Subdivision Review Comments
All Subdivision Review Comments for Case # 11CP0006




For VDOT’s comments please contact Virginia Department of Transportation at (804) 674-2814 or send e-mail to Boris.Solomonov@VDOT.Virginia.gov

For Tentative Subdivision resubmittals:

1. Please note that submittal fees include the original submittal and two (2) additional reviews.

2. A letter of transmittal is required to accompany each submittal.

3. Please verify that Environmental Engineering, Fire, CDOT, VDOT, and Planning have reviewed the submittal before resubmitting. A resubmittal tendered, prior to receiving all the required departments’ review, will be counted as an additional submittal. Go to Case Selection Form or Go to Project List


 
CASE NO: 11CP0006 STATUS: PENDING APPROVAL
PROJECT NAME: WESTCHESTER TOWNHOUS - LAST INTERNET UPDATE: 11/20/17
SUBMITTAL TYPE: CONSTRUCTION PLAN
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 03 08/04/14 08/25/14 COMPLETE 08/26/14 LAG 706-2116
FIRE DEPT.--: 03 08/04/14 08/25/14 ******** 08/12/14 JKL 748-1489
PLANNING----: 03 08/04/14 08/25/14 COMPLETE 08/21/14 GWK 706-7691
TRANSPORT.--: 03 08/04/14 08/25/14 COMPLETE 09/02/14 SES 751-4912
UTIL.PLAN.--: 03 08/04/14 08/25/14 ******** ********
UTILITIES---: 03 08/04/14 08/25/14 AMENDED* 08/21/14 WBV 748-1343
UTIL.R.O.W.-: 03 08/04/14 08/25/14 ******** ********
VDOT--------: 03 08/04/14 08/25/14 ******** ********
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: WESTCHESTER TOWNHOUSES, SECTION 4
PLAN NUMBER: 11CP0006/10-0171
ORIGINAL PLAN DATE: 7/16/10
REVIEW DATE: 8/23/10
LATEST SUBMISSION DATE: 8/10/10
SUBMITTAL NUMBER: 1
STATUS: REVISIONS REQUIRED
TABLE REVIEW: NO
1. A COPY OF VIRGINIA DEPARTMENT OF TRANSPORTATION'S
APPROVAL LETTER REGARDING PAVEMENT REPLACEMENT, METHOD OF
CROSSING, AND ALIGNMENT OF UTILITY WITH STATE RIGHT OF WAY,
AND A COPY OF ENVIRONMENTAL ENGINEERING'S INITIAL REVIEW
LETTER MUST BE SUBMITTED BEFORE REVISED PLANS ARE SUBMITTED
FOR RE-REVIEW.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION, A COPY
OF THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER AND/OR ALL
OTHER APPLICABLE LOCAL STATE AND FEDERAL AGENCIES' APPROVAL
LETTERS MUST BE RECEIVED BY THIS DEPARTMENT. IN ADDITION,
ALL EASEMENTS NOT INCLUDED WITH THE SUBDIVISION PLAT MUST
BE DEDICATED WITH A SEPARATE PLAT AND AGREEMENT TO THE
COUNTY PRIOR TO RELEASING THE PROJECT TO THE CONSTRUCTION
SECTION.
3. SHOW THE COUNTY PROJECT NUMBER 10-0171 ON THE LOWER
RIGHT HAND CORNER OF EACH SHEET.
4. SHOW ALL EXISTING WATERLINES USING A "DARK, DASHED"
LINE TYPE.
5. PROVIDE A SIGNED COMPLETED "WATER METER SIZING FORM"
FOR EACH PROPOSED IRRIGATION METER.
6. CONSPICUOUSLY DISPLAY EACH OF THE FOLLOWING NOTES:
A. THE CONTRACTOR SHALL USE A MECHANICAL HOLE CUTTER WHEN
TAPPING THE EXISTING SEWER LINE.
B. FOR EACH LOT THAT "FRONTS" ON A SIDEWALK, THE "FRONT"
SIDE OF THE WATER METER BOX IS TO BE LOCATED 3 LF FROM
THE "HOUSE" SIDE OF THE SIDEWALK.
7. THE WATERLINE THAT IS PROPOSED TO BE VERTICALLY
DEFLECTED DOES NOT APPEAR TO BE SHOWN CORRECTLY IN THE
PROFILE VIEW. SHOULD NOT THE 90 º HORIZONTAL BEND BE
LOCATED PAST THE LAST 45 º BEND? REVISE AS NECESSARY
INCLUDING ALL CALCULATIONS PERFORMED TO DETERMINE THE
LENGTHS OF PIPE REQUIRING JOINT RESTRAINT AND CLEARLY SHOW
THOSE LENGTHS IN THE PROFILE VIEW. IN ADDITION, PROVIDE A
COPY OF DETAIL DRAWING NUMBER WAT-8 ON THE PLANS, REFERENCIN
8. REVISE ALL DRAFTING AS NOTED IN RED.
9. REVISE THE "MATERIALS LIST" AS NECESSARY.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: WESTCHESTER TOWNHOUSES, SECTION 4
PLAN NUMBER: 11CP0006
ORIGINAL PLAN DATE: 7/16/10
REVIEW DATE: 1/3/11
LATEST SUBMISSION DATE: 12/21/10
SUBMITTAL NUMBER: 2
STATUS: REVISIONS REQUIRED
TABLE REVIEW: N/A
1. A COPY OF VIRGINIA DEPARTMENT OF TRANSPORTATION'S
APPROVAL LETTER REGARDING PAVEMENT REPLACEMENT, METHOD OF
CROSSING, AND ALIGNMENT OF UTILITY WITH STATE RIGHT OF WAY,
AND A COPY OF ENVIRONMENTAL ENGINEERING'S INITIAL REVIEW
LETTER MUST BE SUBMITTED BEFORE REVISED PLANS ARE SUBMITTED
FOR RE-REVIEW.
2. PRIOR TO RELEASING TO THE CONSTRUCTION SECTION, A COPY
OF THE ENVIRONMENTAL ENGINEERING APPROVAL LETTER AND/OR ALL
OTHER APPLICABLE LOCAL STATE AND FEDERAL AGENCIES' APPROVAL
LETTERS MUST BE RECEIVED BY THIS DEPARTMENT. IN ADDITION,
ALL EASEMENTS NOT INCLUDED WITH THE SUBDIVISION PLAT MUST
BE DEDICATED WITH A SEPARATE PLAT AND AGREEMENT TO THE
COUNTY PRIOR TO RELEASING THE PROJECT TO THE CONSTRUCTION
SECTION.
3. FOLLOWING ADDITIONAL INTEROFFICE DISCUSSION, IT HAS
BEEN DETERMINED THAT THE APPLICABLE DETAIL TO BE USED IN
THIS CASE IS "TYPICAL PLAN VIEW OF PROPOSED 2" OR SMALLER
SINGLE FAMILY RESIDENTIAL FIRE LINE SYSTEMS (WITH DOMESTIC
SERVICE LINES)", DETAIL DRAWING NUMBER FIR-1B, 1 / 4 (LAST
REVISED JANUARY, 2005). PROVIDE A COPY OF THIS DETAIL ON
THE PLAN VIEW SHEET AND PROCEED EXACTLY AS NOTED THEREIN.
4. PROVIDE A "BLOW-UP" DETAIL OF THE FIRE LINE AND
DOMESTIC SERVICE ARRANGEMENT TYPICAL FOR THIS PROJECT WITH
ALL APPLICABLE SIZES AND SEPARATION DISTANCES NOTED.
5. PROVIDE COPIES OF ALL CALCULATIONS PERFORMED TO
DETERMINE THE DISTANCE BEYOND THE PROPOSED 90? BEND THAT
JOINT RESTRAINT WILL BE REQUIRED CLEARLY NOTING THAT
DISTANCE IN THE PROFILE VIEW.
