Subdivision Review Comments
All Subdivision Review Comments for Case # 09TS0110




For VDOT’s comments please contact Virginia Department of Transportation at (804) 674-2814 or send e-mail to Boris.Solomonov@VDOT.Virginia.gov

For Tentative Subdivision resubmittals:

1. Please note that submittal fees include the original submittal and two (2) additional reviews.

2. A letter of transmittal is required to accompany each submittal.

3. Please verify that Environmental Engineering, Fire, CDOT, VDOT, and Planning have reviewed the submittal before resubmitting. A resubmittal tendered, prior to receiving all the required departments’ review, will be counted as an additional submittal. Go to Case Selection Form or Go to Project List


 
CASE NO: 09TS0110 STATUS: PENDING APPROVAL
PROJECT NAME: BRANNER STATION PHAS - LAST INTERNET UPDATE: 11/21/17
SUBMITTAL TYPE: TENTATIVE SUBDIVISION
DEPARTMENT...REV..ROUTED..RESPONSE..STATUS....DATE...RVW..PHONE
ENVIR.ENGR.-: 00 07/14/08 08/04/08 ******** ********
FIRE DEPT.--: 00 07/14/08 08/04/08 COMPLETE 08/06/08 JKL 748-1489
HOUSE NUMBER: 00 07/14/08 08/04/08 ******** ********
MAPPING/GIS-: 00 07/14/08 08/04/08 ******** ********
PLANNING----: 00 07/14/08 08/04/08 COMPLETE 07/23/08 RPR 768-7592
PARKS & REC.: 00 07/14/08 08/04/08 ******** ********
SCHOOL BOARD: 00 07/14/08 08/04/08 ******** ********
SOILS-------: 00 07/14/08 08/04/08 ******** ********
TRANSPORT.--: 00 07/14/08 08/04/08 COMPLETE 08/04/08 LWC 768-7386
UTIL.PLAN.--: 00 07/14/08 08/04/08 COMPLETE 10/13/08 TVM 751-4435
UTILITIES---: 00 07/14/08 08/04/08 ******** ********
UTIL.R.O.W.-: 00 07/14/08 08/04/08 ******** ********
VDOT--------: 00 07/14/08 08/04/08 ******** ********
REVIEW DEPARTMENT: UTILITIES
REVIEWER / PHONE # : TERRY MAPLES 751-4435
PLAN NAME: BRANNER STATION 1-B
PLAN NUMBER: 09TS0110
ORIGINAL PLAN DATE: 0711/08
REVIEW DATE: 8/12/08
LATEST SUBMISSION DATE:
SUBMITTAL NUMBER: INITIAL
STATUS:
THE UTILITIES DEPT. IS CURRENTLY REVIEWING THE OVERALL
WATER AND WASTEWATER PLAN FOR "BRANNER STATION"
DEVELOPMENT. BASED ON OUR REVIEW COMMENTS THERE
MAY BE CHANGES IN THE SIZING AND LOCATION OF THE
WATER AND WASTEWATER LINES. A CONDITION OF
ZONING STATES THAT THE OVERALL WATER AND WASTEWATER
PLAN MUST BE APPROVED PRIOR TO FINAL APPROVAL
OF ANY TENTATIVE OR SITE PLANS. SINCE THERE MAY BE
SIGNIFICANT CHANGES IN THE WATER AND WASTEWATER
SYSTEM AS IT IS CURRENTLY DESIGNED, A MORE DETAILED
REVIEW OF THIS TENTATIVE IS NOT POSSIBLE. (U)
