND ABUNDANTLY VISIBLE.
23. REVISE THE "MATERIALS LIST" AS NECESSARY.
PLEASE MAKE ALL OF THE SUGGESTED CHANGES AND SUBMIT
ONE(1) SET OF REVISED PLANS.
THE OWNER MUST ENTER INTO A COUNTY CONTRACT PRIOR TO THE
START OF CONSTRUCTION. PLEASE SEND ME A COPY OF THE
"ACCEPTED" BID PROPOSAL BETWEEN THE DEVELOPER AND THE
CONTRACTOR SO WE MAY PREPARE THE COUNTY CONTRACT. THE
BID PROPOSAL MUST BE BASED ON THE LATEST REVISED
UTILITIES PLANS REFLECTING THE REVIEWER'S STAMP, AND ALL
WORK MUST BE PERFORMED BY AN ACCEPTABLE UTILITIES
CONTRACTOR. IF PLANS ARE REVISED AFTER CONTRACT
PREPARATION DUE TO A CHANGE BECAUSE OF VIRGINIA
DEPARTMENT OF TRANSPORTATION'S AND/OR ENVIRONMENTAL
ENGINEERING DEPARTMENT'S APPROVAL OF THE ROAD, DRAINAGE,
AND EROSION CONTROL DESIGN OR BECAUSE OF STATE AGENCIES'
REVIEW AND APPROVAL OF THE UTILITIES DESIGN, A REVISED
BID PROPOSAL MAY BE NECESSARY TO ACCURATELY REFLECT THE
LATEST UTILITIES DESIGN AND A NEW CONTRACT PREPARATION
MAY BE NECESSARY AND EXECUTED PRIOR TO THE START OF
CONSTRUCTION.
IF YOU HAVE ANY QUESTIONS, DO NOT HESITATE TO CONTACT ME
AT 748-1343.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: MIKE LARSON/748-1338
PLAN NAME: HARPER'S MILL SOUTH, SECTION 2
PLAN NUMBER: 16CP0061
ORIGINAL PLAN DATE: 2/9/16
REVIEW DATE: 8/269/16
LATEST SUBMISSION DATE: 8/18/16
SUBMITTAL NUMBER: 3
STATUS: REVISIONS REQUIRED
TABLE REVIEW: NO
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR THE
ABOVE REFERENCED PROJECT DATED FEBRUARY 9, 2016, WITH
THE LATEST REVISION DATED AUGUST 16, 2016, WE MAKE THE
FOLLOWING COMMENTS AND RECOMMENDATIONS:
1. ON THE EROSION AND SEDIMENT CONTROL PLANS, THE NEW
SANITARY SEWER OFF BLOOMING COURT IS SHOWN TO GO RUN
UNDER A SEDIMENT TRAP. AFTER DISCUSSING WITH
ENVIRONMENTAL ENGINEERING, THE BEST SOLUTION MAY BE TO
RELOCATE THE SEDIMENT TRAP TO AVOID THE CONFLICT.
2. LOT 18 DOES NOT SHOW A SEWER LATERAL OR WATER
SERVICE.
3. LOT 32 SHOWS 2 WATER SERVICES.
4. LOT 34 DOES NOT SHOW A WATER SERVICES.
5. THE SEWER LATERAL FOR LOT 31 SHOULD BE PERPENDICULAR
TO THE SEWER MAIN.
6. THE WATER SERVICE FOR LOT 31 IS SHOWN GOING THROUGH
MH 25, PLEASE RELOCATE.
7. MOVE THE SEWER LATERALS FOR LOTS 13 AND 48 OUT FROM
UNDER THE DRIVEWAY.
8. RELOCATE THE FIRE HYDRANTS FOR LOTS 2 AND 43 SO THAT
THEY ARE NOT IN THE MIDDLE OF THE FRONT YARD. THEY
SHOULD BE CLOSE TO A PROPERTY LINE.
9. MH 28 AND THE WATER FLUSHING HYDRANT ARE SHOWN
OUTSIDE THE LIMITS OF THE SUBDIVISION. A SEPARATE
OFFSITE EASEMENT PLAT IS REQUIRED.
10. THE PLUG NEAR STATION 0+50 OF BLOOMING RD REQUIRES
A 2" FLUSHING HYDRANT. PLEASE LOCATE THE HYDRANT AND
PLUG INSIDE THE LIMITS OF THE SUBDIVISION TO AVOID AN
OFFSITE EASEMENT.
11. PROVIDE A MAIN LINE GATE VALVE AT THE HYDRANT NEAR
LOT 17 TO FACILITATE A FUTURE EXTENSION OF THE WATER
SYSTEM DOWN BLOOMING RD.
12. IDENTIFY THE PURPOSE OF THE WATER SERVICE SHOWN ON
NEAR THE BMP AT APPROXIMATELY STA 10+50 OF BLOOMING RD.
WE ASSUME THIS IS FOR IRRIGATION. IF SO, SUBMIT A METER
SIZING FORM, LABEL THE SIZE OF THE METER AND CALL OUT A
PRIVATE BACKFLOW PREVENTER.
13. WILL THE LOTS LABELED "FOCAL POINT" REQUIRE
IRRIGATION? IF SO, PLEASE PROVIDE A METER SIZING FORM
AND SHOW A METER ON THE PLANS.
14. INSTEAD OF AN 8 X 8 TEE AND REDUCER ON BLOOMING CT,
WHY NOT USE AN 8 X 6 TEE AND A 6" GATE VALVE TO REDUCE
COST?
15. AS SHOWN ON DETAIL WAT-11, THE MINIMUM BENDING
RADIUS FOR 8" PVC IS 326 FT. THE RADII OF SEVERAL OF
THE CURVES ON BLOOMING ROAD IS SHOWN WELL BELOW THAT
MINIMUM AND THE WATER LINE IS FOLLOWING THE CURVE WITH
NO BENDS. PROVIDE ADDITIONAL BENDS AS NECESSARY.
16. PER COUNTY STANDARDS, SHOW THE STORM PIPES ON
SHEET 3.0 SO THAT POTENTIAL CONFLICTS CAN BE IDENTIFIED.
17. THE PROFILE INDICATES A 10" SEWER FROM MH 5 TO EXMH
6; HOWEVER, THIS SECTION IS NOT REFLECTED ON THE
HYDRAULIC ANALYSIS.
18. WITH THE EXCEPTION OF LOCATIONS WHERE THE WATER LINE
MUST BE LOWERED TO GO UNDER STORM PIPES, THE WATER LINE
SHOULD BE SHOWN AS 3.5 FT DEEP. SINCE PVC CANNOT BE
DEFLECTED AT THE JOINT, LOWERING MUST BE ACCOMPLISHED
THROUGH RESTRAINED VERTICAL BENDS PER DETAIL WAT-8.
JOINT RESTRAINT CALCULATIONS NEED TO BE PROVIDED.
19. THE FIRE HYDRANT AT APPROXIMATELY STA 10+25 ON
BLOOMING RD IS SHOWN AT NEARLY 10 FT DEEP, WHICH IS NOT
ACCEPTABLE. VALVES CAN BE NO DEEPER THAN 6 FT; RELOCATE
THE HYDRANT AS NECESSARY.
20. THE SEWER AT MH 18 SEEM UNNECESSARILY DEEP, PLEASE
REVISIT THE PROFILE AT BLOOMING CT AND BLOOMING RD TO
MINIMIZE THE DEPTH.
21. REVISE THE WATER LINE ON KENBROOK DR TO GO OVER THE
TOP OF STORM SEWER 2-2. WE CAN ALLOW LESS THAN 1.5 FT
CLEARANCE WHEN THE WATER PIPE IS GOING OVER THE TOP OF A
STORM AND DI PIPE IS USED.
22. PER COUNTY STANDARDS, MANHOLE TOPS IN EASEMENTS
THAT ARE NOT IN MAINTAINED AREAS SHOULD BE 6 INCHES
ABOVE GRADE. THIS CONDITION APPEARS TO APPLY TO
MANHOLES 7, 9, 10, 16, 4, 3, AND 2.
23. ON SHEET C5.3, LABEL THE SEWER BETWEEN MH EX8 AND
EX9 AS EXISTING CONSTRUCTED IN PROJECT 06-0465.
24. THE SEWER INTO MH3, MH 5, AND MH 6 NEEDS TO MATCH
CROWS WITH THE SEWER OUT.
25. ON SANITARY TRUNK 3 PROFILE, SHOW THE 30" D.I.
WATER LINE AND LABEL AND LABEL AS COUNTY PROJECT 09-
0094. .
26. LABEL THE CONNECTION INTO EX MH6 AND EX MH 1B AS
BEING CORE DRILLED WITH A KOR-N-SEAL GASKET INSTALLED.
27. ON SHEET C5.4, THE INVERT IN TO MH 3 SHOULD BE FROM
28. THE SEWER ENCASED IN CONCRETE NEEDS TO BE DUCTILE
IRON.
29. THE CONNECTION FROM MH 19 TO MH 18 SHOULD BE AN
INTERNAL DROP MANHOLE.
30. THE DEPTH OF THE WATER ON BLOOMING PLACE SHOULD BE
3.5 FT COVER, PLUS THE PLUG AND FLUSHING HYDRANT SHOULD
BE SHOWN ON THE PROFILE. THE DEPTH OF THE SEWER SHOULD
BE ABOUT 6 FT COVER WITH AN INTERNAL DROP CONNECTION
INTO MH 27.
31. SHOW THE PLUG AND FLUSHING HYDRANT ON THE PROFILE
FOR BLOOMING COURT.
32. THE WATER LINE ON BLOOMING COURT SHOULD BE 3.5 FT
DEEP AND CALLED OUT AS CLASS 52 DI WITH RESTRAINED
JOINTS WHERE APPLICABLE.
33. SHOW THE 30 DI WATERLINE ON ALL PROFILES ALONG WITH
THE BOTTOM ELEVATIONS ON THE CUT-SHEETS PROVIDED BY THE
UTILITIES DEPARTMENT. EACH WATER LINE SHOULD BE LABELED
AS 30" D.I. COUNTY PROJECT 09-0094.
34. CHANGE THE DETAIL ON SHEET C7.3 TO MAN-16, INTERIOR
DROP CONNECTION.
35. JORDAN CONSULTING ENGINEERING WILL BE MAKING SOME
ADJUSTMENTS TO THE EXISTING SEWER LINES CROSSING
OTTERDALE RD, WHICH MAY INCLUDE INVERT CHANGES, MANHOLE
LOCATION CHANGES, AND LEAVING PLUGGED OPENINGS. PLEASE
COORDINATE WITH THEM TO SHOW THE FINAL INFORMATION ON
THESE PLANS.
36. TO FACILITATE INCORPORATING THESE COMMENTS INTO THE
REVIEW, THE UTILTIES DEPARTMENT IS PROVIDING A MARKED
SET OF PLANS ALONG WITH AS-BUILT INFORMATION AND CUT-
SHEETS FOR THE 30-INCH WATERLINE AT OUR MEETING
SCHEDULED FOR AUGUST 29, 2016.
37. THE MATERIALS LIST NEEDS TO BE UPDATED TO SHOW THE
ADDITIONAL FLUSHING HYDRANT AND GATE VALVE, CHANGE IN
TEE SIZE, REMOVE A REDUCER, CHANGE A VALVE FROM 8" TO
6", AND ADD BENDS FOR THE CURVES AND VERTICAL
TRANSITIONS. ALSO, THE MATERIALS LIST DOES NOT INCLUDE
THE 144 FT OF 10" SEWER.
IF YOU HAVE ANY QUESTIONS, DO NOT HESITATE TO CONTACT ME
AT 748-1338 OR EMAIL PDFS FOR INTERIM REVIEW TO
LARSONM@CHESTERFIELD.GOV.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: MIKE LARSON/748-1338
PLAN NAME: HARPER'S MILL SOUTH, SECTION 2
PLAN NUMBER: 16CP0061
ORIGINAL PLAN DATE: 2/9/16
REVIEW DATE: 12/6/16
LATEST SUBMISSION DATE: 11/17/16
SUBMITTAL NUMBER: 4
TABLE REVIEW: YES
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR THE
ABOVE REFERENCED PROJECT DATED FEBRUARY 9, 2016, WITH
THE LATEST REVISION DATED NOVEMBER 10, 2016, WE MAKE THE
FOLLOWING COMMENTS AND RECOMMENDATIONS:
1. THE WATER SERVICE FOR LOT 34 IS STILL MISSING. WE SUGGES
ING IT NEAR THE LOT 33 PROPERTY LINE.
2. THE PLUG AND FLUSHING HYDRANT NEAR STA 0+50 OF BLOOMING
RD IS SHOWN OUTSIDE THE SUBDIVISION LIMITS.
EITHER REVISE THE LOCATION OR PROVIDE A 16 FT WIDE WATER
3. IF POSSIBLE, FIND OUT FROM THE DEVELOPER IF THEY PLAN TO
PROVIDE IRRIGATION TO THE FOCAL POINT. IT IS MUCH SIMPLER
TO PROVIDE A TAP AND 10 X 10 EASEMENT DURING THE PLAN APPROV
AL STAGE THAN TO TRY AND ADD IT
LATER. WE HAVE HAD SEVERAL INSTANCES OVER THE LAST YEAR WHE
HAVE HAD TO CUT PAVEMENT TO ADD AN IRRIGATION
4. PLEASE REVISIT THE LOCATION AND DEGREE OF THE BENDS ON T
HE WATER LINE NEAR MH 22. IF 11-1/4 BENDS ARE USED, IT MAY
BE POSSIBLE TO MAINTAIN 10 FT OF HORIZONTAL
SEPARATION FROM THE MANHOLE.
5. THE VERTICAL BENDS ARE NOT SHOWN CORRECTLY ON
PROFILE. WITH A SKEWED PROFILE, THE OUTSIDE OF EACH BEND WO
LY BE LOCATED ABOUT 10 FT FROM THE STORM PIPE. EACH B
6. THE TYPICAL WAY TO SHOW THE EXTEND OF JOINT RESTRAINT OF
TICAL DEFLECTION IS TO CALL OUT THE DISTANCE HORIZONTA
LLY FROM THE TOP OF EACH VERTICAL BEND (E.G. 20 FT) AND THEN
SHOW ARROWS TO "RESTRAIN ALL JOINTS IN THIS AREA". CURRENT
LY, THE DISTANCE OF RESTRAINT IS NOT SHOWN PAST EACH OF THE
TOP BENDS.