6. ALL RESTRAINED JOINT WATERLINE IS TO BE SPECIFIED AS
DUCTILE IRON, CLASS 52 MINIMUM AND CLEARLY NOTED AS SUCH AT
EACH APPLICATION LOCATION THROUGHOUT THE PLANS.
7. DELETE THE PROPOSED FIRE HYDRANT AT THE NORTHERN POINT
OF THE PROPOSED WATERLINE IN PERDUE SPRINGS COURT AND
PROVIDE A 6" PLUG AND 2" FLUSHING HYDRANT.
8. PROVIDE A DETAILED PROFILE VIEW OF EVERY FOOT OF
WATERLINE PROPOSED WITH THIS PROJECT.
9. REVISE ALL DRAFTING AS NOTED IN RED.
10. REVISE THE "MATERIALS LIST" AS NECESSARY.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: WESTCHESTER TOWNHOUSES, SECTION 4
PLAN NUMBER: 11CP0006
ORIGINAL PLAN DATE: 7/16/10
REVIEW DATE: 2/14/11
LATEST SUBMISSION DATE: 2/2/10
SUBMITTAL NUMBER: 3
STATUS: APPROVED
TABLE REVIEW: N/A
IN REGARD TO YOUR RECENT SUBMITTAL OF THE REVISED UTILITIES
PLANS ON THE ABOVE REFERENCED PROJECT DATED JULY 16,
2010, WITH THE LAST REVISION DATED JANUARY 14, 2011, THIS
IS TO INFORM YOU THAT THE PLANS HAVE BEEN REVIEWED BY THE
UTILITIES DEPARTMENT WITH NO EXCEPTIONS TAKEN. THIS REVIEW
IS EFFECTIVE UNTIL FEBRUARY 14, 2016.
PLEASE FORWARD TWO (2) ADDITIONAL SETS OF PLANS ONCE ALL
APPROVALS HAVE BEEN OBTAINED. IF, AFTER ALL OTHER
REVIEWS/APPROVALS HAVE BEEN MADE, THE UTILITY PLANS REFLECT
A LATER REVISION DATE THAN THE LAST REVISION NOTED ABOVE,
PLEASE SUBMIT TWO (2) NEW SETS OF UTILITY PLANS FOR FURTHER
REVIEW AND APPROVAL.
YOUR COOPERATION IS GREATLY APPRECIATED. PLEASE CALL ME AT
748-1343 IF YOU HAVE ANY FURTHER QUESTIONS REGARDING THIS
MATTER.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: UTILITIES
REVIEW/PHONE #: BILL VIER/748-1343
PLAN NAME: WESTCHESTER TOWNHOUSES, SECTION 4
PLAN NUMBER:11CP0006
ORIGINAL PLAN DATE:7/16/10
REVIEW DATE:8/13/14
LATEST SUBMISSION DATE:8/4/14
SUBMITTAL NUMBER:4
STATUS: APPROVED
TABLE REVIEW: NO
IN REGARD TO YOUR RECENT SUBMITTAL OF THE REVISED UTILITIES
PLANS ON THE ABOVE REFERENCED PROJECT DATED JULY 16, 2010,
WITH THE LAST REVISION DATED MAY 1, 2014, THIS IS TO INFORM
YOU THAT THE PLANS HAVE BEEN REVIEWED BY THE UTILITIES
DEPARTMENT WITH NO EXCEPTIONS TAKEN. THIS REVIEW IS
EFFECTIVE UNTIL AUGUST 13, 2019.
PLEASE FORWARD TWO (2) ADDITIONAL SETS OF PLANS ONCE ALL
APPROVALS HAVE BEEN OBTAINED. IF, AFTER ALL OTHER
REVIEWS/APPROVALS HAVE BEEN MADE, THE UTILITY PLANS REFLECT
A LATER REVISION DATE THAN THE LAST REVISION NOTED ABOVE,
PLEASE SUBMIT TWO (2) NEW SETS OF UTILITY PLANS FOR FURTHER
REVIEW AND APPROVAL.
YOUR COOPERATION IS GREATLY APPRECIATED. PLEASE CALL ME AT
748-1343 IF YOU HAVE ANY FURTHER QUESTIONS REGARDING THIS
MATTER.
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: JESSE W. SMITH, P.E. (804)748-1998
NAME OF PLAN: WESTCHESTER TOWNHOUSES, SECTION 4
CASE NUMBER: 11CP0006
LATEST PLAN DATE: 07/16/10
DEPT. REC'D. DATE: 08/05/10
SUBMITTAL NUMBER: ONE
REVIEW DATE: 08/24/10
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
============================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: JESSE W. SMITH, P.E. (804)748-1998
NAME OF PLAN: WESTCHESTER TOWNHOUSES, SECTION 4
CASE NUMBER: 11CP0006
LATEST PLAN DATE: 12/13/10
DEPT. REC'D. DATE: 12/22/10
SUBMITTAL NUMBER: TWO
REVIEW DATE: 01/07/10
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
============================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: JESSE W. SMITH, P.E. (804)748-1998
NAME OF PLAN: WESTCHESTER TOWNHOUSES, SECTION 4
CASE NUMBER: 11CP0006
LATEST PLAN DATE: 01/14/11
DEPT. REC'D. DATE: 02/02/11
SUBMITTAL NUMBER: THREE
REVIEW DATE: 02/21/11
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
============================================================
REVIEW DEPARTMENT: CHESTERFIELD TRANSPORTATION DEPARTMENT
REVIEWER/PHONE#: STEVEN E. SIMONSON, P.E. (804)748-1037
NAME OF PLAN: WESTCHESTER TOWNHOUSES, SECTION 4
CASE NUMBER: 11CP0006
LATEST PLAN DATE: XX/XX/XX
DEPT. REC'D. DATE: 08/22/14
SUBMITTAL NUMBER: FOUR
REVIEW DATE: 09/02/14
RECOMMENDATION: APPROVED
TABLE REVIEW: YES
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : AMY SOMERVELL / 751-4321
PLAN NAME : WESTCHESTER SECTION 4
PLAN NUMBER : 11CP0006
ORIGINAL PLAN DATE : 7-16-10
REVIEW DATE : 8-19-10
LATEST SUBMISSION DATE : 7-28-10
SUBMITTAL NUMBER : 1
STATUS : REVISIONS REQUIRED
TABLE REVIEW : NO
1. PLEASE PROVIDE ARCHITECTURAL RENDERINGS FOR
PROPOSED UNITS
2. PLEASE PROVIDE A STREET TREE PLAN
3. PLEASE PROVIDE A DETAILED SKETCH OF THE ACTIVE
RECREATIONAL AREA LOCATED IN THE NORTHERN PORTION OF
THE COMMON OPEN SPACE.
4. ZONING CONDITION 15 OF CASE 80SN0129 REQUIRES A 75
FOOT BUFFER TO BE LOCATED ALONG THE EASTERN BOUNDARY
OF THIS PROPERTY, ADJACENT TO THE COMMERCIAL ZONED
PROPERTY. PLEASE PROVIDE THE 50' BUFFER WITHIN THE
BOUNDARY OF THIS CONSTRUCTION PLAN. WE CAN FURTHER
DISCUSS THE BUFFER WIDTH IN CONJUNCTION WITH
PROPOSED UNITS AND PLANTING REQUIREMENTS.
STANDARD COMMENTS:
· STANDARD COMMENT: ANY BULK REQUIREMENTS (LOT AREA, LOT
WIDTH, SETBACKS, BUILDING ENVELOPES, ETC.) SHOWN ON THE
APPROVED CONSTRUCTION PLANS WILL BE SUBJECT TO REVIEW FOR
COMPLIANCE AT TIME OF FINAL CHECK.
