All Subdivision Review Comments for Case # 15CP0103




For VDOT’s comments please contact Virginia Department of Transportation at (804) 674-2814 or send e-mail to Boris.Solomonov@VDOT.Virginia.gov

For Tentative Subdivision resubmittals:

1. Please note that submittal fees include the original submittal and two (2) additional reviews.

2. A letter of transmittal is required to accompany each submittal.

3. Please verify that Environmental Engineering, Fire, CDOT, VDOT, and Planning have reviewed the submittal before resubmitting. A resubmittal tendered, prior to receiving all the required departments’ review, will be counted as an additional submittal. Go to Case Selection Form or Go to Project List


 
CASE NO: 15CP0103 STATUS: PENDING APPROVAL
PROJECT NAME: WESTERLEIGH SEC 10 - LAST INTERNET UPDATE: 11/22/17
SUBMITTAL TYPE: CONSTRUCTION PLAN
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 04 06/02/16 06/23/16 AMENDED* 06/23/16 RWB 748-1035
FIRE DEPT.--: 04 06/02/16 06/23/16 AMENDED* 06/02/16 JKL 748-1489
HOUSE NUMBER: 04 06/02/16 06/23/16 ******** ********
MAPPING/GIS-: 04 06/02/16 06/23/16 ******** ********
PLANNING----: 04 06/02/16 06/23/16 COMPLETE 06/21/16 SCP 751-4321
TRANSPORT.--: 04 06/02/16 06/23/16 COMPLETE 06/20/16 SES 751-4912
UTIL.PLAN.--: 04 06/02/16 06/23/16 ******** ********
UTILITIES---: 04 06/02/16 06/23/16 AMENDED* 06/07/16 WBV 748-1343
UTIL.R.O.W.-: 04 06/02/16 06/23/16 ******** ********
VDOT--------: 04 06/02/16 06/23/16 ******** ********
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME:WESTERLEIGH, SECTION 10
PLAN NUMBER: 15CP0103
ORIGINAL PLAN DATE: 4/30/15
REVIEW DATE: 5/28/15
LATEST SUBMISSION DATE: 5/18/15
SUBMITTAL NUMBER: 1
STATUS: REVISIONS REQUIRED
TABLE REVIEW: NO
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR THE
ABOVE REFERENCED PROJECT DATED APRIL 30, 2015,
WE MAKE THE FOLLOWING COMMENTS AND RECOMMENDATIONS:
1. A COPY OF VIRGINIA DEPARTMENT OF TRANSPORTATION'S
APPROVAL LETTER REGARDING PAVEMENT REPLACEMENT, METHOD
OF CROSSING, AND ALIGNMENT OF UTILITY WITH STATE RIGHT
OF WAY, AND A COPY OF ENVIRONMENTAL ENGINEERING'S
INITIAL REVIEW LETTER MUST BE SUBMITTED BEFORE REVISED
PLANS ARE SUBMITTED FOR RE-REVIEW.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION, A
COPY OF THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER
AND/OR ALL OTHER APPLICABLE LOCAL STATE AND FEDERAL
AGENCIES' APPROVAL LETTERS MUST BE RECEIVED BY THIS
DEPARTMENT. IN ADDITION, ALL EASEMENTS NOT INCLUDED
WITH THE SUBDIVISION PLAT MUST BE DEDICATED WITH A
SEPARATE PLAT AND AGREEMENT TO THE COUNTY PRIOR TO
RELEASING THE PROJECT TO THE CONSTRUCTION SECTION.
3. SHOW THE COUNTY PROJECT NUMBER 15-0155 ON THE LOWER
RIGHT HAND CORNER OF EACH SHEET.
4. REVISE THE ELEVATION SHOWN IN ITEM 22 UNDER
"STANDARD NOTES" TO 225' AND NOTE THIS CONDITION ON EACH
APPLICABLE LOT IN THE PLAN VIEWS.
5. RELOCATE THE WATER SERVICE FOR LOT #1 TO THE OTHER
PROPERTY CORNER.
6. LOTS #30 AND #31 DO NOT APPEAR TO NEED 1" WATER
SERVICES AS THE SERVICES ARE ?60 L.F. PLEASE EXAMINE
THOROUGHLY, REVISING AS NECESSARY.
7. CALL OUT ALL VALVES THAT ARE TO BE CLOSED DURING
EACH WATERLINE TIE-IN, LABELING EACH AS SUCH.
8. REVISE THE SLOPES OF MANHOLE #10 TO 11 AND #13 TO
14 TO 0.52%.
9. ALWAYS DRAW THE PLAN AND PROFILE VIEWS IN THE SAME
DIRECTION.
10. PROCEED AS FOLLOWS REGARDING THE SEWER FROM
EXISTING MANHOLE #7 TO PROPOSED MANHOLE #1:
A. PROVIDE THE DISTANCE, SLOPE, DIAMETER,
MATERIAL AND INVERT FOR THE EXISTING "STUB" SEWER.
B. PROVIDE THE TOTAL DISTANCE, SLOPE, DIAMETER
AND MATERIAL FOR THE ENTIRE RUN OF SEWER.
C. THOROUGHLY CHECK FOR SEWER SLOPE CALCULATION
ERRORS, REVISING AS NECESSARY.
11. THOROUGHLY EXAMINE ALL SHEETS TO CORRECT ALL
EXTRANEOUS MARKINGS, OVERLAPPING TEST, ILLEGIBLE TEXT
AND DRAWING FEATURES, ETC. IN ORDER TO FACILITATE A
CLEAN DRAWING WITH ALL TEXT AND DRAWING FEATURES
COMPLETELY LEGIBLE AND ABUNDANTLY VISIBLE.
12. REVISE THE "MATERIALS LIST" AS NECESSARY.
PLEASE MAKE ALL OF THE SUGGESTED CHANGES PREVIOUSLY
MENTIONED, AND SUBMIT TWO (2) SETS OF REVISED PLANS.
THE OWNER MUST ENTER INTO A COUNTY CONTRACT PRIOR TO THE
START OF CONSTRUCTION. PLEASE SEND ME A COPY OF THE
"ACCEPTED" BID PROPOSAL BETWEEN THE DEVELOPER AND THE
CONTRACTOR SO WE MAY PREPARE THE COUNTY CONTRACT. THE
BID PROPOSAL MUST BE BASED ON THE LATEST REVISED
UTILITIES PLANS REFLECTING THE REVIEWER'S STAMP, AND ALL
WORK MUST BE PERFORMED BY AN ACCEPTABLE UTILITIES
CONTRACTOR. IF PLANS ARE REVISED AFTER CONTRACT
PREPARATION DUE TO A CHANGE BECAUSE OF VIRGINIA
DEPARTMENT OF TRANSPORTATION'S AND/OR ENVIRONMENTAL
ENGINEERING DEPARTMENT'S APPROVAL OF THE ROAD, DRAINAGE,
AND EROSION CONTROL DESIGN OR BECAUSE OF STATE AGENCIES'
REVIEW AND APPROVAL OF THE UTILITIES DESIGN, A REVISED
BID PROPOSAL MAY BE NECESSARY TO ACCURATELY REFLECT THE
LATEST UTILITIES DESIGN AND A NEW CONTRACT PREPARATION
MAY BE NECESSARY AND EXECUTED PRIOR TO THE START OF
CONSTRUCTION.
IF YOU HAVE ANY QUESTIONS, DO NOT HESITATE TO CONTACT ME
AT 748-1343.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME:WESTERLEIGH, SECTION 10
PLAN NUMBER: 15CP0103
ORIGINAL PLAN DATE: 4/30/15
REVIEW DATE: 8/21/15
LATEST SUBMISSION DATE: 8/14/15
SUBMITTAL NUMBER: 2
STATUS: REVISIIONS REQUIRED
TABLE REVIEW: NO
IN REGARD TO YOUR SUBMITTAL OF UTILITIES PLANS FOR THE
ABOVE REFERENCED PROJECT DATED APRIL 30, 2015, WITH THE
LAST REVISION DATED AUGUST 11, 2015, WE MAKE THE
FOLLOWING COMMENTS AND RECOMMENDATIONS:
1. A COPY OF VIRGINIA DEPARTMENT OF TRANSPORTATION'S
APPROVAL LETTER REGARDING PAVEMENT REPLACEMENT, METHOD
OF CROSSING, AND ALIGNMENT OF UTILITY WITH STATE RIGHT
OF WAY, AND A COPY OF ENVIRONMENTAL ENGINEERING'S
INITIAL REVIEW LETTER MUST BE SUBMITTED BEFORE REVISED
PLANS ARE SUBMITTED FOR RE-REVIEW.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION, A
COPY OF THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER
AND/OR ALL OTHER APPLICABLE LOCAL STATE AND FEDERAL
AGENCIES' APPROVAL LETTERS MUST BE RECEIVED BY THIS
DEPARTMENT. IN ADDITION, ALL EASEMENTS NOT INCLUDED
WITH THE SUBDIVISION PLAT MUST BE DEDICATED WITH A
SEPARATE PLAT AND AGREEMENT TO THE COUNTY PRIOR TO
RELEASING THE PROJECT TO THE CONSTRUCTION SECTION.
3. PROVIDE THE DEED BOOK AND PAGE NUMBER OF THE
EXISTING SANITARY SEWER EASEMENT.
4. LABEL SECTION 11 IN THE PLAN VIEW.
5. LABEL THE EXISTING WATERLINE IN GLENSFORD DRIVE
WITH ITS COUNTY PROJECT NUMBER (I.E. 07-0047).
6. THERE APPEARS TO BE AN ERROR IN THE SANITARY SEWER
SLOPE CALCULATION BETWEEN EXISTING MANHOLE NUMBER 7 AND
PROPOSED MANHOLE NUMBER 1. EXAMINE THOROUGHLY REVISING
AS NECESSARY.
9. THOROUGHLY EXAMINE ALL SHEETS TO CORRECT ALL
EXTRANEOUS MARKINGS, OVERLAPPING TEST, ILLEGIBLE TEXT
AND DRAWING FEATURES, ETC. IN ORDER TO FACILITATE A
CLEAN DRAWING WITH ALL TEXT AND DRAWING FEATURES
COMPLETELY LEGIBLE AND ABUNDANTLY VISIBLE.
10. REVISE THE "MATERIALS LIST" AS NECESSARY.
PLEASE MAKE ALL OF THE SUGGESTED CHANGES PREVIOUSLY
MENTIONED, AND SUBMIT ONE (1) SET OF REVISED PLANS.
THE OWNER MUST ENTER INTO A COUNTY CONTRACT PRIOR TO THE
START OF CONSTRUCTION. PLEASE SEND ME A COPY OF THE
"ACCEPTED" BID PROPOSAL BETWEEN THE DEVELOPER AND THE
CONTRACTOR SO WE MAY PREPARE THE COUNTY CONTRACT. THE
BID PROPOSAL MUST BE BASED ON THE LATEST REVISED
UTILITIES PLANS REFLECTING THE REVIEWER'S STAMP, AND ALL
WORK MUST BE PERFORMED BY AN ACCEPTABLE UTILITIES
CONTRACTOR. IF PLANS ARE REVISED AFTER CONTRACT
PREPARATION DUE TO A CHANGE BECAUSE OF VIRGINIA
DEPARTMENT OF TRANSPORTATION'S AND/OR ENVIRONMENTAL
ENGINEERING DEPARTMENT'S APPROVAL OF THE ROAD, DRAINAGE,
AND EROSION CONTROL DESIGN OR BECAUSE OF STATE AGENCIES'
REVIEW AND APPROVAL OF THE UTILITIES DESIGN, A REVISED
BID PROPOSAL MAY BE NECESSARY TO ACCURATELY REFLECT THE
LATEST UTILITIES DESIGN AND A NEW CONTRACT PREPARATION
MAY BE NECESSARY AND EXECUTED PRIOR TO THE START OF
CONSTRUCTION.
IF YOU HAVE ANY QUESTIONS, DO NOT HESITATE TO CONTACT ME
AT 748-1343.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: WESTERLEIGH, SECTION 10
PLAN NUMBER: 15CP0103
ORIGINAL PLAN DATE: 4/30/15
REVIEW DATE: 9/29/15
LATEST SUBMISSION DATE: 9/22/15
SUBMITTAL NUMBER: 3
STATUS: APPROVED
TABLE REVIEW: NO
IN REGARD TO YOUR RECENT SUBMITTAL OF THE REVISED
UTILITIES PLANS ON THE ABOVE REFERENCED PROJECT DATED
APRIL 30, 2015, WITH THE LAST REVISION DATED SEPTEMBER 18, 2
REVIEWED BY THE UTILITIES DEPARTMENT WITH NO EXCEPTIONS
TAKEN. THIS REVIEW IS EFFECTIVE UNTIL SEPTEMBER 29, 2020.