7. TEES FOR FIRE HYDRANTS CANNOT BE SHOWN ON THE VERTICAL D
EFLECTION AS SHOWN AT APPROXIMATELY STA 10+75 ON BLOOMING RD
. ONCE THE VERTICAL BENDS ARE SHOWN
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: MIKE LARSON/748-1338
PLAN NAME: HARPER'S MILL SOUTH, SECTION 2
PLAN NUMBER: 16CP0061
ORIGINAL PLAN DATE: 2/9/16
REVIEW DATE: 3/2/17
LATEST SUBMISSION DATE: 3/2/17
SUBMITTAL NUMBER: 5
STATUS: APPROVED
TABLE REVIEW: YES
.
.
YOUR SUBMITTAL OF HARPER'S MILL SOUTH SECTION 2 DATED FEBRUA
RY 9, 2016 WITH A MOST RECENT REVISION DATE OF JANUARY 19, 2
017 IS APPROVED. THIS REVIEW IS EFFECTIVE UNTIL MARCH 2, 20
22.
.
YOU ARE REMINDED THIS PROJECT HAS UTILITY EASEMENTS OUTSIDE
SUBDIVISION WHICH MUST BE SUBMITTED AND SIGNED
PRIOR TO BEING RELEASED TO CONSTRUCTION.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: HARPER'S MILL SOUTH PHASE, SECTION 2
CASE NUMBER: 16CP0061
LATEST PLAN DATE: 02/08/2016
DEPT. REC'D. DATE: 02/26/2016
SUBMITTAL NUMBER: ONE
REVIEW DATE: 03/21/2016
RECOMMENDATION: NOT APPROVED
TABLE REVIEW: YES
PLEASE SHOW THE ADTS FROM THE APPROVED TENTATIVE ON SHEET
C1.0, "OVERALL PLAN".
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: HARPER'S MILL SOUTH PHASE, SECTION 2
CASE NUMBER: 16CP0061
LATEST PLAN DATE: 05/26/2016
DEPT. REC'D. DATE: 06/06/2016
SUBMITTAL NUMBER: TWO
REVIEW DATE: 06/20/2016
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: HARPER'S MILL SOUTH PHASE, SECTION 2
CASE NUMBER: 16CP0061
LATEST PLAN DATE: 08/16/2016
DEPT. REC'D. DATE: 08/23/2016
SUBMITTAL NUMBER: THREE
REVIEW DATE: 08/29/2016
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: HARPER'S MILL SOUTH PHASE, SECTION 2
CASE NUMBER: 16CP0061
LATEST PLAN DATE: 11/10/2016
DEPT. REC'D. DATE: 11/22/2016
SUBMITTAL NUMBER: FOUR
REVIEW DATE: 12/08/2016
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: HARPER'S MILL SOUTH PHASE, SECTION 2
CASE NUMBER: 16CP0061
LATEST PLAN DATE: 01/19/2017
DEPT. REC'D. DATE: 03/02/2017
SUBMITTAL NUMBER: FIVE
REVIEW DATE: 03/02/2017
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
.
REVIEW DEPARTMENT: PLANNING
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : AMY SOMERVELL / 751-4321
PLAN NAME : HARPERS MILL SOUTH SECTION 2
PLAN NUMBER : 16CP0061
ORIGINAL PLAN DATE : 2/9/16
REVIEW DATE : 3/21/16
LATEST SUBMISSION DATE : 2/10/16
SUBMITTAL NUMBER : 1
STATUS : CORRECTIONS REQUIRED
TABLE REVIEW : N
1.PLACE THE CONSTRUCTION PLAN NUMBER ON THE BOTTOM
RIGHT HAND CORNER OF ALL SHEETS. 16CP0061
2. THE PLAN SHALL REFLECT THE TREE CANOPY AREA AS
APPROVED ON THE OVERALL TREE CANOPY PLAN. BE SURE TO
INCLUDE THE TOTAL SITE AREA, AREA REMOVED FROM
CALCULATION, CANOPY REQUIRED AND PROVIDED.
4. ON THE TREE CANOPY PLAN, INCLUDE THE FOLLOWING
NOTE: (LIMITS OF THE TREE CANOPY PRESEVATION AREAS
SHALL BE SHOWN AND LABELLED ON THE SUBDIVISION
PLATS WHERE APPLICABLE. A NOTE SHOULD BE INCLUDED
STATING"TREE CANOPY PRESERVATION AREAS TO REMAIN
UNDISTURBED. NO TREES WITHIN THE TREE CANOPY
PRESERVATION AREAS SHALL BE REMOVED WITHOUT
COUNTY APPROVAL" . SUCH LANGUAGE SHALL ALSO
BE INCLUDED WITHIN THE COVENANTS, RESTRICTIONS,
AND BYLAWS FOR THE SUBDIVISION.)
3. THE FOCAL POINT ADJACENT TO AVINGTON DRIVE AS
DEPICTED ON THE APPROVED PRELIMINARY PLAT IS MISSING.
4. KEEP THE SAME LINE TYPE FOR THE LOT LINES. IT CHANGES
FROM BROKEN TO SOLID.
5. A 100 FOOT BUFFER IS REQUIRED ALONG OTTERDALE ROAD
WITHIN THE OPEN SPACE.
6. PROVIDE BUILDING LINES FOR ALL CUL-DE-SAC LOTS THAT
DO NOT MEET THE REQUIRED LOT WIDTH AS THE MINIMUM
FROM SETBACK. THE BUILDING LINE SHALL BE LOCATED
WHERE THE LOT ACHIEVES THE REQUIRED 50 FOOT LOT
WIDTH.
7. PROVIDE VDOT TYPE 3 BARRICADES AT THE END OF
CONSTRUCTION ON EMBERTON ROAD. CALL THESE OUT
ON THE PLAN SHEET.
8. PROVIDE AN AUTOCAD FILE DEPICTING THE BOUNDARIES
OF THIS CONSTRUCTION PLAN.
LANDSCAPE AND LIGHTING:
9. THE TEXTUAL STATEMENT REQUIRES PERIMETER
LANDSCAPING AROUND ALL DWELLING UNITS. PROVIDE
A LANDSCAPE PLAN THAT DEPICTS TYPICAL UNIT
LANDSCAPING.
8. THE TEXTUAL STATEMENT REQUIRES STREET LIGHTS BE PROVIDED
ALONG EACH SIDE OF THE ROAD. THE LIGHTS SHOULD BE, AT A
MINIMUM, SPACED AT 150' ON EACH SIDE OF THE STREET EACH SIDE
STAGGERED TO ROUGHLY EQUAL 75' ON CENTER. PROVIDE THE
HEIGHT AND STYLE OF THE PROPOSED STREET LIGHT. (PROVIDE
CUT SHEETS).
9.PROVIDE A STREET TREE PLAN. STREET TREES SHALL BE PLANTED
40' ON CENTER
10. PROVIDE A DETAILED PLAN PLAN FOR THE FOCAL POINTS PRIOR
TO CONSTRUCTION PLAN APPROVAL.
11. PER 19.1-211 ANY STORMWATER MANAGEMENT FACILITY
OR BMP BASIN VISIBLE TO THE PUBLIC SHALL BE LANDSCAPED
OR OTHERWISE IMPROVED SO THAT THE FACILITIES ARE
VISUALLY ENHANCED. INCLUDE A PLAN DEPICTING VISUAL
ENHANCEMENTS IN THE LANDSCAPE PLAN.
----------------------------------------------------------
REVIEW DEPARTMENT: PLANNING
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : WHIT KIRTLEY/ 706-7691
PLAN NAME : HARPERS MILL SOUTH SECTION 2
PLAN NUMBER : 16CP0061
ORIGINAL PLAN DATE : 2/9/16
REVIEW DATE : 7/6/16
LATEST SUBMISSION DATE 6/2/16
SUBMITTAL NUMBER : 2
STATUS : CORRECTIONS REQUIRED
TABLE REVIEW : N
1. THE PLAN SHALL REFLECT THE TREE CANOPY AREA AS
APPROVED ON THE OVERALL TREE CANOPY PLAN. BE SURE TO
INCLUDE THE TOTAL SITE AREA, AREA REMOVED FROM
CALCULATION, CANOPY REQUIRED AND PROVIDED.
2. ON THE TREE CANOPY PLAN, INCLUDE THE FOLLOWING
NOTE: (LIMITS OF THE TREE CANOPY PRESEVATION AREAS
SHALL BE SHOWN AND LABELLED ON THE SUBDIVISION
PLATS WHERE APPLICABLE. A NOTE SHOULD BE INCLUDED
STATING"TREE CANOPY PRESERVATION AREAS TO REMAIN
UNDISTURBED. NO TREES WITHIN THE TREE CANOPY
PRESERVATION AREAS SHALL BE REMOVED WITHOUT
COUNTY APPROVAL" . SUCH LANGUAGE SHALL ALSO
BE INCLUDED WITHIN THE COVENANTS, RESTRICTIONS,
AND BYLAWS FOR THE SUBDIVISION.)
3. BE SURE TO UPDATE THE E&S PLANS TO MARK THE
CANOPY AREAS WITH TREE PROTECTION TAPE.
4. THE FOCAL POINT ADJACENT TO AVINGTON DRIVE AS
DEPICTED ON THE APPROVED PRELIMINARY PLAT IS MISSING.
5. LABEL THE 100 FOOT BUFFER ON THE LAYOUT AND UTILITY
PLAN.
6. ON PAGE C1.0 LABEL THE 100 BUFFER AS A BUFFER, NOT
AS A 100 FOOT SETBACK.
7. BUFFERS SHALL BE EXCLUSIVE OF EASEMENTS WHICH ARE
GENERALLY PARALLEL TO THE BUFFER. THE BUFFER NEEDS
TO BE ADJUSTED TO ACCOUNT FOR THE SANITERY SEWER
EASEMENT.
8. RELOCATION OF THE BUFFER MAY REQUIRE THE BMP TO
ENCROACH INTO THE BUFFER AREA. ENCROACHMENT
IS PERMITTED IN ACCORDANCE WITH 19.1-262 (D)(2) AND
19.1-211. THIS WILL REQUIRE AMENDMENT TO THE
PRELIMINARY PLAT.
9. PROVIDE TREE PROTECTION TAPE FOR THE BUFFER ALONG
OTTERDALE ROAD.
10. YOU MAY REMOVE ANY BUILDING LINE THAT WERE
NOT REQUESTED BY THE COUNTY. IF YOU LEAVE THEM,
THE FRONT SETBACKS ARE SHOWN GREATER THEN 10
FEET
11. PROVIDE AN AUTOCAD FILE DEPICTING THE BOUNDARIES
OF THIS CONSTRUCTION PLAN.
LANDSCAPE AND LIGHTING:
12. THE TEXTUAL STATEMENT REQUIRES PERIMETER
LANDSCAPING AROUND ALL DWELLING UNITS. PROVIDE
A LANDSCAPE PLAN THAT DEPICTS TYPICAL UNIT
LANDSCAPING.
13. THE TEXTUAL STATEMENT REQUIRES STREET LIGHTS BE PROVIDED
ALONG EACH SIDE OF THE ROAD. THE LIGHTS SHOULD BE, AT A
MINIMUM, SPACED AT 150' ON EACH SIDE OF THE STREET EACH SIDE
STAGGERED TO ROUGHLY EQUAL 75' ON CENTER. PROVIDE THE
HEIGHT AND STYLE OF THE PROPOSED STREET LIGHT. (PROVIDE
CUT SHEETS).
14. PROVIDE A STREET TREE PLAN. STREET TREES SHALL BE PLANTE
40' ON CENTER
15. PROVIDE A DETAILED PLAN PLAN FOR THE FOCAL POINTS PRIOR
TO CONSTRUCTION PLAN APPROVAL.
16. PER 19.1-211 ANY STORMWATER MANAGEMENT FACILITY
OR BMP BASIN VISIBLE TO THE PUBLIC SHALL BE LANDSCAPED
OR OTHERWISE IMPROVED SO THAT THE FACILITIES ARE
VISUALLY ENHANCED. INCLUDE A PLAN DEPICTING VISUAL
ENHANCEMENTS IN THE LANDSCAPE PLAN
CONDITION
A LANDSCAPE PLAN SHALL BE PROVIDED FOR THE VISUAL
ENHANCEMENT OF THE BMP PER 19-1.211 PRIOR TO FINAL
PLAN APPROVAL.
-----------------------------------------------------------
REVIEW DEPARTMENT: PLANNING
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : WHIT KIRTLEY/ 706-7691
PLAN NAME : HARPERS MILL SOUTH SECTION 2
PLAN NUMBER : 16CP0061
ORIGINAL PLAN DATE : 2/9/16
REVIEW DATE : 9/20/16
LATEST SUBMISSION DATE 6/2/16
SUBMITTAL NUMBER : 3
STATUS : CORRECTIONS REQUIRED
TABLE REVIEW : N
1. THE SEWER AND WATER EASEMENTS MAY NOT BE
INCLUDED IN THE TREE CANOPY AREA CALCULATOION.
REMOVE THESE AREAS FROM THE PROVIDED
ACREAGE.
2. PROVIDE AN AUTOCAD FILE DEPICTING THE BOUNDARIES
OF THIS CONSTRUCTION PLAN.
LANDSCAPE AND LIGHTING:
1. THE TEXTUAL STATEMENT REQUIRES PERIMETER
LANDSCAPING AROUND ALL DWELLING UNITS. PROVIDE
A LANDSCAPE PLAN THAT DEPICTS TYPICAL UNIT
LANDSCAPING.
2. ADJUST THE STREET LIGHTS TO PROVIDE A 5 FOOT
SEPARATION BETWEEN ANY UTILITY SERVICE LINE
AND ANY PROPOSED DRIVEWAY. THE PERTAINS TO
LOTS 32, 14, 11
3. PROVIDE THE HEIGHT AND STYLE OF THE PROPOSED
STREET LIGHT. (PROVIDE CUT SHEETS).