· STANDARD COMMENT: BUFFER IS EXCLUSIVE OF EASEMENTS
AND SETBACKS. BUFFER MUST REMAIN IN A NATURAL STATE.
BUFFER WILL BE FIELD REVIEWED AT TIME OF FINAL CHECK. ANY
CLEARING OR REMOVAL OF VEGETATION FROM BUFFER WILL RESULT IN
LANDSCAPE PLAN SUBMITTAL AND BOND AT FINAL CHECK.
· RETAINING WALL STANDARD NOTE: RETAINING WALLS ARE
SUBJECT TO REVIEW AT TIME OF TENTATIVE AND CONSTRUCTION
PLAN REVIEW. RETAINING WALLS SHALL BE RECORDED IN OPEN
SPACE IF THE WALL IS SEVEN (7') FEET OR GREATER IN HEIGHT
AND SPANS TWO OR MORE LOTS IN A SINGLE-FAMILY
DEVELOPMENT OR IS LOCATED IN A RESIDENTIAL TOWNHOUSE
DEVELOPMENT.
*NOTE: THIS E-MAIL NOTIFICATION IS BEING SENT TO REPORT THE
PLANNING DEPARTMENT'S STATUS OF THE ABOVE MENTIONED RT THE
CONSTRUCTION PLANS. THE STATUS REPORTED ABOVE IS SOLELY
INTENDED FOR THE REVISION NOTED ABOVE. FINAL APPROVAL IS
DETERMINED BY THE ENVIRONMENTAL ENGINEERING DEPARTMENT FOR
ALL CONSTRUCTION PLAN SUBMITTALS.
SUBDIVISION ORDINANCE REFERENCE: SEC. 17-32 (A)(5); SEC. 17-
(B)(1)(D); SEC. 17-43; SEC. 17-70 ZONING ORDINANCE REFERENC
SEC. 19-518
*** UPDATED COMMENTS 8-26-10
PLANNING HAS UPDATED THE BUFFER COMMENT TO REFLECT A 50'
BUFFER INSTEAD OF A 75' BUFFER AT THE DIRECTION OF GREG
ALLEN.
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : AMY SOMERVELL / 751-4321
PLAN NAME : WESTCHESTER SECTION 4
PLAN NUMBER : 11CP0006
ORIGINAL PLAN DATE : 7-16-10
REVIEW DATE : 1-5-11
LATEST SUBMISSION DATE : 12-15-10
SUBMITTAL NUMBER : 2
STATUS : REVISIONS REQUIRED
TABLE REVIEW : NO
1.AS PREVIOUSLY REQUESTED: PLEASE PROVIDE ARCHITECTURAL
RENDERINGS FOR PROPOSED UNITS
2. ZONING CONDITION 15 OF CASE 80SN0129 REQUIRES A 75
FOOT BUFFER TO BE LOCATED ALONG THE EASTERN BOUNDARY
OF THIS PROPERTY, ADJACENT TO THE COMMERCIAL ZONED
PROPERTY. PLEASE PROVIDE THE 50' BUFFER WITHIN THE
BOUNDARY OF THIS CONSTRUCTION PLAN APPROVED BY
GREG ALLEN. PLEASE SHOW THE REMAINING 25' OF BUFFER ON THE
COMMERCIAL PROPERTY IN GHOST TO REFLECT THE ENTIRE
75' BUFFER REQUIREMENT.
3. LABEL THE COMMON AREA. THIS SHALL BE RECORDED WITH
SECTION 4.
4. THE LANDSCAPE PLAN/STREET TREE/ PLAY GROUND SUBMITTED
DOES REQUIRE A REVISION. COMMENTS WERE SENT DIRECTLY TO
DAVID LISOWSKI.
5. CORRECT THE VICINITY MAP TO REFLECT THE COMMON AREA
IN SECTION 4.
6. THE PLAY AREA SHALL BE CONSTRUCTED CONCURRENTLY .
WITH SECTION 4.
NOTES:
ALL PREVIOUS NOTES FROM 1ST REVIEW STILL APPLY.
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : AMY SOMERVELL / 751-4321
PLAN NAME : WESTCHESTER SECTION 4
PLAN NUMBER : 11CP0006
ORIGINAL PLAN DATE : 7-16-10
REVIEW DATE : 2-23-11
LATEST SUBMISSION DATE : 1-31-11
SUBMITTAL NUMBER : 3
STATUS : ADDITIONAL INFORMATION REQUIRED
TABLE REVIEW : YES
1.AS PREVIOUSLY REQUESTED: PLEASE PROVIDE ARCHITECTURAL
RENDERINGS FOR PROPOSED UNITS
AS PREVIOUSLY REQUESTED:
2. THE LANDSCAPE PLAN/STREET TREE/ PLAY GROUND SUBMITTED
DOES REQUIRE A REVISION. COMMENTS WERE SENT DIRECTLY TO
DAVID LISOWSKI.
AS PREVIOUSLY REQUESTED:
3. ZONING CONDITION 15 OF CASE 80SN0129 REQUIRES A 75
FOOT BUFFER TO BE LOCATED ALONG THE EASTERN BOUNDARY
OF THIS PROPERTY, ADJACENT TO THE COMMERCIAL ZONED
PROPERTY. PLEASE PROVIDE THE 50' BUFFER WITHIN THE
BOUNDARY OF THIS CONSTRUCTION PLAN APPROVED BY
GREG ALLEN. PLEASE SHOW THE REMAINING 25' OF BUFFER ON THE
COMMERCIAL PROPERTY IN GHOST TO REFLECT THE ENTIRE
75' BUFFER REQUIREMENT.
CONDITION:
1.THE PLAY AREA SHALL BE CONSTRUCTED CONCURRENTLY
WITH SECTION 4.
2. STANDARD CONDITIONS
STANDARD COMMENT: ANY BULK REQUIREMENTS (LOT AREA, LOT
WIDTH, SETBACKS, BUILDING ENVELOPES, ETC.) SHOWN ON THE
APPROVED CONSTRUCTION PLANS WILL BE SUBJECT TO REVIEW FOR
COMPLIANCE AT TIME OF FINAL CHECK
STANDARD COMMENT: BUFFER IS EXCLUSIVE OF EASEMENTS
AND SETBACKS. BUFFER MUST REMAIN IN A NATURAL STATE.
BUFFER WILL BE FIELD REVIEWED AT TIME OF FINAL CHECK. ANY
CLEARING OR REMOVAL OF VEGETATION FROM BUFFER WILL
RESULT IN LANDSCAPE PLAN SUBMITTAL AND BOND AT FINAL CHECK.
RETAINING WALL STANDARD NOTE: RETAINING WALLS ARE
SUBJECT TO REVIEW AT TIME OF TENTATIVE AND CONSTRUCTION
PLAN REVIEW. RETAINING WALLS SHALL BE RECORDED IN OPEN
SPACE IF THE WALL IS SEVEN (7') FEET OR GREATER IN HEIGHT
AND SPANS TWO OR MORE LOTS IN A SINGLE-FAMILY
DEVELOPMENT OR IS LOCATED IN A RESIDENTIAL TOWNHOUSE
DEVELOPMENT.
REVIEWER / PHONE # : WHIT KIRTLEY / 706-7691
PLAN NAME : WESTCHESTER SECTION 4
PLAN NUMBER : 11CP0006
ORIGINAL PLAN DATE : 7-16-10
REVIEW DATE : 8-21-14
LATEST SUBMISSION DATE : 8/1/14
SUBMITTAL NUMBER : 4
STATUS : ADDITIONAL INFORMATION REQUIRED
TABLE REVIEW : YES
1.AS PREVIOUSLY REQUESTED: PLEASE PROVIDE
ARCHITECTURAL RENDERINGS FOR PROPOSED UNITS
CONDITION:
1.THE PLAY AREA SHALL BE CONSTRUCTED CONCURRENTLY
WITH SECTION 4.