REVIEW DEPARTMENT: TRANSPORTATION
REVIEWER/PHONE #: LOUIS CORDE / 768-7386
PLAN NAME: BRANNER STATION PHASE 1B
PLAN NUMBER: 09TS0110
ORIGINAL PLAN DATE: 07/11/08
REVIEW DATE: 08/04/08 07/14/08
LATEST SUBMISSION DATE: 07/11/08
SUBMITTAL NUMBER: 1
STATUS: NOT APPROVED - ADDITIONAL INFORMATION NEEDED
THE TRANSPORTATION DEPARTMENT HAS THE FOLLOWING COMMENTS:
ALL REVIEW ON THIS TENTATIVE HAS BEEN SUSPENDED UNTIL AN
ACCESS PLAN FOR THE NORTH/SOUTH PARKWAY AND HAPPY HILL ROAD
EXTENDED IS PROVIDED. CONDITION 8.A OF ZONING REQUIRES
AN ACCESS PLAN FOR THE NORTH/SOUTH PARKWAY AND HAPPY HILL
ROAD EXTENDED SHALL BE SUBMITTED TO AND APPROVED BY
TRANSPORTATION PRIOR TO TENTATIVE SUBDIVISION APPROVAL. THIS
ACCESS PLAN IS NEEDED NOW SO THAT THE PROPOSED TENTATIVE AND
OVERALL CONCEPTUAL PLAN CAN BE PROPERLY EVALUATED. (T)
CONCERNING THE OVERALL CONCEPTUAL PLAN, ACCESS FOR THE
VARIOUS PODS, PROPOSED PHASING LINES AND PROPOSED ACCESS TO
THOROUGHFARE PLAN ROADS NEEDS TO BE CLARIFIED BEFORE THIS
PLAN CAN BE PROPERLY EVALUATED. (T)
REVIEW DEPARTMENT : PLANNING
REVIEWER / PHONE # : RYAN RAMSEY / 768-7592
PLAN NAME : BRANNER STATION, PHASE 1B
PLAN NUMBER : 09TS0110
ORIGINAL PLAN DATE : 7/11/2008
REVIEW DATE : 7/23/2008
LATEST SUBMISSION DATE : 7/11/2008
SUBMITTAL NUMBER : 1
STATUS : REVISIONS REQUIRED
USE THE SPACES BELOW EACH COMMENT TO DESCRIBE HOW YOU HAVE A
ADDRESSED EACH REVIEW COMMENT. PROVIDE A TRANSMITTAL LETTER.
1) PER THE TRANSPORTATION DEPARTMENT'S COMMENTS
ON PHASE 1A, PLANNING'S COMMENTS ARE SUBJECT TO
CHANGE UPON APPROVAL OF THE ACCESS PLAN REQUIRED
BY PROFFERED CONDITION NUMBER 8.A.
2) ON THE OVERALL CONCEPTUAL PLAN, PLEASE PROVIDE
THE ZONING CLASSIFICATION FOR THE PROPERTY LABELED WITH
TAX ID 778-645-5711. IN ADDITION, PROVIDE THE
OWNER, TAX ID NUMBER AND ZONING CLASSIFICATION FOR
THE PROPERTY AT 5000 LONG CREEK LANE.
3) ON THE OVERALL CONCEPTUAL PLAN, PLEASE DESIGNATE
PARCELS OR LAND INTENDED TO BE DEDICATED FOR PUBLIC
USE. USES SUCH AS SCHOOL SITES AND PUBLIC PARKS
SHOULD BE NOTED ON THE PLAN.
4) ON THE OVERALL CONCEPTUAL PLAN, PLEASE CHANGE
THE TITLE OF THE OVERALL CONCEPTUAL PLAN TO "BRANNER
STATION OVERALL CONCEPTUAL PLAN, PHASE 1B" FROM
"BRANNER STATION, PHASE 1B".
5) ON THE OVERALL CONCEPTUAL PLAN, PLEASE PROVIDE
THE APPROXIMATE ACREAGE AND DENSITY OF THE
RESIDENTIAL PODS INCLUDED IN THIS DEVELOPMENT. WHILE
THIS INFORMATION IS INCLUDED ON THE COVER SHEET, THIS
DATA IS ALSO REQUIRED ON THE OVERALL CONCEPTUAL PLAN.