4. PROVIDE A MINIMUM 5 FOOT SPACING BETWEEN STREET
TREES AND ANY WATER OR SEWER SERVICE LINE /METER.
TREES LOCATED ON LOTS 3, 14 AND 49 APPEAR RIGHT ON
TOP OF THESE UTILITIES.
5. PROVIDE A DETAILED PLAN FOR THE FOCAL POINTS PRIOR
TO CONSTRUCTION PLAN APPROVAL.
6. PER 19.1-211 ANY STORMWATER MANAGEMENT FACILITY
OR BMP BASIN VISIBLE TO THE PUBLIC SHALL BE LANDSCAPED
OR OTHERWISE IMPROVED SO THAT THE FACILITIES ARE
VISUALLY ENHANCED. INCLUDE A PLAN DEPICTING VISUAL
ENHANCEMENTS IN THE LANDSCAPE PLAN.
7. THE STREET TREE PLAN APPEARS TO SHOW A FENCING
AROUND THE BMP AND FOCAL POINT ADJACENT TO
KENBROOK DRIVE. THE FOCAL POINT PLAN AND BMP
LANDSCAPING PLAN SHALL INCLUDE DETAILS
FOR THE STYLE AND MATERIAL FOR THE FENCE.
8. RED MAPLES TEND TO HAVE A VERY EXTENSIVE ROOT
STRUCTURES THAT MAY PENETRATE NEARBY UTILITY
LINES OVERTIME. CONSIDER REPLACING THE RED
MAPLES ADJACENT TO LOTS.
9. LANDSCAPE PLANS ARE REQUIRED TO BE DESIGN AND
STAMPS BY A LANDSCAPE ARCHITECT OR CERTIFIED
LANDSCAPER.
CONDITION
A LANDSCAPE PLAN SHALL BE PROVIDED FOR THE VISUAL
ENHANCEMENT OF THE BMP PER 19-1.211 PRIOR TO FINAL
PLAN APPROVAL.
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: HARPERS MILL SOUTH PHASE, SECTION 2
PLAN NUMBER: 16CP0061
LATEST REVISION DATE: 2/9/16
REVIEW DATE: 2/29/16
LATEST SUBMISSION DATE: 2/25/16
SUBMITTAL NUMBER: 1ST REVIEW
STATUS: NOT APPROVED
TABLE REVIEW: NO
PROVIDE A COMPUTER GENERATED WATER FLOW TEST DATA,
ALONG WITH THE NODE MAP THAT IS PROVIDED BY THE
CHESTERFIELD COUNTY UTILITIES DEPARTMENT, VERIFYING
THE REQUIRED WATER FLOW FOR FIRE PROTECTION IS AVAILABLE
AT THE SITE THE WATER FLOW TEST RESULTS AND GRAPH SHALL
BE SHOWN ON THE SUBMITTED PLAN. IFC 2012, SECTION B105.1
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: ANTHONY BATTEN / 717-6167
PLAN NAME: HARPERS MILL SOUTH PHASE, SECTION 2
PLAN NUMBER: 16CP0061
LATEST REVISION DATE: 5/26/16
REVIEW DATE: 6/8/16
LATEST SUBMISSION DATE: 6/7/16
SUBMITTAL NUMBER: 2ND REVIEW
STATUS: NOT APPROVED
TABLE REVIEW: NO
PROVIDE A COMPUTER GENERATED WATER FLOW TEST DATA,
ALONG WITH THE NODE MAP THAT IS PROVIDED BY THE
CHESTERFIELD COUNTY UTILITIES DEPARTMENT, VERIFYING
THE REQUIRED WATER FLOW FOR FIRE PROTECTION IS AVAILABLE
AT THE SITE THE WATER FLOW TEST RESULTS AND GRAPH SHALL
BE SHOWN ON THE SUBMITTED PLAN. IFC 2012, SECTION B105.1.
COPY ONTO THE CONSTRUCTION PLAN
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / (804) 748-1489
PLAN NAME: HARPERS MILL SOUTH PHASE, SECTION 2
PLAN NUMBER: 16CP0061
LATEST REVISION DATE: 8/16/16
REVIEW DATE: 8/25/16
LATEST SUBMISSION DATE: 8/24/16
SUBMITTAL NUMBER: 3RD REVIEW
STATUS: APPROVED
TABLE REVIEW: YES
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / (804) 748-1489
PLAN NAME: HARPERS MILL SOUTH PHASE, SECTION 2
PLAN NUMBER: 16CP0061
LATEST REVISION DATE: 11/10/16
REVIEW DATE: 12/5/16
LATEST SUBMISSION DATE: 11/22/16
SUBMITTAL NUMBER: 4TH REVIEW
STATUS: APPROVED
TABLE REVIEW: YES
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / (804) 748-1489
PLAN NAME: HARPERS MILL SOUTH PHASE, SECTION 2
PLAN NUMBER: 16CP0061
LATEST REVISION DATE: 1/19/17
REVIEW DATE: 3/3/17
LATEST SUBMISSION DATE: 3/2/17
SUBMITTAL NUMBER: 5TH REVIEW
STATUS: APPROVED
TABLE REVIEW: YES
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
============================================================
============================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : ADAM MARSHALL, P.E. (717-6711)
NAME OF PLAN : HARPERS MILL SOUTH PHASE - SECTION 2
SITE PLAN NO. : 16CP0061
LATEST PLAN DATE : 02/09/16
DEPT. REC'D DATE : 03/25/16
SUBMITTAL NUMBER : 1
REVIEW DATE : 03/28/16
RECOMMENDATION : REVISIONS REQUIRED
TABLE REVIEW : NO
-------- GENERAL NOTES --------
001. THE RESPONSIBILITY FOR COMPLIANCE WITH CHESTERFIELD
COUNTY STANDARDS AND POLICIES, AND WITH STATE AND
FEDERAL REGULATIONS WILL BE PLACED ON THE PROFESSIONAL
ENGINEER WHO SIGNS AND SEALS THE CONSTRUCTION PLANS
APPROVED.
002. THE RESPONSIBILITY FOR ACHIEVING AND MAINTAINING
SATISFACTORY LOT DRAINAGE WILL BE THAT OF THE DEVELOPER
UP THROUGH A PERIOD OF ONE YEAR AFTER STATE ACCEPTANCE
OF THE SUBDIVISION ROADS.
-------- EROSION CONTROL --------
001. PRIOR TO A LAND DISTURBANCE PERMIT ISSUANCE:
A) CONSTRUCTION PLANS RECEIVE FINAL PLANNING DEPARTMENT
APPROVAL.
B) THE ENVIRONMENTAL ENGINEERING DEPARTMENT SHALL
REQUIRE COPIES OF APPLICABLE CORRESPONDENCE FROM THE
U.S. ARMY CORPS OF ENGINEERS AND DEPARTMENT OF
ENVIRONMENTAL QUALITY SUCH THAT IT MAY BE DETERMINED
THAT ANY REQUIRED WETLANDS PERMITS HAVE BEEN
RECEIVED.
C) A COPY OF THE PROCESSED VSMP REGISTRATION AND FEE
FORM MUST BE RECEIVED BY ENVIRONMENTAL ENGINEERING.
D) AN EROSION CONTROL BOND MUST BE POSTED AND APPROVED.
E) COPIES OF THE ACTUAL VDOT LAND USE PERMIT(S) FOR THE
TIE-IN TO OTTERDALE ROAD (IF IN THE STATE
SYSTEM AT THE TIME OF LDP APPLICATION) MUST BE
PROVIDED TO ENVIRONMENTAL ENGINEERING.
F) FLAGGING AND/OR SAFETY FENCE AROUND USACOE
JURISDICTIONAL WETLANDS AND/OR OTHER ENVIRONMENTALLY
SENSITIVE AREAS MUST BE INSTALLED AND CLEARLY
VISIBLE.
G) DB/PG FOR ANY OFFSITE EASEMENTS MUST BE PROVIDED TO
ENVIRONMENTAL ENGINEERING.
H) PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO
CAROLE CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE
AUTOCAD FILE MUST BE SAVED AS A .DWG OR .DXF IN
AUTOCAD VERSION 2009 OR EARLIER AND REFERENCED
DIRECTLY TO THE VIRGINIA STATE PLANE COORDINATE
SYSTEM, SOUTH ZONE IN THE NAD83 DATUM. THE AUTOCAD
FILE MAY BE SUBMITTED ON A CD, DVD, OR VIA EMAIL
AND MUST BE CLEARLY LABELED WITH THE SUBDIVISION
NAME AND SECTION, SUBDIVISION PLAN NUMBER, THE
ENGINEERING FIRM AND THE CAD FILE PREPARER'S NAME
AND PHONE NUMBER. THE FILE MUST CONTAIN THE
FOLLOWING, EACH CLEARLY LABELED IN SEPARATE LAYERS:
1. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND,
2. EDGES OF SIDEWALKS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL
ENGINEERING PRIOR TO ISSUANCE OF THE LAND
DISTURBANCE PERMIT.
I) PROVIDE A COPY OF THE SWPPP BOOKLET (THREE-RING
BINDER) TO ENVIRONMENTAL ENGINEERING.
002. PROVIDE AN EC BOND ESTIMATE FOR REVIEW.
003. REVISE THE EC PHASE I LIMITS OF CLEARING TO REFLECT
ONLY WHAT IS NECESSARY TO INSTALL THE PHASE I INITIAL
MEASURES.
004. SPECIFY SAFETY FENCE AROUND THE FULL PERIMETER OF THE
SEDIMENT BASIN AND TRAPS, TO BE INSTALLED DURING EC
PHASE I.
005. SPECIFY IN THE PHASE I PLANS AND NARRATIVE HOW THE
EXISTING STREAM WILL BE CROSSED TO ACCESS THE SITE
(E.G. TEMPORARY CULVERT OR STRUCTURE 5-2, ETC.).
PROVIDE A DETAILED NARRATIVE SPECIFYING THAT FAVORABLE
WEATHER MUST BE FORECAST PRIOR TO BEGINNING
INSTALLATION, PIPE/MATERIALS MUST BE STOCKPILED ONSITE
PRIOR TO BEGINNING INSTALLATION, AND PROCEDURES FOR
CONSTRUCTION OF DIVERSIONS AND/OR COFFER DAMS,
INSTALLATION OF PUMPS, ETC.
006. SPECIFY SSF ALONG THE DOWNSTREAM EDGE OF THE SANITARY
SEWER INSTALLATION THAT RUNS FROM OTTERDALE ROAD TO
APPROX. STA. 16+55 OF THE MAIN SEWER LINE, AS WELL AS A
UTILITY STREAM CROSSING WHERE IT CROSSES THE EXISTING
CHANNEL.
007. REVISE THE "OFF-SITE AREAS" SECTION OF THE EC NARRATIVE
ON SHEET C2.2 TO MORE ACCURATELY REFLECT THIS
CONSTRUCTION PROJECT.
008. IT APPEARS THAT BAFFLES ARE REQUIRED FOR THE SEDIMENT
BASIN. SHOW AND LABEL THE LOCATION OF THE BAFFLES IN
PLAN VIEW ON SHEET C2.0 AND C2.1.
009. PROVIDE ADDITIONAL INFORMATION IN THE ELEVATION-VOLUME
TABLE FOR THE BASIN FOR ELEVATIONS BELOW 229'.
010. SHOW AND LABEL THE SEDIMENT BASIN EMERGENCY SPILLWAY ON
SHEETS C3.0 AND C3.1.
011. PROVIDE PRE- AND POST-DEVELOPMENT DRAINAGE AREA MAPS
FOR THE MS-19 ANALYSIS LOCATIONS.
012. PROVIDE ADDITIONAL MS-19 ANALYSIS DIRECTLY AT THE
OUTFALLS OF STRUCTURES 3-2 AND 4-4. FURTHER DISCUSSION
MAY BE HELPFUL.
013. IT APPEARS THAT BED/BANK CONTAINMENT PER SITUATION 'B'
IS NOT PRESENT AT MS-19 LOCATION 'B-B'. PLEASE
ADDRESS. FURTHER DISCUSSION MAY BE HELPFUL.
014. IT IS UNCLEAR WHETHER SITUATION 'F' WOULD BE MORE
APPLICABLE FOR MS-19 SECTION 'A-A', INSTEAD OF
SITUATION 'B'. FURTHER DISCUSSION MAY BE HELPFUL.
015. SPECIFY ADEQUACY SITUATION 'H' FOR MS-19 SECTION 'D-D',
AND PROVIDE THE REQUIRED WRITTEN VARIANCE REQUEST FOR
APPROVAL.
016. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND/OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR STATE
PERMITS IN RELATION TO ENVIRONMENTAL FEATURES
INCLUDING, BUT NOT LIMITED TO, WETLANDS, SURFACE WATER,
GROUND WATER, AND AIR QUALITY. FINAL APPROVAL OF THESE
PLANS WILL NOT RELIEVE YOU OF YOUR RESPONSIBILITIES.
-------------- CBPA ---------------
001. PLEASE BE REMINDED THAT A TECHNICAL CORRECTION TO THE
HARPERS MILL SOUTH PHASE PRELIMINARY AS PREVIOUSLY
DISCUSSED IS STILL REQUIRED, TO ALLOW THE SOUTH PHASE
TO BE INCORPORATED INTO THE HARPERS MILL OVERALL MASTER
BMP PLAN FOR CBPA COMPLIANCE.
002. PROVIDE AN UPDATED COPY OF THE MOST RECENTLY UPDATED
CBPA COMPLIANCE PLAN SHEET, A COPY OF WHICH CAN BE
PROVIDED VIA EMAIL, IF NEEDED. FURTHER DISCUSSION MAY
BE HELPFUL.
003. IN THE IMPERVIOUS AREA CALCULATIONS ON SHEET C8.0, IT
APPEARS THAT THE TABLE 2 INTERPOLATION FOR A 0.36-ACRE
AVERAGE LOT SIZE SHOULD BE 24% IN LIEU OF 25%. PLEASE
ADDRESS.
004. THE 24% IMPERVIOUS NOTED ABOVE SHOULD BE MULTIPLIED BY
THE TOTAL SITE AREA OF 21.07 ACRES, NOT JUST THE
LOT/OPEN SPACE AREA OF 18.14 ACRES. PLEASE ADDRESS.