2. STANDARD CONDITIONS
STANDARD COMMENT: ANY BULK REQUIREMENTS (LOT
AREA, LOT WIDTH, SETBACKS, BUILDING ENVELOPES, ETC.)
SHOWN ON THE APPROVED CONSTRUCTION PLANS WILL
BE SUBJECT TO REVIEW FOR COMPLIANCE AT TIME OF
FINAL CHECK
STANDARD COMMENT: BUFFER IS EXCLUSIVE OF
EASEMENTS AND SETBACKS. BUFFER MUST REMAIN IN A
NATURAL STATE. BUFFER WILL BE FIELD REVIEWED AT
TIME OF FINAL CHECK. ANY CLEARING OR REMOVAL OF
VEGETATION FROM BUFFER WILL RESULT IN LANDSCAPE
PLAN SUBMITTAL AND BOND AT FINAL CHECK. RETAINING
WALL STANDARD NOTE: RETAINING WALLS ARE SUBJECT
TO REVIEW AT TIME OF TENTATIVE AND CONSTRUCTION
PLAN REVIEW. RETAINING WALLS SHALL BE RECORDED IN
OPEN SPACE IF THE WALL IS SEVEN (7') FEET OR GREATER
IN HEIGHT AND SPANS TWO OR MORE LOTS IN A SINGLE-
FAMILY DEVELOPMENT OR IS LOCATED IN A RESIDENTIAL
TOWNHOUSE DEVELOPMENT
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: WESTCHESTER TOWNHOUSES SECTION 4
PLAN NUMBER: 11CP0006
ORIGINAL PLAN DATE: 07/16/10
REVIEW DATE: 8/25/10
LATEST SUBMISSION DATE: 8/05/10
SUBMITTAL NUMBER: 1
STATUS: REVISION REQUIRED
TABLE REVIEW: NO
1) IT DOES NOT LOOK LIKE EITHER ONE OF THE BUILDINGS MEET
THE HOSE LAY REQUIREMENTS. THE FIRE APPARATUS ACCESS ROAD
SHALL COMPLY WITH THE REQUIREMENTS OF THIS SECTION AND
SHALL EXTEND TO WITHIN 150 FEET OF ALL PORTION OF THE
FACILITY AND ALL PORTIONS OF THE EXTERIOR WALLS OF THE FIRST
STORY OF THE BUILDING AS MEASURED BY AN APPROVED ROUTE
AROUND THE EXTERIOR OF THE BUILDING OR FACILITY.
IFC 2006, 503.1
2) ALL FIRE ACCESS ROADS SHALL BE CONSTRUCTED OF AN ALL
WEATHER SURFACE AND THE MINIMUM ROAD DESIGN WEIGHT BEARING
CAPACITY FOR EMERGENCY FIRE APPARATUS TRAVEL SHALL BE 75,000
POUNDS. THE GEOTECHNICAL REPORT SHALL BE SUBMITTED TO THE
CHESTERFIELD FIRE & EMS DEPARTMENT, DIVISION OF FIRE AND
LIFE SAFETY, PRIOR TO THE ISSUANCE OF A CERTICATE OF
OCCUPANCY. A NOTE TO THIS EFFECT SHALL BE PLACED IN THE
GENERAL NOTES SECTION OF THE PLAN. IFC 2006, D102.1
3) THE MINIMUM TURNING RADIUS TO BE PROVIDED FOR EMERGENCY
FIRE APPARATUS TO TRAVEL, INCLUDING CUL-DE-SACS, SHALL BE AT
LEAST 42' (OUTSIDE). THE TURNING RADIUS SHALL BE DEMONSTRATE
ON THE PLAN BY TEMPLATE. IFC 2006, D103.3
4) WILL THE BUILDINGS BE THE SAME AS SECTION 2 AND 3? IF
NOT, PLEASE PROVIDE A SET OF ARCHITECTURAL PLANS THAT ARE TO
SCALE SHOWING THE HEIGHT OF THE BUILDING TO THE MIDLINE OF
THE ROOF.
5) ON SHEET C3 THE NOTE THAT REFERENCES THE FIRE LANES IS
SHOWING THAT YOU COULD SEE THE DETAIL ON SHEET C13A IT
SHOULD BE SHEET C11.
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: WESTCHESTER TOWNHOUSES SECTION 4
PLAN NUMBER: 11CP0006
ORIGINAL PLAN DATE: 07/16/10
REVIEW DATE: 1/11/11
LATEST SUBMISSION DATE: 12/21/10
SUBMITTAL NUMBER: 2
STATUS: REVISION REQUIRED
TABLE REVIEW: NO
BASED ON CONVERSATION WITH CHIEF DAWSON THE PLANS
WILL NEED TO BE REVISED AND THE LETTER REQUESTING FOR A
CODE MODIFICATION WILL NEED TO REFLECT NOT JUST THE
HOSE LAY REQUIREMENTS. THIS PROJECT DOES NOT MEET THE
TURNING RADIUS AT ALL OF THE ENTRANCES, PROXIMITY OF THE
BUILDINGS IS NOT MET, AND WIDTH OF THE ROADS DOES NOT MEET
THE 26 FEET THAT IS REQUIRED DUE TO AERIAL ACCESS. PLEASE
REFER TO IFC 2006, APPENDIX D105 AND IFC 2006, 503.1
EVEN THOU THE BUILDINGS ARE GOING TO BE SPRINKLE THERE ARE
SOME REQUIREMENTS THAT SHALL BE MET. PLEASE ADDRESS ITEM
NUMBER 2 FROM THE PREVIOUS REVIEW.
IF THE FIRE LINE DESIGN IS GOING TO CHANGE MAKE SURE THE
CORRECT DETAIL IS SHOWN ON THE PLANS.
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
THE FOLLOWING SHALL BE ADDED TO THE PLANS."APPROVAL OF THE
SPRINKLER SYSTEM UNDERGROUND PIPING. PRIOR TO INSTALLATION,
SHOP DRAWINGS AND A SEPARATE PERMIT APPLICATION SHALL BE
SUBMITTED THROUGH THE DEPARTMENT OF BUILDING INSPECTIONS
FOR REVIEW AND APPROVAL."
THERE IS A LATER REVISION DATE FOR THE FIR-1 DETAIL. PLEASE
UPDATE THE DETAIL TO THE LATEST REVISION DATE. REFER TO THE
UTILITIES SPECIFICATIONS ON THE INTERNET.
PLACE A COPY OF THE REQUEST FOR THE CODE MODIFICATION, AS WE
WELL AS, THE REPLY ON THE CONSTRUCTION PLANS.
+++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: WESTCHESTER TOWNHOUSES SECTION 4
PLAN NUMBER: 11CP0006
ORIGINAL PLAN DATE: 07/16/10
REVIEW DATE: 2/23/11
LATEST SUBMISSION DATE: 2/3/11
SUBMITTAL NUMBER: 3
STATUS: APPROVED
TABLE REVIEW
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
REVIEW DEPARTMENT: FIRE AND LIFE SAFETY
REVIEWER / PHONE#: KIM LESTER / 748-1489
PLAN NAME: WESTCHESTER TOWNHOUSES SECTION 4
PLAN NUMBER: 11CP0006
LATEST REVISION DATE: 5/1/2014
REVIEW DATE: 8/12/14
LATEST SUBMISSION DATE: 8/4/14
SUBMITTAL NUMBER: 4
STATUS: APPROVED
TABLE REVIEW
NOTE:
PRIOR TO INSTALLATION OF THE UNDERGROUND FIRE LINE AND
SPRINKLER SYSTEM, A SEPARATE FIRE PERMIT WILL NEED TO BE
APPLIED FOR AND SHALL BE SUBMITTED THROUGH THE
DEPARTMENT OF BUILDING INSPECTIONS FOR REVIEW AND
APPROVAL.