6) ON THE OVERALL CONCEPTUAL PLAN, PLEASE CORRECT THE
SPELLING ON "PEDESTRIAN TUNNEL".
7) ON THE OVERALL CONCEPTUAL PLAN, PLEASE PROVIDE
BOUNDARIES OF TRACTS 11A & 11B PER PROFFERED
CONDITION NUMBER FOUR (4).
8) ON THE OVERALL CONCEPTUAL PLAN, PLEASE DETAIL THE
LOCATION OF ANY PLANNED OR PROPOSED RECREATIONAL
FACILITIES. IF NONE ARE PLANNED FOR THIS PHASE OF THE
DEVELOPMENT, PLEASE NOTE ON THE PLAN.
9) CORRECT THE ADJACENT PROPERTY OWNER INFORMATION
FOR THE PROPERTY LABELED AS "44" ON THE OVERALL
CONCEPTUAL MASTER PLAN (SHEET 2).
10) PER THE TEXTUAL STATEMENT (IV.B.1.A.(2)), PLEASE
PROVIDE A NOTE ON THE TENTATIVE PLAT STATING THE TOTAL
NUMBER OF ACCESSORY DWELLING UNITS (ADUS) TO BE
LOCATED WITHIN PHASE 1B. SINCE THE LOTS WILL BE LESS
THAN 6,000 SF, NO ADUS WILL BE PERMITTED IN THIS
TOWNHOUSE DEVELOPMENT.
11) PER THE TEXTUAL STATEMENT (III.I), A STREET TREE
PLAN IS REQUIRED FOR SECTIONS WITH AVERAGE LOT SIZES
SMALLER THAN 12,000 SQUARE FEET. CONSEQUENTLY, A
STREET TREE PLAN WILL BE REQUIRED FOR MATSON AND
SOUTHBEND AT BRANNER STATION. PLEASE SUBMIT THE
STREET TREE PLAN(S) FOR REVIEW AND APPROVAL PRIOR TO
TENTATIVE APPROVAL. PLEASE ALSO SUBMIT THE STREET TREE
PLAN AS A SEPARATE SHEET FROM THE TENTATIVE PLAT AND
OVERALL CONCEPTUAL PLAN.
12) PER SECTION 17-38(C)(3) OF THE SUBDIVISION
ORDINANCE, ON AN ADDITIONAL SHEET PLEASE PROVIDE
THE PROFFERED CONDITIONS FROM THE APPROVED BOS
MINUTES.
13) SECTION 19-551 OF THE ZONING ORDINANCE REQUIRES
THAT LOTS WITHIN A SUBDIVISION WILL NEED STREET FRONTAGE
ON A PUBLIC RIGHT-OF-WAY. THE TOWN HOUSE LOTS DO NOT
HAVE PHYSICAL FRONTAGE ON THE PUBLIC STREETS.
14) THE UNDERLYING ZONING FOR THE PROPERTY IS R-12.
IN THE R-12 ZONING DISTRICT, PRIVATE STREETS ARE NOT
PERMITTED PER SECTION 19-551(A) OF THE ZONING
ORDINANCE. PLEASE REVISE THE PLAT TO SHOW EACH LOT
HAVING THE REQUIRED STREET FRONTAGE ON PUBLIC RIGHTS
OF-WAY.
15) PER THE TEXTUAL STATEMENT (V.C.1.C.(5)), PLEASE
PROVIDE FIVE FEET OF COMMON AREA AROUND EACH
TOWNHOUSE UNIT. UNIT 55 IN MATSON AND UNIT 58 IN
SOUTHBEND NEED ADDITIONAL COMMON AREA TO MEET
THIS REQUIREMENT.
16) IF ANY PASSIVE OR ACTIVE RECREATION AREAS ARE
PLANNED, PLEASE NOTE THEIR LOCATION ON THE TENTATIVE
PLAT FOR REVIEW.
17) PER THE TEXTUAL STATEMENT (III.F.), PLEASE PROVIDE
AN ELEVATION DRAWING AND FLOOR PLAN DRAWING TO
ENSURE THAT THESE STRUCTURES WILL NOT HAVE GARAGES
THAT EXCEED THE FRONT FACADE OF THE HOME.