PLEASE FORWARD TWO (2) ADDITIONAL SETS OF PLANS ONCE
ALL APPROVALS HAVE BEEN OBTAINED. IF, AFTER ALL OTHER
REVIEWS/APPROVALS HAVE BEEN MADE, THE UTILITY PLANS
REFLECT A LATER REVISION DATE THAN THE LAST REVISION NOTED
ABOVE, PLEASE SUBMIT TWO (2) NEW SETS OF UTILITY PLANS FOR
FURTHER REVIEW AND APPROVAL.
YOUR COOPERATION IS GREATLY APPRECIATED. PLEASE CALL ME
AT 748-1343 IF YOU HAVE ANY FURTHER QUESTIONS REGARDING
THIS MATTER.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: WESTERLEIGH, SECTION 10
PLAN NUMBER: 15CP0103
ORIGINAL PLAN DATE: 4/30/15
REVIEW DATE: 3/17/16
LATEST SUBMISSION DATE: 3/9/16
SUBMITTAL NUMBER: 4
STATUS: APPROVED
TABLE REVIEW: NO
IN REGARD TO YOUR RECENT SUBMITTAL OF THE REVISED
UTILITIES PLANS ON THE ABOVE REFERENCED PROJECT DATED
APRIL 30, 2015, WITH THE LAST REVISION DATED FEBRUARY 23,
2016, THIS IS TO INFORM YOU THAT THE PLANS HAVE BEEN
REVIEWED BY THE UTILITIES DEPARTMENT WITH NO EXCEPTIONS
TAKEN. THIS REVIEW IS EFFECTIVE UNTIL MARCH 17, 2021.
PLEASE FORWARD TWO (2) ADDITIONAL SETS OF PLANS ONCE
ALL APPROVALS HAVE BEEN OBTAINED. IF, AFTER ALL OTHER
REVIEWS/APPROVALS HAVE BEEN MADE, THE UTILITY PLANS
REFLECT A LATER REVISION DATE THAN THE LAST REVISION NOTED
ABOVE, PLEASE SUBMIT TWO (2) NEW SETS OF UTILITY PLANS FOR
FURTHER REVIEW AND APPROVAL.
YOUR COOPERATION IS GREATLY APPRECIATED. PLEASE CALL ME
AT 748-1343 IF YOU HAVE ANY FURTHER QUESTIONS REGARDING
THIS MATTER.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: WESTERLEIGH SECTION 10
PLAN NUMBER: 15CP0103
ORIGINAL PLAN DATE: 4/30/14
REVIEW DATE: 6/7/16
LATEST SUBMISSION DATE: 6/2/16
SUBMITTAL NUMBER: 5
STATUS: APPROVED
TABLE REVIEW: NO
IN REGARD TO YOUR RECENT SUBMITTAL OF THE REVISED
UTILITIES PLANS ON THE ABOVE REFERENCED PROJECT DATED
APRIL 30, 2015, WITH THE LAST REVISION DATED MAY 24, 2016,
THIS IS TO INFORM YOU THAT THE PLANS HAVE BEEN REVIEWED BY
THE UTILITIES DEPARTMENT WITH NO EXCEPTIONS TAKEN. THIS
REVIEW IS EFFECTIVE UNTIL JUNE 7, 2021.
PLEASE BE ADVISED THAT THE PLANS FOR THIS PROJECT WILL NOT
BE RELEASED TO THE CONSTRUCTION SECTION UNTIL SUCH TIME
COUNTY PROJECT NUMBER 15-0191, WESTERLEIGH, SECTION 11 IS
UNDER CONTRACT. IN ADDITION, TAKE ALL STEPS NECESSARY TO
PROVIDE COMPLETE AGREEMENT BETWEEN THESE TWO (2) SETS OF
PLANS.
PLEASE FORWARD TWO(2) ADDITIONAL SETS OF PLANS ONCE
ALL APPROVALS HAVE BEEN OBTAINED. IF, AFTER ALL OTHER
REVIEWS/APPROVALS HAVE BEEN MADE, THE UTILITY PLANS
REFLECT A LATER REVISION DATE THAN THE LAST REVISION NOTED
ABOVE, PLEASE SUBMIT ONE (1) NEW SET OF UTILITY PLANS FOR
FURTHER REVIEW AND APPROVAL.
YOUR COOPERATION IS GREATLY APPRECIATED. PLEASE CALL ME
AT 748-1343 IF YOU HAVE ANY FURTHER QUESTIONS REGARDING
THIS MATTER.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: WESTERLEIGH, SEC 10
CASE NUMBER: 15CP0103
LATEST PLAN DATE: 04/30/15
DEPT. REC'D. DATE: 05/15/15
SUBMITTAL NUMBER: ONE
REVIEW DATE: 06/02/15
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: WESTERLEIGH, SEC 10
CASE NUMBER: 15CP0103
LATEST PLAN DATE: 08/11/15
DEPT. REC'D. DATE: 08/17/15
SUBMITTAL NUMBER: TWO
REVIEW DATE: 09/03/15
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: WESTERLEIGH, SEC 10
CASE NUMBER: 15CP0103
LATEST PLAN DATE: 09/18/15
DEPT. REC'D. DATE: 09/21/15
SUBMITTAL NUMBER: THREE
REVIEW DATE: 10/05/15
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: WESTERLEIGH, SEC 10
CASE NUMBER: 15CP0103
LATEST PLAN DATE: 02/23/2016
DEPT. REC'D. DATE: 03/09/2016
SUBMITTAL NUMBER: FOUR
REVIEW DATE: 03/17/2016
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: WESTERLEIGH, SEC 10
CASE NUMBER: 15CP0103
LATEST PLAN DATE: 05/24/2016
DEPT. REC'D. DATE: 06/06/2016
SUBMITTAL NUMBER: FIVE
REVIEW DATE: 06/20/2016
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : AMY SOMERVELL / 751-4321
PLAN NAME : WESTERLEIGH SECTION 10
PLAN NUMBER : 15CP0103
ORIGINAL PLAN DATE : 4-30-15
REVIEW DATE : 6-9-15
LATEST SUBMISSION DATE : 5-7-15 ACCEPTED 5-14-15
SUBMITTAL NUMBER : 1
STATUS : CORRECTIONS REQUIRED
TABLE REVIEW : N
1.PROVIDE DIMENSION OF THE TREE CANOPY WHERE THEY ARE
PROVIDED ON INDIVIDUAL LOTS. THIS SHALL BE SHOWN ON THE LOT
LAYOUT AND FINAL PLAT.
2. DIMENSION ALL BUILDING ENVELOPES
3. LOT 22 MAY NOT MEET REQUIRED FRONT YARD SETBACK AT THE
FRONT BUILDING LINE - VERIFY
4. BOTH LOTS 22 AND 23 APPEAR TO HAVE INCORRECT BUILDING
ENVELOPES - VERIFY
5. PLACE CASE NUMBER 15CP0103 PN THE BOTTOM RIGHT HAND
CORNER OF ALL SHEET.
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : AMY SOMERVELL / 751-4321
PLAN NAME : WESTERLEIGH SECTION 10
PLAN NUMBER : 15CP0103
ORIGINAL PLAN DATE : 4-30-15
REVIEW DATE : 9-10-15
LATEST SUBMISSION DATE : 8-13-15
SUBMITTAL NUMBER : 2
STATUS : CORRECTIONS REQUIRED
TABLE REVIEW :
1. ACCORDING TO THE DIMINSIONS PLACED ON THE BUILDING
ENV'S FOR LOTS 5-7, 12-15, 20-22 & 30 ) IT DOES NOT
APPEAR THE MINIMUM LOTS WIDTH OF 90' IS BEING MET. REVISE
2.FOR CLARIFICATION, THE BUILDING ENVELOPES NEED TO REFLECT
THE MEASUREMENT FROM THE PROPERTY LINES TO THE PROPOSED
ENVELOPE NOT THE ENVELOPE ALONE DIMENSIONED.
3. WHERE THE TREE CANOPY IS PROPOSED WITHIN LOTS, SHOW THIS
AREA ON THE EC SHEETS AND PROVIDE A MEASUREMENT WITHIN THE
LOT BOUNDARY.
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : AMY SOMERVELL / 751-4321
PLAN NAME : WESTERLEIGH SECTION 10
PLAN NUMBER : 15CP0103
ORIGINAL PLAN DATE :
REVIEW DATE : 10-14-15
LATEST SUBMISSION DATE :
SUBMITTAL NUMBER : 3
STATUS : APPROVED WITH NOTES
TABLE REVIEW
NOTES:
1. ON THE FINAL PLAT, CONSIDER REMOVING THE BUILDING
ENVELOPES THAT ONLY REFLECT THE TYPICAL SETBACKS.
2. ON THE FINAL PLAT, THE LOTS THAT REQUIRE A FRONT
BUILDING LINE TO ACHIEVE LOT WIDTH, SHALL SHOW THE
MEASUREMENTS PARALLEL TO THE SIDE PROPERTY LINES TO THE
FRONT BUILDING LINE (WHEN THE MEASUREMENT IS GREATER THAN
THE REQUIRED SETBACK)
________________________________________________________
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE # : STEVE PRUSIK/ 751-4321
PLAN NAME: WESTERLEIGH SECT. 10
PLAN NUMBER: 15CP0103
ORIGINAL PLAN DATE: 04/30/15
REVIEW DATE: 03/29/16
LATEST SUBMISSION DATE: 02/23/16
SUBMITTAL NUMBER: 4
STATUS: APPROVED
TABLE REVIEW: YES
COMMENTS:
1. THE SITE PLAN IS APPROVED AS SUBMITTED
NOTES:
1) ANY CHANGE IN THE CURRENT PLAN,
WHETHER IT STEMS FROM DEPARTMENT
COMMENTS OR AN ENGINEERING CHANGE
REQUESTED BY THE APPLICANT, MAY
GENERATE ADDITIONAL COMMENTS FROM
THE REVIEWING DEPARTMENTS,
RESULTING IN REQUIRED REVISIONS.
2) COMPLIANCE WITH SEC. 17-76 MUST BE
MAINTAINED AT ALL TIMES.
3) ANY ROAD AND LOT CONFIGURATIONS
OUTSIDE THE LIMITS OF THE SECTION 1
CONSTRUCTION PLANS ARE NOT INCLUDED
IN THIS REVIEW.
4) ANY BULK REQUIREMENTS (LOT AREA,
LOT WIDTH, SETBACKS, BUILDING
ENVELOPES, ETC.) SHOWN ON THE
APPROVED CONSTRUCTION PLANS WILL BE
SUBJECT TO REVIEW FOR COMPLIANCE AT
TIME OF FINAL CHECK.
GENERATE ADDITIONAL COMMENTS FROM
THE REVIEWING DEPARTMENTS, ********************************
RESULTING IN REQUIRED REVISIONS.
END OF COMMENTS.
************************************************************
REVIEW DEPARTMENT: PLANNING
REVIEWER / PHONE #: STEVE PRUSIK/ 751-4321
PLAN NAME: WESTERLEIGH SECT. 10
PLAN NUMBER: 15CP0103
ORIGINAL PLAN DATE: 04/30/15
REVIEW DATE: 06/22/16
LATEST SUBMISSION DATE: 02/23/16
SUBMITTAL NUMBER: 5
STATUS: APPROVED
TABLE REVIEW:
COMMENTS:
NOTES:
1) ANY CHANGE IN THE CURRENT PLAN,
WHETHER IT STEMS FROM DEPARTMENT
COMMENTS OR AN ENGINEERING CHANGE
REQUESTED BY THE APPLICANT, MAY
GENERATE ADDITIONAL COMMENTS FROM
THE REVIEWING DEPARTMENTS,
RESULTING IN REQUIRED REVISIONS.
2) COMPLIANCE WITH SEC. 17-76 MUST BE
MAINTAINED AT ALL TIMES.
3) ANY ROAD AND LOT CONFIGURATIONS
OUTSIDE THE LIMITS OF THE SECTION 10
CONSTRUCTION PLANS ARE NOT INCLUDED
IN THIS REVIEW.