005. PROVIDE THE SUPPORTING CALCULATIONS USED TO DETERMINE
THE IMPERVIOUS ACREAGE DRAINING TO THE BMP.
006. THE ACREAGES (TOTAL AND IMPERVIOUS) DRAINING TO THE BMP
ARE LISTED AS 14.76 AND 9.15 IN STEP 4 OF THE WORKSHEET
A CALCS, BUT AS 16.61 AND 8.34 IN STEP 6. PLEASE
CLARIFY.
007. IT IS NOTED THAT DESIGN 6 HAS BEEN LISTED IN THE
WORKSHEET A CALCULATIONS, BUT DESIGN 7 HAS BEEN NOTED
IN THE CBPA/MS-4 TABLE. PLEASE CLARIFY. BASED ON THE
DESIGN SHOWN, IT IS ASSUMED THAT DESIGN 6 IS INTENDED
(4VR); HOWEVER, AN EFFICIENCY OF 65% MAY ONLY BE TAKEN
THROUGH THE USE OF A PLANTED AQUATIC BENCH OR WITH A
DESIGN 7 BASIN (10VR). OTHERWISE, THE EFFICIENCY SHALL
BE 50%. PLEASE ADDRESS.
008. EXTEND THE AQUATIC AND SAFETY BENCHES AROUND THE FULL
PERIMETER OF THE SWM/BMP BASIN, TO INCLUDE THE FOREBAY
AREA.
009. IT APPEARS THAT THE SEDIMENT FOREBAY EXCEEDS THE
MAXIMUM 20' DIMENSION FOR MAINTENANCE PURPOSES. PLEASE
REVISE.
010. RAISE THE SEDIMENT FOREBAY EMBANKMENT TO ONE FOOT BELOW
THE NORMAL WSE OF THE BASIN.
011. SPECIFY RIPRAP ARMORING WITH FABRIC UNDERLAYMENT WITHIN
THE FULL SEDIMENT FOREBAY AREA, INCLUDING THE
EMBANKMENT.
012. LABEL THE SAFETY AND AQUATIC BENCHES ON SHEET C4.2.
013. LABEL THE BASIN BOTTOM ELEVATION ON SHEET C4.2.
014. SHOW AND LABEL THE REQUIRED 50' VEGETATED PERIMETER
YARD SETBACK AROUND THE BASIN, MEASURED FROM THE 100-
YEAR WSE OR TOE OF EMBANKMENT, WHICHEVER IS MORE
RESTRICTIVE.
015. ALIGN (AND LABEL) 12' MAINTENANCE CORRIDORS (MAX. 15%
GRADE) FOR USE IN ACCESSING THE INFLOW AND OUTFLOW
LOCATIONS.
016. ADJUST THE LIMITS OF THE SWM/BMP EASEMENT SUCH THAT
THEY DO NOT OVERLAP THE SAINITARY EASEMENT.
017. DUE TO THE LOCATION AND SLOPES OF THE BASIN IN
PROXIMITY TO THE AVINGTON DRIVE AND EMBERTAN ROAD,
SPECIFY ADEQUATE VEHICULAR SAFETY MEASURES JUST OUTSIDE
THE R/W. FURTHER DISCUSSION MAY BE NECESSARY.
018. SPECIFY A 12" DEWATERING PIPE AND VALVE FOR USE IN
LOWERING THE BASIN WATER SURFACE. ADDITIONALLY,
PROVIDE A NOTE STATING THAT A PUMP CAPABLE OF DRAINING
THE BASIN WITHIN A 24-HOUR PERIOD SHALL BE USED TO
DEWATER THE BASIN BELOW THE VALVE ELEVATION.
019. DUE TO THE 100-YEAR BACKWATER ELEVATION OF 231.75'
CREATED AT STRUCTURE 5-2, WHICH WILL BACK UP INTO THE
POND VIA THE OUTLET STRUCTURE, THIS BASIN WOULD BE
BETTER SUITED WITH A CONCRETE WEIR OUTFALL AND PLUNGE
POOL IN LIEU OF A RISER/BARREL. FURTHER DISCUSSION MAY
BE NECESSARY.
020. THE EMERGENCY SPILLWAY SHOWN TO BE CONSTRUCTED WITHIN
THE EMBANKMENT FILL WILL REQUIRE A PAVED LINING TO THE
100-YEAR DEPTH. PLEASE SPECIFY.
021. SHOW THE ALIGNMENT OF THE PROFILE THROUGH THE BASIN ON
SHEET C4.2.
022. REVISE THE DRAWING SCALE IN THE TITLE BLOCK OF SHEET
C4.2.
023. REPLACE THE NOTES SECTION ON SHEET C4.2 WITH THE
SPECIFIC LANGUAGE PER TENTATIVE CONDITION 3.
024. SPECIFY 24" CLASS I RIPRAP OUTLET PROTECTION WITH
FABRIC UNDERLAYMENT AT THE OUTFALL OF STRUCTURE 3-2, AT
0% GRADE TO THE EDGE OF THE EXISTING CHANNEL.
025. SPECIFY IN PLAN AND PROFILE AN IMPERMEABLE CLAY CORE
KEYED INTO IMPERMEABLE SUBGRADE.
026. SHOW THE 100-YEAR BACKWATER FROM STRUCTURE 5-2 ON THE
WET POND PROFILE ON SHEET C5.6.
027. EXTEND THE WET POND PROFILE ACROSS THE EXISTING
CHANNEL, SHOWING BOTH BANKS.
028. SHOW THE FULL HEIGHT OF THE BMP RISER (INCLUDING BASE)
ON THE WET POND PROFILE.
029. PROVIDE THE SWM/BMP BASIN DETAIL TO SCALE.
030. SPECIFY THE TRASH RACK MAKE AND MODEL NUMBER ON THE
SWM/BMP BASIN DETAIL.
031. IT APPEARS THAT BAFFLES WILL BE REQUIRED TO MEET THE
MINIMUM 2:1 LENGTH-TO-WIDTH RATIO. PLEASE ADDRESS.
-------- ROAD AND DRAINAGE --------
001. OUR CONCERNS ARE BASED ON THE INFORMATION SHOWN IN THE
CONSTRUCTION PLANS. THE RESPONSIBILITY FOR IDENTIFYING
CRITICAL AREAS IS PLACED ON THE PROFESSIONAL ENGINEER
WHO SEALS THE CONSTRUCTION PLANS APPROVED. WE RESERVE
THE RIGHT TO INSPECT CONVEYANCE SYSTEMS PRIOR TO PLAT
RECORDATION AND/OR STATE ACCEPTANCE TO DETERMINE IF
ADDITIONAL IMPROVEMENTS ARE REQUIRED.
002. UPDATE THE TENTATIVE INFORMATION ON THE COVER SHEET TO
REFLECT THE UPCOMING TECHNICAL CORRECTION, ONCE
APPROVED.
003. IT APPEARS THAT TENTATIVE CONDITIONS 14 AND 15
REGARDING MINING ACTIVITY HAVE NOT BEEN SATISFACTORILY
ADDRESSED. PLEASE ADDRESS. FURTHER DISCUSSION MAY BE
HELPFUL.
004. REMOVE REFERENCE TO FUTURE SOUTH PHASE L-2 FROM SHEET
C1.0.
005. IT APPEARS THAT THERE IS AN INCORRECT SOUTH PHASE
SECTION 2 LABEL ON SHEET C1.0. PLEASE ADDRESS.
006. SHOW AND LABEL THE SOUTH PHASE SECTION 1 SWM/BMP BASINS
ON SHEET C1.0, AND LABEL THE SECTION 2 BASIN AS
"SWM/BMP BASIN" AS WELL.
007. SHOW AND LABEL ALL EXISTING/PROPOSED EASEMENTS ALONG
OTTERDALE ROAD IN THE VICINITY OF THIS SUBDIVISION
SECTION (INCLUDE DB/PG REFERENCE, IF AVAILABLE).
008. LABEL THE FUTURE ROAD NAMES AND R/W WIDTHS ON THE PLAN
SHEETS.
009. SHOW THE LOCATION OF ALL CG-9 ENTRANCES ON SHEET C3.0
AND C4.0.
010. LABEL THE SIDEWALK WIDTH/MATERIAL ON SHEET C3.0.
011. IT IS UNCLEAR WHAT THE "CONSERVATION ESMT" IS INTENDED
TO ENCOMPASS, OR WHO THE GRANTEE IS. IT CURRENTLY
APPEARS THAT THE EASEMENT MAY COINCIDE WITH THE
REQUIRED SETBACKS, WHICH MAY NOT BE CORRECT. PLEASE
CLARIFY AND PROVIDE NOTES IN THE PLAN SET ACCORDINGLY.
PLEASE ALSO ENSURE THAT NONE OF THE PROPOSED DRAINAGE,
SLOPE & DRAINAGE, OR SWM/BMP EASEMENTS ENCROACH INTO
THE CONSERVATION EASEMENT. FURTHER DISCUSSION MAY BE
HELPFUL.
012. THE APPROVED HARPERS MILL SOUTH PHASE PRELIMINARY PLAN
ALLOWS FOR 25' SETBACKS FROM WETLANDS, FLOODPLAIN,
BACKWATER, ETC. IN LIEU OF THE 35' TYPICALLY REQUIRED
IN THE UPPER SWIFT CREEK WATERSHED. PLEASE ADDRESS.
013. SHOW AND LABEL THE 25' SETBACK FROM THE 100-YEAR
FLOODPLAIN IN THE VICINITY OF LOTS 5-6, AND TO THE REAR
OF LOTS 45 AND 47.
014. REVISE THE 100-YEAR BACKWATER AND FLOODPLAIN LINETYPES
SUCH THAT THEY CAN BE BETTER DISTINGUISHED WHERE THEY
CROSS THROUGH THE WETLAND AREAS.
015. LABEL ALL OPEN SPACE AREAS IN PLAN VIEW.
016. PLEASE CLARIFY THE TEXT OVERLAPS TO THE REAR OF LOTS
49-50 ON SHEET C3.0.
017. LABEL ALL SWM/BMP WATER SURFACE ELEVATIONS ON SHEET
C3.0, C4.0 AND C4.1.
018. EXTEND THE EMBERTAN ROAD R/W ALL THE WAY THROUGH THE
TEMPORARY TURNAROUND, AND SPECIFY VARIABLE-WIDTH
TEMPORARY TURNAROUND EASEMENTS BEYOND THE R/W AS
NECESSARY TO ENCLOSE THE TURNAROUND AND ASSOCIATED
GRADING.
019. SPECIFY THE RADIUS POINT OF THE TEMPORARY TURNAROUND ON
SHEET C3.0, AS WELL AS THE RADIUS OF THE TURNAROUND.
020. STIPPLE THE PROPOSED TURNAROUND PAVEMENT ON ALL PLAN
SHEETS.
021. REMOVE THE DEPICTION OF CURB & GUTTER AND SIDEWALK
THROUGH THE TEMPORARY TURNAROUND ON ALL PLAN SHEETS.
022. PROVIDE A FULL DESIGN, TO INCLUDE GRADING, PROFILE,
DITCH CROSS-SECTIONS, ETC. FOR THE TEMPORARY
TURNAROUND.
023. REVISE THE LABEL FOR THE DRAINAGE EASEMENT ENCLOSING
STRUCTURE 1-4 TO READ "VARIABLE-WIDTH DRAINAGE EASEMENT
FOR VDOT MAINTENANCE".
024. CLARIFY THE FULL LIMITS OF THE VARIABLE-WIDTH SLOPE &
DRAINAGE ESMT FOR VDOT MAINTENANCE ALONG THE SOUTHERN
FILL LIMITS FOR AVINGTON DRIVE ON ALL PLAN SHEETS.
025. ADJUST THE VIEWPORT, OR PROVIDE AN INSET (OR ADDITIONAL
PLAN SHEETS) AS NECESSARY, TO DEPICT THE FULL
SUBDIVISION SECTION LIMITS ON SHEETS C3.0, C4.0, AND
C4.1.
026. PROVIDE LABELED 100-YEAR FLOODPLAIN CROSS-SECTION
LOCATIONS (INCLUDING ELEVATIONS) FOR THE FULL LENGTH OF
THE FLOODPLAIN WHICH RUNS ALONG THE WEST OF THIS
SECTION. FURTHER DISCUSSION MAY BE HELPFUL.
027. IT APPEARS THAT THE CONTINUATION OF THE WESTERN SIDE OF
THE 100-YEAR FLOODPLAIN IS MISSING FROM THE PLAN
SHEETS. PLEASE ADDRESS.
028. SPECIFY A 16' TEMPORARY DRAINAGE EASEMENT TO ENCLOSE
STRUCTURES 1-11A, 1-12, AND 1-13 WHERE THEY FALL WITHIN
THE FUTURE EMBERTAN ROAD R/W.
029. SPECIFY A MIN. 10' TEMPORARY CONSTRUCTION EASEMENT IN
THE REAR OF LOT 39 TO ALLOW FOR THE FUTURE EXTENSION OF
EMBERTAN ROAD.
030. THERE APPEARS TO BE A STRAY SETBACK LINE AROUND THE
SWM/BMP. PLEASE ADDRESS.
031. SPECIFY A 50' VEGETATED PERIMETER YARD SETBACK AROUND
THE SWM/BMP ON SHEETS C3.0, C3.1, AND C4.1, MEASURED
FROM THE 100-YEAR WSE OR TOE OF EMBANKMENT, WHICHEVER
IS MORE RESTRICTIVE.
032. SPECIFY "MFF(SAG)=235.43'" NOTATION ON LOTS 49 AND 50.
033. SPECIFY "NBP1" NOTATION ON ALL LOTS, EXCEPT 1, 21, 22,
32 AND 49.
034. PROVIDE EXISTING CONTOUR LABELS ON ALL PLAN SHEETS.
035. SPECIFY A TEMPORARY DISSIPATER PIT AT THE SEDIMENT TRAP
LOCATION BEYOND THE EMBERTAN ROAD TEMPORARY TURNAROUND,
AND ENCLOSE WITHIN A TEMPORARY DRAINAGE EASEMENT.
PROVIDE THE DISSIPATER PIT DETAIL IN THE PLAN SET.