18) ALL CONDITIONS AND PROFFERED CONDITIONS OF ZONING
CASE 06SN0244 SHALL APPLY TO THE LAND SHOWN WITHIN
THIS APPROVED TENTATIVE. ALL CONSTRUCTION PROFFERS
SHALL BE PLACED ON THE FINAL CHECK AND RECORD PLAT.
(P)
19) IN CONJUNCTION WITH THE SUBMITTAL OF THE FINAL
CHECK PLATS, THE SUBDIVIDER SHALL FLAG ALL BUFFERS FOR
INSPECTION BY THE PLANNING DEPARTMENT. IF INSUFFICIENT
VEGETATION REMAINS, THE SUBDIVIDER SHALL SUBMIT A
LANDSCAPE PLAN TO THE DIRECTOR OF PLANNING TO ENSURE
COMPLIANCE WITH THIS CONDITION. IF CONDITIONS ON SITE
ARE NOT CONDUCIVE TO PLANT SURVIVAL, THE SUBDIVIDER
SHALL PROVIDE SURETY TO THE COUNTY IN THE AMOUNT
REQUIRED TO IMPLEMENT THE PLAN. AN ESTIMATE FROM A
LANDSCAPE CONTRACTOR SHALL SERVE AS THE BASIS FOR THE
SURETY AMOUNT. (P)
20) A NOTE SHALL BE PLACED ON THE FINAL CHECK AND
RECORD PLAT THAT INDICATES THE BUFFERS ARE EXCLUSIVE OF
EASEMENTS, CUT AND FILL SLOPES AND SETBACKS. THE
BUFFERS ARE TO REMAIN UNDISTURBED AND NO ACCESS IS
PERMITTED THROUGH THEM TO ANY ADJACENT ROADS. (P)
21) INSERT THE TENTATIVE CASE NUMBER IN THE SITE
STATISTICS NOTE ON THE CONSTRUCTION PLANS. (P)
22) ON THE CONSTRUCTION PLANS, IN THE EROSION CONTROL
NARRATIVE, INSERT THE PROVISIONS FOR THE INSTALLATION OF
TREE PROTECTION FENCING OR TREE PROTECTION TAPE TO
PROTECT THE REQUIRED BUFFERS. (P)
23) IN CONJUNCTION WITH ALL APPLICABLE ROAD
CONSTRUCTION, THE SUBDIVIDER SHALL INSTALL A STANDARD
BARRICADE AND PLACE M 4-6 AND M 4-7 (MANUAL
UNIFORM: TRAFFIC DEVICES REFERENCE MANUAL) SIGNS ON
SAID BARRICADE AT THE END OF ALL STUB LOCATIONS.
PROVIDE A DETAIL OF THE SIGNS ON THE BARRICADE DETAIL
IN THE CONSTRUCTION PLANS. (P)
24) PER SECTION 19-559, A HOMEOWNERS ASSOCIATION
WITH MANDATORY MEMBERSHIP WILL BE REQUIRED.