4) ANY BULK REQUIREMENTS (LOT AREA,
LOT WIDTH, SETBACKS, BUILDING
ENVELOPES, ETC.) SHOWN ON THE
APPROVED CONSTRUCTION PLANS WILL BE
SUBJECT TO REVIEW FOR COMPLIANCE AT
TIME OF FINAL CHECK.
************************************************************
END OF COMMENTS
REVIEW DEPARTMENT : FIRE DEPARTMENT
REVIEWER / PHONE # : KIM LESTER / 804-748-1489
PLAN NAME : WESTERLEIGH SECT. 10
PLAN NUMBER : 15CP0103
PLAN RECEIVED DATE : 5/18/15
LATEST REVISION DATE: 4/30/15
REVIEW DATE : 5/20/15
SUBMITTAL NUMBER : 1ST REVIEW
STATUS : NOT APPROVED
TABLE REVEW : YES
PROVIDE A COMPUTER GENERATED WATER FLOW TEST DATA,
ALONG WITH THE NODE MAP THAT IS PROVIDED BY THE
CHESTERFIELD COUNTY UTILITIES DEPARTMENT, VERIFYING
THE REQUIRED WATER FLOW FOR FIRE PROTECTION IS AVAILABLE
AT THE SITE THE WATER FLOW TEST RESULTS AND GRAPH SHALL
BE SHOWN ON THE SUBMITTED PLAN. IFC 2012, SECTION B105.1
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT : FIRE DEPARTMENT
REVIEWER / PHONE # : KIM LESTER / 804-748-1489
PLAN NAME : WESTERLEIGH SECT. 10
PLAN NUMBER : 15CP0103
PLAN RECEIVED DATE : 8/17/15
LATEST REVISION DATE: 8/11/15
REVIEW DATE : 8/17/15
SUBMITTAL NUMBER : 2ND REVIEW
STATUS : APPROVED
TABLE REVEW : YES
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT : FIRE DEPARTMENT
REVIEWER / PHONE # : KIM LESTER / 804-748-1489
PLAN NAME : WESTERLEIGH SECT. 10
PLAN NUMBER : 15CP0103
PLAN RECEIVED DATE : 9/22/15
LATEST REVISION DATE: 9/18/15
REVIEW DATE : 10/7/15
SUBMITTAL NUMBER : 3RD REVIEW
STATUS : APPROVED
TABLE REVEW : YES
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT : FIRE DEPARTMENT
REVIEWER / PHONE # : KIM LESTER / 804-748-1489
PLAN NAME : WESTERLEIGH SECT. 10
PLAN NUMBER : 15CP0103
PLAN RECEIVED DATE : 3/14/16
LATEST REVISION DATE: 2/23/16
REVIEW DATE : 3/15/16
SUBMITTAL NUMBER : 4TH REVIEW
STATUS : APPROVED
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT : FIRE DEPARTMENT
REVIEWER / PHONE # : KIM LESTER / 804-748-1489
PLAN NAME : WESTERLEIGH SECT. 10
PLAN NUMBER : 15CP0103
PLAN RECEIVED DATE : 6/2/16
LATEST REVISION DATE: 5/24/16
REVIEW DATE : 6/2/16
SUBMITTAL NUMBER : 5TH REVIEW
STATUS : APPROVED
TABLE REVEW : YES
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
MR. TODD CHALMERS, P.E.
BALZER AND ASSOCIATES, INC.
15871 CITY VIEW DRIVE, SUITE 200
MIDLOTHIAN, VA 23113
SUBJECT:
WESTERLEIGH SECTION 10
ENVIRONMENTAL ENGINEERING PLAN REVIEW
DEAR MR. CHALMERS:
REVIEW OF THE ABOVE REFERENCED PLANS ACCEPTED BY THE COUNTY
ON MAY 14, 2015 HAS BEEN COMPLETED. CHRIS SOLDAN WITH
ARCADIS, INC. (ARCADIS) PROVIDED THE REVIEW OF THE PLANS AS
AN AGENT FOR CHESTERFIELD COUNTY, DEPARTMENT OF
ENVIRONMENTAL ENGINEERING (EE). RESPONSIBILITY FOR
COMPLIANCE WITH CHESTERFIELD COUNTY STANDARDS AND POLICIES
AND STATE AND FEDERAL REGULATIONS WILL BE PLACED ON THE
PROFESSIONAL ENGINEER WHO SIGNS AND SEALS THE CONSTRUCTION
PLANS APPROVED. WE OFFER THE FOLLOWING COMMENTS:
GENERAL
1. AS A PREREQUISITE TO THE ISSUANCE OF A LAND DISTURBANCE
PERMIT:
A. A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD FILE
MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD VERSION 2009 OR
EARLIER AND REFERENCED DIRECTLY TO THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83 DATUM. THE
AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD, OR VIA EMAIL AND
MUST BE CLEARLY LABELED WITH THE SUBDIVISION NAME AND
SECTION, SUBDIVISION PLAN NUMBER, ENGINEERING FIRM AND CAD
FILE PREPARER'S NAME AND PHONE NUMBER. THE FILE MUST
CONTAIN THE FOLLOWING, EACH CLEARLY LABELED IN SEPARATE
LAYERS:
I. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
II. EDGES OF SIDEWALKS
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING PRIOR
TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
B. FLAGGING AROUND USACOE JURISDICTIONAL WETLANDS, BUFFERS,
AND SENSITIVE AREAS MUST BE VISIBLE.
C. DOCUMENTATION FROM THE USACOE/DEQ MUST BE RECEIVED
VERIFYING COMPLIANCE TO WETLAND PERMIT REGULATIONS
D. A VSMP REGISTRATION AND FEE FORM MUST BE PROCESSED AND/OR
RECEIVED.
E. THE LIMITS OF THE RPA MUST BE FLAGGED IN THE FIELD
(SURVEY LOCATED) WITH OPTIC ORANGE SAFETY FENCE PRIOR TO
ISSUANCE OF A LAND DISTURBANCE PERMIT.
F. A COPY OF VDOT LAND USE PERMIT MUST BE RECEIVED, IF
APPLICABLE.
G. AN EROSION CONTROL BOND MUST BE POSTED.
H. TWO ADDITIONAL SETS OF CONSTRUCTION PLANS TO BE STAMPED
"APPROVED FOR CONSTRUCTION" MUST BE RECEIVED.
I. THE ENVIRONMENTAL ENGINEERING DEPARTMENT MUST HAVE
RECEIVED SIGNED, WRITTEN NOTIFICATIONS FROM THE ADJACENT
PROPERTY OWNERS, N/F MARONEY, N/F MARSHALECK, AND N/F
BURLOCK WHICH SHOULD BE SENT U.S. POSTAL CERTIFIED MAIL,
RETURN RECEIPT REQUESTED. INCLUDE AN 8½ X11 COPY OF THE
PROPOSED CONSTRUCTION ACTIVITY ADJACENT TO THEIR PROPERTIES.
2. AS A PREREQUISITE TO SUBDIVISION PLAT RECORDATION:
A. A $100/LOT BMP MAINTENANCE FEE MUST BE RECEIVED.
3. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY WITH
AND/OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR STATE PERMITS
IN RELATION TO ENVIRONMENTAL FEATURES INCLUDING, BUT NOT
LIMITED TO, WETLANDS, SURFACE WATER, GROUND WATER, AND AIR
QUALITY. FINAL APPROVAL OF THESE PLANS WILL NOT RELIEVE YOU
OF YOUR RESPONSIBILITIES.
-----SUBDIVISION PLAN FORMAT/DESIGN-----
1. SHEET 1: INCLUDE DB 8052-860 REFERENCE FOR REGIONAL BMP
IN CBPA COMPLIANCE NOTE.
2. SHEET 1: INCLUDE IN THE LEGEND THE LINE TYPES FOR
PROPOSED WATER LINE, WATER METERS, STREAM, WETLANDS, AND
FLOODPLAIN AS SHOWN IN THE PLANS.
3. SHEET 2: PROVIDE RECORDED LOT INFO FOR ADJACENT PARCELS
FROM WESTERLEIGH SECTION 3 AND SUMMER LAKE SECTION 9
INCLUDING PROPERTY OWNER'S NAMES. LABEL THE SUMMER LAKE
DEVELOPMENT TO THE WEST AS "FUTURE DEVELOPMENT". REVISE ALL
PLAN VIEWS AS APPLICABLE.
4. SHEET 2: PROPERTY LINES SHOWN FOR THE SUMMER LAKE
SECTION 9 PARCELS TO THE NORTHEAST OF LOT 25 VARY DO NOT
EXACTLY MATCH THE RECORDED LOT LINES. REVISE ALL PLAN VIEWS
AS APPLICABLE.
5. SHEET 2: SHOW THE RECORDED RPA AND 100 YEAR FLOOD PLAIN
WITH BW = 231.1 ON THE SUMMER LAKE SECTION 9 PARCELS TO THE
NORTHEAST OF LOT 25. REVISE ALL PLAN VIEWS AS APPLICABLE.
6. SHEET 3: LABEL GLENSFORD DRIVE AS SR 7764
7. SHEET 3: INDICATE LOCATION AND DESCRIPTION OF ALL
BENCHMARKS AND THEIR ELEVATION REFERENCED TO MEAN SEA LEVEL.
AT LEAST ONE BENCHMARK MUST BE SHOW WITHIN THE LIMITS OF THE
SUBDIVISION SECTION.
8. SHEET 3: LABEL ALL WETLANDS/WOUS.
9. SHEET 3: PROVIDE "25' DIMENSION" ON THE BUILDING SETBACK
LINE FROM THE WETLAND AREAS.
10. SHEET 3: SHOW STATIONING ON PIPES AND DITCHES WHICH ARE
LOCATED OUTSIDE OF THE STATIONED ROAD AREAS. THIS
STATIONING SHOULD MATCH THE STATIONING ON THE PROFILES ON
SHEETS 4 AND 5.
11. SHEET 3: ADD THE " 10' " DIMENSION TO THE EX. TCE LABEL
AT GLENSFORD DRIVE.
12. SHEET 3: PROVIDE 10' TEMP CONSTRUCTION EASEMENT ALONG
THE SOUTHEASTERN EDGE OF LOT 28 FOR FUTURE EXTENSION OF OLD
WESTRIDGE DRIVE.
13. SHEET 3: LABEL OF ELLERBY DRIVE AND OLD WESTRIDGE DRIVE
INTERSECTION SHOULD READ 18+08.63 "= 17+08.56" AND NOT "=
10+00.00".
14. SHEET 3: PROVIDE A DI-6 INLET WITH 2' GUTTER FOR
STRUCTURES 13 AND 21 INSTEAD OF A 48" MH. ADD DETAIL OF
DI-6 TO SHEET 13.
15. SHEET 5: OPEN CHANNEL SLOPES < 0.75% SHALL BE PAVED.
A. SUGGEST REVISING THE GRADING FOR SWALES ON LOTS 31 AND 32
DITCHES TO BRING UP TO 0.75% THEN FLATTEN TO SHEET FLOW INTO
WETLANDS.
B. SEE MS-19 COMMENTS BELOW FOR SHEET 11 ON POINT DISCHARGE
OF SWALE ON LOT 7.
C. SEE MS-19 COMMENTS BELOW FOR SHEET 11 ON REAR DITCHES
LOTS 18-20 SHOULD BE REMOVED.
16. SHEET 5: STRUCTURE 34 IS LABELED AS 12" IN PROFILE, BUT
15" IN TABLE ON SHEET 3. SEE MS-19 COMMENTS BELOW FOR SHEET
11 ON WHETHER STRUCTURE 34 SHOULD BE REVISED.
17. SHEET 5: SHOW EXISTING/PROPOSED PROFILES 300 FEET BEYOND
CONSTRUCTION LIMITS OF ROADS THAT STUB INTO FUTURE SECTIONS.
OLD WESTRIDGE DRIVE PROFILE ONLY SHOWS 200' BEYOND.
-----EROSION AND SEDIMENT CONTROL-----
19. SHEET 1: UPDATE EROSION CONTROL QUANTITIES TO INCLUDE
UTILITY STREAM CROSSING (USC) AND TEMPORARY SLOPE DRAIN
(TSD). REVISE SECOND LISTING OF DIVERSION DIKE TO
RIGHT-OF-WAY DIVERSION (RWD). CONFIRM WHETHER TREE
PROTECTION TAPE SHOULD BE TREE PROTECTION "FENCE". REVISE
ANY QUANTITIES THAT CHANGE DUE TO OTHER REVIEW COMMENTS.