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
=========================================================
=========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : LYNDA GILBERTSON, P.E. / 706-2116
NAME OF PLAN : WESTCHESTER TOWNHOUSES SECTION 4
SITE PLAN NO. : 11CP0006
LATEST PLAN DATE : 8-4-10
DEPT. REC'D DATE : 8-5-10
SUBMITTAL NUMBER : 2
REVIEW DATE : 8-16-10
RECOMMENDATION : REVISIONS REQUIRED
TABLE REVISION : NO
========== EROSION CONTROL ========
1. SUBMIT AN ITEMIZED COST ESTIMATE FOR REVIEW OF THE
EROSION AND SEDIMENT CONTROL BOND AMOUNT.
2. AS A PREREQUISITE TO ISSUANCE OF A LAND DISTURBANCE
PERMIT:
A. A PROCESSED VSMP REGISTRATION AND FEE FORM MUST BE
RECEIVED.
B. EROSION AND SEDIMENT CONTROL BOND MUST BE POSTED.
C. A COPY OF THE VDOT LAND USE PEMIT MUST BE RECEIVED
D. TWO ADDITIONAL COPIES OF THE CONSTUCTION PLANS TO BE
STAMPED APPROVED FOR CONSTRUCTION" MUST RECEIVED.
E. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
DISKETTE/CD, THE FORMAT OF WHICH SHALL BE AUTOCAD.DWG
OR DXF, MUST BE SUBMITTED TO CAROLE CLIBORNE OF
ENVIRONMENTAL ENGINEERING. THE DISKETTE/CD MUST
CONTAIN THE FOLLOWING, EACH IN A SEPARATE LAYER:
I.EDGES OF IMPERVIOUS AREA OF ROADS TO INCLUDE C&G
AND EDGES OF SIDEWALKS.
II. THE STORM SEWER SYSTEM AND ALL CULVERTS. A LAYER
REPORT PRINTED FROM AUTOCAD MUST BE SUBMITTED WITH
THE DISKETTE/CD. ARCGIS SHAPEFILES SHOULD HAVE EACH
ITEM CLEARLY IDENTIFIED IN THE ATTRIBUTE TABLE. BOTH
THE SUBDIVISION NAME AND SECTION, SUBDIVSION PLAN
NUMBER, AND THE ENGINEERING FIRM. ALL AUTOCAD FILES
MUST BE REFERENCED DIRECTLY TO VIRINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, IN THE NAD83 DATUM.
III.ALL JURISDICTIONAL WETLAND AREAS AND OR WATERS OF THE
STATE.
IV. STREAMS AND OTHER WATER BODIES.
V. LOCATIONS OF FIELD VERFIED RESOURCE PROTECTION AREA
DESIGNATIONS TO INCLUDE, WATER BODIES WITH PERNNIAL
FLOW, TIDAL SHORES, TIDAL WETLANDS, NON-TIDAL
WETLANDS, CONNECTED AND CONTIGUOUS TO TIDAL WETLANDS
OR PERNNIAL FLOW.
IV. LOCATIONS OF PERNNIAL FLOW ORIGINS AND THEIR
ASSOCIATED GPS COORDINATES (NAD83 STATE PLANE VA
SOUTH FEET).
IIV.LOCATION(S) OF BREAK POINT(S) IN SURFACE FLOW AND/OR
NON-CONTIGUOUS WETLANDS AND THEIR ASSOCIATED GPS
COORDINATES (NAD83 STATE PLANE VE SOUTH FEET).
XI.FLOOD PLAINS.
3.INCLUDE IN THE MS-19 TABLE ON SHEET C7 THE INCREASE
IN IMPERVIOUS AREA TO STRUCTURES 12 AND 79. THE
ADEQUACY SITUATIONS WILL BE D AND E TO ENSURE THE
10-YEAR IS CONTAINED WITHIN THE EXISTING PIPE SYSTEM
AND THE DISCHARGE INTO THE SWM / BMP. A VARIANCE
REQUEST WILL BE REQUIRED.
4.PLEASE DELETE FROM THE ADEQUANCY SITUATION B
DESCRIPTION ABOVE THE MS-19 TABLE ON SHEET C7 THE
FOLLOWING SENTENCE (EXCEPT C AND Q ARE NOT APPLICABLE
IF THE CHANNEL IS IN THE 100-YEAR FLOODPLAIN, RPA OR
WETLANDS). THIS SETENCE IS NOT APPLICABLE TO THE
SITUATION.
5.A NOTE MUST BE ADDED TO THE PHASE 1 SEQUENCE OF
CONSTRUCTION ON SHEET C5 STATING THAT THE CERTIFIED
RESPONSIBLE LAND DISTURBER (CRLD) AND THE
ENVIRONMENTAL ENGINEERING INSPECTOR MUST MEET TO
INSPECT EC MEASURES BEFORE PROCEEDING TO PHASE 2.
6.ADJUST THE TEMPORARY DIVERSION DIKE TO TURN AT THE
125 CONTOUR LINE AT THE TOE OF THE SLOPE AND
DISCHARGE INTO SEDIMENT TRAP #2 ON SHEET C5.
7.SHOW AND LABEL THE APPROXIMATE LIMITS OF THE EXISTING
SOIL STOCKPILE WITHIN THE SECTION LIMITS ON SHEET C5.
8.INCLUDE A NOTE ON SHEET C6 THAT NO SEDIMENT TRAPS
WILL BE REMOVED WITHOUT ENVIRONMENTAL ENGINNERING
APPROVAL.
9.INCLUDE THE FOLLOWING NOTE ON SHEET C6 "THE
CONTRACTOR IS RESPONSIBLE FOR THE INSTALLATION OF
ANY ADDITIONAL EROSION CONTROL MEASURES NECESSARY TO
PREVENT EROSION AND SEDIMENTATION AS DETERMINED BY
THE ENVIRONMENTAL ENGINEERING DEPARTMENT".
10.GHOST LABEL THE PROPERTY LINE AND LOTS NUMBERS ON
SHEET C5 AND C6.
11.THE DRAINAGE AREA, SPILLWAY LENGTH, AND THE LENGTH
AND WIDTH DIMENSIONS IN TABULAR FORM NECESSARY TO
ACHIEVE THE REQUIRED STORAGE VOLUMES IN ACCORDANCE
WITH STD. & SPEC. 3.13 MUST BE SHOWN ON SHEET C7.
THE ELEVATIONS OF THE TRAP BOTTOM, TOP OF WET VOLUME,
TOP OF DRY VOLUME, TOP OF EMBANKMENT AND THE 1:1 OR
FLATTER EXCAVATED SIDE SLOPES MUST BE SHOWN ON THE
SEDIMENT TRAP DETAIL.
12.DELETE EROSION CONTROL GENERAL NOTES #8, 9 AND 10
FROM SHEET C7. THE BMP HAS BEEN CERTIFIED ON
12/5/01, THE BMP EASEMENT RECORDED ON 4/30/97 AND
THERE ARE NO SEDIMENT BASINS REQUIRED FOR THE
PROJECT.
13.COMPLETE THE MS-4 TABLE COLUMNS AND INFORMATION,
ORGINAL BMP AND WORKSHEET A CALCULATIONS CAN BE
OBTAINED FROM ENVIRONMENTAL ENGINEERING DEPARTMENT.
======== ROAD AND DRAINAGE ========
1.AS A REMINDER TENTATIVE CONDITION #3 STATES PRIOR TO
RECORDATION OF LOTS 50-67 ALL ISSUES RELATED TO THE
LAKE AS DISCUSSED IN THE ENVIRONMENTAL ENGINEERING
REPORT OF DECEMBER 10, 2004 SHALL HAVE BEEN
SATISFACTORILY ADRESSED.
A. INCLUDE AS AN EMBOLDEN NOTE ON THE COVER
SHEET.