036. LABEL ALL ROADS ON SHEET C4.0.
037. PROVIDE DESIGN CROSS-SECTIONS FOR ALL PROPOSED DITCHES
AND SWALES ON SHEET C4.0.
038. LABEL DITCH 1 AND DITCH 2 AS SUCH IN PLAN VIEW, TO
CORRELATE WITH THE PROFILES.
039. REVISE THE GRADING FOR DITCH 1 TO THE REAR OF LOTS 24-
29 SUCH THAT THE 2:1 PORTION DOES NOT EXCEED THREE FEET
IN DEPTH. ANYTHING BEYOND THREE FEET MUST BE LAID BACK
AT 5:1 OR FLATTER SLOPES. ADDITIONAL PIPE/INLET
DRAINAGE IMPROVEMENTS MAY ALSO BE USED IN THIS AREA TO
AVOID DITCHES EXCEEDING 3' IN DEPTH. FURTHER
DISCUSSION MAY BE HELPFUL.
040. SPECIFY AN ADDITIONAL DI-6 INLET (WITH SLOT OPENINGS
AND 2' CONCRETE GUTTERS ON THE SOUTH AND EAST) IN THE
OPEN SPACE OUTSIDE THE SOUTHWEST CORNER OF LOT 23,
TYING INTO THE REAR OF STRUCTURE 1-23. ENCLOSE WITHIN
A 16' DRAINAGE EASEMENT.
041. SPECIFY 3:1 DITCH IMPROVEMENTS ALONG THE REAR OF LOTS
19-23, TYING INTO THE EASTERN SLOT OPENING OF THE DI-6
STRUCTURE NOTED IN THE PREVIOUS COMMENT. ENCLOSE
WITHIN A 16' DRAINAGE EASEMENT.
042. SPECIFY A USCW SPECIAL END TREATMENT STRUCTURE (MOD.
DI-7) AT THE END OF STRUCTURE 4-4 IN LIEU OF AN END
SECTION, AND PROVIDE THE DETAIL IN THE PLAN SET. PIPE
4-4 MAY NEED TO BE REALIGNED SLIGHTLY TO ACHIEVE
FLATTER TOPOGRAPHY AT THE DI-7 OUTFALL. FURTHER
DISCUSSION MAY BE HELPFUL.
043. SPECIFY A DI-6 AS STRUCTURE 1-18 (IN LIEU OF A DI-1)
WITH SLOT OPENINGS AND 2' CONCRETE GUTTERS ON THE WEST,
NORTH, AND EAST SIDES.
044. SPECIFY ADDITIONAL FILL GRADING ON LOTS 33 AND 34 TO
COMPLETELY REMOVE THE LOW AREA WHICH IS CURRENTLY
CREATED BY THE PROPOSED FILL.
045. SPECIFY A 5:1 SIDEYARD SWALE ON THE UPSTREAM SIDE OF
LOT 34, DRAINING TO THE PROPOSED DITCH TO THE REAR.
046. SPECIFY A 5:1 SWALE CENTERED ON THE LOT 32/33 LOT LINE,
DRAINING INTO THE EASTERN SLOT OPENING AT STRUCTURE 1-
18 (DI-6).
047. SPECIFY ADDITIONAL FILL GRADING ON LOTS 2-5 TO FULLY
REMOVE THE LOW AREA CREATED BY THE CURRENTLY PROPOSED
GRADING.
048. SPECIFY A 5:1 SIDEYARD SWALE ON THE UPSTREAM SIDE OF
LOT 3, DRAINING TO THE OPEN SPACE TO THE REAR OF THIS
LOT. PROVIDE A NOTE STATING THAT THIS SWALE SHALL
FLATTEN TO SHEET FLOW UPON ENTERING THE OPEN SPACE.
049. SPECIFY A 5:1 SIDEYARD SWALE ON THE UPSTREAM SIDE OF
LOT 38, DRAINING TO THE PROPOSED DITCH TO THE REAR OF
THIS LOT.
050. SPECIFY A 5:1 SIDEYARD SWALE ON THE UPSTREAM SIDE OF
LOT 34, DRAINING TO THE PROPOSED DITCH TO THE REAR.
051. SPECIFY A DI-6 INLET IN LIEU OF A DI-1 AT STRUCTURE 1-
11, WITH SLOT OPENINGS AND 2' CONCRETE GUTTERS ON THE
NORTH AND EAST SIDES.
052. ENSURE THAT ALL DI-6 SLOT INFORMATION IS INCLUDED IN
THE DRAINAGE SUMMARY TABLE ON SHEET C4.0.
053. PROVIDE ADDITIONAL INFORMATION (E.G. STANDARD STRUCTURE
TYPE, MATERIAL, DIAMETER, O-RING, ETC.) FOR STRUCTURE
3-1 IN THE DRAINAGE SUMMARY ON SHEET C4.0.
054. PROVIDE INFORMATION FOR STRUCTURES 5-1, 5-2, AND 5-3 IN
THE DRAINAGE STRUCTURE SUMMARY.
055. REMOVE "DRAINAGE" AND "FOR VDOT MAINTENANCE" FROM THE
CALLOUT FOR THE VAR. WIDTH SWM/BMP EASEMENT IN ALL
LOCATIONS.
056. SHOW THE INCREMENTAL DRAINAGE AREA TO THE SWM/BMP BASIN
ON SHEET C4.1, AND ENSURE THIS IS INCLUDED IN THE
CALCULATIONS AS APPLICABLE.
057. USE A DIFFERENT LINETYPE TO DISTINGUISH FUTURE ROAD
GRADES FROM PROPOSED GRADES ON ALL ROAD PROFILES.
058. LABEL ALL INTERSECTION POINTS (PROPOSED AND FUTURE) ON
ALL PROFILES, TO INCLUDE STATION AND ELEVATION.
059. LABEL THE LIMITS OF SECTION 2 CONSTRUCTION (INCLUDE
STATION) ON THE EMBERTAN ROAD PROFILES.
060. SHOW AND LABEL THE RADIUS POINT OF THE TEMPORARY
TURNAROUND ON THE EMBERTAN ROAD PROFILE, INCLUDING
STATION.
061. SHOW OTTERDALE ROAD GRADES ON THE AVINGTON DRIVE
PROFILE.
062. SHOW AND LABEL STRUCTURES 2-1 AND 2-3 ON THE AVINGTON
DRIVE PROFILE.
063. EXTEND THE EMBERTAN PLACE PROFILE ACROSS THE CUL-DE-
SAC, SHOWING CURB & GUTTER, SIDEWALK, AND TIE-INS TO
EXISTING GRADE.
064. ACCURATELY SHOW THE EMBERTAN ROAD GRADES ON THE
EMBERTAN COURT PROFILE, AND EXTEND ACROSS EMBERTAN
DRIVE AND THE EMBERTAN COURT CUL-DE-SAC, SHOWING CURB &
GUTTER, SIDEWALK, AND TIE-INS TO EXISTING GRADE.
065. SHOW STRUCTURE 3-2 ON THE SANITARY TRUNK 1 PROFILE.
066. SHOW AND LABEL THE R/W LIMITS ON ALL PROFILES, AS
APPLICABLE.
067. LOWER THE OUTFALL ENDS OF STRUCTURES 1-33 AND 2-6 SUCH
THAT THE SPRINGLINE OF THE PIPES ARE SET AT THE NORMAL
WSE OF THE SWM/BMP.
068. SHOW THE SWM/BMP WATER SURFACE ELEVATIONS ON ALL
APPLICABLE PROFILES.
069. SHOW THE PROPOSED SANITARY SEWER CROSSING ON THE STORM
4-1 PROFILE.
070. SPECIFY DITCH DESIGN CROSS-SECTIONS FOR EACH SEGMENT OF
DITCH ON THE DITCH 1 AND DITCH 2 PROFILES. NOTE THAT
THE 2:1 PORTION OF THE DITCH MAY NOT EXCEED 3' IN
DEPTH.
072. SPECIFY 24" OF CL. I RIP-RAP WITH FABRIC UNDERLAYMENT
AT THE UPSTREAM END OF STRUCTURE 5-2, IN PLAN AND
PROFILE VIEWS.
073. EXTEND THE PROFILE FOR STORM 4-1 ACROSS THE EXISTING
CHANNEL. NOTE THAT THE OUTFALL STRUCTURE MAY NEED TO
BE RELOCATED SO AS NOT TO FALL DIRECTLY IN THE EXISTING
CHANNEL.
074. SHOW AND LABEL ALL STORM STRUCTURES AND PIPE ON SHEET
C4.1.
075. SPECIFY A 5:1 OVERFLOW SWALE TO CONVEY THE 100-YEAR HGL
ESCAPE FROM STRUCTURES 1-18 AND 1-20 TO THE EMBERTAN
ROAD R/W. THE SWALE SHOULD BE 12" DEPTH AND CENTERED
IN THE 16' DRAINAGE EASEMENT, FLATTENING TO SHEET FLOW
PRIOR TO ENTERING THE R/W.
076. IT APPEARS THAT THE INCREMENTAL DRAINAGE AREAS FOR 1-14
AND 1-22 ARE INCORRECT IN THE VICINITY OF THE EMBERTAN
ROAD / EMBERTAN PLACE INTERSECTION. PLEASE ADDRESS.
077. PROVIDE AN INSET OR SEPARATE PLAN SHEET WHICH DEPICTS
THE FULL LIMITS OF THE DRAINAGE AREA TO STRUCTURE 1-12
ON SHEET C4.1.
078. SHOW THE OVERALL DRAINAGE AREA TO CULVERT STRUCTURE 5-
2.
079. IT APPEARS THAT THE REQUIRED SATURATION FACTOR OF 1.25
HAS NOT BEEN APPLIED TO ALL 100-YEAR PEAK FLOW
CALCULATIONS, INCLUDING THE BASIN ROUTING. PLEASE
ADDRESS.
080. THE CULVERT CALCULATIONS INDICATED A 100-YEAR BACKWATER
ELEVATION AT STRUCTURE 5-1 OF 229.65', BUT THE PLANS
SHOW 231.75'. PLEASE CLARIFY.
081. IN THE TIME OF CONCENTRATION DETERMINATIONS, PLEASE
REVISE TO REFLECT A MAXIMUM OVERLAND FLOW LENGTH OF
200'.
082. IN THE BASIN ROUTING CALCULATIONS, IT APPEARS THAT THE
AREA USED WAS APPROXIMATELY 7.12 ACRES, BUT THE PLANS
INDICATE A 16.61-ACRE DRAINAGE AREA. PLEASE ADDRESS.
083. PROVIDE TIME OF CONCENTRATION INFORMATION IN THE
ROUTING CALCULATIONS.
084. IT IS UNCLEAR WHETHER METHOD 'T' OR 'I' WAS UTILIZED IN
THE BASIN ROUTING CALCULATIONS. PLEASE ADDRESS, NOTING
THAT METHOD 'I' IS REQUIRED.
085. IN THE COMPOSITE OUTFLOW FOR THE BASIN, IT APPEARS THAT
THE EFFECTS OF THE VARYING STAGES OF BACKWATER AT
STRUCTURE 5-2 HAVE NOT BEEN ACCOUNTED FOR AS TAILWATER
CONDITIONS. PLEASE ADDRESS.
086. SHOW AND LABEL THE LOCATION OF THE REQUIRED BENCHMARK
WITHIN THE SECTION LIMITS ON SHEET C3.0.
087. PROVIDE A WRITTEN RESPONSE IN THE MARGIN OF A COPY OF
THESE REVIEW COMMENTS WITH YOUR NEXT PLAN SUBMITTAL.
DESIGN, DETAIL AND CALCULATIONS REQUIRED BY THE ABOVE
COMMENTS SHALL BE SUBJECT TO FURTHER REVIEW.
============================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : ADAM MARSHALL, P.E. (717-6711)
NAME OF PLAN : HARPERS MILL SOUTH PHASE - SECTION 2
SITE PLAN NO. : 16CP0061
LATEST PLAN DATE : 05/26/16
DEPT. REC'D DATE : 06/02/16
SUBMITTAL NUMBER : 2
REVIEW DATE : 06/23/16
RECOMMENDATION : REVISIONS REQUIRED
TABLE REVIEW : NO
-------- GENERAL NOTES --------
001. THE RESPONSIBILITY FOR COMPLIANCE WITH CHESTERFIELD
COUNTY STANDARDS AND POLICIES, AND WITH STATE AND
FEDERAL REGULATIONS WILL BE PLACED ON THE PROFESSIONAL
ENGINEER WHO SIGNS AND SEALS THE CONSTRUCTION PLANS
APPROVED.
002. THE RESPONSIBILITY FOR ACHIEVING AND MAINTAINING
SATISFACTORY LOT DRAINAGE WILL BE THAT OF THE DEVELOPER
UP THROUGH A PERIOD OF ONE YEAR AFTER STATE ACCEPTANCE
OF THE SUBDIVISION ROADS.
-------- EROSION CONTROL --------
001. PRIOR TO A LAND DISTURBANCE PERMIT ISSUANCE:
A) CONSTRUCTION PLANS RECEIVE FINAL PLANNING DEPARTMENT
APPROVAL.
B) THE ENVIRONMENTAL ENGINEERING DEPARTMENT SHALL
REQUIRE COPIES OF APPLICABLE CORRESPONDENCE FROM THE
U.S. ARMY CORPS OF ENGINEERS AND DEPARTMENT OF
ENVIRONMENTAL QUALITY SUCH THAT IT MAY BE DETERMINED
THAT ANY REQUIRED WETLANDS PERMITS HAVE BEEN
RECEIVED.
C) A COPY OF THE PROCESSED VSMP REGISTRATION AND FEE
FORM MUST BE RECEIVED BY ENVIRONMENTAL ENGINEERING.
D) AN EROSION CONTROL BOND MUST BE POSTED AND APPROVED.
E) COPIES OF THE ACTUAL VDOT LAND USE PERMIT(S) FOR THE
TIE-IN TO OTTERDALE ROAD (IF IN THE STATE
SYSTEM AT THE TIME OF LDP APPLICATION) MUST BE
PROVIDED TO ENVIRONMENTAL ENGINEERING.
F) FLAGGING AND/OR SAFETY FENCE AROUND USACOE
JURISDICTIONAL WETLANDS AND/OR OTHER ENVIRONMENTALLY
SENSITIVE AREAS MUST BE INSTALLED AND CLEARLY
VISIBLE.