20. SHEET 3: LOCATE STRUCTURES 1 AND 4 (SPECIAL END
TREATMENT DI-7 MOD) WITHIN OPEN SPACES RATHER THAN WITHIN
THE LOTS. FURTHER DISCUSSION MAY BE HELPFUL.
21. SHEET 6: ON PHASE 1 PLAN TURN OFF FLOW PHASE 2 FLOW
ARROWS THAT CONFLICT WITH EXISTING CONTOURS. FOR EXAMPLE IN
THE CUL-DE-SAC OF OLD WESTRIDGE DRIVE.
22. SHEET 6: SEDIMENT TRAP 3 ON LOT 31 INCORRECTLY LABELED
AS ST2.
23. SHEET 6: PLEASE CONFIRM THE INTENT OF THE XXXXXX LABEL
AT EACH ROAD INTERSECTION.
24. SHEET 6: PLEASE CONFIRM THE MAXIMUM DRAINAGE AREA TO THE
TEMPORARY SLOPE DRAIN. STD. AND SPEC 3.15 LIMITS A 12"
SLOPE DRAIN TO 0.5 ACRES. THE OUTLET OF A TSD MUST ALSO BE
PROTECTED FROM EROSION AS SET FORTH IN STD. AND SPEC 3.18,
OUTLET PROTECTION. PROVIDE A DETAIL FOR THE TEMPORARY
SLOPE DRAIN ON SHEET 9.
25. SHEET 6: PHASE I NARRATIVE NOTE 7A CALLS FOR OUTLET
PROTECTION ON STRUCTURE 34. PROVIDE A CALLOUT FOR OP ON THE
PLANS AND PROVIDE APRON DIMENSIONS WITH ASSOCIATED RIPRAP
SIZING/DEPTH. SEE MS-19 COMMENTS BELOW FOR SHEET 11 ON
WHETHER STRUCTURE 34 SHOULD BE REVISED.
26. SHEET 6/7: COORDINATE NOTE ON SHEET 6 STATING "SILT
FENCE ADJACENT TO WETLANDS SHALL REMAIN IN PLACE THROUGH
SUBDIVISION BUILD OUT" AND NOTE 18 ON SHEET 7 STATING "UPON
COMPLETION OF THE PROJECT… ALL SILT FENCES ARE TO BE REMOVED
FROM THE SITE"
27. SHEET 7: NOTE REFERENCES A SOILS MAP "BELOW AND
DESCRIPTIONS TO THE LEFT" HOWEVER THE MAP IS LOCATED ON
SHEET 6 HOWEVER THE DESCRIPTIONS ARE MISSING.
28. SHEET 7: PHASE II NARRATIVE NOTE 6: ADD LANGUAGE
SIMILAR TO NOTE 7B FROM SHEET 6 ABOUT FAVORABLE WEATHER
FORECASTS FOR INSTALLATION OF SANITARY SEWER WITH UTILITY
STREAM CROSSINGS.
29. SHEET 7: PHASE II NARRATIVE NOTE 7 REFERENCES REMOVAL
OF TEMPORARY CULVERT #1. PROVIDE CLARIFICATION ON THIS ITEM
AS INSTALLATION OF THE CULVERT IS NOT DISCUSSED IN THE
PREVIOUS NARRATIVE. DOES THIS REFER TO THE TEMPORARY SLOPE
DRAIN?
30. SHEET 7: PROVIDE SSF INSTEAD OF SF AT THE END OF
DITCHES OR DISCHARGE POINTS NEAR THE WETLANDS AT LOTS 26,
31, AND 32/33.
31. SHEET 7: SAFETY FENCE SAF IS SHOWN IN THE LEGEND AND A
DETAIL PROVIDED ON SHEET 9 HOWEVER IT IS NOT CALLED OUT ON
THE PLANS OR NARRATIVE. SAFETY FENCE SHOULD SURROUND ALL
SEDIMENT TRAPS. PLEASE REVISE EC PLANS ACCORDINGLY.
32. SHEET 8: REVISE MINIMUM STANDARD 1 AND 3.31 TEMPORARY
SEEDING NOTE TO "AREAS THAT WILL NOT BE BROUGHT TO FINAL
GRADE FOR 14 DAYS" NOT 30 DAYS.
33. SHEET 8: EROSION CONTROL NARRATIVE
A. CONFIRM #1 WHETHER SPRING 2015 AND FALL 2015 IS STILL
ANTICIPATED CONSTRUCTION TIMELINE.
B. CONFIRM # 3 ADJACENT AREAS. FOR EXAMPLE, THE EXISTING
WESTERLEIGH SECTION 3 DEVELOPMENT LIES TO THE SOUTH, NOT
UNDEVELOPED WOODS.
C. REVISE # 5 TO UPDATE LOCATION OF SOIL DESCRIPTIONS.
D. REVISE #8 TO PROVIDE EROSION CONTROL BLANKETS ON SLOPES
3:1 OR STEEPER, NOT 2:1.
34. SHEET 9: PROVIDE A DETAIL FOR THE EC-2 LINING
STABILIZATION OF CRITICAL AREAS AS DESCRIBED IN MANAGEMENT
STRATEGY C.
35. SHEET 9: PROVIDE A DETAIL FOR THE TEMPORARY SLOPE
DRAIN.
36. SHEET 9: TEMPORARY CULVERT CROSSING DETAIL IS SHOWN BUT
IS NOT CALLED OUT ON THE PLANS NARRATIVE. PLEASE CONFIRM
WHETHER IT WILL BE USED ON THIS PROJECT.
37. SHEET 10: REVISE BMP SERVICE AREA TO "WESTERLEIGH
OVERALL" INSTEAD OF SECTION 6.
38. SHEET 11: MS-19 COMPLIANCE: A PORTION OF THE DRAINAGE
WAY ALONG THE FUTURE SUMMER LAKE DEVELOPMENT TO THE WEST OF
THE PROJECT IS ENCUMBERED BY A JURISDICTIONAL FEATURE BUT
NOT A 100 YEAR FLOOD PLAIN. THE TOPO AND CROSS SECTION DOES
NOT CLEARLY SHOW AN ADEQUATE BED/BANK CHANNEL. AREA DOES
NOT MEET THE 1% RULE. PROFILES ON SHEET 5 LABEL CHANNEL AS
WUS. PLEASE CONFIRM WHETHER THIS IS A JURISDICTIONAL
FEATURE.
A. MS-19 #3: IT DOES NOT APPEAR AN ADEQUATE BED/BANK CHANNEL
EXISTS BELOW THE DI-7/STRUCTURE 4. HOW DO YOU INTEND TO
SATISFY MS-19 - SITUATION L MAY APPLY. FURTHER DISCUSSION
MAY BE HELPFUL.
B. DITCH BETWEEN LOTS 7/12 APPEARS TO CREATE A POINT SOURCE
DISCHARGE WITHOUT AN ADEQUATE RECEIVING CHANNEL, PLEASE
ADDRESS. ADD AS MS-19 POINT #5.
39. SHEET 11: MS-19 #4 COMPLIANCE: IDA DOES NOT ACCOUNT FOR
THE ADDITIONAL DRAINAGE FROM ADDITIONAL LOTS THROUGH
STRUCTURE 34. RECEIVING CHANNEL IN SUMMER LAKE IS NOT
ADEQUATE.
A. SUGGEST LOWERING CUL-DE-SAC TO ELEVATION 251, FILLING
FRONT OF LOTS 18/19 TO SHEET FLOW INTO RIGHT-OF-WAY.
B. SUGGEST REMOVING STRUCTURE 34
C. DITCH AND DRAINAGE EASEMENT ALONG REAR OF LOTS 18-20 MAY
NOT BE NECESSARY FOR SURFACE FLOW.
D. SUGGEST SHOWING BUILDING PAD AT ELEVATION 251 ON LOT 24
DIRECTING HOUSE DRAINAGE TOWARDS RIGHT-OF-WAY.
E. REVISE ALL HYDROLOGIC/HYDRAULIC CALCULATIONS AS
APPLICABLE.
40. SHEET 11/12: CONSIDER GREY-SCALING DRAINAGE AREAS
OUTSIDE OF THE WESTERLEIGH SECTION 10 DEVELOPMENT.
41. SHEET 13: PROVIDE DETAIL FOR DI-6 INLET WITH 2' GUTTER.
42. SHEET 14 (POLLUTION PREVENTION PLAN): REVISE REFERENCES
TO DEPARTMENT OF PUBLIC WORKS TO "DEPARTMENT OF
ENVIRONMENTAL ENGINEERING" UNDER THE LEAKS, SPILLS, AND
OTHER RELEASES SECTION.
-----STORMWATER COMPUTATIONS-----
43. HYDRAULIC GRADE LINE CALCULATIONS: STRUCTURE 27 [31]
USES THE 0.5HT VALUE FOR INLET SHAPING HOWEVER THE TABLE ON
SHEET 3 DOES NOT LIST IS-1 FOR THIS STRUCTURE.
44. STRUCTURE P1 CULVERT CALCULATIONS: CONFIRM THIS CULVERT
WILL BE INSTALLED DURING CONSTRUCTION OF THE FUTURE SECTION
11 WORK AND NOT PART OF THE SECTION 10 DEVELOPMENT.
45. STRUCTURE 31 TOP ELEVATION APPEARS TO BE INCORRECT ON
BOTH THE HYDRAULIC GRADE LINE CALCULATIONS AND THE STRUCTURE
TABLE ON SHEET 3. PLEASE ADDRESS.
46. A SATURATION FACTOR OF 1.25 SHOULD BE APPLIED TO THE
RUNOFF COEFFICIENTS FOR THE 100 YEAR STORM CALCULATIONS.
PLEASE REVISE AS APPLICABLE.
47. DITCH AND SWALE CALCULATIONS:
A. THE DITCHES CALCULATION SHEET INDICATES 3:1 SIDE SLOPES
WHILE SHEET 3 OF THE PLANS INDICATE 5:1. PLEASE CONFIRM
WHICH IS CORRECT.
B. THE CALCULATION SHEETS INDICATE DESIGN AND VELOCITIES FOR
10 YEAR STORM WHILE SHEET 3 OF THE PLANS INDICATES A V2
VELOCITY. PLEASE CONFIRM WHICH IS CORRECT.
48. CLEARLY INDICATE AND LABEL THE FLOW PATHS ON PLAN SHEETS
11 AND 12 FOR TIME OF CONCENTRATION CALCULATIONS - SHEET
FLOW, SHALLOW CONCENTRATED FLOW, AND CHANNEL FLOW AS
APPLICABLE.
49. HOW HAS THE 10 YEAR PRE VS. 10 YEAR POST FLOOD
PROTECTION BEEN ADDRESSED AS STRUCTURE 4?
50. PLEASE SUBMIT AN ITEMIZED COST ESTIMATE FOR REVIEW
AND/OR APPROVAL OF THE EROSION CONTROL BOND AMOUNT.
SINCERELY,
ARCADIS U.S., INC.
CHRIS SOLDAN, P.E.
PROJECT ENVIRONMENTAL ENGINEER
COPIES:
ROBERT BOSWELL - ENVIRONMENTAL ENGINEERING
AMY SUMMERVILLE - PLANNING
-----END OF ENV ENG COMMENTS-----
DEAR MR. CHALMERS:
REVIEW OF THE ABOVE REFERENCED PLANS ACCEPTED BY THE COUNTY
ON AUG. 13, 2015 HAS BEEN COMPLETED. CHRIS SOLDAN WITH
ARCADIS, INC. (ARCADIS) PROVIDED THE REVIEW OF THE PLANS AS
AN AGENT FOR CHESTERFIELD COUNTY, DEPARTMENT OF
ENVIRONMENTAL ENGINEERING (EE). RESPONSIBILITY FOR
COMPLIANCE WITH CHESTERFIELD COUNTY STANDARDS AND POLICIES
AND STATE AND FEDERAL REGULATIONS WILL BE PLACED ON THE
PROFESSIONAL ENGINEER WHO SIGNS AND SEALS THE CONSTRUCTION
PLANS APPROVED. WE OFFER THE FOLLOWING COMMENTS:
GENERAL
1. AS A PREREQUISITE TO THE ISSUANCE OF A LAND DISTURBANCE
PERMIT:
A. A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD FILE
MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD VERSION 2009 OR
EARLIER AND REFERENCED DIRECTLY TO THE VIRGINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE IN THE NAD83 DATUM. THE
AUTOCAD FILE MAY BE SUBMITTED ON A CD, DVD, OR VIA EMAIL AND
MUST BE CLEARLY LABELED WITH THE SUBDIVISION NAME AND
SECTION, SUBDIVISION PLAN NUMBER, ENGINEERING FIRM AND CAD
FILE PREPARER'S NAME AND PHONE NUMBER. THE FILE MUST
CONTAIN THE FOLLOWING, EACH CLEARLY LABELED IN SEPARATE
LAYERS:
I. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
II. EDGES OF SIDEWALKS
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING PRIOR
TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
B. FLAGGING AROUND USACOE JURISDICTIONAL WETLANDS, BUFFERS,
AND SENSITIVE AREAS MUST BE VISIBLE.