OWNERSHIP AND MAINTENANCE RESPONSIBILITIES OF THE
ASSOCIATION SHALL BE STATED ON ALL FINAL CHECK AND
RECORDATION PLATS. THE SUBDIVIDER SHALL SUBMIT DRAFT
BYLAWS AND COVENANTS OF THE ASSOCIATION WITH THE
STATE CORPORATION COMMISSION. THE APPROVED BYLAWS
AND COVENANTS SHALL BE RECORDED PRIOR TO OR IN
CONJUNCTION WITH THE RECORD PLAT. THE RECORDATION
INFORMATION SHALL BE SHOWN ON THE RECORD PLAT AND
EACH SUBSEQUENT FINAL CHECK AND RECORD PLAT. THE
SUBDIVIDER SHALL FUND THE FIRST YEAR OPERATIONAL
EXPENSES OF THE ASSOCIATION. (P)
25) STANDARD CONDITIONS. (P)
REVIEW DEPARTMENT: FIRE DEPARTMENT
REVIEWER / PHONE#: KIM LESTER, 748-1489
NAME OF PLAN: BRANNER STATION PHASE 1B
SUBDIVISION PLAN NUMBER: 09TS0110
LATEST PLAN DATE: 07/11/08
DEPARTMENT RECEIVED DATE: 07/15/08
SUBMITTAL NUMBER: 1ST REVIEW
REVIEW DATE: 08/05/08
COMMENTS:
A SECOND ACCESS SHALL BE DESIGNED AND CONSTRUCTED TO A
PUBLIC ROAD PRIOR TO OCCUPANCY OF MORE THAN FIFTY (50) UNITS
BUILDINGS OR PORTIONS OF BUILDINGS OR FACILITIES
EXCEEDING THIRTY FOOT IN HEIGHT ABOVE THE LOWEST LEVEL OF
FIRE DEPARTMENT VEHICLE ACCESS SHALL BE PROVIDED WITH AN
AERIAL FIRE APPARATUS ACCESS ROAD. THE AERIAL FIRE
APPARATUS ACCESS ROAD SHALL BE A MINIMUM OF TWENTY-SIX FEET
UNOBSTRUCTED CLEAR WIDTH IN THE IMMEDIATE VICINITY OF THE
BUILDING. OVERHEAD OBSTRUCTIONS IN FORM OF UTILITY OR
POWER LINES SHALL NOT BE LOCATED WITHIN THE AERIAL FIRE
APPARATUS ACCESS ROADWAY. AT LEAST ONE AERIAL FIRE
APPARATUS ACCESS ROADWAY SHALL BE LOCATED A MINIMUM OF
FIFTEEN FEET AND A MAXIMUM OF THIRTY FEET FROM THE BUILDING
AND POSITIONED PARALLEL TO ONE ENTIRE SIDE OF THE BUILDING.
A NOTE NEEDS TO BE PROVIDED ON THE PLAN FOR THE ABOVE.
SHOW ON THE PLANS WHAT METHOD TO BE USED TO PROVIDE
ACCESS TO ALL EXTERIOR POINTS OF THE BUILDING FROM
WITHIN 150 FEET OF AN APPROVED EMERGENCY FIRE APPARATUS
ACCESS ROADWAY. SEE THE 2003 INTERNATIONAL FIRE CODE,
SECTION 503.1.1 FOR CODE INFORMATION AND EXCEPTIONS.
ALL ROADS INTENDED TO BE USE FOR EMERGENCY VEHICLES
AND ARE NOT GOING TO BE DEDICATED TO THE STATE NEEDS TO
HAVE A MINIMUM OF 20' PAVEMENT WITH NO PARKING ON
EITHER SIDE OF THE ROAD. THE ROADS NEED TO BE POSTED
AS FIRE ACCESS LANES. (SEE IFC 2006 APPENDIX "D" FOR
OTHER ROADWAY REQUIREMENTS.)
IF THERE'S ANY PARALLEL PARKING SHOW IT ON THE PLAN.
NOTE: HYDRANT REQUIREMENTS AND LOCATIONS SHOWN ON THE
TENTATIVE PLAN MAY NOT BE ACCEPTABLE. HYDRANT(S) REQUIRED
AND THEIR LOCATION WILL BE EVALUATED AT THE TIME OF
CONSTRUCTION PLAN REVIEW.
NOTE: COMPLIANCE WITH 17-76 OF THE SUBDIVISION ORDINANCE
IN THE CHESTERFIELD COUNTY CODE SHALL BE MAINTAINED
AT ALL TIMES.
WHEN SUBMITTING THE CONSTRUCTION PLANS, PROVIDE AN
ADDITIONAL COPY TO GO TO THE FIRE DEPARTMENT FOR REVIEW.
************************************************************

Go to Case Selection Form or Go to Project List