B. REVISE NOTE 1 ON SHEET C3 TO READ "SWM/BMP
MAINTENANCE TO BE COMPLETED PRIOR TO RECORDATION"
2.AS A REMINDER THE BMP MAINTENANCE FEE FOR TOWNHOUSES
OF $100/UNIT MUST BE RECEIVED PRIOR TO RECORDATION.
3.PER TENTATIVE CONDITION #6 "THE USACOE JUSDICTIONAL
WETLANDS SHALL BE SHOWN ON THE CONSTRUCTION PLANS AND
SUBDIVISION PLAT." PLEASE INCLUDE THE LIMITS OF THE
WETLANDS ON SHEETS C4 OR C5.
4.PER TENTATIVE CONDITION #8 "ROOF GUTTERS AND
DOWNSPOUTS SHALL BE INSTALLED ON THE DWELLLINGS. ALL
ROOF DRAINAGE LEADERS WILL BE TIED DIRECTLY INTO
STORM SEWER OR OTHER CONVEYANCE SYSTEMS DEEMED
APPROPRIATE BY THE ENVIRONMENTAL ENGINEERING
DEPARTMENT."
I.REVISE THE SIX-INCH INSERTA TEE ON SHEET C3 TO
TEN-INCH TO ACCOMADATE THE TEN-INCH HDPE
CONNECTING TO STRUCTURE 33A.
II.SHOW AND LABEL A MANHOLE STRUCTURE AT THE
MECHANICAL BOOT CONNECTION OF THE HDPE ROOF DRAINS
PROVIDE MAINTENACE ACCESS (SHEET C4).
5.SHOW AND LABEL CLEAN OUTS AT EACH CHANGE IN DIAMETER
FROM 6-INCH TO 10-INCH AND 90-DEGREE CHANGE IN
DIRECTION OF THE HDPE ROOF DRAIN (SHEET C4).
6.REVISE THE 50' PERIMETER YARD NOTE TO READ "50'
PERIMETER YARD SETBACK" ON SHEETS C4 AND C13.
7.INCLUDE THE MINUMUM CRAWL SPACE ELEVATION DETAIL ON
SHEET C3.
8.AFTER A SITE VITE VISIT THE TOP OF THE EXISTING
UTILITY MANHOLE NUMBER 4 FROM COUNTY PROJECT #940252
IS ABOVE THE FINISHED GRADE. PLEASE INCLUDE A NOTE
ON SHEET 3.
9.REVISE THE VARIBLE WIDTH SWM/BMP EASEMENT DB/PG
NUMBER ON SHEETS C3 AND C13 3040/428 AND 3732 /680.
CORRECT THE LABEL OF THE INGRESS EGRESS EASEMENT DB /
PG 4026 /594 TO REFERENCE THE EASEMENT IN THE
VICINITY OF STRUCTURE 33 AND THE DRAINAGE EASEMENT
3965 / 45.
10.ADDRESS THE CONDITION OF EXISTING STURCTURES 4 AND
79, AFTER A SITE VISIT THE STURCTURE ARE LOCATED
UNDERNEATH THE EXISTING STOCKPILE. WERE THESE
STRUCTURE BLOCKED UP AND WILL NEED TO BE CLEANED?
PLEASE INCLUDE A NOTE ON SHEET C6.
11.PLEASE PROVIDE ADDITIONAL CLARITY IN THE EXISTING
STRUCTURE SCHEDULE ON SHEET C4 INSTALLED WITH SECTION
ONE AND TWO, USE OF A DIFFERENT LINE TYPE OR WEIGHT
WOULD BE BENEFITICAL.
12.VERIFY THE DIAMETER OF STRUCTURES 1, 3 AND 5
INSTALLED WITH SECTION 1 THE PLAN INDICATES 18-INCHES
AND THE STRUCTURE SCHEDULE INDICATE 30", 24" AND 21"
RESPECTIVELY.
13.INCLUDE THE REVISE DATE 8-04-10 NOTED ON THE COVER
SHEET ON SHEETS C4, C7 AND C9.
14.PROVIDE A STROM SEWER PROFILE VIEW FROM THE INLET
STRUCTURES 12 AND 79 TO THE OUTFALL INTO THE SWM/BMP
SWM/BMP(SHEET C10).
============================================================
=========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : LYNDA GILBERTSON, P.E. / 706-2116
PLAN NAME : WESTCHESTER TOWNHOUSES SECTION 4
PLAN NUMBER : 11CP0006
ORIGINAL PLAN DATE : 7-16-10
REVIEW DATE : 1-3-11
LASTEST SUBMISSION DATE : 12-17-10
SUBMITTAL NUMBER : 3
RECOMMENDATION : REVISIONS REQUIRED
TABLE REVISION : NO
========= EROSION CONTROL ==========
1. AS A PREREQUISITE TO ISSUANCE OF A LAND DISTURBANCE
PERMIT:
A. PLANNING DEPARTMENT APPROVAL MUST BE RECEIVED.
B. A PROCESSED VSMP REGISTRATION AND FEE FORM MUST BE
RECEIVED.
C. AN EROSION AND SEDIMENT CONTROL BOND IN THE AMOUNT OF
$29,568 MUST BE POSTED.
D. A COPY OF THE VDOT LAND USE PEMIT MUST BE RECEIVED
E. TWO ADDITIONAL COPIES OF THE CONSTUCTION PLANS TO BE
STAMPED APPROVED FOR CONSTRUCTION" MUST RECEIVED.
F. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
DISKETTE/CD, THE FORMAT OF WHICH SHALL BE AUTOCAD.DWG
OR DXF, MUST BE SUBMITTED TO CAROLE CLIBORNE OF
ENVIRONMENTAL ENGINEERING. THE DISKETTE/CD MUST
CONTAIN THE FOLLOWING, EACH IN A SEPARATE LAYER:
I. EDGES OF IMPERVIOUS AREA OF ROADS TO INCLUDE C&G
AND EDGES OF SIDEWALKS.
II. THE STORM SEWER SYSTEM AND ALL CULVERTS. A LAYER
REPORT PRINTED FROM AUTOCAD MUST BE SUBMITTED WITH
THE DISKETTE/CD. ARCGIS SHAPEFILES SHOULD HAVE EACH
ITEM CLEARLY IDENTIFIED IN THE ATTRIBUTE TABLE. BOTH
THE DISKETTE / CD AND THE REPORT MUST BE LABELED WITH
THE SUBDIVISION NAME AND SECTION, SUBDIVSION PLAN
NUMBER, AND THE ENGINEERING FIRM. ALL AUTOCAD FILES
MUST BE REFERENCED DIRECTLY TO VIRINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, IN THE NAD83 DATUM.
III.ALL JURISDICTIONAL WETLAND AREAS AND OR WATERS OF THE
STATE.
IV. STREAMS AND OTHER WATER BODIES.
V. LOCATIONS OF FIELD VERFIED RESOURCE PROTECTION AREA
DESIGNATIONS TO INCLUDE, WATER BODIES WITH PERNNIAL
FLOW, TIDAL SHORES, TIDAL WETLANDS, NON-TIDAL
WETLANDS, CONNECTED AND CONTIGUOUS TO TIDAL WETLANDS
OR PERNNIAL FLOW.
IV. LOCATIONS OF PERNNIAL FLOW ORIGINS AND THEIR
ASSOCIATED GPS COORDINATES (NAD83 STATE PLANE VA
SOUTH FEET).
IIV.LOCATION(S) OF BREAK POINT(S) IN SURFACE FLOW AND/OR
NON-CONTIGUOUS WETLANDS AND THEIR ASSOCIATED GPS
COORDINATES (NAD83 STATE PLANE VE SOUTH FEET).
XI.FLOOD PLAINS.
2. AS PREVIOUSLY REQUESTED ADJUST THE TEMPORARY DIVERSION
DIKE TO TURN AT THE 125 CONTOUR LINE AT THE TOE OF THE
SLOPE AND DISCHARGE INTO SEDIMENT TRAP #2 ON SHEET C5.