C. DOCUMENTATION FROM THE USACOE/DEQ MUST BE RECEIVED
VERIFYING COMPLIANCE TO WETLAND PERMIT REGULATIONS
D. A VSMP REGISTRATION AND FEE FORM MUST BE PROCESSED AND/OR
RECEIVED.
E. THE LIMITS OF THE RPA MUST BE FLAGGED IN THE FIELD
(SURVEY LOCATED) WITH OPTIC ORANGE SAFETY FENCE PRIOR TO
ISSUANCE OF A LAND DISTURBANCE PERMIT.
F. A COPY OF VDOT LAND USE PERMIT MUST BE RECEIVED, IF
APPLICABLE.
G. AN EROSION CONTROL BOND MUST BE POSTED.
H. TWO ADDITIONAL SETS OF CONSTRUCTION PLANS TO BE STAMPED
"APPROVED FOR CONSTRUCTION" MUST BE RECEIVED.
I. THE ENVIRONMENTAL ENGINEERING DEPARTMENT MUST HAVE
RECEIVED SIGNED, WRITTEN NOTIFICATIONS FROM THE ADJACENT
PROPERTY OWNERS, N/F MARONEY, N/F MARSHALECK, AND N/F
BURLOCK WHICH SHOULD BE SENT U.S. POSTAL CERTIFIED MAIL,
RETURN RECEIPT REQUESTED. INCLUDE AN 8½ X11 COPY OF THE
PROPOSED CONSTRUCTION ACTIVITY ADJACENT TO THEIR PROPERTIES.
2. AS A PREREQUISITE TO SUBDIVISION PLAT RECORDATION:
A. A $100/LOT BMP MAINTENANCE FEE MUST BE RECEIVED.
3. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY WITH
AND/OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR STATE PERMITS
IN RELATION TO ENVIRONMENTAL FEATURES INCLUDING, BUT NOT
LIMITED TO, WETLANDS, SURFACE WATER, GROUND WATER, AND AIR
QUALITY. FINAL APPROVAL OF THESE PLANS WILL NOT RELIEVE YOU
OF YOUR RESPONSIBILITIES.
SUBDIVISION PLAN FORMAT/DESIGN
4. SHEET 3: PROVIDE "25' DIMENSION" ON THE BUILDING SETBACK
LINE FROM THE WETLAND AREAS. THE DIMENSION LEADER/LABEL
CLEARLY SHOWS WHICH FEATURE THE BSL IS APPLIED TO.
5. SHEET 3: ADD THE "10' DIMENSION" TO THE EX. TCE LABEL AT
GLENSFORD DRIVE.
6. SHEET 3: ADD THE "10' DIMENSION" TO THE PROPOSED TCE
ALONG THE SOUTHEASTERN EDGE OF LOT 28 FOR FUTURE EXTENSION
OF OLD WESTRIDGE DRIVE.
7. SHEET 3: AS PREVIOUSLY REQUESTED, PROVIDE A DI-6 INLET
WITH 2' GUTTER FOR STRUCTURES 9 AND 17 INSTEAD OF A 48" MH.
ADD DETAIL OF DI-6 TO SHEET 13.
8. SHEET 3: LOCATE STRUCTURES 1 (SPECIAL END TREATMENT DI-7
MOD) WITHIN OPEN SPACES RATHER THAN WITHIN THE LOTS. FURTHER
DISCUSSION MAY BE HELPFUL.
9. SHEET 3: THE PROPOSED SWALE BETWEEN LOTS 21/22 MAY NOT
BE NEEDED AS ONLY A NEGLIGIBLE AMOUNT OF DRAINAGE AREA FROM
LOT 20 WILL CROSS LOT 21. IF IT IS TO REMAIN, THE SWALE
SHOULD BE LOCATED ON THE UPSTREAM SIDE OF THE DOWNSTREAM LOT
(LOT 22). PLEASE REVISE.
10. SHEET 3: CALLOUT THE USACOE UNDISTURBED BUFFER ON LOTS
1/2 AND 4/5 AS LABELED ON SHEET 6. SPECIFY/DIMENSION A 25'
BSL OFF THE USACOE BUFFER. REVISE SHEET 2 AS APPLICABLE.
11. ALTHOUGH NOT PREVIOUSLY REQUESTED, MAINTENANCE FREE
DRAINAGE IMPROVEMENTS (PIPE OR PAVE) SHOULD EXTEND BEYOND
THE HOMES AT LOTS 18/19. THIS IS A QUALITY OF LIFE GOAL FOR
CHESTERFIELD COUNTY. PLEASE REVISE PLANS, 10/100-YR CALCS,
PROFILE, ETC.
EROSION AND SEDIMENT CONTROL
12. SHEET 3: CONSIDER INSTALLING A DI-6 INLET WITH 2'
GUTTER AT THE MIDPOINT OF THE DITCH BETWEEN LOTS 7/8 WHICH
WOULD DISCHARGE TO THE STORM SEWER IN ELLERBY COURT IN ORDER
TO REDUCE THE DRAINAGE AREA DISCHARGING TO THE SUMMER LAKE
DEVELOPMENT REGARDING MS-19 CHANNEL ADEQUACY ISSUE.
13. SHEET 5: SHOW PROPERTY LINE ON THE SWALE LOT 21
PROFILE, IF SWALE IS TO REMAIN.
14. SHEET 6: PROVIDE TEMPORARY OUTLET PROTECTION FOR THE
TEMPORARY CULVERT TC1. PROVIDE A CALLOUT FOR OP ON THE
PLANS AND PROVIDE APRON DIMENSIONS WITH ASSOCIATED RIPRAP
SIZING/DEPTH.
15. SHEET 7: THE 1ST SUBMISSION PHASE II NARRATIVE NOTE 7
REFERENCED REMOVAL OF TEMPORARY CULVERT #1 AND WAS DELETED.
THIS NOTE SHOULD BE ADDED BACK AND UPDATED TO REFERENCE
TIMING WITH THE INSTALLATION OF THE APPLICABLE PERMANENT
STRUCTURES.
16. SHEET 7: PHASE II NARRATIVE NOTE 6: ADD LANGUAGE
SIMILAR TO NOTE 7 ABOUT FAVORABLE WEATHER FORECASTS FOR
INSTALLATION OF SANITARY SEWER WITH UTILITY STREAM
CROSSINGS.
17. SHEET 8: MS-19 #3: THERE DOES NOT APPEAR TO BE AN
ADEQUATE BED/BANK CHANNEL BELOW THE END OF THE DITCH. MS-19
IS NOT SATISFIED. FURTHER DISCUSSION MAY BE HELPFUL.
18. SHEET 8: MS-19 TABLE: A FORMAL VARIANCE MUST BE
REQUESTED FOR COMPLIANCE WITH MS-19 USING SITUATION E.
PLEASE ADDRESS.
19. SHEET 13: PROVIDE DETAIL FOR DI-6 INLET WITH 2' GUTTER
FOR STRUCTURES 9 AND 17.
20. SHEET 13: REVISE USCSET DETAIL TO REFERENCE APPLICABLE
STRUCTURES.
21. MS-19: A 2-YR PRE/POST ANALYSIS HAS NOT BEEN PROVIDED
TO SHOW HOW MS-19 IS BEING SATISFIED FOR THE SHEET
FLOW/CHANNEL FLOW INTO THE FUTURE SUMMER LAKE PROPERTY ALONG
THE WESTERN BOUNDARY. INCREASED VOLUMES OF SHEET FLOWS THAT
MAY CAUSE EROSION/SEDIMENTATION ISSUES ARE NOT EXEMPT.
PLEASE ADDRESS.
STORMWATER COMPUTATIONS
22. DITCH AND SWALE CALCULATIONS:
A. LOT 18 DITCHES SLOPE (0.5%) DOES NOT MATCH PLANS (0.8%).
PLEASE ADDRESS.
23. HYDRAULIC GRADE LINE CALCULATIONS
B. OUTLET WATER SURFACE ELEVATIONS FOR THE USCSET OUTFALLS
SHOULD BE SET TO THE TOP OF STRUCTURE OR KNOWN WSE,
WHICHEVER IS GREATER. THIS MAY AFFECT THE DESIGN OF THE
SYSTEM UPSTREAM OF STRUCTURE 1 OR 7. PLEASE REVISE.
24. THE REVISION OF THE STORM SEWER DISCHARGING THROUGH
STRUCTURE 7 TO INCLUDE THE DRAINAGE AREA FROM ELLERBY COURT
AND THE END OF ELLERBY DRIVE HAS INCREASED THE TOTAL
DISCHARGE TO THE STREAM FEATURE WHICH FLOWS INTO THE SUMMER
LAKE DEVELOPMENT. PLEASE PROVIDE 10/100-YR CALCULATIONS
VERIFYING THAT THE INCREASE WILL NOT EXCEED THE CAPACITY OF
DOWNSTREAM IMPROVEMENTS NOR THE CALCULATED 100 YEAR
BACKWATER. POTENTIAL CHANGES IN THE WESTERLEIGH SECTION 11
DEVELOPMENT MAY ALSO IMPACT THESE CALCULATIONS. DOWNSTREAM
INFRASTRUCTURE CALCULATIONS FROM SUMMER LAKE SECTION 9
DEVELOPMENT HAVE BEEN PROVIDED BY SEPARATE ATTACHMENT.
FURTHER DISCUSSION MAY BE HELPFUL.
25. PROVIDE 10-YR PRE/POST CALCULATIONS SHOWING HOW FLOOD
PROTECTION HAS BEEN PROVIDED WITHIN FUTURE SUMMER LAKE ALONG
THE WESTERN BOUNDARY.
26. CLEARLY INDICATE AND LABEL THE FLOW PATHS ON PLAN SHEETS
11 AND 12 FOR TIME OF CONCENTRATION CALCULATIONS - SHEET
FLOW, SHALLOW CONCENTRATED FLOW, AND CHANNEL FLOW AS
APPLICABLE.
SINCERELY,
ARCADIS U.S., INC.
CHRIS SOLDAN, P.E.
PROJECT ENVIRONMENTAL ENGINEER
============================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : CHRIS SOLDAN, P.E. (ARCADIS, 740-0181)
: ROBERT BOSWELL, P.E. (748-1977)
NAME OF PLAN : WESTERLEIGH, SECTION 10
SITE PLAN NO. : 15CP0103
LATEST PLAN DATE : 09/18/15
DEPT. REC'D DATE : 09/21/15
SUBMITTAL NUMBER : 3
REVIEW DATE : 10/12/15
RECOMMENDATION : REVISIONS REQUIRED
TABLE REVIEW : NO
MR. TODD CHALMERS, P.E.
BALZER AND ASSOCIATES, INC.
15871 CITY VIEW DRIVE, SUITE 200
MIDLOTHIAN, VA 23113
SUBJECT:
WESTERLEIGH SECTION 10
ENVIRONMENTAL ENGINEERING PLAN REVIEW - 3RD SUBMISSION
DEAR MR. CHALMERS:
REVIEW OF THE ABOVE REFERENCED PLANS ACCEPTED BY THE COUNTY
ON SEPT. 21, 2015 HAS BEEN COMPLETED. CHRIS SOLDAN WITH
ARCADIS, INC. (ARCADIS) PROVIDED THE REVIEW OF THE PLANS AS
AN AGENT FOR CHESTERFIELD COUNTY, DEPARTMENT OF
ENVIRONMENTAL ENGINEERING (EE). RESPONSIBILITY FOR
COMPLIANCE WITH CHESTERFIELD COUNTY STANDARDS AND POLICIES
AND STATE AND FEDERAL REGULATIONS WILL BE PLACED ON THE
PROFESSIONAL ENGINEER WHO SIGNS AND SEALS THE CONSTRUCTION
PLANS APPROVED.