G) DB/PG FOR ANY OFFSITE EASEMENTS MUST BE PROVIDED TO
ENVIRONMENTAL ENGINEERING.
H) PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO
CAROLE CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE
AUTOCAD FILE MUST BE SAVED AS A .DWG OR .DXF IN
AUTOCAD VERSION 2009 OR EARLIER AND REFERENCED
DIRECTLY TO THE VIRGINIA STATE PLANE COORDINATE
SYSTEM, SOUTH ZONE IN THE NAD83 DATUM. THE AUTOCAD
FILE MAY BE SUBMITTED ON A CD, DVD, OR VIA EMAIL
AND MUST BE CLEARLY LABELED WITH THE SUBDIVISION
NAME AND SECTION, SUBDIVISION PLAN NUMBER, THE
ENGINEERING FIRM AND THE CAD FILE PREPARER'S NAME
AND PHONE NUMBER. THE FILE MUST CONTAIN THE
FOLLOWING, EACH CLEARLY LABELED IN SEPARATE LAYERS:
1. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND,
2. EDGES OF SIDEWALKS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL
ENGINEERING PRIOR TO ISSUANCE OF THE LAND
DISTURBANCE PERMIT.
I) PROVIDE A COPY OF THE SWPPP BOOKLET (THREE-RING
BINDER) TO ENVIRONMENTAL ENGINEERING.
002. PROVIDE AN EC BOND ESTIMATE FOR REVIEW.
003. REVISE THE EC PHASE I LIMITS OF CLEARING TO REFLECT
ONLY WHAT IS NECESSARY TO INSTALL THE PHASE I INITIAL
MEASURES. CLEARING OF THE FULL ROAD RIGHT-OF-WAY IS
NOT NECESSARY TO INSTALL THE INITIAL MEASURES.
004. SPECIFY SAFETY FENCE AROUND THE FULL PERIMETER OF THE
SEDIMENT TRAPS, TO BE INSTALLED DURING EC PHASE I.
005. SPECIFY IN THE PHASE I PLANS AND NARRATIVE HOW THE
EXISTING STREAM WILL BE CROSSED TO ACCESS THE SITE.
PROVIDE A DETAILED NARRATIVE OUTLINING PROCEDURES FOR
CONSTRUCTION OF DIVERSIONS AND/OR COFFER DAMS,
INSTALLATION OF PUMPS, ETC., AS WELL AS ANY STREAM
CROSSING AND/OR DIVERSION DETAILS, AS APPLICABLE.
06. SPECIFY SSF TO BE INSTALLED IN EC PHASE I ALONG THE
DOWNSTREAM TOE OF FILL FOR SEDIMENT TRAP ST1.
007. SPECIFY SF TO BE INSTALLED IN EC PHASE I ALONG TOE
DOWNSTREAM TOE OF FILL FOR SEDIMENT TRAP ST2.
008. SPECIFY EITHER THE PERMANENT CONCRETE, OR TEMPORARY
PLYWOOD, BAFFLES TO BE CONSTRUCTED WITH THE SEDIMENT
BASIN, IN LIEU OF GABIONS.
009. PROVIDE AN UPDATED ELEVATION-VOLUME TABLE WHICH
INCLUDES INCREMENTAL VOLUMES STARTING AT THE BOTTOM
ELEVATION OF THE SEDIMENT BASIN.
010. PROVIDE A DETAIL FOR THE SEDIMENT BASIN EMERGENCY
SPILLWAY.
011. PROVIDE FULL PRE- AND POST-DEVELOPMENT HYDROLOGIC
CALCULATIONS FOR ALL MS-19 LOCATIONS FOR WHICH ADEQUACY
SITUATION 'G' IS NOTED. THIS INCLUDES THE 2-YEAR STORM
FOR ALL LOCATIONS DISCHARGING INTO A NATURAL CHANNEL.
012. PROVIDE ADDITIONAL MS-19 ANALYSIS DIRECTLY AT THE
OUTFALLS OF STRUCTURES 3-2 AND 4-4. FURTHER DISCUSSION
MAY BE HELPFUL.
013. SUBMIT THE REQUIRED WRITTEN VARIANCE REQUEST FOR ALL
APPLICABLE MS-19 LOCATIONS, FOR REVIEW AND APPROVAL.
014. SPECIFY CULVERT INLET PROTECTION AT THE UPSTREAM END OF
STRUCTURE 5-2 IN THE EC PHASE I PLANS.
015. SPECIFY OUTLET PROTECTION AT THE DOWNSTREAM ENDS OF
STRUCTURE 5-2 AND THE SEDIMENT BASIN OUTFALL IN THE EC
PHASE I PLANS.
016. IT IS UNCLEAR WHY THE SEDIMENT BASIN DRAINAGE AREA IS
NOTED AS 13.49 ACRES, BUT THE OVERALL DRAINAGE AREA TO
THE SAME BASIN IS 21.00 ACRES, AS THERE ARE NO
DIVERSIONARY MEASURES SPECIFIED WHICH WILL ELIMINATE
THE PORTION OF THE CONTRIBUTING DRAINAGE AREA UPSTREAM
TO THE EAST OF WHAT IS CURRENTLY SHOWN. PLEASE
ADDRESS.
017. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND/OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR STATE
PERMITS IN RELATION TO ENVIRONMENTAL FEATURES
INCLUDING, BUT NOT LIMITED TO, WETLANDS, SURFACE WATER,
GROUND WATER, AND AIR QUALITY. FINAL APPROVAL OF THESE
PLANS WILL NOT RELIEVE YOU OF YOUR RESPONSIBILITIES.
-------------- CBPA ---------------
001. REPLACE SHEET C8.1 WITH AN UPDATED COPY OF THE MOST
RECENTLY UPDATED OVERALL CBPA COMPLIANCE PLAN SHEET, A
COPY OF WHICH CAN BE PROVIDED VIA EMAIL, IF NEEDED.
FURTHER DISCUSSION MAY BE HELPFUL.
002. PROVIDE THE SUPPORTING CALCULATIONS WHICH WERE USED TO
DETERMINE THE IMPERVIOUS AREAS NOTED FOR THE SITE (19%)
AND SWM/BMP BASIN DRAINAGE AREA (21%).
003. PROVIDE A FULL SET OF SWM/BMP ROUTING CALCULATIONS,
WHICH INCLUDE THE SPILLWAY "WEIR 1" OUTLET
CONFIGURATION AND PERFORMANCE, AS WELL AS THE FULL
ELEVATION-VOLUME TABLE WHICH INCLUDES THE TOTAL BASIN
VOLUME DOWN TO THE BOTTOM ELEVATION (220'). IT ALSO
NEEDS TO BE SHOWN THAT METHOD 'I' WAS UTILIZED.
ADDITIONAL COMMENTS MAY BE GENERATED BASED UPON THIS
INFORMATION. FURTHER DISCUSSION MAY BE HELPFUL.
004. REMOVE THE TRASH RACK DETAIL FROM SHEET C8.0.
005. SPECIFY CONCRETE BAFFLES IN LIEU OF GABIONS.
006. SHOW AND LABEL THE 50' VEGETATED PERIMETER YARD SETBACK
ON SHEET C4.4.
007. ADJUST THE ALIGNMENT OF THE PROFILE THROUGH THE BMP TO
MORE ACCURATELY ALIGN WITH THE CONCRETE SPILLWAY
LOCATION.
008. EXTEND THE BMP SPILLWAY/CHANNEL AND PLUNGE POOL SUCH
THAT IT DISCHARGES AT A LOCATION CLOSER TO THE EXISTING
STREAM CHANNEL, AND PROMOTES MORE OF A SHEET FLOW
CONDITION.
009. SPECIFY THAT A GATE VALVE SHALL BE USED FOR THE
DEWATERING PIPE, AND PROVIDE THE SIZE, MATERIAL,
MAKE/MODEL, ETC.
010. PROVIDE A REFERENCE TO SHEET C5.6 WITH THE "CONCRETE
WEIR SPILLWAY" CALLOUT ON SHEET C4.4.
011. SHOW THE CONCRETE BAFFLES ON THE BASIN PROFILE ON SHEET
C5.6.
012. SHOW AND LABEL THE FABRIC UNDERLAYMENT AND RIP-RAP
LINING FOR THE PLUNGE POOL ON THE PROFILE ON SHEET
C5.6.
013. REVISE THE CALLOUT FOR THE "CONC. WEIR OUTFALL
STRUCTURE" ON THE PROFILE ON SHEET C5.6 TO READ THE
CORRECT ELEVATION OF 228.00', INSTEAD OF 128.00'.
014. SHOW AND LABEL THE PLANTED AQUATIC AND SAFETY BENCHES
ON THE PROFILE ON SHEET C5.6.
015. ON THE CLAY CORE DETAIL, REVISE THE NOTE TO READ,
"...TO POND BOTTOM ELEVATION AND A MINIMUM OF 1' INTO
IMPERMEABLE SUBGRADE...".
016. PROVIDE AN ENLARGED, SCALED PLAN VIEW OF THE CONCRETE
SPILLWAY.
017. PROVIDE ALL SPILLWAY DETAILS TO SCALE.
018. SPECIFY MINIMUM 36" CONCRETE CURTAINWALLS AT THE ENDS
OF THE CONCRETE SPILLWAY.
019. SPECIFY AND PROVIDE DETAILS FOR THE REQUIRED PEDESTRIAN
FOOTBRIDGE OVER THE CONCRETE SPILLWAY.
020. LABEL THE AQUATIC BENCH AS "PLANTED AQUATIC BENCH" IN
ALL LOCATIONS IN THE PLANS, AND PROVIDE AN AQUATIC
BENCH PLANTING PLAN FOR REVIEW AND APPROVAL.
021. SHOW THE 100-YEAR BACKWATER FROM STRUCTURE 5-2
EXTENDING UP THROUGH THE CONCRETE SPILLWAY ON SHEETS
C4.4 AND C5.6.
022. ADJUST THE LIMITS OF THE VARIABLE-WIDTH SWM/BMP
EASEMENT TO EXTEND 25' BEYOND THE TOE OF EMBANKMENT,
UNLESS THERE IS A CONFLICT WITH THE CONSERVATION
EASEMENT, IN WHICH CASE THE LIMITS MAY BE ADJUSTED TO
FOLLOW THE CONSERVATION EASEMENT LIMITS.
-------- ROAD AND DRAINAGE --------
001. OUR CONCERNS ARE BASED ON THE INFORMATION SHOWN IN THE
CONSTRUCTION PLANS. THE RESPONSIBILITY FOR IDENTIFYING
CRITICAL AREAS IS PLACED ON THE PROFESSIONAL ENGINEER
WHO SEALS THE CONSTRUCTION PLANS APPROVED. WE RESERVE
THE RIGHT TO INSPECT CONVEYANCE SYSTEMS PRIOR TO PLAT
RECORDATION AND/OR STATE ACCEPTANCE TO DETERMINE IF
ADDITIONAL IMPROVEMENTS ARE REQUIRED.
002. UPDATE THE TENTATIVE INFORMATION ON THE COVER SHEET TO
REFLECT THE TECHNICAL CORRECTION APPROVAL DATE.
003. IT APPEARS THAT TENTATIVE CONDITIONS 14 AND 15
REGARDING MINING ACTIVITY HAVE NOT BEEN SATISFACTORILY
ADDRESSED. PLEASE ADDRESS. NOTES WILL NEED TO BE
PLACED ON THE COVER SHEET, AS PER THE CONDITIONS.
FURTHER DISCUSSION MAY BE HELPFUL.
004. ADD "DB.___ PG.___" TO THE CALLOUTS FOR ALL
EXISTING/PROPOSED EASEMENTS ALONG OTTERDALE ROAD IN THE
VICINITY OF THIS SUBDIVISION SECTION (INCLUDE ACTUAL
DB/PG REFERENCE, WHERE AVAILABLE).
005. IF ALLOWABLE, ADJUST THE LIMITS OF THE CONSERVATION
EASEMENT SUCH THAT THERE ARE NO DRAINAGE OR SWM/BMP
EASEMENT ENCROACHMENTS INTO THE CONSERVATION EASEMENT
LIMITS. FURTHER DISCUSSION MAY BE HELPFUL.
006. REVISE ALL REFERENCES TO THE 25' SETBACK FROM
FLOODPLAIN, WETLANDS, ETC. TO READ "25' SETBACK", NOT
"25' BUFFER".
007. EXTEND THE BLOOMING ROAD R/W ALL THE WAY THROUGH THE
TEMPORARY TURNAROUND, AND ADJUST THE SECTION LIMITS TO
FOLLOW THE R/W LIMITS IN THIS AREA. FURTHER DISCUSSION
MAY BE HELPFUL.
008. CLARIFY THE FULL LIMITS OF THE VARIABLE-WIDTH SLOPE &
DRAINAGE ESMT FOR VDOT MAINTENANCE ALONG THE SOUTHERN
FILL LIMITS FOR KENBROOK DRIVE ON ALL PLAN SHEETS, AND
LABEL EXACTLY AS SUCH IN ALL LOCATIONS. THERE IS
CURRENTLY NO DELINEATION BETWEEN THIS EASEMENT AND THE
SWM/BMP EASEMENT LIMITS.
009. SHOW AND LABEL THE LOCATION OF ALL 100-YEAR FLOODPLAIN
CROSS-SECTIONS ON ALL PLAN SHEETS (INCLUDE ELEVATIONS),
AND SHOW/LABEL THE 100-YEAR ELEVATIONS ON ALL CROSS-
SECTIONS ON SHEET C5.8. PROVIDE A COPY OF THE 100-YEAR
FLOODPLAIN CALCULATIONS WHICH CORRELATE WITH THESE
SECTIONS, AS WELL. FURTHER DISCUSSION MAY BE HELPFUL.
010. SPECIFY A 16' TEMPORARY DRAINAGE EASEMENT (NOT 10'
TEMPORARY CONSTRUCTION EASEMENT) ENCLOSING STRUCTURES
1-20, 1-21, AND 1-22 WHERE THEY FALL WITHIN THE FUTURE
BLOOMING ROAD R/W.