3. APPROVAL OF THE MS-19 VARIANCE REQUEST FOR SITUATION E
ON THE OUTFALL STRUCTURES 1 AND 33A HAS BEEN GRANTED.
============== ROAD AND DRAINAGE ========
1. AS A REMINDER TENTATIVE CONDITION #3 STATES PRIOR TO
RECORDATION OF LOTS 50-67 ALL ISSUES RELATED TO THE
LAKE AS DISCUSSED IN THE ENVIRONMENTAL ENGINEERING
REPORT OF DECEMBER 10, 2004 SHALL HAVE BEEN
SATISFACTORILY ADRESSED.
A. REVISE NOTE 1 ON SHEET C3 TO READ "SWM/BMP ISSUE AND
MAINTENANCE TO BE COMPLETED PRIOR TO RECORDATION" IN
LIEU OF BUILDOUT
2. AS A REMINDER THE BMP MAINTENANCE FEE FOR TOWNHOUSES
OF $100/UNIT MUST BE RECEIVED PRIOR TO RECORDATION.
3. PER TENTATIVE CONDITION #8 "ROOF GUTTERS AND
DOWNSPOUTS SHALL BE INSTALLED ON THE DWELLLINGS. ALL
ROOF DRAINAGE LEADERS WILL BE TIED DIRECTLY INTO
STORM SEWER OR OTHER CONVEYANCE SYSTEMS DEEMED
APPROPRIATE BY THE ENVIRONMENTAL ENGINEERING
DEPARTMENT."
A. INCLUDE THE MANHOLE STRUCTURE 33B IN THE STRUCTURE
SCHEDULE (SHEET C4).
B. REVISE NOTE 3 ON SHEET C4 TO STATE "…TYING INTO
PROPOSED MANHOLE STRUCTURE 33B…" IN LIEU OF EXISTING
STRUCTURE 33.
C. ADD NOTE 4 STATING THAT HDPE ROOF DRAIN
LATERALS/LEADERS ARE PRIVATELY OWED AND MAINTAINED BY
THE HOA.
4. LABEL THE CLEAN OUTS WITH A MORE DISTINGUISHABLE SYMBOL
AT EACH 90-DEGREE CHANGE IN DIRECTION OF THE HDPE ROOF
DRAIN ON SHEET C4.
5. REMOVE THE MINIMUM CRAWL SPACE NOTE AND LABELS FROM
SHEET C3. THE UNITS ARE SLAB-ON-GRADE WITH BF ELEVATIONS
SPECIFIED ON SHEET C4.
=========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : LYNDA GILBERTSON, P.E. / 706-2116
PLAN NAME : WESTCHESTER TOWNHOUSES SECTION 4
PLAN NUMBER : 11CP0006
ORIGINAL PLAN DATE : 7-16-10
REVIEW DATE : 2-7-11
LASTEST SUBMISSION DATE : 1-31-11
SUBMITTAL NUMBER : 3
RECOMMENDATION : REVISION REQUIRED
TABLE REVISION : NO
IT HAS RECENTLY COME TO OUR ATTENTION THAT THE STATE
STORMWATER POLLUTION PREVENTION PLAN (SWPPP)
REQUIREMENTS CONCERNING THE 10-YEAR STORM PEAK
ATTENUATION AND WATER QUALITY COMPLIANCE WHICH VARIES
FROM BAY ACT COMPLIANCE MAY BECOME AN ISSUE DURING THE
STATE SITE INSPECTION PROCESS. COUNTY CONSTRUCTION PLAN
APPROVAL DOES NOT RELIEVE THE OWNER/DEVELOPER OF
RESPONSIBILITY FOR COMPLIANCE TO STATE REGULATIONS -
E.G. VAC50-60-80 FLOODING AND 4VAC50-60-60 WATER
QUALITY, ETC. TECHNICAL ASSISTANCE FROM DCR IS
AVAILABLE AND RECOMMENDED.
RESPONSIBILITY FOR THE COMPLIANCE TO CHESTERFIELD
COUNTY STANDARDS AND POLICIES AND STATE AND FEDERAL
REGULATIONS WILL BE PLACED ON THE PROFESSIONAL
ENGINEER WHO SIGNS AND SEALS THE CONSTRUCTION PLANS
FOR FURTHER REVIEW.
AS A REMINDER $100.00 BMP MAINTENANCE FEE PER LOT
MUST BE PAID PRIOR TO SUBDIVISION PLAT RECORDATION
========= EROSION CONTROL ==========
1. AS A PREREQUISITE TO ISSUANCE OF A LAND DISTURBANCE
PERMIT:
A. PLANNING DEPARTMENT APPROVAL MUST BE RECEIVED.
B. A PROCESSED VSMP REGISTRATION AND FEE FORM MUST BE
RECEIVED.
C. AN EROSION AND SEDIMENT CONTROL BOND IN THE AMOUNT OF
$29,568 MUST BE POSTED.
D. A COPY OF THE VDOT LAND USE PEMIT MUST BE RECEIVED
E. TWO ADDITIONAL COPIES OF THE CONSTUCTION PLANS TO BE
STAMPED APPROVED FOR CONSTRUCTION" MUST RECEIVED.
F. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
DISKETTE/CD, THE FORMAT OF WHICH SHALL BE AUTOCAD.DWG
OR DXF, MUST BE SUBMITTED TO CAROLE CLIBORNE OF
ENVIRONMENTAL ENGINEERING. THE DISKETTE/CD MUST
CONTAIN THE FOLLOWING, EACH IN A SEPARATE LAYER:
I. EDGES OF IMPERVIOUS AREA OF ROADS TO INCLUDE C&G
AND EDGES OF SIDEWALKS.
II. THE STORM SEWER SYSTEM AND ALL CULVERTS. A LAYER
REPORT PRINTED FROM AUTOCAD MUST BE SUBMITTED WITH
THE DISKETTE/CD. ARCGIS SHAPEFILES SHOULD HAVE EACH
ITEM CLEARLY IDENTIFIED IN THE ATTRIBUTE TABLE. BOTH
THE DISKETTE / CD AND THE REPORT MUST BE LABELED WITH
THE SUBDIVISION NAME AND SECTION, SUBDIVSION PLAN
NUMBER, AND THE ENGINEERING FIRM. ALL AUTOCAD FILES
MUST BE REFERENCED DIRECTLY TO VIRINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, IN THE NAD83 DATUM.
III.ALL JURISDICTIONAL WETLAND AREAS AND OR WATERS OF THE
STATE.
IV. STREAMS AND OTHER WATER BODIES.
V. LOCATIONS OF FIELD VERFIED RESOURCE PROTECTION AREA
DESIGNATIONS TO INCLUDE, WATER BODIES WITH PERNNIAL
FLOW, TIDAL SHORES, TIDAL WETLANDS, NON-TIDAL
WETLANDS, CONNECTED AND CONTIGUOUS TO TIDAL WETLANDS
OR PERNNIAL FLOW.
IV. LOCATIONS OF PERNNIAL FLOW ORIGINS AND THEIR
ASSOCIATED GPS COORDINATES (NAD83 STATE PLANE VA
SOUTH FEET).
IIV.LOCATION(S) OF BREAK POINT(S) IN SURFACE FLOW AND/OR
NON-CONTIGUOUS WETLANDS AND THEIR ASSOCIATED GPS
COORDINATES (NAD83 STATE PLANE VE SOUTH FEET).
XI.FLOOD PLAINS.
2. APPROVAL OF THE MS-19 VARIANCE REQUEST FOR SITUATION E
ON THE OUTFALL STRUCTURES 1 AND 33A HAS BEEN GRANTED.