WE OFFER THE FOLLOWING COMMENTS:
---------GENERAL---------
001. AS A PREREQUISITE TO THE ISSUANCE OF A LAND DISTURBANCE
PERMIT:
A. A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO
CAROLE CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE
AUTOCAD FILE MUST BE SAVED AS A .DWG OR .DXF IN
AUTOCAD VERSION 2009 OR EARLIER AND REFERENCED
DIRECTLY TO THE VIRGINIA STATE PLANE COORDINATE
SYSTEM, SOUTH ZONE IN THE NAD83 DATUM. THE AUTOCAD
FILE MAY BE SUBMITTED ON A CD, DVD, OR VIA EMAIL AND
MUST BE CLEARLY LABELED WITH THE SUBDIVISION NAME
AND SECTION, SUBDIVISION PLAN NUMBER, ENGINEERING
FIRM AND CAD FILE PREPARER'S NAME AND PHONE NUMBER.
THE FILE MUST CONTAIN THE FOLLOWING, EACH CLEARLY
LABELED IN SEPARATE LAYERS:
I) EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
II) EDGES OF SIDEWALKS.
B. THE FILE MUST BE APPROVED BY ENVIRONMENTAL
ENGINEERING PRIOR TO ISSUANCE OF THE LAND
DISTURBANCE PERMIT.
C. FLAGGING AROUND USACOE JURISDICTIONAL WETLANDS,
BUFFERS, AND SENSITIVE AREAS MUST BE VISIBLE.
D. DOCUMENTATION FROM THE USACOE/DEQ MUST BE RECEIVED
VERIFYING COMPLIANCE TO WETLAND PERMIT REGULATIONS.
E. A VSMP REGISTRATION AND FEE FORM MUST BE PROCESSED
AND/OR RECEIVED.
F. THE LIMITS OF THE RPA MUST BE FLAGGED IN THE FIELD
(SURVEY LOCATED) WITH OPTIC ORANGE SAFETY FENCE
PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT.
G. A COPY OF VDOT LAND USE PERMIT MUST BE RECEIVED, IF
APPLICABLE.
H. AN EROSION CONTROL BOND MUST BE POSTED.
I. TWO ADDITIONAL SETS OF CONSTRUCTION PLANS TO BE
STAMPED "APPROVED FOR CONSTRUCTION" MUST BE
RECEIVED.
J. THE ENVIRONMENTAL ENGINEERING DEPARTMENT MUST HAVE
RECEIVED SIGNED, WRITTEN NOTIFICATIONS FROM THE
ADJACENT PROPERTY OWNERS, N/F MARONEY, N/F
MARSHALECK, AND N/F BURLOCK WHICH SHOULD BE SENT
U.S. POSTAL CERTIFIED MAIL, RETURN RECEIPT
REQUESTED. INCLUDE AN 8½ X11 COPY OF THE PROPOSED
CONSTRUCTION ACTIVITY ADJACENT TO THEIR PROPERTIES.
002. AS A PREREQUISITE TO SUBDIVISION PLAT RECORDATION:
A $100/LOT BMP MAINTENANCE FEE MUST BE RECEIVED.
003. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND/OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR STATE
PERMITS IN RELATION TO ENVIRONMENTAL FEATURES
INCLUDING, BUT NOT LIMITED TO, WETLANDS, SURFACE WATER,
GROUND WATER, AND AIR QUALITY. FINAL APPROVAL OF THESE
PLANS WILL NOT RELIEVE YOU OF YOUR RESPONSIBILITIES.
---------EROSION AND SEDIMENT CONTROL---------
004. SHEET 8: MS-19 #3: THERE DOES NOT APPEAR TO BE AN
ADEQUATE BED/BANK CHANNEL BELOW THE END OF THE DITCH.
PER THE FIELD VISIT CONDUCTED WITH COUNTY STAFF ON
6/8/15, WHILE A BED/BANK CHANNEL DOES EXIST ALONG SOME
OF THIS AREA, IT IS NOT CONTINUOUS AND A PORTION
FLATTENS OUT AND THE CLEAR BED/BANK CHANNEL CEASES FOR
SOME DISTANCE. MS-19 IS NOT SATISFIED. IF A REAR
DITCH IS INSTALLED DURING THE DEVELOPMENT OF THE
ADJACENT SUMMERLAKE LOTS, IT MAY SATISFY THE
REQUIREMENT IF CALCULATIONS CAN SHOW IT IS AN ADEQUATE
RECEIVING CHANNEL. IN THAT CASE, CONSTRUCTION OF THE
OUTFALL AND THE DEVELOPMENT OF THE CONTRIBUTING LOTS IN
WESTERLEIGH SECTION 10 WOULD NEED TO BE DELAYED UNTIL
SUCH TIME THAT THE DEFINED CHANNEL IS CONSTRUCTED.
FURTHER DISCUSSION MAY BE HELPFUL.
---------STORMWATER COMPUTATIONS---------
005. THE PROPOSED INCREASE IN STORMWATER PEAK
DISCHARGE/VOLUME FROM THE DEVELOPMENT OF LOTS 1 THROUGH
14 BORDERING ON THE FUTURE SUMMER LAKE DEVELOPMENT
DOES NOT HAVE AN ADEQUATE RECEIVING FACILITY BASED ON
THE 6/8/15 FIELD VISIT. THE 2-YR PRE/POST CALCULATIONS
INCLUDED ONLY ACCOUNT FOR ONSITE DRAINAGE AND MUST
INCLUDE THE OFFSITE DRAINAGE FROM THE OTHER SECTION OF
WESTERLEIGH AND THE FUTURE SUMMERLAKE DEVELOPMENT.
WRITTEN ACKNOWLEDGMENT FROM THE DEVELOPER/OWNER OF
SUMMERLAKE THAT THE INCREASES IN STORMWATER IN A NON-
ERODIBLE CONVEYANCE WITHOUT BED/BANK CONSTRAINS IS ONE
ALTERNATIVE. DELAYING RECORDATION OF LOTS OR
INSTALLATION OF AN ATTENUATION BASIN IS ANOTHER
ALTERNATIVE. FURTHER DISCUSSION MAY BE HELPFUL.
006. HYDRAULIC GRADE LINE COMPUTAIONS:
A. OUTLET WATER SURFACE ELEVATIONS FOR THE USCSET
OUTFALLS SHOULD BE SET TO THE TOP OF STRUCTURE OR
KNOWN WSE, WHICHEVER IS GREATER. THIS MAY AFFECT
THE DESIGN OF THE SYSTEM UPSTREAM OF STRUCTURE 1 OR
7. THIS WAS ADDRESSED IN THE 10-YR CALCULATIONS
SPREADSHEET BUT NOT THE 100-YR. PLEASE REVISE.
B. IT APPEARS THAT THE 100 YEAR WSE AT STRUCTURE 33
WILL OVERTOP THE CURB AT THE ELLERBY COURT CUL-DE-
SAC AND COULD POTENTIALLY FLOW LOTS 5/6. PLEASE
ADDRESS.
007. IT APPEARS THAT THE REVISIONS OF THE DRAINAGE AREAS FOR
BOTH WESTERLEIGH SECTION 10 AND 11 DRIVE HAVE INCREASED
THE TOTAL DISCHARGE TO THE STREAM FEATURE WHICH FLOWS
INTO THE SUMMER LAKE DEVELOPMENT THAT WILL EXCEED THE
CAPACITY OF THE DOWNSTREAM CULVERT AND 100 YEAR
BACKWATER AT SHORELAND DRIVE. THE SUBMITTED 100-YR
FLPL XSEC 8 INDICATES A PROPOSED FLOW OF 96.89 CFS
WHILE THE DOWNSTREAM CULVERT WAS DESIGNED FOR A 100-YR
FLOW OF 69.8 CFS. PLEASE ADDRESS AND COORDINATE
REVISIONS AND CALCULATIONS WITH THE SUBMITTAL OF
WESTERLEIGH SECTION 11. DOWNSTREAM INFRASTRUCTURE
CALCULATIONS FROM SUMMER LAKE SECTION 9 DEVELOPMENT
HAVE BEEN PROVIDED BY SEPARATE ATTACHMENT. FURTHER
DISCUSSION MAY BE HELPFUL.
SINCERELY,
ARCADIS U.S., INC.
CHRIS SOLDAN, P.E.
PROJECT ENVIRONMENTAL ENGINEER
COPIES:
ROBERT BOSWELL - ENVIRONMENTAL ENGINEERING
AMY SUMMERVILLE - PLANNING
--------- END OF ENV. ENG. COMMENTS ---------
============================================================
============================================================
============================================================
============================================================
REVIEW DEPARTMENT: ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE #: CHRIS SOLDAN (AGENT REVIEWER)/665-1095
NAME OF PLAN: WESTERLEIGH SECTION 10
SITE PLAN NO.: 15CP0103
LATEST PLAN DATE: 02/23/2016
DEPT. REC'D DATE: 03/09/2016
SUBMITTAL NUMBER: 4
REVIEW DATE: 03/29/2016
RECOMMENDATION: REVISION REQUIRED
TABLE REVIEW: NO
-------- GENERAL NOTES --------
001. AS A PREREQUISITE TO THE ISSUANCE OF A LAND
DISTURBANCE PERMIT:
A) A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD
FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD
VERSION 2009 OR EARLIER AND REFERENCED DIRECTLY TO
THE VIRGINIA STATE PLANE COORDINATE SYSTEM, SOUTH
ZONE IN THE NAD83 DATUM. THE AUTOCAD FILE MAY BE
SUBMITTED ON A CD, DVD, OR VIA EMAIL AND MUST BE
CLEARLY LABELED WITH THE SUBDIVISION NAME AND
SECTION, SUBDIVISION PLAN NUMBER, ENGINEERING
FIRM AND CAD FILE PREPARER'S NAME AND PHONE
NUMBER. THE FILE MUST CONTAIN THE FOLLOWING, EACH
CLEARLY LABELED IN SEPARATE LAYERS:
1. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
2. EDGES OF SIDEWALKS
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
B) FLAGGING AROUND USACOE JURISDICTIONAL WETLANDS, BUFFERS
AND SENSITIVE AREAS MUST BE VISIBLE.
C) DOCUMENTATION FROM THE USACOE/DEQ MUST BE RECEIVED
VERIFYING COMPLIANCE TO WETLAND PERMIT REGULATIONS
D) A VSMP REGISTRATION AND FEE FORM MUST BE PROCESSED
AND/OR RECEIVED.
E) AS APPLICABLE A SWPPP BOOKLET IN A 3-RING BINDER MUST
BE PROVIDED.
F) A COPY OF VDOT LAND USE PERMIT MUST BE RECEIVED, IF
APPLICABLE.
G) AN EROSION CONTROL BOND MUST BE POSTED IN THE AMOUNT OF
$53,794.00.
H) TWO ADDITIONAL SETS OF CONSTRUCTION PLANS TO BE STAMPED
"APPROVED FOR CONSTRUCTION" MUST BE RECEIVED.
I) PRIOR TO CONSTRUCTION PLAN APPROVAL, ENVIRONMENTAL
MUST HAVE RECEIVED SIGNED, WRITTEN NOTIFICATIONS FROM
ADJACENT PROPERTY OWNERS, N/F MARONEY, N/F MARSHALECK,
AND N/F BURLOCK WHICH SHOULD BE SENT U.S. POSTAL
CERTIFIED MAIL, RETURN RECEIPT REQUESTED. INCLUDE AN
8.5X11 COPY OF THE PROPOSED CONSTRUCTION ACTIVITY
ADJACENT TO THEIR PROPERTIES.
002. AS A PREREQUISITE TO SUBDIVISION PLAT RECORDATION:
A) A $100/LOT BMP MAINTENANCE FEE MUST BE RECEIVED.
003. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND/OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR STATE
PERMITS IN RELATION TO ENVIRONMENTAL FEATURES
INCLUDING, BUT NOT LIMITED TO, WETLANDS, SURFACE WATER,
GROUND WATER, AND AIR QUALITY. FINAL APPROVAL OF THESE
PLANS WILL NOT RELIEVE YOU OF YOUR RESPONSIBILITIES.