011. SPECIFY A MIN. 10' TEMPORARY CONSTRUCTION EASEMENT IN
THE REAR OF LOT 40 TO ALLOW FOR THE FUTURE EXTENSION OF
BLOOMING ROAD.
012. SPECIFY "MFF(SAG)=235.43'" NOTATION ON LOT 50.
013. ADD "NBP1" NOTATION TO LOTS 22, 23, AND 33.
014. SPECIFY A TEMPORARY DISSIPATER PIT AT THE SEDIMENT TRAP
LOCATION BEYOND THE BLOOMING ROAD TEMPORARY TURNAROUND,
AND ENCLOSE WITHIN A TEMPORARY DRAINAGE EASEMENT. THE
TRAP MAY BE CONVERTED TO A DISSIPATER PIT BY SPECIFYING
THAT THE TRAP SHALL BE CLEANED OUT, AND THEN FABRIC
UNDERLAYMENT AND CLASS I RIP-RAP BACKFILL AT 0% GRADE
SHALL BE PLACED. PROVIDE THE DISSIPATER PIT DETAIL IN
THE PLAN SET.
015. SPECIFY "GRASS" IN LIEU OF "EARTH" LINING IN ALL
APPLICABLE DITCH CROSS-SECTION CALLOUTS (PLAN AND
PROFILE).
016. REVISE THE GRADING FOR DITCHES 1 AND 2 SUCH THAT THE
3:1 PORTION DOES NOT EXCEED THREE FEET IN DEPTH.
ANYTHING BEYOND THREE FEET MUST BE LAID BACK AT 5:1 OR
FLATTER SLOPES. HOWEVER, IT IS STRONGLY RECOMMENDED,
DUE TO THE TOPOGRAPHY, THAT ADDITIONAL PIPE/INLET
DRAINAGE IMPROVEMENTS BE USED IN THIS AREA INSTEAD, TO
AVOID DITCHES EXCEEDING 3' IN DEPTH. FURTHER
DISCUSSION MAY BE HELPFUL.
017. SHIFT THE LOCATION OF STRUCTURE 1-3 SUCH THAT IT FALLS
ENTIRELY IN THE OPEN SPACE ADJACENT TO LOT 24, INSTEAD
OF IN THE LOT.
018. PROVIDE THE USCW SPECIAL END TREATMENT (MOD. DI-7)
DETAIL IN THE PLANS.
019. SPECIFY AN ADDITIONAL SLOT OPENING AND 2' CONCRETE
GUTTER ON THE SOUTH AND EAST SIDES OF STRUCTURE 1-27.
020. SPECIFY ADDITIONAL FILL GRADING ON LOTS 34 AND 35 TO
COMPLETELY REMOVE THE LOW AREA WHICH IS CURRENTLY
CREATED BY THE PROPOSED FILL. SHEET C4.1 "LOT GRADING"
SHOULD BE REMOVED FROM THE PLAN SET, AS THE DEVELOPER
IS RESPONSIBLE FOR ACHIEVING THE FINAL GRADES AS SHOWN
IN THE APPROVED CONSTRUCTION PLANS, PRIOR TO ISSUANCE
OF BUILDING PERMITS FOR ANY AFFECTED LOTS. FURTHER
DISCUSSION IS RECOMMENDED.
021. SPECIFY A 5:1 SIDEYARD SWALE ON THE UPSTREAM SIDE OF
LOT 35, DRAINING TO THE PROPOSED DITCH TO THE REAR.
022. SPECIFY A 5:1 SWALE CENTERED ON THE LOT 33/34 LOT LINE,
DRAINING INTO THE EASTERN SLOT OPENING AT STRUCTURE 1-
18 (DI-6).
023. SPECIFY ADDITIONAL FILL GRADING ON LOTS 2-5 TO FULLY
REMOVE THE LOW AREA CREATED BY THE CURRENTLY PROPOSED
GRADING.
024. SPECIFY A 5:1 SIDEYARD SWALE ON THE UPSTREAM SIDE OF
LOT 3, DRAINING TO THE OPEN SPACE TO THE REAR OF THIS
LOT. PROVIDE A NOTE STATING THAT THIS SWALE SHALL
FLATTEN TO SHEET FLOW UPON ENTERING THE OPEN SPACE.
025. SPECIFY A 5:1 SIDEYARD SWALE ON THE UPSTREAM SIDE OF
LOT 39, DRAINING TO THE PROPOSED DITCH TO THE REAR OF
THIS LOT.
026. SPECIFY A SLOT OPENING AND 2' CONCRETE GUTTERS ON THE
EAST SIDE INSTEAD OF THE WEST SIDE OF STRUCTURE 1-19.
027. SHOW AND LABEL THE INCREMENTAL DRAINAGE AREA TO THE
SWM/BMP BASIN ON SHEET C4.2.
028. REVISE ALL INCREMENTAL DRAINAGE AREA LIMITS AND
INFORMATION TO REFLECT THE GRADING AS PER SHEET C4.0,
INSTEAD OF SHEET C4.1. IF THE FINAL GRADING AS PER THE
PROPOSED LOT GRADING PLAN IS DESIRED, THEN THE GRADING
ON SHEET C4.0 NEEDS TO BE REVISED ACCORDINGLY. FURTHER
DISCUSSION MAY BE HELPFUL.
029. SHOW THE TIE-INS TO EXISTING GRADE ON ALL ROAD
PROFILES.
030. FIX THE GRADING SHOWN ON THE BLOOMING PLACE PROFILE TO
MORE ACCURATELY REFLECT THE CUL-DE-SAC GRADES.
031. ADJUST THE LOCATION OF STRUCTURE 4-4 TO A FLATTER, MORE
SUITABLE OUTFALL LOCATION, CLOSER TO THE EXISTING
STREAM CHANNEL. FURTHER DISCUSSION MAY BE HELPFUL.
032. IT APPEARS THAT THE PROPOSED DRAINAGE AREA TO STRUCTURE
1-21 (9.31 ACRES) MAY BE EXCESSIVE. PLEASE ADDRESS.
033. IT APPEARS THAT THE REQUIRED SATURATION FACTOR OF 1.25
HAS NOT BEEN APPLIED TO THE STORM SEWER AND HGL CALCS.
PLEASE ADDRESS.
034. PROVIDE UPDATED HYDROLOGIC CALCULATIONS FOR EACH
INCREMENTAL DRAINAGE AREA, MS-19, ETC.
035. REMOVE THE PORTIONS OF BUILDING ENVELOPES OF LOTS 5, 6,
AND 50 WHICH ARE SHOWN ENCROACHING INTO THE 25' WETLAND
OR FLOODPLAIN SETBACKS. IT IS RECOMMENDED THAT ALL
DEPICTED BUILDING ENVELOPES BE REMOVED FROM THE PLANS
UNLESS SPECIFICALLY REQUESTED BY THE COUNTY.
036. ADJUST THE LIMITS OF THE 100-YEAR BACKWATER OF
STRUCTURE 5-2 SUCH THAT THEY FOLLOW THE CONTOUR OF THE
PROPOSED SWM/BMP BASIN EMBANKMENT.
037. ADJUST THE LIMITS OF THE 100-YEAR FLOODPLAIN SUCH THAT
IT DOES NOT CROSS THE KENBROOK DRIVE R/W.
038. LABEL THE EASEMENTS TO THE NORTH AND SOUTH OF KENBROOK
DRIVE TO READ, "VARIABLE-WIDTH SLOPE & DRAINAGE
EASEMENT FOR VDOT MAINTENANCE".
039. LABEL THE VARIABLE-WIDTH TEMPORARY TURNAROUND EASEMENT
ON THE NORTH SIDE OF THE TURNAROUND.
040. PROVIDE STATIONED ALIGNMENTS IN PLAN VIEW FOR ALL
PROPOSED DITCHES.
041. REMOVE THE DEPICTION OF THE VARIABLE-WIDTH TEMPORARY
CONSTRUCTION EASEMENT FROM LOTS 25-31 AND THE ADJACENT
FOCAL POINT AREA, AS THE TEMPORARY EASEMENT IS ONLY
NEEDED IN AREAS OUTSIDE THE SECTION LIMITS.
042. REMOVE STRUCTURES 1-11 THROUGH 1-14 FROM THE DRAINAGE
SUMMARY.
043. SPECIFY AN ADDITIONAL SLOT OPENING WITH 2' CONCRETE
GUTTER ON THE WEST SIDE OF STRUCTURE 1-3.
044. IT APPEARS THAT THE SANITARY SEWER ALIGNMENT IN THE
VICINITY OF STA. 20+00 CONFLICTS WITH THE LOCATION OF A
MODIFIED DI-7 OUTFALL FROM THE OTTERDALE ROAD PROJECT.
PLEASE ADDRESS.
045. CORRECT THE ROAD NAMES ON SHEET C6.0.
046. SHOW AND LABEL THE LOCATION OF THE REQUIRED BENCHMARK
WITHIN THE SECTION LIMITS ON SHEET C3.0.
047. PROVIDE A WRITTEN RESPONSE IN THE MARGIN OF A COPY OF
THESE REVIEW COMMENTS WITH YOUR NEXT PLAN SUBMITTAL.
DESIGN, DETAIL AND CALCULATIONS REQUIRED BY THE ABOVE
COMMENTS SHALL BE SUBJECT TO FURTHER REVIEW.
============================================================
============================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : ADAM MARSHALL, P.E. (717-6711)
NAME OF PLAN : HARPERS MILL SOUTH PHASE - SECTION 2
SITE PLAN NO. : 16CP0061
LATEST PLAN DATE : 11/10/16
DEPT. REC'D DATE : 11/21/16
SUBMITTAL NUMBER : 4
REVIEW DATE : 12/13/16
RECOMMENDATION : REVISIONS REQUIRED
TABLE REVIEW : NO
-------- GENERAL NOTES --------
001. THE RESPONSIBILITY FOR COMPLIANCE WITH CHESTERFIELD
COUNTY STANDARDS AND POLICIES, AND WITH STATE AND
FEDERAL REGULATIONS WILL BE PLACED ON THE PROFESSIONAL
ENGINEER WHO SIGNS AND SEALS THE CONSTRUCTION PLANS
APPROVED.
002. THE RESPONSIBILITY FOR ACHIEVING AND MAINTAINING
SATISFACTORY LOT DRAINAGE WILL BE THAT OF THE DEVELOPER
UP THROUGH A PERIOD OF ONE YEAR AFTER STATE ACCEPTANCE
OF THE SUBDIVISION ROADS.
-------- EROSION CONTROL --------
001. PRIOR TO A LAND DISTURBANCE PERMIT ISSUANCE:
A) CONSTRUCTION PLANS RECEIVE FINAL PLANNING DEPARTMENT
APPROVAL.
B) THE ENVIRONMENTAL ENGINEERING DEPARTMENT SHALL
REQUIRE COPIES OF APPLICABLE CORRESPONDENCE FROM THE
U.S. ARMY CORPS OF ENGINEERS AND DEPARTMENT OF
ENVIRONMENTAL QUALITY SUCH THAT IT MAY BE DETERMINED
THAT ANY REQUIRED WETLANDS PERMITS HAVE BEEN
RECEIVED.
C) A COPY OF THE PROCESSED VSMP REGISTRATION AND FEE
FORM MUST BE RECEIVED BY ENVIRONMENTAL ENGINEERING.
D) AN EROSION CONTROL BOND MUST BE POSTED AND APPROVED.
E) COPIES OF THE ACTUAL VDOT LAND USE PERMIT(S) FOR THE
TIE-IN TO OTTERDALE ROAD (IF IN THE STATE
SYSTEM AT THE TIME OF LDP APPLICATION) MUST BE
PROVIDED TO ENVIRONMENTAL ENGINEERING.
F) FLAGGING AND/OR SAFETY FENCE AROUND USACOE
JURISDICTIONAL WETLANDS AND/OR OTHER ENVIRONMENTALLY
SENSITIVE AREAS MUST BE INSTALLED AND CLEARLY
VISIBLE.
G) DB/PG FOR ANY OFFSITE EASEMENTS MUST BE PROVIDED TO
ENVIRONMENTAL ENGINEERING.
H) PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO
CAROLE CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE
AUTOCAD FILE MUST BE SAVED AS A .DWG OR .DXF IN
AUTOCAD VERSION 2009 OR EARLIER AND REFERENCED
DIRECTLY TO THE VIRGINIA STATE PLANE COORDINATE
SYSTEM, SOUTH ZONE IN THE NAD83 DATUM. THE AUTOCAD
FILE MAY BE SUBMITTED ON A CD, DVD, OR VIA EMAIL
AND MUST BE CLEARLY LABELED WITH THE SUBDIVISION
NAME AND SECTION, SUBDIVISION PLAN NUMBER, THE
ENGINEERING FIRM AND THE CAD FILE PREPARER'S NAME
AND PHONE NUMBER. THE FILE MUST CONTAIN THE
FOLLOWING, EACH CLEARLY LABELED IN SEPARATE LAYERS:
1. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND,
2. EDGES OF SIDEWALKS.
THE FILE MUST BE APPROVED BY ENVIRONMENTAL
ENGINEERING PRIOR TO ISSUANCE OF THE LAND
DISTURBANCE PERMIT.
I) PROVIDE A COPY OF THE SWPPP BOOKLET (THREE-RING
BINDER) TO ENVIRONMENTAL ENGINEERING.
002. IN THE MS-19 CALCS FOR SECTION A-A, IT IS UNCLEAR WHY
THE TIME OF CONCENTRATION IS DIFFERENT BETWEEN THE
PRE- AND POST-DEVELOPMENT SCENARIO, AS THE FLOW PATH
SHOULD BE THE SAME FOR BOTH. PLEASE ADDRESS.
003. PROVIDE THE 2-YEAR INFO FOR SECTION A-A BELOW THE
TABLE ON SHEET C4.2.
004. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND/OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR STATE
PERMITS IN RELATION TO ENVIRONMENTAL FEATURES
INCLUDING, BUT NOT LIMITED TO, WETLANDS, SURFACE WATER,
GROUND WATER, AND AIR QUALITY. FINAL APPROVAL OF THESE
PLANS WILL NOT RELIEVE YOU OF YOUR RESPONSIBILITIES.