============== ROAD AND DRAINAGE ========
1. REMOVE THE MINIMUM CRAWL SPACE NOTE AND LABELS FROM
SHEET C3. THE UNITS ARE SLAB-ON-GRADE WITH BF ELEVATIONS
SPECIFIED ON SHEET C4.
=========================================================
=========================================================
REVIEW DEPARTMENT : ENVIRONMENTAL ENGINEERING
REVIEWER/PHONE # : LYNDA GILBERTSON, P.E. / 706-2116
PLAN NAME : WESTCHESTER TOWNHOUSES SECTION 4
PLAN NUMBER : 11CP0006
ORIGINAL PLAN DATE : JULY 16, 2010
REVIEW DATE : AUGUST 18, 2014
LASTEST SUBMISSION DATE : AUGUST 20, 2014
SUBMITTAL NUMBER : 4
RECOMMENDATION : APPROVED
TABLE REVISION : YES
RESPONSIBILITY FOR THE COMPLIANCE TO CHESTERFIELD
COUNTY STANDARDS AND POLICIES AND STATE AND FEDERAL
REGULATIONS WILL BE PLACED ON THE PROFESSIONAL
ENGINEER WHO SIGNS AND SEALS THE CONSTRUCTION PLANS
FOR FURTHER REVIEW.
AS A REMINDER $100.00 BMP MAINTENANCE FEE PER LOT
MUST BE PAID PRIOR TO SUBDIVISION PLAT RECORDATION
========= EROSION CONTROL ==========
1. AS A PREREQUISITE TO ISSUANCE OF A LAND DISTURBANCE
PERMIT:
A. PLANNING DEPARTMENT APPROVAL MUST BE RECEIVED.
B. A PROCESSED VSMP REGISTRATION AND FEE FORM MUST BE
RECEIVED.
C. AN EROSION AND SEDIMENT CONTROL BOND IN THE AMOUNT OF
$29,568 MUST BE POSTED.
D. A COPY OF THE VDOT LAND USE PEMIT MUST BE RECEIVED
E. TWO ADDITIONAL COPIES OF THE CONSTUCTION PLANS TO BE
STAMPED APPROVED FOR CONSTRUCTION" MUST RECEIVED.
F. PRIOR TO ISSUANCE OF A LAND DISTURBANCE PERMIT, A
DISKETTE/CD, THE FORMAT OF WHICH SHALL BE AUTOCAD.DWG
OR DXF, MUST BE SUBMITTED TO CAROLE CLIBORNE OF
ENVIRONMENTAL ENGINEERING. THE DISKETTE/CD MUST
CONTAIN THE FOLLOWING, EACH IN A SEPARATE LAYER:
I. EDGES OF IMPERVIOUS AREA OF ROADS TO INCLUDE C&G
AND EDGES OF SIDEWALKS.
II. THE STORM SEWER SYSTEM AND ALL CULVERTS. A LAYER
REPORT PRINTED FROM AUTOCAD MUST BE SUBMITTED WITH
THE DISKETTE/CD. ARCGIS SHAPEFILES SHOULD HAVE EACH
ITEM CLEARLY IDENTIFIED IN THE ATTRIBUTE TABLE. BOTH
THE DISKETTE / CD AND THE REPORT MUST BE LABELED WITH
THE SUBDIVISION NAME AND SECTION, SUBDIVSION PLAN
NUMBER, AND THE ENGINEERING FIRM. ALL AUTOCAD FILES
MUST BE REFERENCED DIRECTLY TO VIRINIA STATE PLANE
COORDINATE SYSTEM, SOUTH ZONE, IN THE NAD83 DATUM.
III.ALL JURISDICTIONAL WETLAND AREAS AND OR WATERS OF THE
STATE.
IV. STREAMS AND OTHER WATER BODIES.
V. LOCATIONS OF FIELD VERFIED RESOURCE PROTECTION AREA
DESIGNATIONS TO INCLUDE, WATER BODIES WITH PERNNIAL
FLOW, TIDAL SHORES, TIDAL WETLANDS, NON-TIDAL
WETLANDS, CONNECTED AND CONTIGUOUS TO TIDAL WETLANDS
OR PERNNIAL FLOW.
IV. LOCATIONS OF PERNNIAL FLOW ORIGINS AND THEIR
ASSOCIATED GPS COORDINATES (NAD83 STATE PLANE VA
SOUTH FEET).
IIV.LOCATION(S) OF BREAK POINT(S) IN SURFACE FLOW AND/OR
NON-CONTIGUOUS WETLANDS AND THEIR ASSOCIATED GPS
COORDINATES (NAD83 STATE PLANE VE SOUTH FEET).
XI.FLOOD PLAINS.
2. APPROVAL OF THE MS-19 VARIANCE REQUEST FOR SITUATION E
ON THE OUTFALL STRUCTURES 1 AND 33A HAS BEEN GRANTED.
3. IT IS HIGHLY RECOMMENDED TO INCLUDE A CHESTERFIELD
COUNTY POLLUTION PREVENTION PLAN SHEET IN THE
CONSTRUCTION PLANS. PROVIDE TWO SETS FOR THE SUBMITTED
SETS AND INSERTING IN THE ADDITIONAL SETS IS ACCEPTABLE.
4. AS A REMINDER THE TENTATIVE CONDITION #3 STATES "PRIOR
TO RECORDATION OF LOTS 50-67 ALL ISSUED RELATED TO THE
LAKE AS DISCUSSED IN THE ENVIRONMENTAL ENGINEERING
REPORT OF DECEMBER 10, 2004 SHALL HAVE BEEN
SATISFACTORILY ADDRESSED." PLEASE ADDRESS THE FOLLOWING
EROSION CONTROL AND SAFETY CONCERNS THAT WERE OBSERVED
DURING A RECENT SITE VISIT FURTHER DISCUSSION MAYBE
HELPFUL.
A) FROM THE DECEMBER 10, 2004 REPORT "THERE IS EVIDENCE
OF EXTENSIVE SEDIMENTATION IN THE LAKE WHICH MUST BE
REMOVED. THIS WOULD INVOLVE DRAINING THE LAKE AND
REMOVING THE SEDIMENT WITH APPROPRIATE EQUIPMENT.
WHICH THE LAKE IS DRAINED THE DEAD TREES WHICH SHOULD
HAVE BEEN ALREADY HAVE BEEN REMOVED PRIOR TO
CERTIFICATION MUST COME OUT AS WELL."
B) PROVIDE A 4-FOOT ASPHALT PATH ON TOP OF THE DAM FROM
PROPERTY LINE TO PROPERTY LINE WHERE A PATH HAS BEEN
WORN BY PEDESTRIANS.
C) PROVIDE SAFETY MEASURES BETWEEN THE POND AND THE
PATH.
D) PROVIDE TWO REMOVABLE/LOCKABLE BOLLARDS ON EACH SIDE
OF THE 4-FOOT PATH ON THE SOUTHERN PROPERTY LINE TO
PREVENT UNAUTHORIZED VEHICULAR TRAFFIC FROM ACCESSING
THE DAM.
E) STABILIZE THE DAM IN THE VICINITY OF THE RISER AND
REMOVE THE CHAIN LINK FENCE FROM THE TRASH RACK, PUT
TRASH RACK BACK ON.
F) STABILIZE THE SLOPES OF THE POND ON THE INTOWN SUITES
SIDE OF THE POND, THERE APPEARS TO BE RECENT BEAVER
ACTIVITY IN THIS AREA.
G) RESTORE OUTFALL STRUCTURE 0. IT APPEARS SETTLEMENT
HAS OCCURRED AROUND THE LAST SECTION OF PIPE,
SEPARATION AND DEBRIS IS GETTING CAUGHT BETWEEN PIPE
SECTIONS.
H) A BMP INSPECTION NOTIFICATION WAS SENT ON AUGUST 21,
2014, PLEASE ADDRESS THE PAST DUE INSPECTION (AUGUST
1, 2014).