-------- ROAD AND DRAINAGE --------
004. SHEETS 3 & 3A: UPDATE THE STORM STRUCTURE TABLES TO
REMOVE CONFLICTS AND REFLECT THE CHANGES MADE TO REMOVE
STRUCTURE 7 AND ROUTE FLOWS TO POND 1. ALSO CORRECT
STRUCTURE 44 PIPE SIZE LABEL TO 15" NOT 42".
005. SHEETS 11 & 12: THE DRAINAGE AREA DELINEATIONS AND AREA
LABELING VARY SLIGHTLY AND DO NOT MATCH WHAT WAS
PROVIDED IN THE WESTERLEIGH SECTION 11 SUBMITTAL.
PLEASE ADDRESS AND COORDINATE REVISIONS AND
CALCULATIONS WITH THE SUBMITTAL OF WESTERLEIGH
SECTION 11.
006. SHEETS 11: THE WESTERN RUNOFF PRE/POST FLOW RATES DO
NOT MATCH THE CALCULATED VALUES FROM THE HYDROLOGY
WORKSHEET. PLEASE REVISE.
006. SHEETS 11: STRUCTURE 9 IS A DI-6 AND WOULD COLLECT ALL
FLOW FROM THE 0.64 ACRE DRAINAGE AREA. HOWEVER THE 200
LF OLF PATH APPEARS TO BYPASS THE STRUCTURE AND FLOW
DIRECTLY THE CREEK. PLEASE ADDRESS.
007. SHEETS 3/11/12 STILL SHOW THE PREVIOUS P9 OUTFALL (FROM
SECTION 11). PLEASE REVISE ACCORDINGLY.
-------- EROSION CONTROL --------
008. MS-19 #3 & OVERALL WESTERN PROPERTY LINE:
A) THERE IS NOT AN ADEQUATE RECEIVING CHANNEL IMMEDIATELY
BELOW THE DITCH ALONG LOTS 7/12. SITUATION B IS NOT
APPLICABLE. THE DITCH SHOULD FLATTEN TO SHEET FLOW AT
THE PROPERTY LINE TO AVOID CREATING A POINT DISCHARGE.
HOWEVER, THE POST DEVELOPMENT FLOW RATE EXCEEDS THE
PREDEVELOPMENT RATE (1.58 VS 1.29). THEREFORE MS-19 AT
POINT #3 IS NOT SATISFIED. PLEASE REVISE.
B) SITUATION F MAY BE APPLICABLE FOR THE OVERALL WESTERN
PROPERTY LINE IF THE POST DEVELOPMENT FLOWS ARE LESS
THAN PRE-DEVELOPMENT. HOWEVER THE 2-YR PRE/POST
CALCULATIONS SUBMITTED ONLY ACCOUNT FOR ONSITE DRAINAGE
AND MUST INCLUDE THE OFFSITE DRAINAGE FROM THE OTHER
SECTION OF WESTERLEIGH AND THE FUTURE SUMMERLAKE
DEVELOPMENT. A WRITTEN VARIANCE REQUEST WILL ALSO BE
REQUIRED SINCE NO ADEQUATE RECEIVING CHANNEL EXISTS.
IF THIS CAN BE DEMONSTRATED, LOTS 1, 2, 4, 5, & 6 CAN
BE RECORDED AT THIS TIME.
B) IF POST DEVELOPMENT FLOWS CANNOT BE SHOWN TO BE LESS
THAN PREDEVELOPMENT, LOTS DISCHARGING ALONG THE WESTERN
PROPERTY LINE AND FROM DITCH 7/12 SHOULD BE GHOSTED.
THIS WOULD APPLY TO LOTS 4, 7-9, & 11-14 IN ADDITION TO
LOTS 1, 2, 5, & 6 ALREADY LISTED. REMOVE ANY REFERENCE
TO NPB FOR THESE LOTS AS THEY SHOULD ALL BE LABELED AS
FUTURE. THE SECTION LIMITS MUST BE REVISED AND LOT
NUMBERING UPDATED EXCLUDING LOTS 1, 2, 4-9, & 11-14.
C) ALSO, REVIEW AND APPROVAL OF AN ADEQUATE RECEIVING
CHANNEL WILL BE REQUIRED BEFORE THE RECORDATION OF
THESE FUTURE LOTS.
D) WRITTEN ACKNOWLEDGMENT FROM THE DEVELOPER/OWNER OF
SUMMERLAKE THAT THE INCREASES IN STORMWATER IN A NON-
ERODIBLE CONVEYANCE WITHOUT BED/BANK CONSTRAINTS IS ONE
ALTERNATIVE. DIVERSION OF ADDITIONAL FLOW TO POND 1 IS
ANOTHER ALTERNATIVE. FURTHER DISCUSSION MAY BE
HELPFUL.
E) REVISE MS-19 TABLE ON SHEET 8 TO REFLECT DEMONSTRATED
METHOD OF COMPLIANCE.
-------- STORMWATER COMPUTATIONS --------
009. HYDRAULIC GRADE LINE CALCULATIONS:
A) AS PREVIOUSLY REQUESTED, THE OUTLET WATER SURFACE
ELEVATIONS (WSE) FOR THE USCSET OUTFALL SHOULD BE SET
TO THE TOP OF STRUCTURE OR KNOWN WSE, WHICHEVER IS
GREATER. FOR STRUCTURE 3 THIS ELEV. = 256.05. THIS
WAS ADDRESSED IN THE 10-YR CALCULATIONS SPREADSHEET BUT
NOT THE 100-YR. PLEASE REVISE.
B) AS PREVIOUSLY REQUESTED, IT APPEARS THAT THE 100 YEAR
WSE AT STRUCTURES 31 & 33 WILL EXCEED THE RIM
ELEVATIONS AND OVERTOP THE CURB AT THE ELLERBY COURT
CUL-DE-SAC AND COULD POTENTIALLY FLOW THROUGH LOTS 5/6.
PLEASE ADDRESS.
C) THE OUTLET WATER SURFACE ELEVATIONS FOR THE OUTFALLS
INTO POND 1 (AT STRUCTURES 17 & 41) SHOULD BE SET TO
THE CALCULATED WSE IN THE POND FOR THE 10-YR AND 100-YR
STORMS AS THESE ELEVATIONS APPEAR TO BE GREATER 0.8
TIMES THE DIAMETER OF THE OUTLET PIPE (0.8D). THIS
COULD CAUSE FLOWS TO EXCEED THE RIM ELEVATIONS OF
UPSTREAM STRUCTURES. PLEASE REVISE.
010. POND ROUTING CALCULATIONS:
B) THE HYDROLOGY WORKSHEET CALCULATIONS DATED 7/13/2015
INDICATED A TOTAL DRAINAGE AREA TO THE 100-YR XSEC #8
AS 31.13 ACRES. THE TOTAL DRAINAGE AREA AT THE
SUMMERLAKE STRUCTURE E15 LOCATED DOWNSTREAM OF XSEC #8
SHOULD BE LARGER, HOWEVER THE ROUTING CALCULATIONS
INDICATE A TOTAL DRAINAGE AREA OF 29.4 ACRES. BASED ON
THE DRAINAGE AREA MAPS PROVIDED, THE TOTAL DRAINAGE
AREA APPEARS TO BE 31.7 ACRES. PLEASE ADDRESS AND
COORDINATE REVISIONS AND CALCULATIONS WITH THE
SUBMITTAL OF WESTERLEIGH SECTION 11.
C) THE SUBCATCHMENT DRAINAGE AREAS LISTED IN THE ROUTING
CALCULATIONS DO NOT APPEAR TO MATCH THE DRAINAGE AREA
MAPS (SHEETS 11 & 12). REVISE THE DRAINAGE AREA MAPS
TO CLEARLY SHOW THE LIMITS OF EACH SUBCATCHMENT.
PLEASE ADDRESS AND COORDINATE REVISIONS AND
CALCULATIONS WITH THE SUBMITTAL OF WESTERLEIGH
SECTION 11.
D) THE SUMMARY SHEETS FOR "POND 9P: SEC11 CULVERT" AND
"LINK 11L: STR E15" WERE INCLUDED FOR THE 1, 2, & 10
YEAR STORMS. HOWEVER THE 100-YR STORM SHEETS WERE
MISSING. PLEASE SUBMIT.
E) THE ROUTING OF ALL SUBCATCHMENTS MUST BE CLEARLY SHOWN
TO ACCOUNT FOR THE VARYING PEAK TIMES. PLEASE REVISE
THE "LINK 11L: STR E15" SUMMARY SHEETS TO SHOW EACH
INDIVIDUAL SUBCATCHMENT HYDROGRAPH AS SEPARATE INFLOWS.
F) IF COMPLIANCE WITH CAPACITY RESTRICTIONS IN DOWNSTREAM
SUMMERLAKE CULVERT CANNOT BE DEMONSTRATED FOR THE
COMBINED WESTERLEIGH SECTIONS 10 & 11 DEVELOPMENT, IT
MAY BE POSSIBLE TO DEMONSTRATE COMPLIANCE FOR ONE
SECTION WHILE THE OTHER IS DELAYED UNTIL COMPLIANCE CAN
BE SHOWN THROUGH REVISED ROUTING CALCULATIONS OR
ANOTHER APPROVED METHOD. A FURTHER DISCUSSION IS
REQUESTED.
-------- SWM/BMP DESIGN --------
011. SHEET 3A: SPECIFY THAT THE OUTFALL PIPE PENETRATING
THE POND EMBANKMENT (STRUCTURE 44) SHALL BE O-RING RCP
PIPE.
012. SHEET 3A: THE SWM/BMP EASEMENT ENCLOSING THE FACILITY
SHOULD BE 25' OFF THE 100-YR WSE OR TOE OF DAM,
WHICHEVER IS MOST RESTRICTIVE. THE WIDTH MAY BE
REDUCED ADJACENT TO WOUS. PLEASE REVISE.
013. SHEET 3A: SHOW AND DIMENSION A 50' VEGETATIVE
PERIMETER YARD SETBACK MEASURED FROM THE 100-YR WSE OR
TOE OF DAM OF POND 1, WHICHEVER IS MORE RESTRICTIVE.
IT APPEARS THIS WILL AFFECT LOT #23 OF SECTION 11.
PLEASE ADDRESS AND COORDINATE REVISIONS WITH THE
SUBMITTAL OF WESTERLEIGH SECTION 11.
014. SHEET 3A: PROVIDE 12' WIDE MAINTENANCE CORRIDOR ALONG
THE TOP OF THE EMBANKMENT ON THE WESTERN (LOT 23) SIDE
OF THE POND TO PROVIDE ACCESS TO THE OUTFLOW LOCATIONS.
015. SHEET 3A: PROVIDE A SCALED X-SECTION THROUGH THE
CONCRETE WEIR SPILLWAY FROM INFLOW TO OUTFLOW.
016. SHEET 3A: LABEL THE WOUS AND 3:1 SLOPES IN THE GRADING
PLAN.
017. SHEET 3A: IT APPEARS THE EMBANKMENT ENCROACHES ON AND
IMPACTS THE 100-YR FLOODPLAIN AT STRUCTURE 44 WHICH IS
NOT DESIRABLE. PLEASE REVISE.
---- END OF ENV. ENG. COMMENTS ----
============================================================
============================================================
============================================================
============================================================
REVIEW DEPARTMENT: ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE #: CHRIS SOLDAN (AGENT REVIEWER)/665-1095
NAME OF PLAN: WESTERLEIGH SECTION 10
SITE PLAN NO.: 15CP0103
LATEST PLAN DATE: 05/24/2016
DEPT. REC'D DATE: 06/02/2016
SUBMITTAL NUMBER: 5
REVIEW DATE: 06/22/2016
RECOMMENDATION: REVISION REQUIRED
TABLE REVIEW: NO
-------- GENERAL NOTES --------
001. AS A PREREQUISITE TO THE ISSUANCE OF A LAND
DISTURBANCE PERMIT:
A) A COPY OF THE AUTOCAD FILE MUST BE SUBMITTED TO CAROLE
CLIBORNE OF ENVIRONMENTAL ENGINEERING. THE AUTOCAD
FILE MUST BE SAVED AS A .DWG OR .DXF IN AUTOCAD
VERSION 2009 OR EARLIER AND REFERENCED DIRECTLY TO
THE VIRGINIA STATE PLANE COORDINATE SYSTEM, SOUTH
ZONE IN THE NAD83 DATUM. THE AUTOCAD FILE MAY BE
SUBMITTED ON A CD, DVD, OR VIA EMAIL AND MUST BE
CLEARLY LABELED WITH THE SUBDIVISION NAME AND
SECTION, SUBDIVISION PLAN NUMBER, ENGINEERING
FIRM AND CAD FILE PREPARER'S NAME AND PHONE
NUMBER. THE FILE MUST CONTAIN THE FOLLOWING, EACH
CLEARLY LABELED IN SEPARATE LAYERS:
1. EDGES OF ROADS TO INCLUDE CURB AND GUTTER; AND
2. EDGES OF SIDEWALKS
THE FILE MUST BE APPROVED BY ENVIRONMENTAL ENGINEERING
PRIOR TO ISSUANCE OF THE LAND DISTURBANCE PERMIT.