-------------- CBPA ---------------
001. REMOVE HARPERS MILL SOUTH PHASE SECTIONS 3 AND 4 FROM
THE TABLE AND PLAN ON SHEET C8.1, AS WELL AS SOUTHEAST
SECTION 2.
002. ADJUST THE 36" CURTAINWALLS SUCH THAT THEY PROJECT
DOWNWARD VERTICALLY, AND SHOW IN THE CONCRETE SPILLWAY
DETAIL AND PROFILE ON SHEET C5.6.
003. PROVIDE DETAILS FOR THE REQUIRED PEDESTRIAN
FOOTBRIDGE OVER THE CONCRETE SPILLWAY IN THE
CONSTRUCTION PLAN SET, TO INCLUDE A DETAIL WITH
DIMENSIONS AND ELEVATIONS, MATERIALS, ANCHORING
POINTS, ETC. FURTHER DISCUSSION MAY BE HELPFUL.
004. PROVIDE ADDITIONAL INFORMATION, NARRATIVES, ETC. IN
THE AQUATIC BENCH PLANTING PLAN, WHICH PROVIDES
REQUIREMENTS FOR SOILS THAT MEET THE PLANTING
GUIDELINES SPECIFIED BY THE NURSERY, SOIL TESTING
REQUIREMENTS, PLANTING TIMEFRAMES, WARRANTIES, ETC.
CONTACT DAVID TAYLOR OF OUR OFFICE FOR MORE
INFORMATION.
005. SPECIFY AQUATIC BENCH SIGNAGE IN SEVERAL LOCATIONS
AROUND THE SWM/BMP, AND INCLUDE THE SIGN DETAIL IN THE
PLANS.
006. IT APPEARS THERE ARE STILL AREAS WHERE THE SWM/BMP
EASEMENT ENCROACH INTO THE CONSERVATION EASEMENT,
WHICH IS NOT ALLOWABLE. PLEASE ADDRESS.
007. IT APPEARS THERE MAY BE AN ERRANT CONSERVATION
EASEMENT LABEL ON SHEET C4.3. PLEASE ADDRESS.
008. THE ADDITION OF THE PLANTED AQUATIC BENCH ALLOWS FOR A
BMP EFFICIENCY OF 65% INSTEAD OF 50%. PLEASE UPDATE.
009. CORRECT THE CBPA/MS-4 TABLE TO REFLECT A BMP VOLUME OF
70,374CF (PER EL./VOL. TABLE IN ROUTING AT 234.50',
ASSUMING THIS IS ACCURATE).
-------- ROAD AND DRAINAGE --------
001. OUR CONCERNS ARE BASED ON THE INFORMATION SHOWN IN THE
CONSTRUCTION PLANS. THE RESPONSIBILITY FOR IDENTIFYING
CRITICAL AREAS IS PLACED ON THE PROFESSIONAL ENGINEER
WHO SEALS THE CONSTRUCTION PLANS APPROVED. WE RESERVE
THE RIGHT TO INSPECT CONVEYANCE SYSTEMS PRIOR TO PLAT
RECORDATION AND/OR STATE ACCEPTANCE TO DETERMINE IF
ADDITIONAL IMPROVEMENTS ARE REQUIRED.
002. PROVIDE SIGNED DOCUMENTATION FROM THE GEOTECHNICAL
PROFESSIONAL WHICH ADDRESSES MINING ACTIVITIES (OR
LACK THEREOF) SPECIFIC TO THIS SECTION.
003. LABEL AND PROVIDE DB/PG NUMBERS FOR ALL EXISTING
EASEMENTS (E.G. ALONG OTTERALE ROAD).
004. SHOW AND LABEL THE LOCATION OF ALL 100-YEAR FLOODPLAIN
CROSS-SECTIONS (INCLUDE ELEVATIONS) ON SHEET C4.0,
AND SHOW/LABEL THE 100-YEAR ELEVATIONS ON ALL CROSS-
SECTIONS ON SHEET C5.8.
007. PROVIDE ADDITIONAL CONTOURS IN THE BLANK AREAS ON
SHEET C5.9, WHICH SUPPORT THE DRAINAGE AREA BOUNDARIES
SHOWN.
008. PROVIDE LEGIBLE CONTOUR LABELS ON SHEET C5.9.
009. THE 100-YEAR ELEVATIONS SHOWN ON SHEET C5.8 DO NOT
APPEAR TO MATCH THE CALCULATIONS PROVIDED (NOTE THAT
SL-1 AND SL-12 WERE PROVIDED). PLEASE ADDRESS.
010. PROVIDE 100-YEAR FLOODPLAIN CALCULATIONS, INCLUDING
HYDROLOGIC CALCS, FOR ALL 100-YEAR LOCATIONS
(CURRENTLY MISSING SL-2 THROUGH SL-11).
011. REVISE THE 100-YEAR FLOODPLAIN CALCULATIONS TO REFLECT
THE ULTIMATE DEVELOPMENT SCENARIO ('C' VALUE) AS PER
THE APPROVED HARPERS MILL TENTATIVES (OR APPROVED LAND
USE MAP FOR OFF-SITE AREAS, AS NEEDED). THIS ALSO
APPLIES TO THE 100-YEAR CULVERT DESIGN FOR STRUCTURE
5-2. FURTHER DISCUSSION MAY BE HELPFUL.
012. IT APPEARS THAT FLOODPLAIN SECTIONS SL-11 AND SL-12
WILL EXCEED THE 200-ACRE MAXIMUM FOR USE OF THE
RATIONAL METHOD. PLEASE UTILIZE SCS FOR ANY LOCATION
WHICH HAS A DRAINAGE AREA GREATER THAN 200 ACRES.
013. IT APPEARS THAT THE 100-YEAR FLOODPLAIN CALCULATIONS
DO NOT INCORPORATE THE REQUIRED 1.25X SATURATION
FACTOR. PLEASE REVISE.
014. THE TWO FLOODPLAIN SECTIONS THAT WERE PROVIDED HAVE
BEEN MODELED WITH AN IRREGULAR CHANNEL SECTION TAKEN
AT A MANNINGS 'N' OF 0.030 FOR THE ENTIRE WIDTH, BUT
THIS VALUE WOULD ONLY BE ALLOWABLE FOR THE NARROW
BED/BANK SECTION, SHOULD IT APPLY. ANY OVERBANK AREAS
NEED TO BE MODELED WITH A SIGNIFICANTLY HIGHER
COEFFICIENT, LIKELY BETWEEN 0.065 AND 0.10, DEPENDING
ON FIELD CONDITIONS. NOTE THAT, IN THE MS-19
ANALYSES, THE NARROW BED/BANK CHANNEL SECTION WAS
TAKEN AT 0.045 IN LIEU OF 0.030, AS WELL. PLEASE
REVISE. FURTHER DISCUSSION MAY BE NEEDED.
015. COUNTY FLOODPLAIN ORDINANCE (SEC. 19-58E(1)) PROHIBITS
CLEARING/FILLING/GRADING WITHIN 100-YEAR FLOODPLAINS
IN THE UPPER SWIFT CREEK WATERSHED WHICH HAVE A
CONTRIBUTING DRAINAGE AREA OF 100 ACRES OR MORE, AND IT
APPEARS THAT THERE ARE SEVERAL AREAS ON SITE FOR WHICH
THIS IS THE CASE (E.G. SWM/BMP GRADING, LOTS 5-6).
PLEASE ADDRESS. FURTHER DISCUSSION MAY BE NEEDED.
016. REVISE THE INCREMENTAL DRAINAGE AREAS ON SHEET C4.1 TO
MATCH THE PROPOSED SITE GRADING AS SHOWN IN THESE
PLANS. FURTHER DISCUSSION MAY BE NEEDED.
017. INDICATE AND LABEL THE WOUS IMPACT AREAS IN THE
KENBROOK DRIVE AREA IN PLAN VIEW.
018. SPECIFY A 5:1 SWALE CENTERED OVER STRUCTURE 1-16 ON
SHEETS C3.0 AND C4.0.
019. PROVIDE A WRITTEN RESPONSE IN THE MARGIN OF A COPY OF
THESE REVIEW COMMENTS WITH YOUR NEXT PLAN SUBMITTAL.
DESIGN, DETAIL AND CALCULATIONS REQUIRED BY THE ABOVE
COMMENTS SHALL BE SUBJECT TO FURTHER REVIEW.
---- END OF ENV. ENG. COMMENTS ----
============================================================
============================================================
============================================================
============================================================
.
.
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : GUOPING TANG, P.E. (796-7103)
NAME OF PLAN : HARPERS MILL SOUTH PHASE - SECTION 3
SITE PLAN NO. : 16CP0061
LATEST PLAN DATE : 06/20/17
DEPT. REC'D DATE : 06/23/17
SUBMITTAL NUMBER : 3
REVIEW DATE : 07/06/17
RECOMMENDATION : REVISIONS REQUESTED
TABLE REVIEW : NO
.
-------- GENERAL NOTES --------
.
001. THE RESPONSIBILITY FOR COMPLIANCE WITH CHESTERFIELD
COUNTY STANDARDS AND POLICIES, AND WITH STATE AND
FEDERAL REGULATIONS WILL BE PLACED ON THE PROFESSIONAL
ENGINEER WHO SIGNS AND SEALS THE CONSTRUCTION PLANS
APPROVED.
.
002. THE RESPONSIBILITY FOR ACHIEVING AND MAINTAINING
SATISFACTORY LOT DRAINAGE WILL BE THAT OF THE DEVELOPER
UP THROUGH A PERIOD OF ONE YEAR AFTER STATE ACCEPTANCE
OF THE SUBDIVISION ROADS.
.
003. PLEASE GHOST THE SECTION LIMIT BEHIND LOTS 47-50 IN
SECTION 1 ON SHEET C1.0.
.
-------- EROSION CONTROL --------
.
004. PLEASE SPECIFY CHECK DAMS ALONG THE LONG DIVERSION DIKE
SOUTH OF HENNINGFORD ROAD TO SLOW DOWN FLOW ON SHEETS
C2.0 AND C2.1.
.
005. PRIOR TO A LAND DISTURBANCE PERMIT ISSUANCE:
.
A) CONSTRUCTION PLANS MUST RECEIVE FINAL PLANNING
DEPARTMENT APPROVAL.
.
B) THE ENVIRONMENTAL ENGINEERING DEPARTMENT SHALL
REQUIRE COPIES OF APPLICABLE CORRESPONDENCE FROM THE
U.S. ARMY CORPS OF ENGINEERS AND DEPARTMENT OF
ENVIRONMENTAL QUALITY SUCH THAT IT MAY BE DETERMINED
THAT ANY REQUIRED WETLANDS PERMITS HAVE BEEN
RECEIVED.
.
C) A COPY OF THE PROCESSED VSMP REGISTRATION AND FEE
FORM MUST BE RECEIVED BY ENVIRONMENTAL ENGINEERING.
.
D) AN EROSION CONTROL BOND MUST BE POSTED AND APPROVED.
.
E) COPIES OF THE ACTUAL VDOT LAND USE PERMIT(S) FOR THE
TIE-IN(S) TO VERNEHAM DRIVE (IF IN THE STATE
SYSTEM AT THE TIME OF LDP APPLICATION) MUST BE
PROVIDED TO ENVIRONMENTAL ENGINEERING.
.
F) FLAGGING AND/OR SAFETY FENCE AROUND USACOE
JURISDICTIONAL WETLANDS AND/OR OTHER ENVIRONMENTALLY
SENSITIVE AREAS MUST BE INSTALLED AND CLEARLY
VISIBLE. .
.
G) DB/PG FOR ANY TEMPORARY OFFSITE EASEMENTS MUST BE
PROVIDED TO ENVIRONMENTAL ENGINEERING PRIOR TO PLAT
RECORDATION.
.
H) PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO
CAROLE CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE
AUTOCAD FILE MUST BE SAVED AS A .DWG OR .DXF IN
AUTOCAD VERSION 2009 OR EARLIER AND REFERENCED
DIRECTLY TO THE VIRGINIA STATE PLANE COORDINATE
SYSTEM, SOUTH ZONE IN THE NAD83 DATUM. THE AUTOCAD
FILE MAY BE SUBMITTED ON A CD, DVD, OR VIA EMAIL
AND MUST BE CLEARLY LABELED WITH THE SUBDIVISION
NAME AND SECTION, SUBDIVISION PLAN NUMBER, THE
ENGINEERING FIRM AND THE CAD FILE PREPARER'S NAME
AND PHONE NUMBER. THE FILE MUST CONTAIN THE
FOLLOWING, EACH CLEARLY LABELED IN SEPARATE LAYERS:
.
1. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND,
.
2. EDGES OF SIDEWALKS.
.
I) PROVIDE A COPY OF THE SWPPP BOOKLET (THREE-RING
BINDER) TO ENVIRONMENTAL ENGINEERING.
.
006. PLEASE INCLUDE THE COST OF SEDIMENT TRAP AND USE AREA
OF DISTURBANCE OF 8.6 ACRE FOR FINE/GRADING/SEEDING/
MULCH FOR EC BOND ESTIMATE.
.
007. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND/OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR STATE
PERMITS IN RELATION TO ENVIRONMENTAL FEATURES
INCLUDING, BUT NOT LIMITED TO, WETLANDS, SURFACE WATER,
GROUND WATER, AND AIR QUALITY. FINAL APPROVAL OF THESE
PLANS WILL NOT RELIEVE YOU OF YOUR RESPONSIBILITIES.
.
-------------- CBPA ---------------
.
009. PLEASE WORK WITH US TO UPDATE THE CBPA TABLE BEFORE
SCHEDULING A TABLE REVIEW.
.
-------- ROAD AND DRAINAGE --------
.
011. PLEASE SEND A DOCUMENTATION SUPPORTING THAT THERE WAS
NO MINING ACTIVITIES IN THIS SECTION.
.
012. IN THE EVENT THAT SECTION 1 LOTS 41-45 ARE PRIVATELY
OWNED PRIOR TO CONSTRUCTION PLAN APPROVAL, SATISFACTORY
EVIDENCE OF ADJACENT PROPERTY OWNER NOTIFICATION FOR
THESE LOTS MUST BE RECEIVED PRIOR TO CONSTRUCTION PLAN
APPROVAL.
.
---- END OF ENV. ENG. COMMENTS ----
.
============================================================
============================================================