B) FLAGGING AROUND USACOE JURISDICTIONAL WETLANDS, BUFFERS
AND SENSITIVE AREAS MUST BE VISIBLE.
C) DOCUMENTATION FROM THE USACOE/DEQ MUST BE RECEIVED
VERIFYING COMPLIANCE TO WETLAND PERMIT REGULATIONS
D) A VSMP REGISTRATION AND FEE FORM MUST BE PROCESSED
AND/OR RECEIVED.
E) AS APPLICABLE A SWPPP BOOKLET IN A 3-RING BINDER MUST
BE PROVIDED.
F) A COPY OF VDOT LAND USE PERMIT MUST BE RECEIVED, IF
APPLICABLE.
G) AN EROSION CONTROL BOND MUST BE POSTED IN THE AMOUNT OF
$53,794.00.
H) TWO ADDITIONAL SETS OF CONSTRUCTION PLANS TO BE STAMPED
"APPROVED FOR CONSTRUCTION" MUST BE RECEIVED.
002. AS A PREREQUISITE TO PLAN APPROVAL THE ENVIRONMENTAL
ENGINEERING DEPARTMENT MUST HAVE RECEIVED SIGNED,
WRITTEN NOTIFICATIONS FROM THE ADJACENT PROPERTY
OWNERS, N/F MARONEY, N/F MARSHALECK, AND N/F BURLOCK
WHICH SHOULD BE SENT U.S. POSTAL CERTIFIED MAIL, RETURN
RECEIPT REQUESTED. INCLUDE AN 8.5X11 COPY OF THE
PROPOSED CONSTRUCTION ACTIVITY ADJACENT TO THEIR
PROPERTIES.
003. AS A PREREQUISITE TO SUBDIVISION PLAT RECORDATION:
A) A $100/LOT BMP MAINTENANCE FEE MUST BE RECEIVED.
004. IT IS THE RESPONSIBILITY OF THE APPLICANT TO COMPLY
WITH AND/OR ACQUIRE ALL APPLICABLE FEDERAL AND/OR STATE
PERMITS IN RELATION TO ENVIRONMENTAL FEATURES
INCLUDING, BUT NOT LIMITED TO, WETLANDS, SURFACE WATER,
GROUND WATER, AND AIR QUALITY. FINAL APPROVAL OF THESE
PLANS WILL NOT RELIEVE YOU OF YOUR RESPONSIBILITIES.
-------- ROAD AND DRAINAGE --------
005. SHEETS 3 & 3A: AS PREVIOUSLY REQUESTED UPDATE THE
STORM STRUCTURE TABLES TO REMOVE CONFLICTS AND REFLECT
THE CHANGES MADE TO DELETE STRUCTURE 7. THERE ARE
MULTIPLE CONFLICTS OF BOTH INVERT AND TOP ELEVATION
BETWEEN THESE TABLES AND THE STORM SEWER CALCULATIONS
WORKSHEETS. PLEASE ADDRESS.
006. SHEET 3: STRUCTURE 9 IS A DI-6 AND SHOULD COLLECT ALL
FLOW FROM THE 0.66 ACRE DRAINAGE AREA. HOWEVER THE TOP
ELEVATION OF THE STRUCTURE IS SET APPROXIMATELY 2.5
FEET ABOVE THE SURROUNDING GRADE. ADDITIONALLY, THE
FILL OVER THE ADJACENT PIPES APPEARS TO CREATE A DAM
EFFECT AT THE REAR OF LOT 27. STRUCTURE 9 IS ALSO ONE
OF THE CONFLICTS BETWEEN THE TABLES ON SHEET 3/3A:
(TOP ELEV. 243.07 VS 245.5). PLEASE ADDRESS.
-------- EROSION CONTROL --------
007. MS-19 #3 & OVERALL WESTERN PROPERTY LINE:
A) AS PREVIOUSLY NOTED THERE IS NOT AN ADEQUATE RECEIVING
CHANNEL IMMEDIATELY BELOW THE DITCH ALONG LOTS 7/12.
SITUATION B IS NOT APPLICABLE. SITUATION F MAY BE
APPLICABLE FOR THE OVERALL WESTERN PROPERTY LINE IF THE
POST DEVELOPMENT FLOWS ARE LESS THAN PRE-DEVELOPMENT.
A WRITTEN VARIANCE REQUEST WILL ALSO BE REQUIRED SINCE
NO ADEQUATE RECEIVING CHANNEL EXISTS.
B) THE 2-YR PRE/POST CALCULATIONS SUBMITTED ONLY ROUTE THE
POST DEVELOPMENT DRAINAGE THROUGH THE WETLAND AREA.
SINCE THE WETLAND POCKETS EXISTED UNDER PREDEVELOPED
CONDITIONS, THEY SHOULD BE ROUTED AS WELL FOR
PREDEVELOPED DISCHARGES.
C) IF THE REVISED ROUTING CALCULATIONS FOR THE WETLANDS
DO NOT PROVIDE ENOUGH ATTENUATION TO ACCOUNT FOR THE
INCREASED FLOWS, AND POST DEVELOPMENT FLOWS CANNOT BE
SHOWN TO BE LESS THAN PREDEVELOPMENT, LOTS DISCHARGING
ALONG THE WESTERN PROPERTY LINE AND FROM DITCH 7/12
SHOULD BE GHOSTED LABELED AS FUTURE. THIS WOULD APPLY
TO LOTS 5-9, & 11-14. THE SECTION LIMITS MUST BE
REVISED AND LOT NUMBERING UPDATED TO EXCLUDE THESE
LOTS. ALSO, REVIEW AND APPROVAL OF AN ADEQUATE
RECEIVING CHANNEL WILL BE REQUIRED BEFORE THE
RECORDATION OF THESE FUTURE LOTS.
D) WRITTEN ACKNOWLEDGMENT FROM THE DEVELOPER/OWNER OF
SUMMERLAKE THAT THE INCREASES IN STORMWATER IN A NON-
ERODIBLE CONVEYANCE WITHOUT BED/BANK CONSTRAINTS IS ONE
ALTERNATIVE. FURTHER DISCUSSION MAY BE HELPFUL.
E) BASED ON THE WESTERN RUNOFF A-6 CALCULATIONS, IT
APPEARS THAT POST DEVELOPMENT FLOW FROM LOTS 1-2, & 4
IS LOWER THAN PREDEVELOPMENT. THESE LOTS MAY BE
DEVELOPED AT THIS TIME. SITUATION F IS APPLICABLE. A
WRITTEN VARIANCE REQUEST SHOULD BE SUBMITTED SINCE NO
ADEQUATE RECEIVING CHANNEL EXISTS.
F) REVISE MS-19 TABLE ON SHEET 8 TO REFLECT DEMONSTRATED
METHOD OF COMPLIANCE.
008. MS-19 #4: PLEASE REVISE THE 2-YR FLOWS ON THE CROSS
SECTION, MS-19 TABLE, AND HYDROLOGY WORKSHEETS TO MATCH
AS THEY CURRENTLY CONFLICT WITH EACHOTHER (31.29,
29.09, AND 30.39 CFS). THE CHANNEL IS ADEQUATE FOR ANY
OF THESE FLOWS AND SITUATION B IS APPROPRIATE.
-------- STORMWATER COMPUTATIONS --------
007. HYDRAULIC GRADE LINE CALCULATIONS:
A) AS PREVIOUSLY REQUESTED, IT APPEARS THAT THE 100 YEAR
WSE AT STRUCTURES 31 & 33 WILL EXCEED THE RIM
ELEVATIONS AND OVERTOP THE CURB AT THE ELLERBY COURT
CUL-DE-SAC AND COULD POTENTIALLY FLOW THROUGH LOTS 5/6.
WHILE THE NEW SWALE DIRECTS FLOW THROUGH LOTS 5/6,
THERE IS NO 100-YR FLOODPLAIN OR OTHER DRAINAGE
IMPROVEMENT AT THE REAR OF THESE LOTS AND THE
CONCENTRATED FLOW WOULD ENTER THE ADJACENT SUMMERLAKE
DEVELOPMENT. THIS IS NOT ACCEPTABLE. PLEASE ADDRESS.
B) AS PREVIOUSLY REQUESTED THE OUTLET WATER SURFACE
ELEVATIONS FOR THE OUTFALLS INTO POND 1 (AT STRUCTURES
17 & 41) SHOULD BE SET TO THE CALCULATED WSE IN THE
POND FOR THE 10-YR STORMS. THIS APPEARS TO HAVE BEEN
ADDRESSED FOR THE 100-YR CALCULATIONS.
C) THE 100-YR HGL CALCULATIONS INDICATE FLOWS WILL EXCEED
THE RIM ELEVATIONS FOR THE MAJORITY OF THE STRUCTURES
UPSTREAM OF SWM 1. AS THE ROUTING CALCULATIONS TO THE
EXISTING SUMMERLAKE CULVERT DEPEND ON THE DETENTION OF
THE 100-YR STORM, THESE FLOWS MUST NOT BE ALLOWED TO
BYPASS SWM 1. PROVIDING A FLOW PATH IN THE RIGHT
OF WAY OR A DRAINAGE EASEMENT TO THE ESTABLISHED
FLOODPLAIN WILL NOT BE AN ACCEPTABLE ALTERNATIVE.
UPSIZING THE PIPES IN THE SYSTEM MAY ELIMINATE THIS
PROBLEM.
008. THE "SITE RUNOFF TO E15" ROUTING CALCULATIONS WHICH
INCLUDE FLOWS FROM BOTH SECTION 10 & 11 ARE
ACCEPTABLE. HOWEVER FINAL APPROVAL IS CONTINGENT ON
APPROVAL OF THE HGL CALCULATIONS DEMONSTRATING ALL
FLOWS ARE DIRECTED INTO SWM 1 AS INDICATED IN THE
ROUTING CALCULATIONS.
009. FOR FUTURE SUBMITTALS, PLEASE UPDATE THE DATE FIELD ON
THE CALCULATION WORKSHEETS TO AVOID CONFUSION WITH
PREVIOUSLY SUBMITTED CALCS.
-------- SWM/BMP DESIGN --------
010. SHEET 3: AS NOTED IN THE SECTION 11 COMMENTS DATED
06/15/16 CONSTRUCTION OF SWM 1 AND ASSOCIATED DRAINAGE
IMPROVEMENTS WILL ENCROACH ON LOT 23 OF SECTION 11.
ONE OPTION IS TO DELAY RECORDATION OF LOT 23 OF SECTION
11 UNTIL SUCH TIME AS THE IMPROVEMENTS HAVE BEEN
INSTALLED. ANOTHER OPTION IS TO INCLUDE THE
CONSTRUCTION OF SWM 1 AND ASSOCIATED INFRASTRUCTURE IN
SECTION 11.
011. SHEET 3A: AS NOTED IN THE SECTION 11 COMMENTS DATED
06/15/16 REVISE THE SWM ESMT LIMITS TO COINCIDE WITH
THE R/W FOR BOTH SWM 1. A SKETCH HAS BEEN PROVIDED
AS A SEPARATE ATTACHMENT FOR CLARIFICATION.
012. SHEET 3: AS NOTED IN THE SECTION 11 COMMENTS DATED
06/15/16 THE RIPRAP OUTLET PROTECTION FROM SWM 1
ENCROACHES ON LOT 24 OF SECTION 11. PLEASE REDUCE THE
EXTENTS OF THE RIPRAP ON THE EASTERN BANK TO THE LIMITS
OF THE 100-YR FLOODPLAIN.
013. PLEASE PROVIDE A WRITTEN RESPONSE TO EACH OF THE
COMMENTS ABOVE WITH YOUR NEXT PLAN SUBMITTAL.
---- END OF ENV. ENG. COMMENTS ----
============================================================
============================================================